Plan Review Details - Permit 07100201
Plan Review Stops For Permit 07100201
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-10-16 Cont ID  
Sent By lursu Date 2007-10-16 Time 08:12 Rev Time 0.00
Received By lursu Date 2007-10-16 Time 08:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-14 Cont ID  
Sent By mjacobs Date 2007-11-14 Time 17:14 Rev Time 0.00
Received By mjacobs Date 2007-11-14 Time 14:02 Sent To  
Notes
2007-11-14 17:15:05 
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07100201
 ADD: 777 S. FLAGLER DR
 CONT: BUTLER CONSTRUCTION
 TEL: (561) 832-9700
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 AND 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 10/17/07
  
 1A)OK
 1B)OK
  
 NOC SHALL BE SUBMITTED BEFORE PERMIT IS ISSUED.
 1C) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) OK
 2)OK
 3)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-24 Cont ID  
Sent By mjacobs Date 2007-10-18 Time 06:50 Rev Time 0.00
Received By mjacobs Date 2007-10-17 Time 18:41 Sent To  
Notes
2007-10-18 06:50:17 
 BUILDING PLAN REVIEW
 PERMIT: 07100201
 ADD: 777 S. FLAGLER DR
 CONT: BUTLER CONSTRUCTION
 TEL: (561) 832-9700
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 AND 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 10/17/07
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1C) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) PLANS SUBMITTED FOR PERMIT AFTER JULY 1ST, 2007
 SHALL BE REVIEWED TO THE 2004 FBC BUILDING WITH THE
 2007 REVISIONS.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
  
 3)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-19 Cont ID  
Sent By dpalmer Date 2007-11-07 Time 08:20 Rev Time 0.00
Received By dpalmer Date 2007-11-07 Time 16:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-14 Cont ID  
Sent By dpalmer Date 2007-10-14 Time 12:23 Rev Time 0.00
Received By dpalmer Date 2007-10-14 Time 12:02 Sent To  
Notes
2007-10-14 12:23:57** DENIED **
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70**2002 IS STATED ON PLANS/IN NOTES ON
 E-1*
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM OTHER TRADES SUCH
 AS BUILDING AS THE *LEVEL OF ALTERATION* PER FBC
 EXISTING BUILDING CODE DOES REQUIRE LEVEL TO BE
 STATED.
  
 2) NOTE: PLEASE SEE THE APPLICATION WAS ROUTED TO THE
 ADDRESSING REVIEWER AS THE PERMIT APPLICATION IS FOR
 12TH FLOOR AND NO UNIT/SUITE WAS APPLIED OR GIVEN.
 THE LOCATION AS ASSESSED AT TIME OF APPLICATION DOES
 NOT PLACE PROJECT IN *EAST* TOWER NOR DOES HAS A
 UNIT/SUITE NUMBER BEEN GENERATED.
 ONCE ANY SUITE/UNIT NUMBER HAS BEEN ASSIGNED, PLEASE BE
 SURE TO ADD TO TITLE BLOCKS.
  
 3) NOTE: PLEASE CORRELATE ELECTRICAL LIGHTING FIXTURES
 ON PLANS WITH THAT OF THE DESIGNATIONS AS SHOWN ON
 FIXTURE LEGEND. PLEASE SEE THE PLANS SHOW SOME FIXTURE
 SYMBOLS WHICH ARE NOT ON THE FIXTURE LEGEND. (HALF
 DARKENED RECESSED LTS) ARE THESE NEW? EXISTING?
 FBC 106.1.2
 PLEASE KNOW, *IF NEW*, NEED TO PROVIDE MAXIMUM LIGHTING
 PERFORMANCE CALCULATIONS PER 13-415.2 AND CONTROLS PER
 13-101, 13-415.1.ABC.1.1, .1.2.
 IF ALL EXISTS PLEASE MATCH TYPES AND INDICATED AS
 SUCH.
  
 ** ALL LIGHTING AND CONTROLS WHICH ARE SHOWN APPEAR TO
 BE EXISTING WITH ONLY ONE NEW FIXTURE BEING ADDED. CAN
 NOT CONFIRM AT THIS TIME.
  
 ** PLEASE ADDRESS THE ABOVE COMMENTS. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-11-19 Cont ID  
Sent By mwennerg Date 2007-11-19 Time 10:01 Rev Time 0.00
Received By mwennerg Date 2007-11-19 Time 10:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By mawillia Date 2007-10-18 Time 17:05 Rev Time 0.00
Received By mawillia Date 2007-10-18 Time 16:13 Sent To  
Notes
2007-10-18 17:04:56*****PROVISO*****
  
 PLANS TO BE FIRE STAMPED UPON ACKNOWLEDGEMENT OF THE
 FOLLOWING:
  
 1.THE REMOVAL AND/OR THE STOCKING OF BUILDING
 MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER
 ACCESS TO/EGRESS FROM THE SAID FLOOR OR BUILDING.
  
 2.ON SHEET E-2, A CARD READER (CR) AND ELECTRIC LOCK
 (EL) ARE NOTED FOR THE NEW DOOR (1202) .WILL THERE BE
 ANY IMPACT TO EGRESSING FROM THE OPEN OFFICE AREA, AND
 IF SO, HOW WILL THE CRITERIA AS PER NFPA 101 -
 7.2.1.6.2 BE ACHIEVED?
  
 3.SPECIFY THE NEW WALL INTERIOR FINISH MATERIAL IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 10:39 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 10:39 Sent To  
Notes
2007-11-07 11:09:06TO "BOB"#11
2007-11-07 10:40:13WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-18 Cont ID  
Sent By mawillia Date 2007-10-18 Time 16:14 Rev Time 0.00
Received By mawillia Date 2007-10-05 Time 15:40 Sent To  
Notes
2007-10-14 12:38:38TO BOB, SPACE #10. DVP
2007-10-05 15:40:45WAITING FOR "BOB"

Review Stop Z ZONING
Rev No 1 Status N Date 2007-10-17 Cont ID  
Sent By choops Date 2007-10-17 Time 15:52 Rev Time 0.00
Received By choops Date 2007-10-17 Time 15:52 Sent To  
Notes
2007-10-17 15:52:26*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.