Plan Review Details - Permit 07100119
Plan Review Stops For Permit 07100119
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-12-27 Cont ID  
Sent By lursu Date 2007-12-27 Time 15:02 Rev Time 0.00
Received By lursu Date 2007-12-27 Time 15:02 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-10-19 Cont ID  
Sent By lursu Date 2007-10-19 Time 08:54 Rev Time 0.00
Received By lursu Date 2007-10-19 Time 08:54 Sent To  
Notes
2007-10-19 08:58:42IF THE STRUCTURE IS DIVIDED IN MULTIPLE UNITS ,THEN
 EACH UNIT MUST HAVE A UNIQUE NUMBER ASSIGNED TO IT.THE
 UNIT NUMBER WILL BE THE SITE ADDRESS FOR THAT UNIT.THE
 NUMBERING OF THE UNITS MUST START AT THE EAST PORTION
 OF THE STRUCTURE GOING HIGHER TO THE WEST.
 PLEASE CLARIFY IN WHICH UNIT THE JOB IS LOCATED?
 IF YOU HAVE ANY QUESTION PLEASE CONTACT ME.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-01-25 Cont ID  
Sent By mjacobs Date 2008-01-25 Time 10:48 Rev Time 0.00
Received By mjacobs Date 2008-01-25 Time 10:46 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-01-12 Cont ID  
Sent By mjacobs Date 2008-01-12 Time 06:57 Rev Time 0.00
Received By mjacobs Date 2008-01-12 Time 06:44 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-12-29 Cont ID  
Sent By mjacobs Date 2007-12-29 Time 08:45 Rev Time 0.00
Received By mjacobs Date 2007-12-29 Time 07:26 Sent To PC
Notes
2007-12-29 07:27:10NEW SHEETS SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-11 Cont ID  
Sent By mjacobs Date 2007-12-11 Time 10:32 Rev Time 0.00
Received By mjacobs Date 2007-12-11 Time 07:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-09 Cont ID  
Sent By mjacobs Date 2007-11-09 Time 16:22 Rev Time 0.00
Received By mjacobs Date 2007-11-09 Time 13:34 Sent To  
Notes
2007-11-30 16:22:34 
  
 BUILDING PLAN REVIEW
 PERMIT: 0710119
 ADD: 2223 PBL BLVD
 CONT: CARLO MERCURIO
 TEL: (561) 329-8167
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
 11/9/07
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) **OK**
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) **OK**
  
 2)**OK**
  
 3)**OK**
 . -------------------------------------
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
  
 4)THE PROPOSED LAYOUT PLAN ON SHEET A-2 SHALL
 INDICATE THE DIMENSION OF EACH WALL AND ROOM. EACH WALL
 SHALL BE LABELED TO INDICATE THE CONSTRUCTION TYPE.
 SHOW HOW THE WALLS WHICH ARE NOT ATTACHED TO THE DECK
 ABOVE WILL BE BRACED. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED. THE FLOOR AND SUITE
 NUMBER SHALL APPEAR ON THE APPLICATION AND ON EACH
 SHEET OF THE PLANS. FBC106.1.1**THE NEW HAND WRITTEN
 INFORMATION ON THE DRAWINGS IS NOT ALLOWED. DUE TO THE
 FACT, THAT OTHER CHANGES MAY BE MADE WITHOUT THE
 APPROVAL OF THE DESIGNER OF RECORD THIS PRACTICE IN NOT
 ACCEPTABLE PER 106.1.3 THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THE
 DRAWINGS ALSO CONTAIN ILLEGIBLE INFORMATION, SEE ALL
 SHEETS.
  
 5)106.3.3* PRODUCT APPROVALS- 2004. THOSE PRODUCTS
 THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. SUBMIT THE PRODUCT APPROVAL
 FOR THE NEW DOOR, INDICATE WHICH DOOR SYSTEM WILL BE
 USED FROM THE PRODUCT APPROVAL PACKAGE BY CIRCLING THE
 INFORMATION. **THE PRODUCT APPROVAL FOR THE PRE-CAST
 LENTIL IS MISSING FROM THE PACKAGE. FBC 2107.2.3 THE
 MINIMUM LENGTH OF LAP SPLICES FOR REINFORCING BARS IN
 TENSION OR COMPRESSION SHALL NOT BE LESS THAN 40 BAR
 DIAMETERS SEE DOOR OPENING DETAIL SHEET A-3**
  
