Plan Review Details - Permit 07090780
Plan Review Stops For Permit 07090780
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-06-14 Cont ID  
Sent By amorse Date 2008-06-14 Time 06:27 Rev Time 0.00
Received By amorse Date 2008-06-14 Time 06:27 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-05-06 Cont ID  
Sent By amorse Date 2008-05-06 Time 16:01 Rev Time 0.00
Received By amorse Date 2008-05-06 Time 16:01 Sent To PC
Notes
2008-05-06 16:07:21 
  
 DENIED
  
 1)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC
 2004. ONLY ONE SET OF REVISED PLANS WAS SIGNED, SEALED
 AND DATED.
  
 2)PLEASE NOTE THAT REVISED DRAWINGS REQUIRE PLUMBING
 REVIEWER TO RESTAMP BE SURE THAT THE PLUMBING BOX IS
 ALSO CHECKED ON THE RESUB SHEET.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-03-15 Cont ID  
Sent By amorse Date 2008-03-15 Time 12:21 Rev Time 0.00
Received By amorse Date 2008-03-15 Time 12:21 Sent To PC
Notes
2008-03-15 12:38:32 
  
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE 1ST
 REVIEW:
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 10)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 12) NO PRODUCT APPROVALS WERE SUBMITTED FORCONNECTORS
 AND STRAPS,IN LUE OF PRODUCT APPROVALS
 STRAPS/CONNECTORS MAY BE LISTED IN A SCHEDULE ON THE
 DRAWINGS COMPLETE WITH THE STATEWIDE PRODUCT APPROVAL
 NUMBERS OR SUBMIT SIMPSON TIE'S COMPLETE FLORIDA INDEX
 WITH CONNECTORS TO BE USED HIGHLIGHTED
  
 NEW 2ND REVIEW COMMENTS:
  
 1)PROVIDE ON CENTER SPACING FOR ROOF AND WALL FRAMING
 MEMBERS
  
 2)ROOF SHEATHING SHALL COMPLY WITH R803.2.3.1 FBC
 RES. 8D RING SHANK NAILS 6" O/C FIELD AND EDGES IN ZONE
 1 AND 2,4" O/C FIELD AND EDGES IN ZONE 3
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-03 Cont ID  
Sent By amorse Date 2007-11-03 Time 12:24 Rev Time 0.00
Received By amorse Date 2007-11-03 Time 12:24 Sent To  
Notes
2007-11-03 13:01:55 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)PROVIDE THE WIND DESIGN DATA THAT APPLIES TO
 BUILDING PER 1603.1.4 FBC
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 4)IF THE ACCESSORY BUILDINGS ARE DEEMED TO BE LIVING
 SPACES THE STATE OF FLORIDA REQUIRES COLLECTION OF A
 RADON SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON
 UNDER ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL
 BE ADDED TO THE PERMIT APPLICATION FEES.
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $785.96FOR
 INCREASED VALUE THIS AMOUNT IS REQUIRED TO BE PAID
 PRIOR TO FURTHER PLAN REVIEW. THESE FEES ARE FOR
 UTILITY BUILDINGS AND AS ABOVE IF DEEMED RESIDENCE
 USAGE THE FEES WILL BE INCREASED.
  
 5)PROVIDE DRAWINGS AND SPECIFICATIONS THAT ARE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION,NATURE, AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE PER 106.1.1
 FBC* PLEASE NOTE THAT PERMIT APPLICATION STOP WORK
 ORDER AND NOTICE OF VIOLATION ALL INDICATE THAT
 BUILDINGS ARE OF CBS CONSTRUCTION.
  
 6)IF BUILDINGS ARE RESIDENCESTWO COPIES OF ENERGY
 CALC'S PER 13-101.2.2 FBC. BE SURE THAT THEY ARE SIGNED
 AND DATED BY PREPARER AND OWNER/AGENT PRIOR TO
 SUBMITTAL
  
 7)PROVIDE SCHEDULE FOR PRECAST LINTEL THAT WILL BE
 USED AND OPENING SIZES TO COMPLY WITH 2104.1.5 FBC FOR
 MIN BEARING
  
 8)DRAWINGS SHALL SHOW THE MINIMUM DEPTH OF FOUNDATION
 ON THE WALL SECTIONS PER R403.1.4 FBC RES.
  
