Plan Review Details - Permit 07100395
Plan Review Stops For Permit 07100395
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-04-16 Cont ID  
Sent By rmcdouga Date 2008-04-16 Time 11:15 Rev Time 0.00
Received By rmcdouga Date 2008-04-16 Time 07:17 Sent To  
Notes
2008-04-16 12:42:59BUILDING PROVISO
  
 THE NEW WALL ADJACENT TO THE GARAGE IS REQUIRED TO BE
 INSULATED IN ACCORDANCE WITH FBC SECTION
 13-602.1.ABC.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-03-21 Cont ID  
Sent By rmcdouga Date 2008-03-21 Time 15:27 Rev Time 0.00
Received By rmcdouga Date 2008-03-21 Time 12:06 Sent To  
Notes
2008-03-21 15:28:442004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 WILL BE REQUIRED.
  
 2) THE SCOPE OF WORK ON THE ORIGINAL PERMIT APPLICATION
 SPECIFIES INSTALLING A FRENCH DOOR AND WINDOWS. PLEASE
 CLARIFY.IF THESE ARE BEING INSTALLED IN NEW OPENINGS
 PROVIDE STRUCTURAL DETAILS FOR THE OPENINGS AND SUBMIT
 PRODUCT APPROVALS FOR THE REQUIRED IMPACT PROTECTION.
 SEE FBC 106.1.1* CITY AMENDMENTS AND 301.2.1.2. ALSO
 SUBMIT PRODUCT APPROVALS FOR THE NEW SINGLE HUNG
 WINDOWS AND FRENCH DOORS. 106.3 PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE STATE
 WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A
 COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE.
  
 3)106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4)THE SCOPE OF WORK ON THE ORIGINAL PERMIT
 APPLICATION SPECIFIES RAISING THE CEILINGS. THE PLANS
 DO NOT INDICATE THE CEILINGS BEING RAISED. PROVIDE
 STRUCTURAL DETAILS OF THE ROOF FRAMING IN THE AREAS
 WHERE THE CEILINGS ARE BEING RAISED.FBC 106.1.1* CITY
 AMENDMENTS
  
 5) SPECIFY THE SCOPE OF THE WORK ON THE PLANS. FBC
 106.1.1* CITY AMENDMENTS
  
 6) IN ORDER TO EXPEDITE PLAN REVIEW, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW THE COMMENTS WERE
 ADDRESSED.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-05 Cont ID  
Sent By rmcdouga Date 2007-11-05 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2007-11-05 Time 08:08 Sent To  
Notes
2007-11-05 09:22:272004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT PRODUCT APPROVALS FOR THE NEW SINGLE HUNG
 WINDOWS AND FRENCH DOORS. 106.3 PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE STATE
 WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A
 COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE.
  
 3)106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4)PLEASE CLARIFY IF THE NEW WINDOWS AND FRENCH DOOR
 ARE BEING INSTALLED INTO EXISTING OPENINGS. IF THESE
 ARE NEW OPENINGS PROVIDE STRUCTURAL DETAILS FOR THE
 OPENINGS AND SUBMIT PRODUCT APPROVALS FOR THE IMPACT
 PROTECTION THAT WILL BE PROVIDED. FBC 106.1.1* CITY
 AMENDMENTS AND 301.2.1.2
  
 5) PROVIDE STRUCTURAL DETAILS OF THE ROOF FRAMING IN
 THE AREAS WHERE THE CEILINGS ARE BEING RAISED.FBC
 106.1.1* CITY AMENDMENTS
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-04-10 Cont ID  
Sent By dpalmer Date 2008-04-10 Time 16:44 Rev Time 0.00
Received By dpalmer Date 2008-04-10 Time 16:44 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-17 Cont ID  
Sent By dpalmer Date 2008-03-17 Time 11:18 Rev Time 0.00
Received By dpalmer Date 2008-03-17 Time 11:18 Sent To M
Notes
2008-03-17 11:19:44** DENIED2ND REVIEW**
  
 ** PLEASE SEE THE NOTES BELOW WHICH ARE FROM THE FIRST
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED
 ON ELECTRICAL PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SUBMIT COMPLETE LAYOUT OF THE EXISTING
 DWELLING SHOWING CURRENT CODE COMPLIANCE FOR SMOKE
 ALARMS EXISTING OR NEW TO BE INSTALLED PER FBC R313
 NFPA-72 11.5.1.1.1, 11.8.3
  
 3) NOTE: PLEASE SEE 210.8A7 AS ALL RECEPTACLES
 INCLUDING DEDICATED CIRCUITS WHICH ARE 15/20AMP 120V
 WITHIN 6FT OF A LAUNDRY SINK SHALL BE GFI/GFI
 PROTECTED.
  
 4) NOTE: PLEASE SEE WATER HEATER BEING REPLACED DOES
 NOT SHOW THE REQUIRED DISCONNECT PER 422.31
  
 5) NOTE: PLEASE INDICATE ON THE NEW PANEL SCHEDULES
 SUBMITTED WHICH CIRCUITS ARE NEW AND WHICH ONES ARE
 EXISTING.
 FBC 106.3.5.4, NEC 408.4
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By dpalmer Date 2007-10-18 Time 17:31 Rev Time 0.00
Received By dpalmer Date 2007-10-18 Time 17:31 Sent To M
Notes
2007-10-18 17:31:24** DENIED **
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE PROVIDE A LAYOUT OF THE EXISTING
 DWELLING WHICH SHOWS EITHER EXISTING SMOKE ALARMS
 MEETING NFPA-72 OR NEW TO BE INSTALLED.
 PLEASE SEE FBC R313 AND NFPA-72 11.5.1.1.1, 118.3
  
 3) NOTE: PLEASE SEE 210.70 AND LS 101 7.8 AS AT LEAST
 ONE ELECTRICAL LIGHT FIXTURE IS REQUIRED OUTSIDE THE
 REAR EGRESS FOR ILLUMINATION. THESE ARE ALL CURRENTLY
 SHOWN AS J-BOXES.
  