 **THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND NEANS COST ANALYSIS SERVICES
 PER 108.3 FBC**
  
 **AN EXISTING BUILDING BEING DEMOLISH OR RENOVATED
 SHALL HAVE AN ASBESTOS NOTIFICATION STATEMENT POSTED AT
 THE SITE WHICH INDICATE THE OWNER?S OR OPERATOR?S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES AND NOTIFY THE DEPARTMENT OF
 ENVIROMENTAL PROTECTION OF HIS OR HER INTENTIONS TO
 REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH
 STATE AND FEDERAL LAW. FBC 105.9**
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-17 Cont ID  
Sent By mjacobs Date 2007-10-17 Time 18:31 Rev Time 0.00
Received By mjacobs Date 2007-10-17 Time 16:15 Sent To  
Notes
2007-10-17 18:31:50 
 BUILDING PLAN REVIEW
 PERMIT: 0710119
 ADD: 2223 PBL BLVD
 CONT: CARLO MERCURIO
 TEL: (561) 329-8167
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3. OK
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601. OK
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED. OK
 . -------------------------------------
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
  
 4)THE PROPOSED LAYOUT PLAN ON SHEET A-2 SHALL
 INDICATE THE DIMENSION OF EACH WALL AND ROOM. EACH WALL
 SHALL BE LABELED TO INDICATE THE CONSTRUCTION TYPE.
 SHOW HOW THE WALLS WHICH ARE NOT ATTACHED TO THE DECK
 ABOVE WILL BE BRACED. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED. THE FLOOR AND SUITE
 NUMBER SHALL APPEAR ON THE APPLICATION AND ON EACH
 SHEET OF THE PLANS. FBC106.1.1
  
 5)106.3.3* PRODUCT APPROVALS- 2004. THOSE PRODUCTS
 THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. SUBMIT THE PRODUCT APPROVAL
 FOR THE NEW DOOR, INDICATE WHICH DOOR SYSTEM WILL BE
 USED FROM THE PRODUCT APPROVAL PACKAGE BY CIRCLING THE
 INFORMATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-01-10 Cont ID  
Sent By dpalmer Date 2008-01-10 Time 08:17 Rev Time 0.00
Received By dpalmer Date 2008-01-09 Time 17:04 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-12-28 Cont ID  
Sent By dpalmer Date 2007-12-28 Time 11:10 Rev Time 0.00
Received By dpalmer Date 2007-12-28 Time 11:10 Sent To B
Notes
2007-12-28 11:11:15NOTE ADDED, PLANS ROUTED TO ZONING AS SETS HAVE NEW
 SHEETS A-1 AND A-3, NEEDS NEW STAMPS.
2007-12-28 11:10:18 
 *** PROVISO/REVISION ***
  
 ** PLEASE SEE THE FOLLOWING ITEMS WHICH ARE TO BE
 REVISED BEFORE ANY ROUGH ELECTRICAL INSPECTION.
  
 1) NOTE: PLEASE SEE THE MAXIMUM TIME ON OVER RIDE
 OCCUPANCY SENSOR IS 30MINS. SHOWN AS MINIMUM TIME.
 13-415.1.ABC.1.1, .1.2
  
 2) NOTE: PLEASE REVISE PANEL SCHEDULE ON M/E SHEET
 SHOWING THE CORRECTED MAIN CIRCUIT BREAKER, PANEL SIZE
 AND BRANCH CIRCUITS.
 THE CONDUCTORS NOW SHOWN ON PANEL SCHEDULE FOR RTU IS
 NOT THE SAME AS RISER. RISER SHOWS #4 AND PANEL
 SCHEDULE NOW SHOWS #2.
 240.4, 310.16, 408.4
  
 3) NOTE: PLEASE SEE BATH ROOMS WHICH STILL SHOW ONLY
 STANDARD SWITCHES. PLEASE KNOW IF THESE ARE NEW MUST
 MEET 13-415.1ABC.1.2.
  
 4) NOTE: 200AMP MAIN CIRCUIT BREAKER ON NEW PANEL.
 240.4, 310.16, 240.21, 408.36 ETC
 THIS WAS CHANGED BY ENGINEER HOWEVER SHEETS NEED TO BE
 RE-PRINTED.
  
  
 IF THERE ARE ANY QUESTIONS ON THE ABOVE PLEASE DO NOT
 HESITATE IN CONTACTING THIS REVIEWER DIRECTLY.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-12-06 Cont ID  
Sent By dpalmer Date 2007-12-06 Time 10:05 Rev Time 0.00
Received By dpalmer Date 2007-12-05 Time 16:58 Sent To  
Notes
2007-12-06 10:05:53** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM TWO PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS DUE
 TO CHANGES MADE TO PLANS.
  
