Plan Review Details - Permit 07100220
Plan Review Stops For Permit 07100220
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-14 Cont ID  
Sent By rmcdouga Date 2007-11-14 Time 14:44 Rev Time 0.00
Received By rmcdouga Date 2007-11-14 Time 14:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-26 Cont ID  
Sent By rmcdouga Date 2007-10-26 Time 16:08 Rev Time 0.00
Received By rmcdouga Date 2007-10-26 Time 16:08 Sent To  
Notes
2007-10-26 16:08:182004 FBC WITH 2007 REVISIONS
  
 LEVEL 2 ALTRATION
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE ENGINEER IS REQUIRED TO LEGIBLY INDICATE THIER
 NAME ON EACH DRAWING PER FAC 61G15-23.002.
  
 3) THE FRAMING DETAILS ON SHEET 2 DO NOT SPECIFY ANY
 CONNECTORS. PLEASE CORRECT. FBC R301.1
  
 4)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-12-07 Cont ID  
Sent By btrobaug Date 2007-12-07 Time 07:25 Rev Time 0.00
Received By btrobaug Date 2007-12-07 Time 06:29 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-06 Cont ID  
Sent By btrobaug Date 2007-11-06 Time 07:44 Rev Time 0.00
Received By btrobaug Date 2007-11-06 Time 06:46 Sent To P
Notes
2007-11-06 07:44:09 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET 3 3, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 THESE COMMENTS WERE NOT CORRECTLY ADDRESSED TO INDICATE
 COMPLIANCE WITH THE CODE;
  
 2} THE SCOPE OF THE ELECTRICAL WORK IS NOT CLEAR ON
 THE PLAN. INDICATE IF THE SERVICE IS NEW OR EXISTING IN
 WHOLE OR IN PART. HAND DRAWN CHANGES TO THE PLAN ARE
 NOT ACCEPTABLE FOR RECORD RETENTION OR CLARITY IN THE
 FIELD. 106.1.3 FBC AS AMENDED. * THERE IS STILL NO
 INDICATION REGARDING IF THE SERVICE IS NEW OR
 EXISTING.
  
 4} IF THE SERVICE IS NEW, PER 110.9 AND 110.10: OBTAIN
 THE AVAILABLE FAULT CURRENT AT THE UTILITY AND
 CALCULATE THE SAME AT THE EQUIPMENT. INDICATE THE AIC
 RATING FOR THE EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT. * NOT ADDRESSED.
  
 5} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66, AND 250.50. INDICATE SAME ON THE RISER
 DIAGRAM.* NO SIZING GIVEN.SEE ARTICLE.
  
 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES. * SEE KITCHEN
  
 8} LOCATE AND INDICATE A DISCONNECTING MEANS FOR THE
 WATER HEATER. SEE 422.16 NEC FOR CORD AND PLUG
 RESTRICTIONS, AND 422.31(B) FOR HARDWIRE
 REQUIREMENTS.*WATER HEATERS INDICATE THEY ARE CORD
 CONNECTED TO A 120 VOLT RECEPTACLE. VERIFY.
  
 9} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B). THE
 FRONT DOES NOT COMPLY.
  
 13} THERE IS APPARENTLY IS AN APARTMENT ATTACHED TO THE
 MAIN HOUSE, BUT THE LOAD CALCULATION FOR THE SERVICE
 DID NOT INCLUDE ANY EQUIPMENT OR BRANCH CIRCUITS
 REQUIRED FOR AN APARTMENT. SHOW ALL CALCULATIONS PER
 220 NEC IF CHANGING THE SERVICE, AND ALL PANEL
 SCHEDULES PER 408.4 NEC. * THE TOTAL LOAD WAS NOT
 CALCULATED FOR THE SERVICE PER 220.83, BUT RATHER PER
 PANEL. THE CONDUIT AND CONDUTOR SIZES FOR THE RISER
 DIAGRAM ARE NOT INDICATED, THEREFORE THE SIZE OF THE
 SERVICE CANNOT BE DETERMINED.
  
 NEW COMMENTS THIS REVIEWDUE TO CHANGES IN THE PLAN,
 SPECIFICALLY THE RISER NOW BEING SHOWN AS PART OF THE
 SCOPE;
  
 1} THE RISER SHOWS TWO PANELS. THE FLOOR PLAN SHOWS TWO
 PANELS AT THE METERS AND ONE PANEL IN THE MAIN HOUSE,
 PLEASE CORRELATE.
  
 2} THERE IS NO BATH RECEPTACLE SHOWN IN PANEL "B" PER
 210.11(C)(3)
  
 TO EXPEDITE REVIEW AND CLARIFY THE DESIGNERS INTENT ON
 THE ABOVE ISSUES, SUBMIT WRITTEN RESPONSE TO THE
 COMMENTS MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-11 Cont ID  
Sent By btrobaug Date 2007-10-11 Time 08:21 Rev Time 0.00
Received By btrobaug Date 2007-10-10 Time 14:03 Sent To M
Notes
2007-10-10 17:08:46 
  
 APPLICATION # 07100220
 ELECTRICAL PLAN REVIEW
 850 SUMMIT BLVD
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET 3 3, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} THE ENGINEER OF RECORD MUST LEGIBLY INDICATE THEIR
 NAME ADDRESS, AND LICENSE NUMBER ON EACH SHEET PER
 61G15-23.002 FAC.
  
