Plan Review Details - Permit 07100199
Plan Review Stops For Permit 07100199
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-10 Cont ID  
Sent By shill Date 2007-10-10 Time 16:08 Rev Time 0.00
Received By shill Date 2007-10-10 Time 16:08 Sent To  
Notes
2007-10-10 16:23:48****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.24" ANCHOR SPACING IS LIMITED TO 47PSF; THIS JOB
 HAS A DESIGN PRESSURE OF 56.2.HOWEVER, IT APPEARS
 THAT THIS SHUTTER CANNOT BE INSTALLED IN THIS LOCATION
 (SEE COMMENT #2).
  
 2.SEE FBC1006.3, MEANS OF EGRESS CONTINUITY.THE
 PATH OF TRAVEL SHALL NOT BE INTERRUPTED BY ANY BUILDING
 ELEMENT OTHER THAN A MEANS OF EGRESS COMPONENT AS
 SPECIFIED IN CHAPTER 10.THE SHUTTER DOES NOT COMPLY
 WITH ANY OF THE MEANS OF EGRESS COMPONENTS REQUIRED FOR
 COMMERCIAL BUILDINGS.ALSO DOES NOT COMPLY WITH
 ACCESSIBLE MEANS OF EGRESS, FBC11.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 16:23 Rev Time 0.00
Received By shill Date 2007-10-05 Time 15:33 Sent To  
Notes
2007-10-05 15:33:22TO "MISC" BOX#1