 1) NOTE: PLEASE SEE THE RESPONSE LETTER PROVIDED BY THE
 DESIGN PROFESSIONAL ONLY RESPONDS PART OF THE NOTES
 FROM THE 2ND REVIEW. THE NOTE #1 FROM PREVIOUS REVIEW
 #2 SPECIFICALLY MENTIONED THAT ALL NOTES FROM FIRST
 REVIEW REMAINED WITH THE EXCEPTION OF NOTE #2. PLEASE
 KNOW A RESPONSE LETTER IS NOT REQUIRED ALTHOUGH IS
 HELPFUL IN THE REVIEW PROCESS IF COMPLETE.
  
 2) NOTE: PLEASE SEE NOTE #1 FROM ORIGINAL REVIEW WHICH
 STILL NEEDS ADDRESSING.
 PLEASE LIST ALL RELEVANT CODES ON PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (WHERE APPLICABLE) AS FIRE ALARM SYSTEM
 HAS NOT BEEN DETERMINED, THIS CODE WILL REMAIN.
  
 2) NOTE: PLEASE SEE PANEL SCHEDULE STILL LIST #8 FOR
 90AMP OVER CURRENT PROTECTION FOR THE RTU. THIS EXCEEDS
 310.16 FOR RATING OF CONDUCTORS.
 PLEASE ALSO SEE THE PANEL LIST THIS AS A 2-POLE WHERE
 SPACES IN PANEL AND CONDUCTORS LEND TO THIS A 3-PHASE?
 240.4, 310.16 ETC
 FBC 106.1.2 FOR COORDINATION.
  
 3) NOTE: PLEASE SEE THE RISER IS MISSING EQUIPMENT
 GROUNDING CONDUCTORS AFTER ALL FIRST MEANS OF
 DISCONNECTS.
 250.110, 250.24, 250.122
  
 4) NOTE: PLEASE SEE NOTES UNDER PERMIT APPLICATION FOR
 OTHER SCOPE OF WORK AT THIS SAME LOCATION AS THE
 SERVICE RISER AS SHOWN CONTAINS SEVERAL NON-CODE
 COMPLIANT ITEMS.
 PLEASE GO OVER THE NEC 2005 AS THE SERVICE WILL BE
 REQUIRED TO MEET THE CURRENT CODE.
 THERE ARE ITEMS ON RISER UNDER THIS REVIEW AND THE
 REVIEW OF THE OTHER APPLIED PERMIT FOR THIS LOCATION
 WHICH NEVER MET THE MINIMUM CODE AS SHOWN.
 PLEASE GIVE MORE DETAILS FOR COMPLETE RISER SHOWING NEW
 AND EXISTING AND ADJUST FOR CODE COMPLIANCE. PLEASE SEE
 SOME EXAMPLES ARE NOTED BELOW:
 PLEASE SEE MISSING EQUIPMENT GROUNDS AS NOTED ABOVE.
 PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR IS NOT
 LARGE ENOUGH PER 250.66.
 PLEASE SEE 40AMP DISCONNECT STILL SHOWN WITH 5-#8
 CONDUCTORS TO A 2-POLE 40AMPS DISCONNECT IN A 3/4 INCH
 CONDUIT.
 PLEASE SEE NO MAIN FOR TAPPED CONDUCTORS FOR NEW PANEL
 PER 240.21, 310.16, 240.4, 408.36 ETC
 PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS (THIS WILL BE NOTED BELOW FOR SPACE). PLEASE SEE
 NO PANEL SCHEDULE WAS SUBMITTED FOR HPB, YET THIS PANEL
 IS IN THE NEW TENANT SPACE BEING CREATED. 408.4, 240.4,
 310.16 ETC.
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 5) NOTE: PLEASE SEE FBC 13-101.1, 13-415.1.ABC.1.1,
 .1.2AS NO LIGHTING CONTROLS OR SYSTEM WAS SUBMITTED
 FOR REVIEW. LIGHTING IS NOTED AS *ALL EXISTING* WITH
 NEW CIRCUITS YET NO LIGHTING CONTROLS WERE SUBMITTED.
  
 6) NOTE: PLEASE SEE CIRCUITING PER 700.12F FOR
 EMERGENCY AND EXIT LIGHTS SHALL BE CIRCUITED TO THE
 LOCAL BRANCH CIRCUIT FEEDING LOCAL LIGHTING.
  
 7) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER
 210.62, 220.43
 THE NEW SIGN CIRCUIT WHICH IS PART OF 600.5 IS NOT THE
 SAME.
  
