Plan Review Details - Permit 07090764
Plan Review Stops For Permit 07090764
Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2008-12-03 Cont ID  
Sent By shill Date 2008-12-03 Time 08:31 Rev Time 0.00
Received By shill Date 2008-12-03 Time 08:31 Sent To Z
Notes
2008-12-03 08:32:03REVISION, T1, A1.1,A6.1 DATED 11/21/08

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2008-09-26 Cont ID  
Sent By jwitmer Date 2008-09-26 Time 08:58 Rev Time 1.22
Received By jwitmer Date 2008-09-26 Time 08:58 Sent To PC
Notes
2008-09-26 09:01:16SUBMITTAL: SHOP DRAWINGS FOR SPIRAL STAIR CASE AND
 GAURD RAIL/ HANDRAIL AND
 GAURD RAIL/ HANDRAIL SYSTEM TO STAIRS TO ROOF LEVEL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2008-09-22 Cont ID  
Sent By shill Date 2008-09-22 Time 16:22 Rev Time 0.00
Received By shill Date 2008-09-22 Time 16:22 Sent To  
Notes
2008-09-22 16:23:22REVISION,INGERSOLL RAND NOA AND SHEETS T1, A8.1 DATED
 9/9/8

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2008-09-22 Cont ID  
Sent By shill Date 2008-09-22 Time 14:28 Rev Time 0.00
Received By shill Date 2008-09-22 Time 14:28 Sent To  
Notes
2008-09-22 14:48:10REVISION DATED 9/17/8
 SHEETS T1, LS0.0, LS0, LS1, LS2, A1.1, A3.1, A5-0.1,
 A5-0.2, A5-1.1, A5-1.2, A6.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-09-22 Cont ID  
Sent By shill Date 2008-09-22 Time 10:01 Rev Time 0.00
Received By shill Date 2008-09-22 Time 10:01 Sent To  
Notes
2008-09-22 10:01:48REVISION DATED 9/2/8, SHEETS T1, LS1, LS2
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-08-11 Cont ID  
Sent By shill Date 2008-08-11 Time 13:42 Rev Time 0.00
Received By shill Date 2008-08-11 Time 13:42 Sent To  
Notes
2008-08-11 13:42:17ROOF REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-07-10 Cont ID  
Sent By shill Date 2008-07-10 Time 17:16 Rev Time 0.00
Received By shill Date 2008-07-10 Time 17:16 Sent To  
Notes
2008-07-10 17:21:41REVISION #5, SHEETS T1, LS1, LS3, A1.1, A3.1, A6.1,
 A8.1, ID2-1.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-06-05 Cont ID  
Sent By shill Date 2008-06-05 Time 12:07 Rev Time 0.00
Received By shill Date 2008-06-05 Time 12:07 Sent To  
Notes
2008-06-05 12:16:01****BUILDING PROVISOS****
  
 1-2.ADDRESSED
  
 3.PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 INGERSOLL-RAND REPORT S07-001 (29A)
  
 4-5. ADDRESSED.
  
 6.SUBMIT PRODUCT APPROVAL FOR DOORS IN ZONE 5.
  
  
  
  
 REVISION OK DATED 5/13/08
 SHEETS T1, LS.1, LS.3, LS1-D.3, A1.1, A2.1, A3.1, A3.2,
 A4.1, A5-1.1, A5-3.1, A5-D.2, A6.1, A7.1, A7.2, A8.1,
 A9.1, A9.2, A9.3, ID2-1.1,

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-04-14 Cont ID  
Sent By shill Date 2008-04-14 Time 16:05 Rev Time 0.00
Received By shill Date 2008-04-14 Time 16:05 Sent To  
Notes
2008-04-14 16:06:48****BUILDING PROVISOS****
  
 1.PROVIDE PRECAST FASTENING (ITEM 23B)
  
 2.PROVIDE METHOD OF ATTACHMENT PRECAST PILASTER (ITEM
 26)
  
 3.APPLY FOR LOCAL PRODUCT APPROVAL, INGERSOLL RAND
 REPORT S07-001 (29A)
  
 4.REVISE FIRE RESISTIVE DESIGN SHEETS (LS1-D1 THROUGH
 3) TO INCLUDE UL U905 AND UL U926.
  
