Plan Review Details - Permit 07100370
Plan Review Stops For Permit 07100370
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-16 Cont ID  
Sent By shill Date 2007-11-16 Time 14:59 Rev Time 0.00
Received By shill Date 2007-11-16 Time 14:59 Sent To  
Notes
2007-11-16 15:00:08RIDGE VENT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-10-31 Cont ID  
Sent By rmcdouga Date 2007-10-31 Time 14:39 Rev Time 0.00
Received By rmcdouga Date 2007-10-31 Time 14:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By rmcdouga Date 2007-10-16 Time 13:32 Rev Time 0.00
Received By rmcdouga Date 2007-10-16 Time 13:32 Sent To  
Notes
2007-10-16 13:56:492004 FBC W/2007 REVISIONS
 REROOF 6/12 AND FLAT
  
 DENIED BY BUILDING
  
 1) SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS FROM A
 FLORIDA LICENSED ENGINEER OR ARCHITECT AS REQUIRED BY
 LIMITATION #7 ON PAGE 44 OF THE NOA FOR THE POLYGLAS
 MODIFIED ROOFING SYSTEM. ENHANCED FASTENING IS REQUIRED
 IN THE CORNER AREAS PER FBC TABLE 1609.6.2.1(2).
  
 2) SUBMIT PRODUCT APPROVALS FOR THE SECONDARY WATER
 BARRIER THAT WILL BE INSTALLED AS REQUIRED PURSUANT TO
 FS 553.844.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  