 8) NOTE: PLEASE SEE TWO SETS OF ENERGY CALCULATIONS
 WERE SUBMITTED SHOWING A METHOD *A* AND METHOD *B*.
 PLEASE SEE THAT METHOD *A* CAN NOT BE USED AS THIS IS
 NOT A *WHOLE BUILDING*.
 PLEASE SEE 13-415.2 AS THIS IS ALREADY A CONDITIONED
 SPACE AND RE-FEEDING THE EXISTING UNIT.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO NOT
 CONTAIN ANY INPUT DATA REPORTS AS REQUIRED. PLEASE SEE
 PAGE #2 WHICH SPECIFICALLY MENTIONS THAT THE
 CALCULATION SUMMARY SHEETS MUST BE ACCOMPANIED BY THE
 INPUT DATA REPORT.
 PLEASE SEE THE JURISTICTION IS LISTED AS PALM BEACH
 COUNTY.
 WE ARE UNABLE TO REVIEW FOR CODE COMPLIANCE AT THIS
 TIME.
 PLEASE BE SURE TO COMPLETE FIXTURE LEGEND FOR
 FIXTURES.
  
 9) NOTE: PLEASE PROVIDE NEW ROOF-TOP GFI PER 210.63,
 210.8.
 AS THIS IS A NEW TENANT, ANY EXISTING DEVICES WOULD
 NOT BE FED FROM OTHER POWER SOURCE LOCATIONS.
  
 10) NOTE: PLEASE VERIFY PANEL AS SHOWN AS 200AMPS IS
 200AMPS. THIS IS MOST LIKELY A 225AMP AND WILL CONTAIN
 A 200AMP MCB.
 PANEL MENTIONS *FUSED AT DISCONNECT* HOWEVER AS NO
 DISCONNECT IS SHOWN ON RISER THIS IS NOT POSSIBLE.
 PLEASE VERIFY AND ADJUST AS NOTED ABOVE FOR TAPPED
 CONDUCTORS.
 240.21, 310.16, 90.7, 110.3 ETC
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 11) NOTE: PLEASE SEE NO RESPONSE WAS PROVIDED ON
 WHETHER OR NOT THE BUILDING CONTAINS A FIRE ALARM
 SYSTEM?
 PLEASE SEE THE MECHANICAL PLANS INDICATE A NEW HORN
 STROBE FOR UNIT AND AS THIS IS NOT SHOWN ON ELECTRICAL
 IT IS BEING *ASSUMED* THIS IS LOCATED IN SPACE. PLEASE
 KNOW IF ANY FA SYSTEM IS LOCATED OR WILL BE MODIFIED,
 ALL DEVICES SHALL COMPLY WITH FBC 11-4.28.1,.2 AND
 .3(4).
  
 12) NOTE: PLEASE SEE WALL WHICH CONTAINS RECEPTACLES
 WHICH MENTIONS TO PROVIDE EXTENSIONS, HOWEVER NO
 CIRCUITING ON HOW THESE ARE FED IS SHOWN.
 PLEASE ALSO COORDINATE SHEET M-1, E-2 AS THE ELECTRICAL
 SHEETS E-1 ONLY CONTAINS TWO ELECTRICAL PANELS AND E-2
 CONTAINS 3.
 FBC 106.1.2, ADDITIONAL INFORMATION/COORDINATION.
  
 13) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 ** PLEASE KNOW THAT A FIELD INSPECTION MAY BE NEEDED TO
 GO OVER EXISTING WORK AND PROPOSED NEW.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-07 Cont ID  
Sent By dpalmer Date 2007-11-07 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2007-11-07 Time 15:42 Sent To  
Notes
2007-11-07 16:09:07** DENIED 2ND REVIEW **
  
  
 1) NOTE: PLEASE SEE NUMEROUS ITEMS ON THE ELECTRICAL
 SERVICE RISER ARE NOT CODE COMPLIANT. EVEN IF SERVICE
 EXISTS THERE ARE ITEMS ON RISER WHICH CAN NOT BE
 POSSIBLE AND HAVE NEVER MET CODE.
 PLEASE SEE COMMENTS FROM PREVIOUS REVIEW AND SUBMIT
 COMPLETE PLANS FOR REVIEW. PLEASE SEE ALL NOTES WITH
 THE EXCEPTION OF NOTE #2.
 ** PLEASE SEE NOTES UNDER 07100482
  
 2) NOTE: PLEASE SEE FBC 13-101.1.3 AS PREVIOUS COMMENTS
 WITH NEW BEING INSTALLED AND THE AMOUNT OF WORK BEING
 DONE AS A WHOLE IS AFFECTED BY SCOPE AS SHOWN.
 PLEASE ALSO SEE 13-101.1.
  