 5.REVISE DETAIL C4 A5-D.1 TO INCLUDE UL ASSEMBLY OR
 CALCULATED FIRE RESISTANCE.
  
 6.SUBMIT PRODUCT APPROVAL FOR DOORS IN ZONE 5.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-04-03 Cont ID  
Sent By shill Date 2008-04-03 Time 18:31 Rev Time 0.00
Received By shill Date 2008-04-03 Time 18:31 Sent To  
Notes
2008-04-03 18:47:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE ELECTRICAL AND MECHANICAL COMMENTS REGARDING
 ENERGY CALCS.CODE COMPLIANT ENERGY CALCS ARE REQUIRED
 PRIOR TO PERMIT ISSUANCE AND CANNOT BE PROVISO'D AS
 FLORIDA STATUTORY ITEMS CANNOT BE PROVISO ITEMS.
  
 2.SEE THE SUBMITTED ENERGY CALCS.NO DOORS ARE
 SHOWN.TWO WINDOWS ARE SHOWN, BUT THE PLAN SHOWS MORE
 THAN TWO WINDOWS.THE DESCRIPTION STATES THAT THE
 DESCRIPTION IS "CLEMATIS GARAGE - ELECTRIC" BUT THE
 ENERGY CALC NEEDS TO SHOW ALL BUILDING COMPONENTS AS
 REQUIRED.
  
 3.OWNER/AGENT IS TO SIGN THE ENERGY CALCS PRIOR TO
 SUBMITTAL, FBC13-103.1.
  
 4.SEE ENERGY CALC PAGE WITH "OTHER REQUIRED
 COMPLIANCE" TITLE, SHEET 7.PLEASE COMPLETE.
  
 5.NOTHING IS SHOWN IN THE COMPONENT "FLOORS", PAGE 5
 OF THE ENERGY CALC, BUT CONFERENCE ROOM AND OFFICES
 HAVE A FLOOR OVER UNCONDITIONED SPACE.
  
 6.THIS IS NOT AN EXHAUSTIVE LIST AS ENERGY CALCS ARE
 SPOT CHECKED FOR COMPLIANCE.PLEASE CHECK ALL
 COMPONENTS AND CONFIRM THAT INSULATION ON THE ENERGY
 CALC MATCHES INSULATION ON THE PLAN.
  
 PURSUANT TO CONTRACTOR'S REQUEST, THE PERMIT WILL BE
 ISSUED WITH THE FOLLOWING PROVISOS:
  
 1.PROVIDE PRECAST FASTENING (ITEM 23B)
  
 2.PROVIDE METHOD OF ATTACHMENT PRECAST PILASTER (ITEM
 26)
  
 3.APPLY FOR LOCAL PRODUCT APPROVAL, INGERSOLL RAND
 REPORT S07-001 (29A)
  
 4.REVISE FIRE RESISTIVE DESIGN SHEETS (LS1-D1 THROUGH
 3) TO INCLUDE UL U905 AND UL U926.
  
 5.REVISE DETAIL C4 A5-D.1 TO INCLUDE UL ASSEMBLY OR
 CALCULATED FIRE RESISTANCE.
  
 6.SUBMIT PRODUCT APPROVAL FOR DOORS IN ZONE 5.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-02-26 Cont ID  
Sent By shill Date 2008-02-26 Time 17:57 Rev Time 0.00
Received By shill Date 2008-02-25 Time 12:41 Sent To  
Notes
2008-02-26 17:57:51****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1A. ---VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 AND REMOVE AND REPLACE ANY PAGES AS NECESSARY.A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILLH HELP TO EXPEDITE YOUR
 PERMIT.THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B. COMMENT ADDRESSED; 3 SETS SUBMITTED.FBC*106.1.1
  
 1C. SEE PREVIOUS LISTS REGARDING PLANS TO BE SPECIFIC
 TO TECHNICAL CODES.THE CODE SHALL NOT BE CITED AS A
 WHOLE OR IN PART.SEE SHEET A5-D.1; AN INCOMPLETE CODE
 REFERENCE NUMBER WAS USED.PLEASE SEE OTHER COMMENTS
 AND REVISE AS NECESSARY TO SHOW CODE COMPLIANCE.
  
 4-5, 23B, 26. PROVISO ITEMS.
  
