Plan Review Details - Permit 07100072
Plan Review Stops For Permit 07100072
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-01-02 Cont ID  
Sent By mperson Date 2008-01-02 Time 10:43 Rev Time 0.00
Received By mperson Date 2008-01-02 Time 10:43 Sent To PC
Notes
2008-01-02 10:48:36IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,500 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 11,250 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By mperson Date 2007-10-16 Time 14:18 Rev Time 0.00
Received By mperson Date 2007-10-16 Time 14:18 Sent To PC
Notes
2007-10-16 14:38:12DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: PLEASE INDICATE THE CORRESPONDING LENGTHS TO ALL
 CUT SECTIONS OF PIPE ON THE RESUBMITTAL AND INDICATE
 THE LOCATION OF THE EXISTING POOL HEATER. SEE ATTACHED
 PERMIT INFORMATION TO THE GAS COMMENTS INDICATING GAS
 TO AN EXISTING POOL HEATER.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: PERMIT INFORMATION INDICATES EXISTING GAS TO A
 POOL HEATER, THE BTU LOAD FOR THE EXISTING SYSTEM NEEDS
 TO BE ON THE RESUBMITTAL.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: LONGEST LENGTH OF THE SYSTEM NEEDS TO BE
 INDICATED ON THE PLANS, THIS INCLUDES THE POOL HEATER.
 IF GAS PIPING TO THE EXISTING POOL HEATER IS LONGER
 THAN THE PROPOSED ADDITION GAS OF 25 FEET GAS SYSTEM
 WILL NEED TO BE RESIZED.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-27 Cont ID  
Sent By spalmer Date 2007-12-27 Time 16:06 Rev Time 0.00
Received By spalmer Date 2007-12-27 Time 16:06 Sent To G
Notes
2007-12-27 16:06:29TO MIKE PERSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-16 Cont ID  
Sent By mperson Date 2007-10-16 Time 14:38 Rev Time 0.00
Received By mperson Date 2007-10-03 Time 16:17 Sent To  
Notes
2007-10-03 16:17:37TO "G" BOX