 3) NOTE: PLEASE SUBMIT REVISED PLANS WITH ALL REQUIRED
 CHANGES COPIED OR RE-PRINTED. HAVING HAND-DRAWN CHANGES
 MADE TO PLANS MAY ALLOW OTHER ITEMS TO BE CHANGED.
  
  
 IF THERE ARE QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-14 Cont ID  
Sent By dpalmer Date 2007-10-14 Time 11:56 Rev Time 0.00
Received By dpalmer Date 2007-10-14 Time 11:15 Sent To  
Notes
2007-10-14 11:57:01** DENIED **
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
  
 2) NOTE: PLEASE SEE MISSING PRINTED LICENSE NUMBER FOR
 DESIGN PROFESSIONAL AS REQUIRED PER FAC 61G15-23.002.
  
 3) NOTE: PLEASE SUBMIT A CODE COMPLIANT RISER FOR
 EXISTING AND NEW. PLEASE SEE THERE ARE SEVERAL ITEMS
 WHICH ARE NOT CORRECT.
 FOR EXAMPLE: CONDUCTOR SIZES ON FEEDERS WHICH ARE SHOWN
 AS 5/0'S AT SEVERAL LOCATIONS WHICH IS NOT POSSIBLE AS
 THERE ARE NO 5/0 CONDUCTORS BASED ON AWG (AMERICAN WIRE
 GAUGE). PLEASE SEE 240.4 AND 310.16 AND ADJUST ALL NEW
 AND EXISTING CONDUCTORS ON RISER FOR CODE COMPLIANCE.
 PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS.
 PLEASE LABEL AND CORRELATE PANELS AND EQUIPMENT ON
 RISER. (HPE, MAIN ETC)
 PLEASE COMPLETE RISER FOR EXISTING AND NEW.215.5, 230,
 240.4, 310.16 ETC
  
 4) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR NEW.
 FBC 106.1.2, 106.3.5.1.2
 NEC 408.4 AS CIRCUITS NEED TO BE SPECIFIC TO ROOMS AND
 AREAS IN WHICH THEY FEED.
 PLEASE SEE 700.12F AS NOTED ABOVE FOR EM/EXT LTS.
  
 5) NOTE: PLEASE SEE 210.62 AND 220.43 FOR MISSING STORE
 FRONT WINDOW RECEPTACLES REQUIRED WHICH ARE NOT SHOWN
 AT THIS TIME.
  
 6) NOTE: PLEASE SEE 600.5 FOR SIGN CIRCUIT. IS THE ONE
 SHOWN ON EXISTING PANEL *MAIN* THE SAME AS HPE? PLEASE
 CORRELATE.
  
 7) NOTE: PLEASE SEE PANEL MAIN, INDICATES A 90AMP
 BREAKER ON #8AWG WHICH IS NOT SUFFICIENT.
 PLEASE COORDINATE AND COMPLETE.
  
 8) NOTE: PLEASE KNOW ONCE THE ADDRESSING REVIEW IS
 COMPLETED, A NEW SUITE/UNIT WILL BE GIVEN AND THIS
 NEEDS TO BE STATED ON PLANS.
 THE SCOPE WORK ON TITLE BLOCK MENTIONS NEW RETAIL
 STORE, YET PLANS CALL FOR SPACE TO BE PART OF FUTURE
 BUILD OUT?
 PLEASE CLARIFY IF THIS IS TWO NEW SPACES BEING CREATED
 FROM THE EXISTING STORE.
 FBC 106.1.2, 110.1.2.
 FAC 61G15-23.002
  
 9) NOTE: PLEASE CLARIFY IF THIS EXISTING BUILDING/SPACE
 HAS A FIRE ALARM SYSTEM. IF YES, PLEASE INDICATE THE
 LOCATIONS AND DEVICE LEVELS FOR ADA COMPLIANCE PER FBC
 11-4.28.1,.2 AND .3(4).
 **(EVEN AS FA WOULD BE UNDER SEPARATE PERMITS)
 ** (THIS IS ONLY NOTED AND THIS REVIEWER IS NOT STATING
 THAT A FA SYSTEM IS REQUIRED. (ONLY REVIEWING FOR ADA
 COMPLIANCE IF SYSTEM EXISTS OR WILL BE REQUIRED PER
 BUILDING REVIEWER OR FIRE MARSHAL)
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-12-19 Cont ID  
Sent By mwennerg Date 2007-12-19 Time 15:20 Rev Time 0.00
Received By mwennerg Date 2007-12-19 Time 15:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-11-13 Cont ID  
Sent By mwennerg Date 2007-11-13 Time 11:21 Rev Time 0.00
Received By mwennerg Date 2007-11-13 Time 11:21 Sent To  
Notes
2007-11-13 11:23:48***DENIED***
  
 SOME COMMENTS ADDRESSED BUT HAND WRITTEN INFORMATION IS
 NOT ALLOWED.
  
