Plan Review Details - Permit 07100348
Plan Review Stops For Permit 07100348
Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-10-26 Cont ID  
Sent By mperson Date 2007-10-26 Time 15:38 Rev Time 0.00
Received By mperson Date 2007-10-26 Time 15:38 Sent To PC
Notes
2007-10-26 16:05:05DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT SHOW ALL CUT SECTIONS OF PIPE AND
 CORRESPONDING LENGTHS. PLEASE CORRECT AND RESUBMIT.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 **NOTE: THE ONLY PIPING MATERIAL BEING INDICATED IS FOR
 THE UNDERGROUND PE PIPE. WHAT IS THE ABOVE GROUND
 PIPING MATERIAL? PLEASE CORRECT AND RESUBMIT.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **NOTE: PLEASE REFERENCE COMMENT #1 AND COMPLY ON THE
 RESUBMITTAL.
  
 4. PER FBC-2004 FUEL GAS SEC. 404.12 OUTLET CLOSURES:
 GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES SHALL BE
 CAPPED GAS TIGHT.
 **NOTE: PLEASE INDICATE THIS FOR THE FUTURE BBQ AND
 POOL HEATER ON THE RESUBMITTAL.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATIONS FOR
 THE MP REGULATORS INDICATING THE MAKE, MODEL NUMBER,
 BTU LOAD CAPACITY, AND A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY.
  
 6. THE VALUE OF $450.00 SEEMS TO LOW PER FBC-2004,
 CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
 **NOTE: PLEASE ADJUST THE VALUE ON THE PERMIT
 APPLICATION PRIOR TO THE RESUBMITTAL AND PAY FEES IF
 APPICABLE OR PROVIDE A COPY OF THE SIGNED CONTRACT THAT
 REFLECTS THE INDICATED VALUE ON THE PERMIT
 APPLICATION.
  
 7. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-26 Cont ID  
Sent By mperson Date 2007-10-26 Time 16:05 Rev Time 0.00
Received By mperson Date 2007-10-12 Time 08:15 Sent To  
Notes
2007-10-12 08:16:24TO "G" BOX