Plan Review Details - Permit 07100265
Plan Review Stops For Permit 07100265
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-24 Cont ID  
Sent By mjacobs Date 2007-10-24 Time 07:03 Rev Time 0.00
Received By mjacobs Date 2007-10-24 Time 06:02 Sent To PC
Notes
2007-10-24 07:03:45BUILDING PLAN REVIEW
 PERMIT: 07100265
 ADD: 300 S. AUSTRALIAN AVE #1011
 CONT: AGILE CONST. CORP.
 TEL: (561) 252-0294
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD 10/24/07
 ACTION: DENIED
  
 1A)OK
  
 1B)OK
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)OK
  
 3)**THIS IS A LEVEL 2 ALTERATION**
  
 4)N/A
  
 5)OK
  
 6)N/A
 7)N/A
  
 **OK
  
 **OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-20 Cont ID  
Sent By mjacobs Date 2007-10-20 Time 16:25 Rev Time 0.00
Received By mjacobs Date 2007-10-20 Time 14:41 Sent To  
Notes
2007-10-20 16:25:16BUILDING PLAN REVIEW
 PERMIT: 07100265
 ADD: 300 S. AUSTRALIAN AVE #1011
 CONT: AGILE CONST. CORP.
 TEL: (561) 252-0294
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND 10/20/07
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS
 & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAILTHAT IT WILL CONFORM TO
 THE PROVISIONS? OF THIS CODE AND RELEVANT LAWS. IF THE
 DESIGN PROFESSIONAL IS AND ARCHITECT OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE, THEN,
 HE/SHE SHALL AFFIX HIS OR HER SEAL, SIGNATURE, LICENSE
 NUMBER AND DATE TO THE DRAWINGS IN ACCORDANCE WITH
 FLORIDA STATUTES CHAPTER 471 AND 481.
 **PROVIDE A WALL DETAIL INDICATING THE STUD TYPE AND
 SPACING OF THE NEW WALLS. A FRAMING DETAIL OF THE
 CEILING IS ALSO REQUIRED SHOWING ALL MATERIALS. THE
 DRAWINGS SHALL BE DRAFTSMAN QUALITY DRAWINGS.**
  
 3)2004 FBC EXISTING: 301.5 A DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 4)N/A
  
 5)OK
  
 6)N/A
 7)N/A
  
 **WPB AMENDMENTS 106.1.3 BUILDING PLANS SHALL BE DRAWN
 TO A MINIMUM 1/8 SCALE AND INDICATE CLEARLY THE AREA OF
 THE WORK PROPOSED. DEPARTMENT POLICY AND STANDARDS FOR
 PLANS AND SPECIFICATIONS PROHIBIT HAND WRITING ON SUCH
 INFORMATION WHICH RELATE TO OUR RECORD MANAGEMENT.
  
 **ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE
 DESIGNED TO THE 2004 FLORIDA BUILDING CODE WITH THE
 2006 REV..**
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-13 Cont ID  
Sent By mjacobs Date 2007-10-13 Time 14:27 Rev Time 0.00
Received By mjacobs Date 2007-10-13 Time 13:12 Sent To  
Notes
2007-10-13 14:27:45 
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07100265
 ADD: 300 S. AUSTRALIAN AVE #1011
 CONT: AGILE CONST. CORP.
 TEL: (561) 252-0294
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 10/13/07
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS
 & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)FBC 106.1.1CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAILTHAT IT WILL CONFORM TO
 THE PROVISIONS? OF THIS CODE AND RELEVANT LAWS. IF THE
 DESIGN PROFESSIONAL IS AND ARCHITECT OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE, THEN,
 HE/SHE SHALL AFFIX HIS OR HER SEAL, SIGNATURE, LICENSE
 NUMBER AND DATE TO THE DRAWINGS IN ACCORDANCE WITH
 FLORIDA STATUTES CHAPTER 471 AND 481.
  
 3)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
  
 5)SUBMIT AN EXISTING AND A PROPOSED FLOOR PLAN,
 INDICATING WHERE THE FRAMING OF THE NEW WALL WILL
 OCCUR.
  
 6)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
 7)MEANS OF EGRESS: A CONTINUOUS AND UNOBSTRUCTED WAY
 OF TRAVEL FROM ANY POINT IN A BUILDING OR STRUCTURE TO
 A PUBLIC WAY, CONSISTING OF THREE SEPARATE AND DISTINCT
 PARTS: (1) THE WAY OF THE EXIT ACCESS, (2) THE EXIT,
 AND (3) THE WAY OF THE EXIT DISCHARGE. A MEANS OF
 EGRESS COMPRISES THE VERTICAL AND HORIZONTAL WAYS OF
 TRAVEL AND INCLUDE THE INTERVENING ROOM SPACE, DOORS
 CORRIDORS, PASSAGEWAYS, BALCONIES, STAIRS, RAMPS,
 ENCLOSURES, LOBBIES, HORIZONTAL EXITS, COURTS AND
 YARDS.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-23 Cont ID  
Sent By dpalmer Date 2007-10-23 Time 12:33 Rev Time 0.00
Received By dpalmer Date 2007-10-23 Time 12:33 Sent To  
Notes
2007-10-23 12:35:46REDLINED PLANS.
 NEW ELECTRICAL IN SLEEPING RMS REQUIRED ARC FAULT
 PROTECTION PER 210.12
 SMOKE ALARM INSTALLATION LOCATIONS FROM CEILINGS AND
 WALLS ETC ARE TO MEET 11.8.3. AS CEILDING IN INSTALLED
 LOWER ANY WALL/CEILING MOUNTED SA'S MAY NEED TO BE
 RELOCATED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-17 Cont ID  
Sent By dpalmer Date 2007-10-17 Time 10:09 Rev Time 0.00
Received By dpalmer Date 2007-10-17 Time 10:09 Sent To  
Notes
2007-10-17 10:09:58 
 *** DENIED 2ND REVIEW *****
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEWS STILL NEED
 TO BE ADDRESSED.
  