 1) PLEASE SEE ADDRESSING COMMENT. IF SEPARATE UNIT
 NUMBERS ARE BEING USED, SHOW ON PLANS WHERE CHARACTERS
 ARE TO BE A MINIMUM OF 3" IN HEIGHT AND CONTRASTING TO
 BACKGROUND. THE MAIN ADDRESS FOR THE BUILDING SHALL BE
 A MINIMUM OF 6" IN HEIGHT.
  
 2) CLEARLY IDENTIFY EXIT SIGNS AND EMERGENCY LIGHTING
 FACILITIES.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 4) OK
  
 5) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 6) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-23 Cont ID  
Sent By mwennerg Date 2007-10-23 Time 13:30 Rev Time 0.00
Received By mwennerg Date 2007-10-23 Time 13:30 Sent To  
Notes
2007-10-23 13:41:11***DENIED***
  
 1) PLEASE SEE ADDRESSING COMMENT. IF SEPARATE UNIT
 NUMBERS ARE BEING USED, SHOW ON PLANS WHERE CHARACTERS
 ARE TO BE A MINIMUM OF 3" IN HEIGHT AND CONTRASTING TO
 BACKGROUND. THE MAIN ADDRESS FOR THE BUILDING SHALL BE
 A MINIMUM OF 6" IN HEIGHT.
  
 2) CLEARLY IDENTIFY EXIT SIGNS AND EMERGENCY LIGHTING
 FACILITIES.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 4) IF BUILDING HAS A FIRE ALARM SYSTEM, DUCT SMOKE
 DETECTORS SHALL BE WIRED TO SYSTEM, AND INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
 5) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 6) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-01-23 Cont ID  
Sent By adarroug Date 2008-01-23 Time 09:52 Rev Time 0.00
Received By adarroug Date 2008-01-23 Time 09:52 Sent To B
Notes
2008-01-23 09:52:15TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-01-10 Cont ID  
Sent By mmiller Date 2008-01-10 Time 16:49 Rev Time 0.00
Received By mmiller Date 2008-01-10 Time 16:49 Sent To B
Notes
2008-01-10 16:49:15SENT TO MYRON JACOB'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-08 Cont ID  
Sent By shill Date 2008-01-08 Time 14:38 Rev Time 0.00
Received By shill Date 2008-01-08 Time 14:38 Sent To M
Notes
2008-01-08 14:50:41TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-26 Cont ID  
Sent By spalmer Date 2007-12-26 Time 15:02 Rev Time 0.00
Received By spalmer Date 2007-12-26 Time 15:02 Sent To E
Notes
2007-12-26 15:02:55TO DEWEY PALMERS DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 16:29 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 16:29 Sent To  
Notes
2007-12-03 14:24:03TO "COMM" BD#17
2007-11-28 16:29:56WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-02 Cont ID  
Sent By adarroug Date 2007-11-02 Time 09:46 Rev Time 0.00
Received By adarroug Date 2007-11-02 Time 09:46 Sent To  
Notes
2007-11-07 10:51:26TO "BOB"#3
2007-11-02 09:46:24WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-25 Cont ID  
Sent By jleech Date 2007-10-25 Time 09:15 Rev Time 0.00
Received By jleech Date 2007-10-04 Time 14:00 Sent To  
Notes
2007-10-10 11:39:39TO "BOB"#8
2007-10-04 14:26:02WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-01-09 Cont ID  
Sent By tgordon Date 2008-01-09 Time 12:04 Rev Time 0.25
Received By tgordon Date 2008-01-09 Time 12:04 Sent To  
Notes
2008-01-09 12:04:55MECHANICAL RE-STAMP.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-05 Cont ID  
Sent By tgordon Date 2007-12-05 Time 11:05 Rev Time 0.25
Received By tgordon Date 2007-12-05 Time 11:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-09 Cont ID  
Sent By tgordon Date 2007-11-09 Time 08:46 Rev Time 0.30
Received By tgordon Date 2007-11-09 Time 08:45 Sent To  
Notes
2007-11-09 08:48:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE PLAN PAGE M-1, YELLOW HIGH LIGHTS SHOW PRINT
 THAT IS NOT LEGIBLE. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY, SEE F.B.C. 106.1.1.
  
