Plan Review Stops For Permit 07100133 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2008-01-15 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-01-15 |
Time |
07:30 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-01-15 |
Time |
07:01 |
Sent To |
PC |
|
Notes |
2008-01-15 07:30:23 | PROCESS PLANS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2008-01-14 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-01-14 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-01-14 |
Time |
09:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-10-13 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-10-13 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-10-13 |
Time |
14:36 |
Sent To |
|
|
Notes |
2007-10-13 16:06:44 | | | BUILDING PLAN REVIEW | | PERMIT: 07100133 | | ADD: 401 N. DIXIE HWY 5TH FL #5259 | | CONT: H.A. CONTRACTING CORP. | | TEL: (305)591-9212 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: 1ST | | ACTION: DENIED | | 10/13/07 | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 1B)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS | | & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO | | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR | | IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED | | AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION | | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE | | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS | | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND | | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. | | | | 2)2004 FBC EXISTING | | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | | 3)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | THAT IS REQUIRED FOR RECORD KEEPING A) THE EDITION OF | | THE CODE UNDER WHICH THE PROJECT IS DESIGNED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | PROVISIONS OF CHAPTER 3. | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | TABLE 601. | | D) THE OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | 4)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION; | | PROVIDE INFORMATION BASED ON INTERIOR FINISH | | REQUIREMENTS BASED ON OCCUPANCY. | | | | 5)INDICATE THE TYPE OF GLASS TO BE INSTALLED AT THE | | NEW WINDOW OPENING PER FBC 2406. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2008-01-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-01-11 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-01-11 |
Time |
12:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-10-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-10-14 |
Time |
10:16 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-10-14 |
Time |
09:56 |
Sent To |
|
|
Notes |
2007-10-14 10:16:49 | ** DENIED ** | | | | 1) NOTE: PLEASE SEE NO CODES AND SCOPE OF WORK IS SHOWN | | ON PLANS FOR DESIGN. | | FBC 106.1.2, 106.3.5.1.2, 110.1.2 | | | | NFPA-70 2005 | | NFPA-72 2002 | | NFPA-101 2003 | | FBC 2004 W/2006 REVS. | | | | ** THESE ARE REQUIRED AT A MINIMUM, SEE COMMENTS FROM | | OTHER TRADES FOR OTHER POSSIBLE CODES. | | | | 2) NOTE: NOTE ON PLANS MENTIONS THE EXISTING PANEL IS | | CAPABLE OF THE ADDITIONAL LOAD, HOWEVER NO INFORMATION | | FOR EXISTING LOAD WITH NEW LOAD OR SIZE OF THIS | | EXISTING PANEL WAS GIVEN. | | FBC 106.3.5.1.2, 16.1.2 | | NEC. 220 | | | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2008-01-14 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-01-14 |
Time |
13:47 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-01-14 |
Time |
13:32 |
Sent To |
|
|
Notes |
2008-01-14 13:42:54 | *****APPROVED***** | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | BEEN ADDRESSED AND/OR ACKNOWLEDGED;PLAN SHEET A-1 | | STAMPED, INITIALED, AND DATED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-10-18 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-10-18 |
Time |
19:25 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-10-18 |
Time |
18:37 |
Sent To |
|
|
Notes |
2007-10-18 19:25:34 | *****DENIED***** | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 2.DURING SCOPE OF WORK ALL REQUIRED EXIT COMPONENTS, | | FIRE RESISTIVE ASSEMBLIES, AND FIRE PROTECTION SYSTEMS | | SHALL BE MAINTAINED.SHALL BE MAINTAINED. | | | | 3.WHEN/IF IT IS NECESSARY TO SHUT DOWN THE SPRINKLER | | SYSTEM FOR THE RELOCATION OF DEVICE(S), THE FIRE | | DEPARTMENT WILL BE NOTIFIED WHEN IT IS SHUT DOWN AND | | WHEN IT IS RETURNED TO SERVICE. | | | | 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 5.SPECIFY THE NEW WALL INTERIOR FINISH MATERIAL IN | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-01-10 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2008-01-10 |
Time |
08:32 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2008-01-10 |
Time |
08:32 |
Sent To |
|
|
Notes |
2008-01-10 08:32:37 | TO "BOB" # 3 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-10-18 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-10-18 |
Time |
18:37 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-10-05 |
Time |
11:02 |
Sent To |
|
|
Notes |
2007-10-10 11:58:05 | TO "BOB"#11 | 2007-10-05 11:03:35 | WAITING FOR "BOB" |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2008-01-10 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-01-10 |
Time |
14:21 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2008-01-10 |
Time |
14:21 |
Sent To |
|
|
Notes |
2008-01-10 14:22:25 | RELOCATE 1 SUPPLY AIR GRILL. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-10-17 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-10-17 |
Time |
11:20 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2007-10-17 |
Time |
11:20 |
Sent To |
|
|
Notes |
2007-10-17 11:22:18 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) SEE ELECTRICAL REVIEW NOTE #1, PLEASE CORRECT. | | | | 1 MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2007-10-10 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-10-10 |
Time |
15:13 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-10-10 |
Time |
15:13 |
Sent To |
|
|
Notes |
2007-10-10 15:13:45 | *ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK | | DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. |
|
|