 27.3RD REQUEST, PLEASE PROVIDE EITHER A LETTER FROM
 THE STRUCTURAL ENGINEER THAT THE FASTENERS FOR THE
 OLDER NOAS HAVE BEEN REVIEWED AND CONFIRMED THAT 1/3
 STRESS INCREASE WAS NOT TAKEN.THE RESPONSE STATES
 THAT ?ALL NOAS SUBMITTED ARE BASED ON THE 2004 FBC NOT
 2001.HOWEVER, SEE FL1589 WHICH WAS SUBMITTED FOR
 INGERSOLL RAND DOOR.THIS PRODUCT APPROVAL IS BASED ON
 FBC2001, NOT FBC2004.FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL IS REQUIRED FAC9B72.A LOCAL PRODUCT APPROVAL
 CANNOT BE ISSUED BECAUSE COMPLIANCE WITH FBC2004 HAS
 NOT BEEN SHOWN.PLEASE PROVIDE THE LETTER AS
 PREVIOUSLY REQUESTED.OTHER NOAS SUBMITTED WERE ISSUED
 PRIOR TO IMPLEMENTATION OF FBC2004; PLEASE CONFIRM THAT
 THE STRESS INCREASE WAS NOT TAKEN AND, IF IT WAS, THAT
 ANCHORING IS NOT AFFECTED.
  
 29A.S07-001 IS NOTED IN THE PREVIOUS CORRECTION LIST,
 THE RESPONSE LETTER, AND SHEET A8.1, BUT I WAS UNABLE
 TO LOCATE THIS PAPERWORK IN THE SUBMITTAL.PLEASE
 ADDRESS.
  
 30.THE PREVIOUS REVIEW REQUESTED PRODUCT APPROVAL
 INFORMATION AND CLARIFICATION.PLEASE NOTE THAT, IF A
 SCHEDULE OF OPENINGS WITH DESIGN PRESSURE FOR EACH
 OPENING IS NOT SUBMITTED, THE PRODUCTS ARE TO COMPLY
 WITH THE MOST STRINGENT PRESSURE ON THE CHART S0-3.0
 WHICH IS +66/-71PSF FOR ZONE 4, +66/-88PSF FOR ZONE 5.
 NOTE THE FOLLOWING:
  
 A.NOA 03 0611.04, +-60PSF LIMITATION, BUT THE DOORS
 ARE LOCATED IN ZONE 5 WITH A +66/-88PSF DP REQUIREMENT
 SHEET S0 3.0.
  
 B.NOA 02 0712.03, SEE ITEM 27.THIS PRODUCT HAS A DP
 OF +-70; APPEARS TO BE OK BASED ON INTERPOLATION.
  
 C.THE STAIRWELL DOORS ARE TO BE FIRE RATED AND ALSO
 MEET DESIGN PRESSURE REQUIREMENTS OF ZONE 5 +66/-88. AS
 THE PAPERWORK S07 001R1 IS NOT IN THE PACKAGE, CODE
 COMPLIANCE CANNOT BE DETERMINED.
  
 D.NOA 03 0327.02 OK FOR ZONE 4, 05 0624.03 OK, 05
 0624.04 OK, 05 0624.06 OK, 07 0416.02 OK, 05 1005.02
 OK
  
 E.PREPARED BY AN ENGINEER AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS FS471.
 PROVIDE ORIGINALS FOR THE OPEN LATTICE WINDLOADS.
 ENGINEER FOR THE OPEN LATTICE IS TO USE ASCE7-02,
 FBC35.ASCE7-02 HAS NOT BEEN ADOPTED BY FBC.
  
 31.PREVIOUS LIST HAD REQUESTED CLARIFICATION AND/OR
 PRODUCT APPROVAL FOR THE WALL LOUVERS.SHEET A8.2
 SPECIFIES A NOA WHICH WAS NOT INCLUDED IN THE NOA
 SUBMITTAL BOOK.PLEASE PROVIDE.
  
 33B.COMMENT FROM PREVIOUS LIST; CODE SUMMARY; PLEASE
 PROVIDE WHAT TYPE OF OCCUPANCY. SEE FBC302.1,
 STRUCTURES OR PORTIONS OF STRUCTURES TO BE CLASSIFIED.
 SHEET LS0.0, BUSINESS, MERCANTILE, AND S2 DECLARED, BUT
 ON LS0 FACTORY INDUSTRIAL AND SPECIAL PURPOSE
 INDUSTRIAL AREAS DECLARED.PLEASE RESOLVE
 INCONSISTENCIES.
  
