Plan Review Details - Permit 07100169
Plan Review Stops For Permit 07100169
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-29 Cont ID  
Sent By mjacobs Date 2007-12-29 Time 06:19 Rev Time 0.00
Received By mjacobs Date 2007-12-29 Time 06:05 Sent To PC
Notes
2007-12-29 06:06:04PROCESS PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-27 Cont ID  
Sent By mjacobs Date 2007-12-27 Time 16:01 Rev Time 0.00
Received By mjacobs Date 2007-12-27 Time 14:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-20 Cont ID  
Sent By mjacobs Date 2007-10-20 Time 12:11 Rev Time 0.00
Received By mjacobs Date 2007-10-20 Time 08:06 Sent To  
Notes
2007-10-20 12:11:36BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1A) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1B) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE
 DESIGNED TO THE 2004 FLORIDA BUILDING CODE.
  
 3)2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 **NOTE** THIS PROJECT WAS SUBMITTED UNDER A DIFFERENT
 ADDRESS PREVIOUSLY. THIS WOULD HAVE BEEN A RESUBMITTED,
 AND A NEW APPLICATION NUMBER WAS NOT NECESSARY FOR THE
 PROJECT. THE PREVIOUS ADDRESS WAS 918 9TH STREET; THE
 SAME PROJECT HAS AN ADDRESS OF 911- 9TH. THE OLD
 APPLICATION NUMBER IS 06110765.CLARIFY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-20 Cont ID  
Sent By dpalmer Date 2007-12-20 Time 19:07 Rev Time 0.00
Received By dpalmer Date 2007-12-20 Time 19:07 Sent To  
Notes
2007-12-20 19:08:16REVIEWED AND STAMPED ELEC DONE BY THE ELECTRICAL
 CONTRACTOR.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By dpalmer Date 2007-10-16 Time 10:12 Rev Time 0.00
Received By dpalmer Date 2007-10-16 Time 09:33 Sent To  
Notes
2007-10-16 10:12:50**** DENIED ****
  
  
 1) NOTE:PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT
 CODES ARE STATED ON PLANS.
 PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER
 DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A
 MINIMUM.
 PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE
 REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE
 FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS
 FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
  
 ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES FOR
 CODES.
  
 2) NOTE: PLEASE SUBMIT PLANS WHICH ARE NOT DONE IN
 PEN/PENCIL. PLEASE SEE MINIMUM CONSTRUCTION DOCUMENTS
 STANDARDS PER FBC 106.1
  
 3) NOTE: PLEASE SUBMIT ELECTRICAL WITH MORE DETAIL FOR
 NEW ELEVATOR. THIS NEEDS TO INCLUDE SIZE OF MOTOR,
 LOADS, ETC.
 THE OVER CURRENT PROTECTION WHICH IS SHOWN AS EXISTING
 ALONG WITH CONDUCTOR SIZES CAN NOT BE VERIFIED FOR
 MOTOR AT THIS TIME.
 PLEASE SEE THAT STATING SOME OF THE CODES IN LIEU OF
 SPECIFIC DETAIL CAN NOT BE ACCEPTED.
 PLEASE SEE THERE ARE SEVERAL SECTIONS OF NEC 620 WHICH
 INFORMATION IS NEEDED. DISCONNECT LOCATIONS FOR BRANCH
 CIRCUITS; MOTORS ETC ARE REQUIRED TO BE GROUPED IN ONE
 LOCATION.
 PLEASE SEE PLANS ARE MISSING AN EQUIPMENT ROOM, PIT,
 AND OTHER ITEMS WHICH ARE NOT CLEAR IF THESE WILL BE
 REQUIRED.
 THERE IS A STRUCTURAL SHEET WHICH DOES SHOW A LAYOUT
 FOR EQUIPMENT HOWEVER THIS DOES NOT CORRELATE WITH
 ELECTRICAL PLANS.
 PLEASE SEE THE ELECTRICAL DETAILS ON SHEETS DO NOT
 CORRELATE WITH THE ELECTRICAL DONE BY THE ELECTRICAL
 CONTRACTOR. THIS SHOWS 3-POLE BREAKERS AND ELECTRICAL
 BY CONTRACTOR SHOWS 2-POLE BREAKERS.
 PLEASE SUBMIT COMPLETE ELECTRICAL PLANS SHOWING LAYOUT
 OF ALL EQUIPMENT. PLEASE INCLUDE ALL DETAILS.
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
 NEC 430, 620, 310.16, 240.4 ETC
  
