Plan Review Details - Permit 07090774
Plan Review Stops For Permit 07090774
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-23 Cont ID  
Sent By rmcdouga Date 2008-01-23 Time 07:14 Rev Time 0.00
Received By rmcdouga Date 2008-01-23 Time 06:48 Sent To  
Notes
2008-01-23 07:15:43REVISED SHEETS D1 AND D2 REVIEWED FOR CODE COMPLIANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-01-15 Cont ID  
Sent By rmcdouga Date 2008-01-15 Time 13:50 Rev Time 0.00
Received By rmcdouga Date 2008-01-15 Time 13:20 Sent To Z
Notes
2008-01-15 13:50:16REVISION DENIED
  
 1) DRAWING D1 OF THE APPROVED PLANS SPECIFIES THAT THE
 CONCRETE SLAB, FOOTINGS AND SECTION OF THE BRICK
 PLANTER WILL BE REMOVED. THIS SHEET OF THE PLANS WILL
 HAVE TO BE REVISED ALSO.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-14 Cont ID  
Sent By rmcdouga Date 2007-11-14 Time 17:45 Rev Time 0.00
Received By rmcdouga Date 2007-11-14 Time 17:45 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By rmcdouga Date 2007-10-16 Time 17:56 Rev Time 0.00
Received By rmcdouga Date 2007-10-16 Time 17:56 Sent To  
Notes
2007-10-16 18:09:102004 FBC W/2007 REVISIONS
 DEMOLISH UNPERMITTED ADDITION AND CONVERT GARAGE TO
 STORAGE ROOM
  
 DENIED BY BUILDING
  
 1) SUBMIT PRODUCT APPROVALS FOR THE NEW EXTERIOR DOORS
 AND THE WINDOWS THAT WERE INSTALLED IN THE GARAGE
 WITHOUT PERMITS.
  
 2) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE.
  
 3)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2007-11-16 Cont ID  
Sent By btrobaug Date 2007-11-16 Time 16:54 Rev Time 0.00
Received By btrobaug Date 2007-11-16 Time 16:54 Sent To Z
Notes
2007-11-16 16:54:51 
  
 NO ELECTRIC WORK ON THIS PERMIT, DEMO ONLY../WRT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-26 Cont ID  
Sent By btrobaug Date 2007-10-26 Time 07:50 Rev Time 0.00
Received By btrobaug Date 2007-10-26 Time 07:41 Sent To P
Notes
2007-10-26 07:50:38 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 SAME COMMENT AS THE PREVIOUS REVIEW:
  
 1} PER 106.1 FBC AS AMMENDED, PLANS ARE REQUIRED FOR
 THE SCOPE OF WORK APPLIED FOR. THE SERVICE RELOCATION
 AND A/C CIRCUIT INDICATED ON SHEET D3 OF 3 REQUIRE AN
 ELECTRICAL PERMIT AND PLANS. SUBMIT SAME.* THE
 RELOCATED SERVICE REQUIRES A RISER DIAGRAM AND AN
 ELECTRICAL PERMIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-11 Cont ID  
Sent By btrobaug Date 2007-10-11 Time 09:37 Rev Time 0.00
Received By btrobaug Date 2007-10-11 Time 09:28 Sent To P
Notes
2007-10-11 09:36:34 
  