 33C. COMMENT FROM PREVIOUS LIST, SHEET LS.1, LS.2 S2 IS
 SHOWN AS INCIDENTAL BUT THIS IS NOT INCIDENTAL USE. THE
 ARCHITECT'S RESPONSE LETTER INDICATES THAT ALL
 REFERENCES TO INCIDENTAL HAVE BEEN REMOVED, SO
 APPARENTLY ARCHITECT IS IN AGREEMENT.PLEASE REMOVE
 REMAINING INCIDENTAL REFERENCES. PLEASE CHECK ALL
 SHEETS AS OTHER SHEETS MAY BE AFFECTED.
  
 34A. WALL TYPE IDENTIFIERS ADDED.SHEET A6.1, FIRST
 FLOOR ENLARGED PLAN SOUTH, WALL TYPE IDENTIFIER BETWEEN
 RETAIL 1.102 AND FPL VAULT 1.103 SHOWS A 3 HOUR WALL
 FOR W2.1-8 AND A 2 HOUR REQUIREMENT BETWEEN RETAIL
 1.102 AND PARKING GARAGE.THE DETAIL FOR W2.1 DOES NOT
 SHOW A FIRE RESISTIVE RATING AND STATES REF FBC 721.2
 WHEN RATED, SHEET A5-D.1.SEE COMMENT 1C, DETAILS AND
 PLANS MUST BE SPECIFIC, CANNOT REFER TO CODE SECTIONS
 TO SHOW CODE COMPLIANCE.ALSO THIS IS NOT THE CORRECT
 CODE REFERENCE.AS THERE ARE TABLES AND UL ASSEMBLY
 DETAILS IN SHEETS LS1-D.1 THROUGH 3, YOU MAY REFER TO
 THE SPECIFIC ASSEMBLY OR PLAN PAGE RATHER THAN AN
 INCORRECT/INCOMPLETE CODE REFERENCE.
  
 34B. THE COMMENT REGARDING OPENING PROTECTIVES WAS
 ADDRESSED BY SHOWING WINDOW W6 AT THE WAITING ROOM AS
 90 MINUTE ON SHEET A8.2.THE IMPACT WINDOW IS NOT
 AVAILABLE AS A FIRE RATED WINDOW.IF YOU FEEL THIS
 COMMENT IS IN ERROR, PLEASE PROVIDE SPEC SHEETS FROM
 THE MANUFACTURER SHOWING COMPLIANCE WITH FIRE RESISTIVE
 RATING REQUIREMENT.
  
 NEW COMMENTS:
  
 37.SEE LS0.0, CODE SUMMARY, FIRE RESISTANT RATINGS OR
 SEPARATIONS.IT STATES THAT EVERY EXTERIOR WALL WITH
 15FT OF A PROPERTY LINE . . . AS REQUIRED BY TABLE 602.
 NOTE THAT OPENING PROTECTION IS REQUIRED BY FBC TABLE
 704.8, SEE ALSO COMMENT 1C.SEE FBC TABLE 704.8, 25%
 UNPROTECTED OPENINGS ALLOWED AS MODIFIED BY FBC704.8.1.
 IT IS ACCEPTABLE TO EXCEED CODE COMPLIANCE, BUT PLEASE
 CLARIFY DESIGN INTENT AS FIRE RESISTIVE RATINGS ARE NOT
 SHOWN FOR THE EAST ELEVATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-16 Cont ID  
Sent By jwitmer Date 2008-01-16 Time 07:33 Rev Time 5.55
Received By jwitmer Date 2008-01-16 Time 07:33 Sent To  
Notes
2008-01-16 07:35:28500 BANYAN BLVD
 CITY PARKING GARAGE
 JAN.08, 2008
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07090764
 ADD: 500 BANYAN BLVD
 CONT: CATALFUMO
 TEL: (561)307-4746
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIEDWPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT HAROLD PISKURA MANAGER
 OF THE SPECIAL INSPECTOR PROGRAM AT (561)805-6711 FOR
 FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) COMPLIED.
  
 1E) COMPLIED.
  
 2-3) COMPLIED.
  
 4-5) BUILDING PROVISOS.
  
