Plan Review Stops For Permit 07100370 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-11-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-11-16 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-11-16 |
Time |
14:59 |
Sent To |
|
|
Notes |
2007-11-16 15:00:08 | RIDGE VENT |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-10-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-10-31 |
Time |
14:39 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-10-31 |
Time |
14:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-10-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-10-16 |
Time |
13:32 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-10-16 |
Time |
13:32 |
Sent To |
|
|
Notes |
2007-10-16 13:56:49 | 2004 FBC W/2007 REVISIONS | | REROOF 6/12 AND FLAT | | | | DENIED BY BUILDING | | | | 1) SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS FROM A | | FLORIDA LICENSED ENGINEER OR ARCHITECT AS REQUIRED BY | | LIMITATION #7 ON PAGE 44 OF THE NOA FOR THE POLYGLAS | | MODIFIED ROOFING SYSTEM. ENHANCED FASTENING IS REQUIRED | | IN THE CORNER AREAS PER FBC TABLE 1609.6.2.1(2). | | | | 2) SUBMIT PRODUCT APPROVALS FOR THE SECONDARY WATER | | BARRIER THAT WILL BE INSTALLED AS REQUIRED PURSUANT TO | | FS 553.844. | | | | - ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] | | |
|
|
|