Plan Review Details - Permit 07100308
Plan Review Stops For Permit 07100308
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-26 Cont ID  
Sent By adarroug Date 2007-11-26 Time 13:38 Rev Time 0.00
Received By adarroug Date 2007-11-26 Time 13:38 Sent To M
Notes
2007-11-26 13:38:36TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-16 Cont ID  
Sent By tgordon Date 2007-11-16 Time 09:47 Rev Time 0.00
Received By tgordon Date 2007-11-15 Time 10:26 Sent To  
Notes
2007-11-15 10:27:13TO "M" BOX/REV

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-29 Cont ID  
Sent By tgordon Date 2007-11-29 Time 16:33 Rev Time 0.25
Received By tgordon Date 2007-11-29 Time 16:33 Sent To  
Notes
2007-11-29 16:34:51REVISING PERMIT TO INCLUDE DUCT WORK, PLANS SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-16 Cont ID  
Sent By tgordon Date 2007-11-16 Time 09:37 Rev Time 0.30
Received By tgordon Date 2007-11-16 Time 09:37 Sent To  
Notes
2007-11-16 09:46:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) NEED TO SIZE THE RETURN AIR DUCT FROM THE MIXING BOX
 TO THE 24X12 RETURN AIR GRILL (SECOND FLOOR), SEE 2004
 WPB AMEND. 106.3.5.4 (10).
  
 2) NEED TO SHOW THE SUPPLY AIR DUCT FROM THE AIR
 HANDLER TO WERE IT GOES DOWN TO THE FIRST FLOOR BACK
 BEDROOM, SEE 2004 WPB AMEND. 106.3.5.4 (10).
  
 3) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]