 2-22) COMPLIED.
  
 23) 2ND REQUEST,SHEET A2.1 DETAIL# 02 PLEASE PROVIDE
 WHAT TYPE OF MATERIAL THE ARCHITECTURAL TRIM WILL BE
 MADE FROM? 1406.2.2 PLANS INDICATE A PRECAST MOLDING
 WHAT TYPE?
  
 23B) THE PLANS INDICATE THAT THE FASTENING SCHEDULE
 WILL BE SUPPLIED BY A SPECIALTY ENGINEER, WITH SHOP
 DRAWINGS THIS CAN BE A PROVISO ONCE REVIEWED BY THE
 DESIGNER OF RECORD.
  
 24) COMPLIED.
  
 25) 2ND REQUEST, SHEET A3.2 PROVIDE THE WIND LOAD
 INFORMATION (CALCULATIONS) FOR THE ROOF TOP LIGHT
 POLES. ASCE 7-02. RESPONSE INDICATES LOCATION TO BE IN
 THE PRODUCT APPROVAL FOLDER, THERE IS A HIGHLIGHTED TAB
 BUT NO DOCUMENTATION.
  
 26) PROVISO: SHOP DRAWINGS.
  
 27) 2ND REQUEST,PLEASE PROVIDE EITHER A LETTER FROM
 THE STRUCTURAL ENGINEER THAT THE FASTENERS FOR THE
 OLDER NOA?S HAVE BEEN REVIEWED AND NO 1 1/3RD INCREASE
 WAS TAKEN FOR THE STEEL FASTENERS.
  
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.ALL OF
 THE PRODUCT APPROVALS ARE STAMPED WITH
 THORTON-TOMASETTIS' SHOP DRAWING STAMP THAT THEY WERE
 REVIEWED. THE ISSUE THAT IS NOT COMMONLY KNOWN THAT THE
 OLDER MIAMI-DADE
 NOA'S THAT WERE TESTED BEFORE THE 2004 FBC MAY OR MAY
 NOT MEET THE CURRENT 2004 FBC. 1605.3.1.1 LOAD
 REDUCTIONS. BEFORE THE 2004 FBC THE MANUFACTURERS WERE
 ALLOWED TO TAKE
 1.33 STEEL INCREASES AND DID SO WITH THERE FASTENERS.
 THE NEWER MIAMI-DADE REPORTS AND THE OLDER REPORTS THAT
 ARE BEING UPDATED ARE BEING REVIEWED FOR THE ANCHOR
 CONNECTIONS. THE
 STATEMENTIS SHOWN UNDER C CALCULATION, REVISED
 ANCHOR CALCULATIONS THAT HAVE BEEN REVIEWED UNDER THE
 2004 FBC WILL STATE THE ANCHOR CALCULATIONS HAVE BEEN
 REVIEWED TO THE 2004 FBC.
 PLEASE REVIEW THE INGERSOLL- RAND AND THE TRAINER GLASS
 FOR THE ANCHOR CONNECTIONS MEETING 1605.3.1.1/ 2004
 FBC. THIS MAY AFFECT THE PRESSURES LISTED IN THE
 REPORT.
  
 28) COMPLIED.
  
 29A)THE EVALUATION REPORT FROM INGERSOLL-RAND REPORT#
 S07-001 IS A COPY AND NEEDS TO BE AN ORIGINAL (3) FOR
 THRESHOLD BUILDING) SIGNED AND SEALED REPORTS.
 29B) THIS REPORT INDICATES UNDER PRODUCT COMPARISON TO
 BE A IN SWING DOOR WHERE AS UNDER EVALUATION FOR A
 POSITIVE WIND APPLICATION THE WIND LOAD APPLIED TO THE
 DOOR PANEL WOULD BE DISTRIBUTED AROUND THE FRAME
 EQUALLY, THIS WOULD REQUIRE THE DOOR & FRAME TO BE
 INSTALLED IN A OUT SWING INSTALLATION. PLEASE CORRECT
 STATEMENTS.
 29C) PLEASE PROVIDE CALCULATIONS INDICATING THE
 EXTRAPOLATION OF PRESSURES OR INTERPOLATION OF
 PRESSURES, DEPENDING ON REPORT.
 29D) IT APPEARS THAT A LOCAL PRODUCT APPROVAL WILL BE
 REQUIRED, PLEASE FILL OUT FORM FOR A LOCAL PRODUCT
 APPROVAL FOR WEST PALM BEACH, SEE FORM ATTACHED.
  
