Plan Review Details - Permit 07100394
Plan Review Stops For Permit 07100394
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-10-24 Cont ID  
Sent By mjacobs Date 2007-10-24 Time 18:22 Rev Time 0.00
Received By mjacobs Date 2007-10-24 Time 17:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-24 Cont ID  
Sent By dpalmer Date 2007-10-24 Time 17:11 Rev Time 0.00
Received By dpalmer Date 2007-10-24 Time 17:11 Sent To  
Notes
2007-10-24 17:12:27NEW ELECTRICAL SHEETS BROUGHT IN WITH CORRECTIONS OF
 FLOOR PLANS AND ELECTRICAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-21 Cont ID  
Sent By dpalmer Date 2007-10-21 Time 09:51 Rev Time 0.00
Received By dpalmer Date 2007-10-21 Time 09:44 Sent To  
Notes
2007-10-21 09:53:232007-10-21 09:53:23
  
 *** DENIED ***
  
 11TH FLOOR
  
 1) NOTE: PLEASE COORDINATE ALL PLANS, PERMIT
 APPLICATION AND SCOPE OF WORK. PLEASE SEE THE BELOW AS
 THE PLANS FOR ELECTRICAL WOULD BE OK. PLANS WERE BEING
 STAMPED HOWEVER AS SEVERAL SHEETS DO NOT CORRELATE
 LOCATION FOR FLOOR ETC THE SHEET IN ONE SET WHICH WAS
 STAMP WILL BE VOIDED AT THIS TIME.
 FOR EXAMPLE:
 PLEASE SEE THE PERMIT APPLICATION IS FOR 11TH FLOOR,
 AND THE COVER SHEET INDICATES 11TH FLOOR, SHEET A-2
 INDICATES THE 11TH FLOOR HOWEVER SHEETS A-3 INDICATES
 2ND AND 3RD FLOORS EVEN AS THE TITLE BLOCK CALLS FOR
 11TH FLOOR.
  
  
 A CALLED WAS PLACED TO THE CONTRACTOR AND A MESSAGE WAS
 LEFT THAT THOSE TWO NEW SHEETS A-3 COULD BE BROUGHT IN
 IF NO OTHER REVIEWS START. THIS WOULD NEED TO BE DONE
 BY FIRST THING MONDAY THE 22ND. PLEASE CALL IF THERE
 ARE ANY QUESTIONS.
 IF PLANS ARE DENIED BY ANY OTHER TRADES, PLEASE REPLACE
 SHEETS WHEN PLANS ARE RE-SUBMITTED FOR ANY OTHER
 POSSIBLE REVIEW COMMENTS.
 ** ELECTRICAL IS OK.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-10-26 Cont ID  
Sent By mwennerg Date 2007-10-26 Time 14:03 Rev Time 0.00
Received By mwennerg Date 2007-10-26 Time 14:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-23 Cont ID  
Sent By dpalmer Date 2007-10-23 Time 12:26 Rev Time 0.00
Received By dpalmer Date 2007-10-15 Time 13:48 Sent To  
Notes
2007-10-23 12:26:5210/22/07 PLANS PLACED ON HOLD PER JEFF FISHER, WAITING
 ON NEW SHEETS. REVIEW PROCESSS ALSO ON HOLD. DV PALMER.
2007-10-21 09:45:13TO BOB BOARD SPACE #5. DVP
2007-10-15 13:50:03WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-10-25 Cont ID  
Sent By tgordon Date 2007-10-25 Time 11:10 Rev Time 0.15
Received By tgordon Date 2007-10-25 Time 11:10 Sent To  
Notes
2007-10-25 11:10:57NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-10-27 Cont ID  
Sent By jleech Date 2007-10-27 Time 09:01 Rev Time 0.00
Received By jleech Date 2007-10-27 Time 08:33 Sent To  
Notes
***NONE***