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-09 Cont ID  
Sent By adarroug Date 2008-04-09 Time 16:31 Rev Time 0.00
Received By adarroug Date 2008-04-09 Time 16:31 Sent To E
Notes
2008-04-09 16:32:17TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-11 Cont ID  
Sent By adarroug Date 2008-03-11 Time 16:16 Rev Time 0.00
Received By adarroug Date 2008-03-11 Time 16:16 Sent To Z
Notes
2008-03-11 16:16:40TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-05 Cont ID  
Sent By rmcdouga Date 2007-11-05 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2007-10-15 Time 10:21 Sent To  
Notes
2007-10-15 10:21:29TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-04-11 Cont ID  
Sent By tgordon Date 2008-04-11 Time 08:01 Rev Time 0.25
Received By tgordon Date 2008-04-11 Time 08:01 Sent To P
Notes
2008-04-11 08:05:45*** PROVISO ***
 1) IF NEEDED PROVIDE COMBUSTION AND MAKE-UP AIR FOR GAS
 CLOTHES DRYER, SEE 2004 FBC/R G2407.1, G2407.4, AND
 G2407.5.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-03-17 Cont ID  
Sent By tgordon Date 2008-03-17 Time 12:09 Rev Time 0.30
Received By tgordon Date 2008-03-17 Time 12:09 Sent To P
Notes
2008-03-17 12:15:22PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLAN A-1 STATES "RELOCATE GAS DRYER" IF THE CLOTHES
 DRYER IS GAS THEN IT WOULD BE IN A CONFINED SPACE AND
 WILL REQUIRE COMBUSTION AND MAKE-UP AIR, PER 2004
 FBC/FG 304.1 AND 304.5.1. PLEASE CORRECT.
  
 2) AS NOTED IN LAST REVIEW 10-22-07 NOTE #3 PLEASE SHOW
 THE JOB ADDRESS IN THE TITLE BLOCK OF ALL PAGES, SEE
 WPB AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By tgordon Date 2007-10-22 Time 11:41 Rev Time 0.30
Received By tgordon Date 2007-10-22 Time 11:41 Sent To P
Notes
2007-10-22 11:50:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE YELLOW HIGH LIGHT ON MECHANICAL PLAN PAGE AC-1
 TWO SUPPLY AIR DUCTS NEED TO BE SIZED (1EXIST. LAUN.
 ROOM & 1 NEW STOR.).
  
 2) SHOW BATHROOM EXHAUST FAN ON MECHANICAL PLAN ALSO.
 SEE 2004 FBC/R R303.3 EXCEPT.
  
 3) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK, ALL
 PAGES, SEE WPB AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-04-14 Cont ID  
Sent By jleech Date 2008-04-14 Time 09:39 Rev Time 0.00
Received By jleech Date 2008-04-14 Time 09:39 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-03-20 Cont ID  
Sent By jleech Date 2008-03-20 Time 10:08 Rev Time 0.00
Received By jleech Date 2008-03-20 Time 09:50 Sent To B
Notes
2008-03-20 10:23:55DENIED;
 1. (2ND REQUEST) ADD A PLUMBING NOTE; " NO DEAD ENDS
 PERMITED IN THE DRAINAGE SYSTEM LONGER THAN 2 FEET
 PLUMBING INSPECTION REQUIRED." SEE FBC-PLUMBING SECTION
 704.5.
 2. SANITARY RISER DIAGRAM IS NOT COMPLETE. AUTOMATIC
 CLOTHES WASHER IS NOT SHOWN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-31 Cont ID  
Sent By jleech Date 2007-10-31 Time 08:41 Rev Time 0.00
Received By jleech Date 2007-10-31 Time 08:41 Sent To B
Notes
2007-10-31 08:51:24DENIED;
 1. ADD A DEMO.NOTE,NO DEAD ENDS PERMITED IN THE
 SANITARY SEWER SYSTEM MORE THAN 2'. FBC-2004 PLUMBING
 SECTION 704.5.
 2. PROVIDE A SANITARY RISER DIAGRAM. SHOW PIPE SIZES
 FOR DRAINAGE AND VENTS AND HOW BRANCH DRAIN WILL TIED
 INTO THE BUILDING SEWER. FBC-2004BUILDING CHAPTER 1
 SECTION 106.3.5.4(9).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status N Date 2008-03-13 Cont ID  
Sent By choops Date 2008-03-13 Time 13:45 Rev Time 0.00
Received By choops Date 2008-03-13 Time 13:45 Sent To E
Notes
2008-03-13 13:47:02***ZONING REVIEW NOT REQUIRED - INTERIOR WORK ONLY AND
 THE VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.***
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By choops Date 2007-10-18 Time 10:52 Rev Time 0.00
Received By choops Date 2007-10-18 Time 10:52 Sent To E
Notes
2007-10-18 10:54:39***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE LOCATION OF THE PROPOSED, WITH SETBACK
 DIMENSIONS TO THE PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720