 9)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 10)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 11)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 12) NO PRODUCT APPROVALS WERE SUBMITTED FOR LINTELS,
 CONNECTORS AND STRAPS, WINDOWS, DOORS AND ROOFING
 MATERIAL, IN LUE OF PRODUCT APPROVALS STRAPS/CONNECTORS
 MAY BE LISTED IN A SCHEDULE ON THE DRAWINGS COMPLETE
 WITH THE STATEWIDE PRODUCT APPROVAL NUMBERS OR SUBMIT
 SIMPSON TIE?S COMPLETE FLORIDA INDEX WITH CONNECTORS TO
 BE USED HIGHLIGHTED
  
 13)PROVIDE 2 COMPLETE SETS OF ALL DRAWINGS AND
 SUBMITTALS
  
 14)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 15)ADDITIONAL PERMITS WILL BE REQUIRED FOR PLUMBING,
 ELECTRICAL AND MECHANICAL AND ROOFING
  
 16)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES
 ONLY FOR REFERENCE
  
 17)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 18)UNTIL INSPECTION OF THE INTERIOR OF THESE
 BUILDINGS IS UNDERTAKEN AND PLANS CAN BE VERIFIED TO BE
 TRUE, A COMPLETE PLAN REVIEW CANNOT BE MADE AND MORE
 COMMENTS MAY BE FORTHCOMING. FOR ANINSPECTION OF
 PREMISES PLEASE CALL CHIEF BUILDING INSPECTOR KEN
 CONRAD AT (561) 805-6666
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-05-28 Cont ID  
Sent By dpalmer Date 2008-05-28 Time 11:58 Rev Time 0.00
Received By dpalmer Date 2008-05-28 Time 11:58 Sent To P
Notes
2008-05-28 12:00:48SA REQUIRED. NFPA-72 11.5.1.1.
  
 BLDGS ARE ONLY STORAGE UNITS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-04-30 Cont ID  
Sent By dpalmer Date 2008-04-30 Time 08:58 Rev Time 0.00
Received By dpalmer Date 2008-04-30 Time 08:58 Sent To B
Notes
2008-04-30 08:59:26** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE THAT BOTH REVISED SETS OF PLANS ARE
 REQUIRED TO BE SIGNED, DATED AND SEALED BY THE
 ARCHITECT.
 ONLY ONE SET WAS SIGNED AND SEALED.
 FS 481.221
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-10 Cont ID  
Sent By dpalmer Date 2008-03-10 Time 08:49 Rev Time 0.00
Received By dpalmer Date 2008-03-10 Time 08:49 Sent To P
Notes
2008-03-10 08:50:06** DENIED REVIEW **
  
  
 1) NOTE: PLEASE SEE 210.52D, 210.11C3 FOR MISSING
 DEDICATE BATH CIRCUIT.
  
 2) NOTE: PLEASE SEE EXISTING HOUSE PANEL IS NOT SHOWING
 ANY BREAKERS FOR THE NEW SUB PANELS.
 408.4, ETC
 FBC 106.3.5.4
  
 3) NOTE: THE FOOTER STEEL AT THE DETACHED BUILDINGS ARE
 REQUIRED TO BE PART OF THE GROUNDING ELECTRODE
 SYSTEMS.
 250.50, 250.32
  
 4) NOTE: PLANS DO NOT SHOW THE LOCATIONS OF THE PANELS
 DISCONNECTS AT THE DETACHED BUILDING. 225.31-225.39,
 110.26, 240.24
  
  
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-20 Cont ID  
Sent By dpalmer Date 2007-10-20 Time 10:23 Rev Time 0.00
Received By dpalmer Date 2007-10-20 Time 09:00 Sent To M
Notes
2007-10-20 10:28:48 
 PLANS WERE NOT SENT TO ELECTRICAL SFR UNTIL 10/19
2007-10-20 10:24:102007-10-20 10:24:10
  
 ** DENIED **
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE EACH BLDG IS SHOWING AN ELECTRICAL
 RISER OF A SEPARATE ELECTRICAL SERVICE WHICH IS NOT
 PERMITTED. 230.2.
 PLEASE SEE THAT THE PANEL SCHEDULES AS SUBMITTED ON
 EACH DO NOT ACCURATELY REFLECT ANY OF THE ELECTRICAL ON
 PLANS.
  
