| APPLICATION # 07100220 |
| ELECTRICAL PLAN REVIEW |
| 850 SUMMIT BLVD |
| WEST PALM BEACH, FL. |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| ALL COMMENTS RELATE TO SHEET 3 3, UNLESS OTHERWISE |
| NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| OTHERWISE NOTED. |
| |
| 1} THE ENGINEER OF RECORD MUST LEGIBLY INDICATE THEIR |
| NAME ADDRESS, AND LICENSE NUMBER ON EACH SHEET PER |
| 61G15-23.002 FAC. |
| |
| 2} THE SCOPE OF THE ELECTRICAL WORK IS NOT CLEAR ON |
| THE PLAN. INDICATE IF THE SERVICE IS NEW OR EXISTING IN |
| WHOLE OR IN PART. HAND DRAWN CHANGES TO THE PLAN ARE |
| NOT ACCEPTABLE FOR RECORD RETENTION OR CLARITY IN THE |
| FIELD. 106.1.3 FBC AS AMENDED. |
| |
| 3} THERE ARE FOUR METERS SHOWN ON THE PLAN, CLARIFY. |
| |
| 4} IF THE SERVICE IS NEW, PER 110.9 AND 110.10: OBTAIN |
| THE AVAILABLE FAULT CURRENT AT THE UTILITY AND |
| CALCULATE THE SAME AT THE EQUIPMENT. INDICATE THE AIC |
| RATING FOR THE EQUIPMENT IS EQUAL TO OR GREATER THAN |
| THE AVAILABLE FAULT. |
| |
| 5} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH |
| 250.66, AND 250.50. INDICATE SAME ON THE RISER |
| DIAGRAM. |
| |
| 6} R313.1.1 RESIDENTIAL BUILDING CODE, SMOKE ALARMS |
| SHALL BE LOCATED AS REQUIRED IN NEW DWELLINGS WHEN |
| REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR. SEE |
| ARTICLE FOR COMPLETE TEXT. THERE ARE NONE SHOWN FOR THE |
| APARTMENT. |
| |
| 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR |
| DEFICIENCIES. |
| |
| 8} LOCATE AND INDICATE A DISCONNECTING MEANS FOR THE |
| WATER HEATER. SEE 422.16 NEC FOR CORD AND PLUG |
| RESTRICTIONS, AND 422.31(B) FOR HARDWIRE REQUIREMENTS. |
| |
| 9} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B). THE |
| FRONT DOES NOT COMPLY. |
| |
| 10} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING |
| AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE |
| LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT |
| GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE |
| GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE |
| DWELLING. INDICATE COMPLIANCE ON THE PLAN. |
| |
| 11} 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION |
| EQUIPMENT OUTLET: A 125-VOLT, SINGLE-PHASE, 15- OR |
| 20-AMPERE-RATED RECEPTACLE OUTLET SHALL BE INSTALLED AT |
| AN ACCESSIBLE LOCATION FOR THE SERVICING OF HEATING, |
| AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE |
| RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND |
| WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING, |
| AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET |
| SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE |
| EQUIPMENT DISCONNECTING MEANS. SEE CONDENSER. |
| |
| 12} THE 60 AMP OCP FOR THE 7500W HEAT IS IN VIOLATION |
| OF 310.16 AND 240.4. 7500/240=31.25 AMPS. |
| |
| 13} THERE IS APPARENTLY IS AN APARTMENT ATTACHED TO THE |
| MAIN HOUSE, BUT THE LOAD CALCULATION FOR THE SERVICE |
| DID NOT INCLUDE ANY EQUIPMENT OR BRANCH CIRCUITS |
| REQUIRED FOR AN APARTMENT. SHOW ALL CALCULATIONS PER |
| 220 NEC IF CHANGING THE SERVICE, AND ALL PANEL |
| SCHEDULES PER 408.4 NEC. |
| |