 2) PLAN IS SIGNED AND DATED AT THE SEAL 9-21-07, REVIEW
 WAS DONE ON 10-17-07 CORRECTIONS COULD NOT HAVE BEEN
 DONE BEFORE THE REVIEW. THE DATE AT THE SEAL IS TO SHOW
 THE DATE THE PLAN IS SIGNED AND SEALED NOT THE DATE THE
 PLAN WAS DRAWN, SEE FAC 61G15-23.002.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-17 Cont ID  
Sent By tgordon Date 2007-10-17 Time 13:35 Rev Time 0.45
Received By tgordon Date 2007-10-17 Time 13:35 Sent To  
Notes
2007-10-17 14:08:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SHOW OUTDOOR AIR CALCULATIONS ON MECHANICAL
 PLAN, SEE 2004 FBC/M 403.2.
  
 2) PLEASE SHOW HOW BATHROOM EXHAUST FANS WILL COMPLY
 WITH 2004 FBC/M 403.2.1 (3)
 *** 2004 FBC/M 403.2.1 (3) WHERE MECHANICAL EXHAUST IS
 REQUIRED BY TABLE 403.3 , RECIRCULATION OF AIR FROM
 SUCH SPACES SHALL BE PROHIBITED. ALL AIR SUPPLIED TO
 SUCH SPACES SHALL BE EXHAUSTED, INCLUDING ANY AIR IN
 EXCESS OF THAT REQUIRED BY TABLE 403.3 .
 (EXAMPLE) FAN MAY RUN CONTINUOUSLY, FAN MAY BE
 CONTROLLED BY A SWITCH AND PARALLEL WITH AIR HANDLER
 UNIT SO THE FAN TURNS ON WHEN EVER SOMEONE IS IN THE
 BATHROOM OR WHEN EVER THE AIR HANDLER TURNS ON, OR THE
 SUPPLY AIR DUCT MAY BE REMOVED FROM THE BATHROOM AND A
 TRANSFER DUCT BE INSTALLED.
  
 3) PLEASE SHOW HOW THE DUCT SMOKE DETECTOR WILL COMPLY
 WITH 2004 FBC/M 606.4.1 OR THE EXCEPTIONS.
 *** 2004 FBC/M 606.4.1SUPERVISION.
 THE DUCT SMOKE DETECTORS SHALL BE CONNECTED TO A FIRE
 ALARM SYSTEM. THE ACTUATION OF A DUCT SMOKE DETECTOR
 SHALL ACTIVATE A VISIBLE AND AUDIBLE SUPERVISORY SIGNAL
 AT A CONSTANTLY ATTENDED LOCATION.
 EXCEPTIONS:
 1. THE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION IS NOT REQUIRED WHERE THE DUCT SMOKE DETECTOR
 ACTIVATES THE BUILDING = S ALARM-INDICATING APPLIANCES.
  
 2. IN OCCUPANCIES NOT REQUIRED TO BE EQUIPPED WITH
 A FIRE ALARM SYSTEM, ACTUATION OF A SMOKE DETECTOR
 SHALL ACTIVATE A VISIBLE AND AN AUDIBLE SIGNAL IN AN
 APPROVED LOCATION. DUCT SMOKE DETECTOR TROUBLE
 CONDITIONS SHALL ACTIVATE A VISIBLE OR AUDIBLE SIGNAL
 IN AN APPROVED LOCATION AND SHALL BE IDENTIFIED AS AIR
 DUCT DETECTOR TROUBLE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-12-15 Cont ID  
Sent By jleech Date 2007-12-15 Time 12:39 Rev Time 0.00
Received By jleech Date 2007-12-15 Time 12:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-17 Cont ID  
Sent By jleech Date 2007-11-17 Time 11:50 Rev Time 0.00
Received By jleech Date 2007-11-17 Time 11:49 Sent To  
Notes
2007-11-17 12:30:00DENIED;
 1. PLANS ARE REQUIRED TO BE OF SUFFICIENT CLARITY WITH
 NO HAND WRITEN COMMENTS. SEE FBC CHAPTER
 1ADMINISTRATION AMENDMENTS, SECTION 106.1.1.
 2. ONE TOILET ROOM IS ONLY 4'- 10" NOT WIDE ENOUGH FOR
 A 5' TURNING RADIUS. REQUIRED BY FBC BUILDING CHAPTER
 11.
 3.THE SANITARY RISER DIAGRAM DOES NOT MATCH THE FLOOR
 PLAN. (SECOND REQUEST). SANITARYRISER DIAGRAM SHOWS
 ONLY 1 W/C AND 1 LAV. A FLOOR DRAIN IS SHOWN ON THE
 RISER DIAGRAM BUT NOT ON THE FLOOR PLANS, AND BREAK
 SINK REQUIRES A VENT. NOT SHOWN.
 4. WATER RISER DIAGRAM; MAIN SHUTOFF VALVE REQUIRED,
 NOT SHOWN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-25 Cont ID  
Sent By jleech Date 2007-10-25 Time 08:50 Rev Time 0.00
Received By jleech Date 2007-10-25 Time 08:50 Sent To  
Notes
2007-10-25 09:15:11DENIED;
 1. SANITARY RISER DIAGRAM DOES NOT MATCH FLOOR PLAN.
 2.WATER RISER DIAGRAM REQUIRED PER FBC BUILDING CHAPTER
 1 SECTION 106.3.5.1.3(3)
 3. SHOW 5' TURNING RADIUS ON PLANS ( IN BATHROOMS) AND
 L & W MESSUREMENTS.
 4. BREAK SINK IS ONLY SHOWN ON PLUMBING PAGE. IF BREAK
 SINK IS TO BE INSTALLED IT MUST MEET ADA REQUIREMENTS
 OF CHAPTER 11 OF THE BUILDING CODE. SEE SECTIONS
 11-4.24.1 THRU 11-4.24.7. SHOW DETAIL WITH ALL REQUIRED
 MEASUREMENTS ON PLANS.
 5. A CUP DISPENSER SHOULD BE INSTALLED WITH THE
 HANDICAP DRINKING FOUNTAIN FOR PEOPLE WITH BAD BACKS.
 SEE SECTION 11-4.1.3(10).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2007-12-07 Cont ID  
Sent By adavila Date 2007-12-07 Time 14:15 Rev Time 0.00
Received By adavila Date 2007-12-07 Time 08:53 Sent To  
Notes
2007-12-07 08:54:09PLANNING AND ZONING DEPARTMENT
  
