Plan Review Details - Permit 07100077
Plan Review Stops For Permit 07100077
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-27 Cont ID  
Sent By shill Date 2007-12-27 Time 18:31 Rev Time 0.00
Received By shill Date 2007-12-27 Time 18:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By shill Date 2007-10-29 Time 10:55 Rev Time 0.00
Received By shill Date 2007-10-29 Time 10:55 Sent To  
Notes
2007-10-29 10:57:17****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1..)PROVIDE A DETAIL FOR THE SLAB INCLUDING ALL
 DIMENSIONS AND STRUCTURAL INFORMATION.USE OF A PREFAB
 SLAB REQUIRES CALCULATIONS PREPARED BY AN ENGINEER. FBC
 R 301.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-07 Cont ID  
Sent By btrobaug Date 2008-01-07 Time 14:13 Rev Time 0.00
Received By btrobaug Date 2008-01-07 Time 10:55 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-10 Cont ID  
Sent By btrobaug Date 2007-12-10 Time 16:03 Rev Time 0.00
Received By btrobaug Date 2007-12-10 Time 15:56 Sent To G
Notes
2007-12-10 16:00:25 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 REPEAT COMMENT
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK'S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-24 Cont ID  
Sent By btrobaug Date 2007-10-24 Time 11:34 Rev Time 0.00
Received By btrobaug Date 2007-10-24 Time 10:51 Sent To M
Notes
2007-10-24 11:34:46 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A) A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 B) ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND
 PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.
  
 3} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH
  
 4} AN EQUIPMENT GROUNDING CONDUCTOR PER 250.122 IS
 REQUIRED FROM THE TRANSFER SWITCH TO THE GENERATOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-12-13 Cont ID  
Sent By mperson Date 2007-12-13 Time 11:56 Rev Time 0.00
Received By mperson Date 2007-12-13 Time 11:56 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-10-26 Cont ID  
Sent By mperson Date 2007-10-26 Time 08:13 Rev Time 0.00
Received By mperson Date 2007-10-26 Time 08:13 Sent To B
Notes
2007-10-26 08:53:29DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
 **CONTRACTOR INFORMATION: THE SUBMITTED GAS PERMIT
 REFERENCED MASTER PERMIT #06060974, THAT PERMIT NUMBER
 IS EXPIRED. THE CORRECT MASTER PERMITNUMBER IS
 #07100077. PLEASE NOTE THE RED LINE CORRECTIONS ON THE
 PERMIT APPLICATION.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NOTE: THE SUBMITTED ISOMETRIC DRAWING MUST INDICATE
 THE CORRESPONDING LENGTHS OF THE CUT SECTIONS OF PIPE
 TO VERIFY THE GIVEN DEVELOPED LENGTH OF 20' ON THE
 RESUBMITTAL.
  
 2. PLEASE CORRELATE THE GENERATOR SIZE AND BTU LOAD ON
 THE RESUBMITTED DRAWINGS WITH THE MASTER GEN/RES PERMIT
 #07100077. THE MASTER GEN/RES PERMIT INDICATES A 35 KW,
 560,000 BTU GENERATOR. THE SUBMITTED GAS ISOMETRIC IS
 INDICATING A 40 KW, 650,000 BTU GENERATOR. PER *106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PER FBC-2004 FUEL GAS SECTION 409.5 EQUIPMENT
 SHUTOFF VALVE: EACH APPLIANCE SHALL BE PROVIDED WITH A
 SHUTOFF VALVE SEPERATE FROM THE APPLIANCE. THE SHUTOFF
 VALVE SHALL BE LOCATED IN THE SAME ROOM AS THE
 APPLIANCE, NOT FURTHER THAN 6 FEET FROM THE APPLIANCE,
 AND SHALL BE INSTALLED UPSTREAM FROM THE UNION,
 CONNECTOR OR QUICK DISCONNECT DEVICE IT SERVES. SUCH
 SHUTOFF VALVES SHALL BE PROVIDED WITH ACCESS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-07 Cont ID  
Sent By adarroug Date 2007-12-07 Time 10:07 Rev Time 0.00
Received By adarroug Date 2007-12-07 Time 10:07 Sent To E
Notes
2007-12-07 10:07:42TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-07 Cont ID  
Sent By adarroug Date 2007-12-07 Time 10:04 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 16:12 Sent To  
Notes
2007-10-03 16:12:42TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-13 Cont ID  
Sent By tgordon Date 2007-12-13 Time 14:20 Rev Time 0.20
Received By tgordon Date 2007-12-13 Time 14:20 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-25 Cont ID  
Sent By tgordon Date 2007-10-25 Time 09:14 Rev Time 0.25
Received By tgordon Date 2007-10-25 Time 09:14 Sent To G
Notes
2007-10-25 09:24:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT DETAILED MANUFACTURER'S INSTALLATION
 INSTRUCTIONS SHOWING REQUIRED CLEARANCES FOR GENERATOR,
 SEE NFPA 37 (4.1.4).
  
 2) PLEASE STATE WHAT THE BUILDING IS MADE OF AND IF
 COMBUSTIBLE, SEE NFPA 37 (4.1.4).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2007-10-09 Cont ID  
Sent By choops Date 2007-10-09 Time 11:06 Rev Time 0.00
Received By choops Date 2007-10-09 Time 11:06 Sent To E
Notes
2007-10-09 11:06:52***APPROVED***
  
 SENT TO "E" - GEN BOX