 1) NOTE: PLEASE SEE MINIMUM CODES/DESIGNS ARE REQUIRED
 TO BE STATED ON PLANS AS REQUIRED BY THE FLORIDA
 BUILDING CODE AND FLORIDA STATUTES.
 THE FOLLOWING CODES ARE REQUIRED FOR ELECTRICAL AT A
 MINIMUM.
 2004 FBC W/2006
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE THERE ARE LOCATION OF FIXTURES
 WHICH ARE *NOTED* ON PLANS HOWEVER NOT ACTUALLY SHOWN.
 PLEASE SEE THERE ARE FIXTURES ON PLANS WHICH DO NOT
 INDICATE ANY CONTROLS FOR LIGHTS. NO SWITCHES ETC.
 210.70.
 PLEASE PROVIDE MORE DETAILED INFORMATION.
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE THAT BESIDES THE PRINTED NAME AND
 SIGNATURE OF THE CONTRACTOR RESPONSIBLE FOR PLANS, CODE
 RELATED PLANS, DETAILS AND NOTES MAY NOT BE DONE IN PEN
 OR PENCIL. (PEN SHOWN).
 PLEASE BE SURE TO PHOTO-COPY PLANS BEFORE
 RESUBMITTING.
 FBC 106.1, 106.3.5
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-14 Cont ID  
Sent By dpalmer Date 2007-10-14 Time 11:12 Rev Time 0.00
Received By dpalmer Date 2007-10-14 Time 11:08 Sent To  
Notes
2007-10-14 11:13:07** DENIED **
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
  
 2) NOTE: PLEASE PROVIDE ELECTRICAL ON PLANS FOR SCOPE
 OF WORK EVEN IF UNDER A SEPARATE PERMIT.
 PLEASE SEE FBC EXISTING BUILDING CODE FOR MINIMUM
 ALTERATION/DESIGN TO BE ON PLANS.
 106.1.2
  
 3) NOTE: PLEASE SEE FS 481.229, 471.003, EVEN WHEN
 SCOPE OF WORK DOES NOT REQUIRE A LICENSE ARCHITECT OR
 ENGINEER, PLANS ARE STILL REQUIRED TO DONE BY LICENSE
 PROFESSIONAL MEETING THE EXCEPTIONS AND TAKING
 RESPONSIBILITY OF PROPOSED SCOPE OF WORK.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-10-23 Cont ID  
Sent By mwennerg Date 2007-10-23 Time 13:56 Rev Time 0.00
Received By mwennerg Date 2007-10-23 Time 13:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-10-22 Cont ID  
Sent By mawillia Date 2007-10-22 Time 11:04 Rev Time 0.00
Received By mawillia Date 2007-10-22 Time 10:55 Sent To  
Notes
2007-10-22 11:03:52*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 ACCESS TO/EGRESS FROM THE OTHER TENANT SPACES ON THE
 SAID FLOOR AND/OR THE BUILDING.
  
 4.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 5.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 6.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-15 Cont ID  
Sent By mawillia Date 2007-10-15 Time 15:32 Rev Time 0.00
Received By mawillia Date 2007-10-15 Time 15:11 Sent To  
Notes
2007-10-15 15:31:57*****DENIED*****
  
 NOT ENOUGH INFORMATION TO CONDUCT A THOROUGH FIRE PLAN
 REVIEW
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 ACCESS TO/EGRESS FROM THE OTHER TENANT SPACES ON THE
 SAID FLOOR AND/OR THE BUILDING.
  
 4.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 5.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 6.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 7.ILLUSTATE THE LOCATION OF EXIT LIGHS, EMERGENCY
 LIGHTS, AND FIRE EXTINGUISHER(S) FOR THIS TENANT
 SPACE.
  
 8. WILL THE SCOPE OF WORK HAVE CAUSE FOR ANY FIRE
 SPRINKLER AND/OR FIRE ALARM DEVICES TO BE RE-LOCATED OR
 MOMIDIFIED?
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-23 Cont ID  
Sent By adarroug Date 2007-10-23 Time 08:16 Rev Time 0.00
Received By adarroug Date 2007-10-23 Time 08:16 Sent To  
Notes
2007-10-23 08:17:04TO "BOB"#4--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 09:32 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 09:32 Sent To  
Notes
2007-10-17 09:32:41TO "BOB"#1--EXPEDITED

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-16 Cont ID  
Sent By rbrown Date 2007-10-16 Time 13:49 Rev Time 0.00
Received By rbrown Date 2007-10-10 Time 10:24 Sent To  
Notes
2007-10-10 10:25:32TO "BOB"#1--EXPEDITED PERMIT--