 NOTE:
  
 PURSUANT TO SECTION 94-441(C)(2), RENOVATIONS, REPAIR,
 ALTERATION OR REDEVELOPMENT EXCEEDING 50 PERCENT OF THE
 VALUE OF THE STRUCTURE SHALL COMPLY WITH THE LANDSCAPE
 REQUIREMENTS OF ARTICLE XIV OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 THE VALUE OF THIS PERMIT IS $12,650 ACCORDING TO THE
 PERMIT APPLICATION.THIS VALUE SHALL BE COUNTED
 TOWARDS THE TOTAL VALUE OF ALL WORK TO BE DONE ON THIS
 BUILDING WITHIN 12 MONTHS FROM OCTOBER 4, 2007
 (SUBMITTAL OF INTERIOR RENOVATION 1ST PERMIT).
  
 BASED ON PAPA, THE VALUE OF THIS BUILDING IS
 $1,164,527.IF TOTAL PERMIT WITHIN A ONE YEAR PERIOD
 EXCEEDS $582,263.50, THEN COMPLIANCE WITH ARTICLE XIV
 IS REQUIRED.
  
 IF THE VALUE OF THIS PERMIT INCREASES, THAN THE NEW
 VALUE SHALL BE COUNTED TOWARDS THE TOTAL WORK VALUE FOR
 THIS BUILDING.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-11-08 Cont ID  
Sent By adavila Date 2007-11-08 Time 17:28 Rev Time 0.00
Received By adavila Date 2007-11-08 Time 17:28 Sent To  
Notes
2007-11-08 17:28:31PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PROVIDE A COPY OF A CURRENT SURVEY.SURVEY SHALL BE
 ABSTRACTED TO SHOW ALL RIGHTS-OF-WAY AND EASEMENTS.
  
 3. IT HAS BEEN BROUGHT TO THE ATTENTION OF STAFF THAT A
 NUMBER OF IMPROVEMENTS AND ALTERATIONS WILL BE DONE TO
 THE SITE UNDER DIFFERENT PERMITS.PROVIDE THE TOTAL
 AMOUNT OF WORK VALUE.
  
 A. PLEASE NOTE THAT PER SECTION 94-441(C)(2) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS, RENOVATIONS,
 REPAIRS, ALTERATIONS OR REDEVELOPMENT EXCEEDING 50
 PERCENT OF THE VALUE OF THE STRUCTURE SHALL BE BROUGHT
 INTO CONFORMANCE WITH THE LANDSCAPE REGULATIONS OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS.
 B. PROVIDE THE VALUE OF THE STRUCTURE.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status N Date 2007-10-10 Cont ID  
Sent By choops Date 2007-10-10 Time 15:14 Rev Time 0.00
Received By choops Date 2007-10-10 Time 15:14 Sent To  
Notes
2007-10-10 15:15:02*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.