Plan Review Stops For Permit 07100378 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2007-10-22 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-10-22 |
Time |
21:20 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-10-22 |
Time |
20:23 |
Sent To |
|
|
Notes |
2007-10-22 21:18:35 | *****APPROVED W/STIPULATION***** | | | | | | PLAN SHEET FP-1 STAMPED, INITIALED, AND DATED;READY | | FOR PERMIT ISSUANCE. | | | | | | PLEASE BE ADVISED, THAT AT THE TIME OF THE SPRINKLER | | HEAD INSPECTION,PROVIDE A LETTER TO THE FIRE | | INSPECTOR WITH THE LANGUAGE ON YOUR COMPANY LETTERHEAD | | STATING THAT THE 2-HOUR PRESSURE TESTAT 200 PSI | | CANNOT BE CONDUCTED AT THE PROJECT SITE AS PER THE | | EXCEPTION OF NFPA 13 - 2002 EDITION.THIS LETTER WILL | | BE ENTERED INTO THE FILES OF WEST PALM BEACH FIRE | | PREVENTION. | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-10-22 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-10-22 |
Time |
20:24 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-10-12 |
Time |
14:49 |
Sent To |
|
|
Notes |
2007-10-12 14:50:04 | TO "F" BOX |
|
|
|