 3) NOTE: PLEASE SEE 225.31-225.39 AS SEPARATE
 SUB-PANELS AT EACH BUILD FED FROM THE MAIN HOUSE WOULD
 BE REQUIRED. THIS IS ONLY BASED ON USE AND PERMITTED
 USE FROM ZONING AND OTHER TRADES.
 AS NONE IS SHOWN, REVIEW CAN NOT BE DONE. (LOCATION,
 SIZE, OVER CURRENT PROTECTION, ETC)
 PLEASE SEE 240.4, 310.16 AND 408.4 FOR REQUIRED PANEL
 SCHEDULE(S) ETC
 FBC 106.3.5.4, 106.1.2
  
 4) NOTE: PLEASE SEE 250.32 AND 250.50 FOR GROUNDING
 ELECTRODE SYSTEM REQUIRED AT EACH STRUCTURE.
 THIS WILL INCLUDE GROUNDING FROM THE PANELS/DISCONNECTS
 FROM NOTE #3 ABOVE TO FOOTER STEEL, AND ANY METAL COLD
 WATER PIPE.
 THESE ARE THE *MINIMUM* THAT ARE REQUIRED.
  
 5) NOTE: PLEASE SEE MISSING BATH ROOM REQUIRED
 DEDICATED CIRCUIT(S) PER 210.52D, 210.8A2, 210.11C3.
 MUST BE 20AMP AND #12.
 THEREARE NONE SHOWN ON PLANS, AND AS NEW PANELS FOR
 EACH BUILDING WILL BE REQUIRED, NO REVIEW CAN BE DONE
 OF THESE.
  
 6) NOTE: PLEASE SEE MISSING SMOKE ALARMS PER NFPA-72
 11.5.1.1.1, 11.8.3
 MUST BE INSTALLED AS THESE ARE CLEARLY ADAPTABLE
 SLEEPING ROOMS/APARTMENTS.
 PLEASE SEE THE NEXT COMMENT ALSO FOR 210.12.
  
 7) NOTE: PLEASE SEE AS THE PLANS APPEAR TO SHOW AND
 LEND TO APARTMENT USE AND THE FACT THAT THESE ROOMS ARE
 ADAPTABLE SLEEPING ROOMS, ARC FAULT PROTECTION WILL BE
 REQUIRED PER 210.12
  
 8) NOTE: PLEASE SEE THAT NO WHITE-OUT OF ANY KIND MAY
 BE PLACED ON PLANS.
 FS 481, FBC 106.1
  
 9) NOTE: PLEASE SEE PLUMB PLANS INDICATE TWO SINKS,
 HOWEVER ONLY ONE IS SHOWN ON PLANS. THIS WILL DIRECTLY
 AFFECT THE ELECTRICAL REQUIREMENTS IF A KITCHEN IS
 BEING INSTALLED OR WIRED ON-SITE. A FIELD INSPECTION OF
 ELECTRICAL SYSTEMS OF WHICH MAY ALREADY BE WIRED ETC
 MAY BE DONE TO ACCURATELY COME UP WITH WHAT WORK IS
 DONE, TO BE DONE, USE ETC.
 PLANS DO NOT CORRELATE FOR USE.
 ARCHITECT TO SEE FS 481 FOR DESIGN RESPONSIBILITY.
 PLANS MAY BE RETAINED BY THIS OFFICE AND PLACED WITH
 OTHER PLANS RETAINED IN FILE FOR THIS DESIGNER. PLANS
 ARE REQUIRED TO BE DESIGNED FOR ACCURATE USE, AND THE
 MINIMUM CODE(S).
  
 10) NOTE: PLEASE SEE AS PLANS INDICATE A WATER HEATER
 WITH WHITE OUT OVER IT, PLEASE INCLUDE ON PLANS IF SO
 INSTALLED OR PROPOSED.
 PLEASE SEE 422.17 AS THE WATER HEATER MAY NOT BE IN A
 CLOSET.
  
 11) NOTE: PLEASE SEE DEPENDING ON USE; PLEASE SEE ALL
 OF 210.52 WHICH SEVERAL ITEMS MAY BE REQUIRED.
  