 4) NOTE: PLEASE SEE SHEET WHICH CONTAINS THE ELECTRICAL
 EQUIPMENT LAYOUT DOES NOT CONTAIN ANY TITLE BLOCK ALONG
 WITH OTHER SHEETS WHICH ARE SIGNED, DATED AND SEALED BY
 THE ENGINEER.
 FAC 61G15-23.002
  
 5) NOTE: PLEASE VERIFY WITH THE STATE ANY POSSIBLE
 REQUIREMENTS FOR A/C TO BE PLACED IN THE EQUIPMENT
 ROOM. THIS HAS COME TO OUR ATTENTION THAT THIS IS BEING
 REQUIRED AT SEVERAL LOCATIONS.
 THIS IS NOTED FOR INFORMATION ONLY.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 COMPLETED ON PLANS FOR REVIEW, NOT ALL COMMENTS MAY BE
 PRESENT AT THIS TIME.
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-28 Cont ID  
Sent By mawillia Date 2007-12-28 Time 12:49 Rev Time 0.00
Received By mawillia Date 2007-12-28 Time 12:25 Sent To B1
Notes
2007-12-28 12:35:43*****PROVISO*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE BUILDING AND/OR PORTIONS OF THE BUILDING SHALL
 BE PERMITTED TO BE OCCUPIED DURING THE SCOPE OF WORK
 ONLY WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE
 RESISTIVE ASSEMBLIES ARE IN PLACE AND CONTINUOUSLY
 MAINTAINED.
  
 3.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.THE NEW ELEVATOR SHALL BE IN ACCORDANCE WITH ASME
 A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS.
  
 6.PROVIDE THE MININIMUM FIRE PROTECTION RATING FOR
 THE NEW ELEVATOR HOISTWAY.IN ADDITION, BUILDING
 ELEMENTS SHALL BE USED TO RESTRICT WATER EXPOSURE OF
 ELEVATOR EQUIPMENT.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-17 Cont ID  
Sent By mawillia Date 2007-10-17 Time 21:21 Rev Time 0.00
Received By mawillia Date 2007-10-17 Time 16:43 Sent To  
Notes
2007-10-19 00:56:46*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE BUILDING AND/OR PORTIONS OF THE BUILDING SHALL
 BE PERMITTED TO BE OCCUPIED DURING THE SCOPE OF WORK
 ONLY WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE
 RESISTIVE ASSEMBLIES ARE IN PLACE AND CONTINUOUSLY
 MAINTAINED.
  
 3.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.THE NEW ELEVATOR SHALL BE IN ACCORDANCE WITH ASME
 A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS.
  
 6.PROVIDE THE MININIMUM FIRE PROTECTION RATING FOR
 THE NEW ELEVATOR HOISTWAY.IN ADDITION, BUILDING
 ELEMENTS SHALL BE USED TO RESTRICT WATER EXPOSURE OF
 ELEVATOR EQUIPMENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-20 Cont ID  
Sent By mmiller Date 2007-12-20 Time 18:03 Rev Time 0.00
Received By mmiller Date 2007-12-20 Time 18:03 Sent To  
Notes
2007-12-20 18:03:48SENT TO BOB BOARD # 14 MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-18 Cont ID  
Sent By adarroug Date 2007-12-18 Time 11:23 Rev Time 0.00
Received By adarroug Date 2007-12-18 Time 11:23 Sent To  
Notes
2007-12-18 11:23:24WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-22 Cont ID  
Sent By lmartine Date 2007-10-22 Time 15:42 Rev Time 0.00
Received By lmartine Date 2007-10-05 Time 14:58 Sent To  
Notes
2007-10-15 11:01:50TO "BOB"#16
2007-10-05 15:00:17WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 1 Status N Date 2007-10-17 Cont ID  
Sent By choops Date 2007-10-17 Time 15:44 Rev Time 0.00
Received By choops Date 2007-10-17 Time 15:44 Sent To  
Notes
2007-10-17 15:44:21*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.