Plan Review Stops For Permit 07100077 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-12-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-12-27 |
Time |
18:31 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-12-27 |
Time |
18:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-10-29 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-10-29 |
Time |
10:55 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-10-29 |
Time |
10:55 |
Sent To |
|
|
Notes |
2007-10-29 10:57:17 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1..)PROVIDE A DETAIL FOR THE SLAB INCLUDING ALL | | DIMENSIONS AND STRUCTURAL INFORMATION.USE OF A PREFAB | | SLAB REQUIRES CALCULATIONS PREPARED BY AN ENGINEER. FBC | | R 301. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2008-01-07 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-01-07 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-01-07 |
Time |
10:55 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-12-10 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-12-10 |
Time |
16:03 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-12-10 |
Time |
15:56 |
Sent To |
G |
|
Notes |
2007-12-10 16:00:25 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | REPEAT COMMENT | | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | AMENDED. | | A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED | | UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID. | | 108.1 FBC. | | | | ADJUST THE VALUE AT THE PERMIT CLERK'S DESK, AND PAY | | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-10-24 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-10-24 |
Time |
11:34 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-10-24 |
Time |
10:51 |
Sent To |
M |
|
Notes |
2007-10-24 11:34:46 | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | AMENDED. | | | | A) A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED | | UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID. | | 108.1 FBC. | | | | B) ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND | | PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. | | | | 2} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE | | GENERATOR INDICATING RECOMMENDED SETBACKS FROM | | STRUCTURES. | | | | 3} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH | | | | 4} AN EQUIPMENT GROUNDING CONDUCTOR PER 250.122 IS | | REQUIRED FROM THE TRANSFER SWITCH TO THE GENERATOR. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2007-12-13 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-12-13 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-12-13 |
Time |
11:56 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2007-10-26 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-10-26 |
Time |
08:13 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-10-26 |
Time |
08:13 |
Sent To |
B |
|
Notes |
2007-10-26 08:53:29 | DENIED | | REFERENCE: | | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | REQUIREMENTS. | | ** FBC-2004 CHAPTER 1, THE CITY OF | | WEST PALM BEACH AMENDMENTS. | | ** FLORIDA ADMINISTRATIVE CODE (FAC). | | ** FLORIDA STATUTES (FS). | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: | | **CONTRACTOR INFORMATION: THE SUBMITTED GAS PERMIT | | REFERENCED MASTER PERMIT #06060974, THAT PERMIT NUMBER | | IS EXPIRED. THE CORRECT MASTER PERMITNUMBER IS | | #07100077. PLEASE NOTE THE RED LINE CORRECTIONS ON THE | | PERMIT APPLICATION. | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | **NOTE: THE SUBMITTED ISOMETRIC DRAWING MUST INDICATE | | THE CORRESPONDING LENGTHS OF THE CUT SECTIONS OF PIPE | | TO VERIFY THE GIVEN DEVELOPED LENGTH OF 20' ON THE | | RESUBMITTAL. | | | | 2. PLEASE CORRELATE THE GENERATOR SIZE AND BTU LOAD ON | | THE RESUBMITTED DRAWINGS WITH THE MASTER GEN/RES PERMIT | | #07100077. THE MASTER GEN/RES PERMIT INDICATES A 35 KW, | | 560,000 BTU GENERATOR. THE SUBMITTED GAS ISOMETRIC IS | | INDICATING A 40 KW, 650,000 BTU GENERATOR. PER *106.1.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 3. PER FBC-2004 FUEL GAS SECTION 409.5 EQUIPMENT | | SHUTOFF VALVE: EACH APPLIANCE SHALL BE PROVIDED WITH A | | SHUTOFF VALVE SEPERATE FROM THE APPLIANCE. THE SHUTOFF | | VALVE SHALL BE LOCATED IN THE SAME ROOM AS THE | | APPLIANCE, NOT FURTHER THAN 6 FEET FROM THE APPLIANCE, | | AND SHALL BE INSTALLED UPSTREAM FROM THE UNION, | | CONNECTOR OR QUICK DISCONNECT DEVICE IT SERVES. SUCH | | SHUTOFF VALVES SHALL BE PROVIDED WITH ACCESS. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-12-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-07 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-07 |
Time |
10:07 |
Sent To |
E |
|
Notes |
2007-12-07 10:07:42 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-12-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-07 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-03 |
Time |
16:12 |
Sent To |
|
|
Notes |
2007-10-03 16:12:42 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2007-12-13 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-12-13 |
Time |
14:20 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2007-12-13 |
Time |
14:20 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-10-25 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-10-25 |
Time |
09:14 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-10-25 |
Time |
09:14 |
Sent To |
G |
|
Notes |
2007-10-25 09:24:26 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) PLEASE SUBMIT DETAILED MANUFACTURER'S INSTALLATION | | INSTRUCTIONS SHOWING REQUIRED CLEARANCES FOR GENERATOR, | | SEE NFPA 37 (4.1.4). | | | | 2) PLEASE STATE WHAT THE BUILDING IS MADE OF AND IF | | COMBUSTIBLE, SEE NFPA 37 (4.1.4). | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2007-10-09 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-10-09 |
Time |
11:06 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-10-09 |
Time |
11:06 |
Sent To |
E |
|
Notes |
2007-10-09 11:06:52 | ***APPROVED*** | | | | SENT TO "E" - GEN BOX |
|
|