 ** PLEASE KNOW PLANS ARE REQUIRED TO BE DESIGNED TO
 *MINIMUM* STANDARDS FOR CODE COMPLIANCE FOR USE AND IT
 IS THE RESPONSIBILITY OF ALL PERSONS INVOLVED.
  
 ** PLEASE KNOW AS THERE ARE NUMEROUS ITEMS NOT YET
 SHOWN OR SUBMITTED UNDER THE DESIGN, THERE MAY BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-23 Cont ID  
Sent By adarroug Date 2008-05-23 Time 10:52 Rev Time 0.00
Received By adarroug Date 2008-05-23 Time 10:52 Sent To E
Notes
2008-05-23 10:52:53TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-24 Cont ID  
Sent By adarroug Date 2008-04-24 Time 13:55 Rev Time 0.00
Received By adarroug Date 2008-04-24 Time 13:55 Sent To E
Notes
2008-04-24 13:56:09TO "DPALMER' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-06 Cont ID  
Sent By adarroug Date 2008-03-06 Time 12:26 Rev Time 0.00
Received By adarroug Date 2008-03-06 Time 12:26 Sent To Z
Notes
2008-03-06 12:27:17TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-11-03 Time   Rev Time 0.00
Received By shill Date 2007-10-19 Time 17:50 Sent To  
Notes
2007-10-19 17:50:53TO RESIDENTIAL RACK
2007-09-28 08:50:24TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-10-22 Cont ID  
Sent By tgordon Date 2007-10-22 Time 11:30 Rev Time 0.15
Received By tgordon Date 2007-10-22 Time 11:30 Sent To P
Notes
2007-10-22 11:31:45NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-06-09 Cont ID  
Sent By jleech Date 2008-06-09 Time 07:46 Rev Time 0.00
Received By jleech Date 2008-06-09 Time 07:43 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-03-10 Cont ID  
Sent By jleech Date 2008-03-10 Time 09:29 Rev Time 0.00
Received By jleech Date 2008-03-10 Time 09:20 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-31 Cont ID  
Sent By jleech Date 2007-10-31 Time 07:29 Rev Time 0.00
Received By jleech Date 2007-10-31 Time 07:28 Sent To B
Notes
2007-10-31 07:41:50DENIED;
 1. PLUMBING PLAN REVIEW CAN NOT PASS TILL ZONING ISSUES
 ARE RESOLVED.
 2. IF THIS IS A LIVING UNIT THEN CLOTHES WASHING
 FACILITIES ARE REQUIRED PER, NOT SHOWN ON PLANS.
 3. SANITARY RISER DIAGRAM SHOWS A SINK, (KITCHEN?) NOT
 SHOWN ON FLOOR PLAN.
 4. IF WATER IS ON THE SAME WATER METERAS THE MAIN
 BUILDING THE A BACKFLOW PREVENTOR IS REQUIRED, SHOW.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2008-03-07 Cont ID  
Sent By choops Date 2008-03-07 Time 12:51 Rev Time 0.00
Received By choops Date 2008-03-07 Time 12:51 Sent To E
Notes
2008-03-07 12:52:39***APPROVED - RESUB #1***
  
 PROVISO:NO SEPARATE DWELLING UNIT ALLOWED (DOES NOT
 MEET LOT AREA REQUIREMENT FOR 3 UNITS).FIELD
 INSPECTOR TO VERIFY NO KITCHEN OR FULL SIZED
 REFRIGERATOR IN UNITS.
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-02 Cont ID  
Sent By choops Date 2007-10-02 Time 10:15 Rev Time 0.00
Received By choops Date 2007-10-02 Time 10:15 Sent To B
Notes
2007-10-02 10:18:45***FAILED***
  
 NOTE:NO SEPARATE DWELLING UNIT ALLOWED (DOES NOT MEET
 LOT AREA REQUIREMENT FOR 3 UNITS).FIELD INSPECTOR TO
 VERIFY NO KITCHEN OR FULL SIZED REFRIGERATOR IN UNITS.
  
 1)SHOW ANY A/C MECHANICAL EQUIPMENT WITH SETBACK
 DIMENSIONS TO THE PROPERTY LINES.
  
 2)INDICATE HEIGHT OF BUILDINGS FROM GRADE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720