 DENIED/INCOMPLETE INFORMATION
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PER 106.1 FBC AS AMMENDED, PLANS ARE REQUIRED FOR
 THE SCOPE OF WORK APPLIED FOR. THE SERVICE RELOCATION
 AND A/C CIRCUIT INDICATED ON SHEET D3 OF 3 REQUIRE AN
 ELECTRICAL PERMIT AND PLANS. SUBMIT SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-01-11 Cont ID  
Sent By swurafti Date 2008-01-11 Time 15:11 Rev Time 0.00
Received By swurafti Date 2008-01-11 Time 15:11 Sent To  
Notes
2008-01-11 15:12:00HISTORIC APPROVED BY GJUDGE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-17 Cont ID  
Sent By shill Date 2008-01-17 Time 15:15 Rev Time 0.00
Received By shill Date 2008-01-17 Time 15:15 Sent To Z
Notes
2008-01-17 15:15:30TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-11 Cont ID  
Sent By spalmer Date 2008-01-11 Time 17:12 Rev Time 0.00
Received By spalmer Date 2008-01-11 Time 17:12 Sent To B
Notes
2008-01-11 17:12:45TO ROBERT MCDOUGALS DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-19 Cont ID  
Sent By adarroug Date 2007-10-19 Time 11:34 Rev Time 0.00
Received By adarroug Date 2007-10-19 Time 11:34 Sent To Z
Notes
2007-10-19 11:34:58TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-16 Cont ID  
Sent By rmcdouga Date 2007-10-16 Time 17:56 Rev Time 0.00
Received By rmcdouga Date 2007-10-05 Time 12:54 Sent To  
Notes
2007-10-05 12:54:49TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-10-12 Cont ID  
Sent By jleech Date 2007-10-12 Time 10:37 Rev Time 0.00
Received By jleech Date 2007-10-12 Time 10:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-16 Cont ID  
Sent By jleech Date 2007-11-16 Time 08:43 Rev Time 0.00
Received By jleech Date 2007-11-16 Time 08:43 Sent To  
Notes
2007-11-16 08:44:54REMOVAL OF BATHROOM SHALL BE DONE BY A LICENSED
 PLUMBING CONTRACTOR PERMIT AND INSECTIONS REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-12 Cont ID  
Sent By jleech Date 2007-10-12 Time 10:28 Rev Time 0.00
Received By jleech Date 2007-10-12 Time 10:28 Sent To B
Notes
2007-10-12 10:37:08DENIED;
 THE TOILET AND SHOWER SHOULD ALSO BE REMOVED, THEY WERE
 PART OF THE UN-PERMITED WORK AND NOT NEEDED IN A
 STORAGE SHED.
 ADD NOTE TO DEMO PLAN, " THE SEWER SHALL BE CAPPED
 WITHIN 2' OF THE HOUSE SEWER. " FBC PLUMBING SECTION
 704.5.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 5 Status P Date 2008-01-22 Cont ID  
Sent By choops Date 2008-01-22 Time 16:01 Rev Time 0.00
Received By choops Date 2008-01-22 Time 16:01 Sent To B
Notes
2008-01-22 16:01:48***APPROVED - REVISION - PLANTER TO REMAIN AND SLAB TO
 REMAIN AS PORCH***
  
  
  
 SENT TO "B" - RMC

Review Stop Z ZONING
Rev No 4 Status F Date 2008-01-15 Cont ID  
Sent By choops Date 2008-01-15 Time 15:13 Rev Time 0.00
Received By choops Date 2008-01-15 Time 15:13 Sent To  
Notes
2008-01-15 15:16:47***FAILED - REVISION - PLANTER TO REMAIN AND SLAB TO
 REMAIN AS PORCH***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY SHOWING
 THE LOCATION OF THE PLANTER AND SLAB, WITH SETBACK
 DIMENSIONS FROM THE PROPERTY LINES.
  
 2)PROVIDE A SECTION DETAIL OF THE PLANTER SHOWING
 THE HEIGHT DIMENSIONS FROM GRADE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 3 Status P Date 2007-11-19 Cont ID  
Sent By choops Date 2007-11-19 Time 08:24 Rev Time 0.00
Received By choops Date 2007-11-19 Time 08:24 Sent To PC
Notes
2007-11-19 08:24:38***APPROVED - RESUB #2***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-24 Cont ID  
Sent By choops Date 2007-10-24 Time 16:27 Rev Time 0.00
Received By choops Date 2007-10-24 Time 16:27 Sent To E
Notes
2007-10-24 16:27:56***FAILED - RESUB #1***
  
  
 1)ALL NEWLY RESUBMITTED PLANS SHALL BE
 STAMPED/APPROVED BY HISTORIC PRESERVATION.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2007-10-10 Cont ID  
Sent By choops Date 2007-10-10 Time 15:45 Rev Time 0.00
Received By choops Date 2007-10-10 Time 15:44 Sent To E
Notes
2007-10-10 15:49:55***APPROVED***
  
 CONVERTING ILLEGAL ADDITION BACK TO WHAT WAS ORIGINALLY
 CONSTRUCTED.