 2} THE SCOPE OF THE ELECTRICAL WORK IS NOT CLEAR ON
 THE PLAN. INDICATE IF THE SERVICE IS NEW OR EXISTING IN
 WHOLE OR IN PART. HAND DRAWN CHANGES TO THE PLAN ARE
 NOT ACCEPTABLE FOR RECORD RETENTION OR CLARITY IN THE
 FIELD. 106.1.3 FBC AS AMENDED.
  
 3} THERE ARE FOUR METERS SHOWN ON THE PLAN, CLARIFY.
  
 4} IF THE SERVICE IS NEW, PER 110.9 AND 110.10: OBTAIN
 THE AVAILABLE FAULT CURRENT AT THE UTILITY AND
 CALCULATE THE SAME AT THE EQUIPMENT. INDICATE THE AIC
 RATING FOR THE EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 5} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66, AND 250.50. INDICATE SAME ON THE RISER
 DIAGRAM.
  
 6} R313.1.1 RESIDENTIAL BUILDING CODE, SMOKE ALARMS
 SHALL BE LOCATED AS REQUIRED IN NEW DWELLINGS WHEN
 REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR. SEE
 ARTICLE FOR COMPLETE TEXT. THERE ARE NONE SHOWN FOR THE
 APARTMENT.
  
 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES.
  
 8} LOCATE AND INDICATE A DISCONNECTING MEANS FOR THE
 WATER HEATER. SEE 422.16 NEC FOR CORD AND PLUG
 RESTRICTIONS, AND 422.31(B) FOR HARDWIRE REQUIREMENTS.
  
 9} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B). THE
 FRONT DOES NOT COMPLY.
  
 10} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING. INDICATE COMPLIANCE ON THE PLAN.
  
 11} 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT OUTLET: A 125-VOLT, SINGLE-PHASE, 15- OR
 20-AMPERE-RATED RECEPTACLE OUTLET SHALL BE INSTALLED AT
 AN ACCESSIBLE LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET
 SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING MEANS. SEE CONDENSER.
  
 12} THE 60 AMP OCP FOR THE 7500W HEAT IS IN VIOLATION
 OF 310.16 AND 240.4. 7500/240=31.25 AMPS.
  
 13} THERE IS APPARENTLY IS AN APARTMENT ATTACHED TO THE
 MAIN HOUSE, BUT THE LOAD CALCULATION FOR THE SERVICE
 DID NOT INCLUDE ANY EQUIPMENT OR BRANCH CIRCUITS
 REQUIRED FOR AN APARTMENT. SHOW ALL CALCULATIONS PER
 220 NEC IF CHANGING THE SERVICE, AND ALL PANEL
 SCHEDULES PER 408.4 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-05 Cont ID  
Sent By adarroug Date 2007-11-05 Time 12:19 Rev Time 0.00
Received By adarroug Date 2007-11-05 Time 12:19 Sent To E
Notes
2007-11-05 12:19:25TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-26 Cont ID  
Sent By rmcdouga Date 2007-10-26 Time 16:08 Rev Time 0.00
Received By rmcdouga Date 2007-10-09 Time 13:58 Sent To  
Notes
2007-10-09 13:58:12TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-10-16 Cont ID  
Sent By tgordon Date 2007-10-16 Time 11:11 Rev Time 0.20
Received By tgordon Date 2007-10-16 Time 11:11 Sent To P
Notes
2007-10-16 11:12:32NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-19 Cont ID  
Sent By jleech Date 2007-11-19 Time 15:13 Rev Time 0.00
Received By jleech Date 2007-11-19 Time 15:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-24 Cont ID  
Sent By jleech Date 2007-10-24 Time 15:04 Rev Time 0.00
Received By jleech Date 2007-10-24 Time 15:01 Sent To B
Notes
2007-10-24 15:17:24DENIED;
 NOT ENOUGH INFORMATION TO DO A PLUMBING PLAN REVIEW. ON
 PERMIT APPLICATION ( DESCRIPTION SECTION)" REPLACE
 C.I AND COPPER WITH PVC".
 THE FOLLOWING IS REQUIRED ON THE PLANS.
 A) A SANITARY RISER DIAGRAM SHOWING ALL PIPE
 SIZES FOR DRAINAGE AND VENTS.
 B) REPLACEMENT OF WATER PIPE, COPPER OR CPVC
 CAN BE USED, NOT PVC FBC PLUMBING SECTION 605.3.
 IS THE HOUSE AND THE APARTMENT ON ONE WATER
 METER? IF SO A BACKFLOE PREVENTOR IS REQUIRED AT THE
 METER. PLEASE SHOW ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-10-11 Cont ID  
Sent By btrobaug Date 2007-10-11 Time 08:47 Rev Time  
Received By btrobaug Date   Time   Sent To M
Notes
2007-10-11 08:48:15 
 THIS IS AN ERROR, NO ZONING REQUIRED PER CHRIS
 HOOPS./WRT.