Plan Review Details - Permit 07100065
Plan Review Stops For Permit 07100065
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 14:00 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 14:00 Sent To M
Notes
2007-11-06 14:00:53TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-30 Cont ID  
Sent By adarroug Date 2007-10-30 Time 10:22 Rev Time 0.00
Received By adarroug Date 2007-10-30 Time 10:22 Sent To M
Notes
2007-10-30 10:22:32TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-18 Cont ID  
Sent By tgordon Date 2007-10-18 Time 09:56 Rev Time 0.00
Received By tgordon Date 2007-10-03 Time 16:19 Sent To  
Notes
2007-10-03 16:19:59TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-11-13 Cont ID  
Sent By tgordon Date 2007-11-13 Time 10:34 Rev Time 0.25
Received By tgordon Date 2007-11-13 Time 10:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-02 Cont ID  
Sent By tgordon Date 2007-11-02 Time 08:53 Rev Time 0.35
Received By tgordon Date 2007-11-02 Time 08:53 Sent To  
Notes
2007-11-02 09:02:04PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SHOW ON PLAN HOW THE OUTDOOR AIR IS GOING TO GET IN
 THE BUILDING, PER 2004 FBC/M 401.2.
  
 2) AS NOTED IN LAST REVIEW 10-18-07 NOTE #7 PLEASE
 SUBMIT PRODUCT APPROVAL OR AN NOA FOR PER-ENGINEERED
 CONDENSER STANDS, SEE FS 553.842(1) AND FAC RULE 9B-72,
 9B-72.005, AND FAC 9B-72.010(31)(G). WHAT WAS SUBMITTED
 WAS ENGINEERING SHEETS NOT PRODUCT APPROVALS.
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By tgordon Date 2007-10-18 Time 09:24 Rev Time 0.30
Received By tgordon Date 2007-10-18 Time 09:24 Sent To  
Notes
2007-10-18 09:55:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1.
  
 2) PLEASE SUBMIT OUTDOOR AIR CALCULATIONS AND PROVIDE
 OUTDOOR AIR, SEE 2004 FBC/M 401.2.
  
 3) NEED TO SHOW THE SUPPLY AIR CFM'S AT THE GRILLS, SEE
 FBC 13-410.1.ABC.4.2.
  
 4) NEED TO PROVIDE FOR RETURN AIR TO OFFICE, SEE FBC/M
 601.4.
  
 5) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 6) PLEASE ADJUST VALUE ON PERMIT APPLICATION TO SHOW
 FAIR MARKET VALUE OR THE CITY WILL ADJUST VALUE USING
 MARSHALL AND SWIFT SEGREGATED COST METHOD, SEE W.P.B.
 108.3.
  
 7) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR
 PER-ENGINEERED CONDENSER STANDS, SEE FS 553.842(1) AND
 FAC RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]