Plan Review Stops For Permit 07100199 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-10-10 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-10-10 |
Time |
16:08 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-10-10 |
Time |
16:08 |
Sent To |
|
|
Notes |
2007-10-10 16:23:48 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.24" ANCHOR SPACING IS LIMITED TO 47PSF; THIS JOB | | HAS A DESIGN PRESSURE OF 56.2.HOWEVER, IT APPEARS | | THAT THIS SHUTTER CANNOT BE INSTALLED IN THIS LOCATION | | (SEE COMMENT #2). | | | | 2.SEE FBC1006.3, MEANS OF EGRESS CONTINUITY.THE | | PATH OF TRAVEL SHALL NOT BE INTERRUPTED BY ANY BUILDING | | ELEMENT OTHER THAN A MEANS OF EGRESS COMPONENT AS | | SPECIFIED IN CHAPTER 10.THE SHUTTER DOES NOT COMPLY | | WITH ANY OF THE MEANS OF EGRESS COMPONENTS REQUIRED FOR | | COMMERCIAL BUILDINGS.ALSO DOES NOT COMPLY WITH | | ACCESSIBLE MEANS OF EGRESS, FBC11. |
|
|