 30) EXTERIOR DOOR PRODUCT APPROVAL SUBMITTED DOES NOT
 TIE TO THE DOOR SCHEDULE FOUND ON
 SHEET A8.1, PLEASE PROVIDE THE FL NUMBER AS IN THE
 WINDOW SCHEDULE FOUND ON A8.2,
 OTHERWISE THE LOCATIONS CAN NOT BE LOCATED. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 31) 2ND REQUEST, SHEET A-8.02 WINDOW 12& 13 BOTH
 INDICATE WALL LOUVERS WITH A SPECIFIC NOA 05-0208.01
 NCA MANUFACTURING, THIS IS A DISCREPANCY FROM THE NOA
 SUBMITTED AND APPROVED BY THE DESIGNER OF RECORD, WHICH
 CAN BE USED ?
  
 32) COMPLIED.
  
 NEW COMMENTS:
  
 33) PLEASE CORRECT,LS0.0 CODE SUMMARY:
 33A)CODE SUMMARY INDICATES A ENCLOSED PARKING GARAGE
 WHERE-AS LS 1 & LS 2 ON EACH LEVEL INDICATE THAT THE
 DESIGN IS AN OPEN PARKING STRUCTURE, PLEASE CORRECT. IF
 OPEN PARKING GARAGE IS TO BE CONSIDERED PROVIDE
 CALCULATION FOR OPENNESS 406.3.3.1.
  
 33B) CODE SUMMARY PLEASE PROVIDE WHAT TYPE OF OCCUPANCY
 THIS BUILDING WILL BE USED FOR, PLEASE SEE 406.2.7 FOR
 MIXED SEPARATION.
  
 33C) LS.1 PLEASE CORRECT THE DESIGNATION OF THE PARKING
 AREA FROM BEING AN INCIDENTAL USE
 TO S-2. TABLE 302.1.1 INDICATE ALLOWABLE AREAS FOR
 INCIDENTAL USE AREAS.
  
 34A) 406.2.7 PARKING GARAGES- MIXED USE, PARKING
 GARAGES SHALL BE SEPARATED FROM OTHER OCCUPANCIES IN
 ACCORDANCE WITH SECTION 302.3.2.
 302.3.2 SEPARATED USES.
 EACH PORTION OF THE BUILDING SHALL BE INDIVIDUALLY
 CLASSIFIED AS TO USE AND SHALL BE COMPLETELY SEPARATED
 FROM ADJACENT AREAS BY FIRE BARRIER WALLS OR HORIZONTAL
 ASSEMBLIES OR BOTH HAVING A FIRE-RESISTANCE RATING
 DETERMINED IN ACCORDANCE WITH TABLE 302.3.2 FOR USES
 BEING SEPARATED. PLEASE SEE TABLE 302.3.2 THAT REQUIRES
 A 2HR SEPARATION BETWEEN OCCUPANCIES. PLEASE PROVIDE
 WALL TAGS INDICATING TYPE OFFIRE RATED WALL.
  
 34B) THIS SEPARATION WILL ALSO REQUIRE 1 ? HR OPENING
 PROTECTIVE ON DOOR NUMBER2-103A & 2-201B AS WELL AS THE
 WAITING ROOM WINDOW AND FIRST FLOOR DOOR NUMBER 1-010A.
 PLEASE SEE TABLE 715.3 & TABLE 715.4.
  
 35) BUSINESS OCCUPANCY ON THE SECOND FLOOR LEVEL, THE
 CONFERENCE ROOM HAS A SECOND MEANS OF EGRESS WHICH
 LEAVES THIS OCCUPANCY AND DOES NOT INDICATE WHERE A
 DISCERNABLE PATH OF EGRESS TRAVEL TO AN EXIT EXIST.
 PLEASE PROVIDE A DISCERNABLE EGRESS PATH OF TRAVEL TO A
 VERTICAL EXIT ENCLOSURE. ALSO CONCERNS THAT CARS CAN
 SWING INTO THIS PATH OF TRAVEL PLEASE PROVIDE A BOLLARD
 SYSTEM OF PROTECTION AND DESIGNATION OF EGRESS PATH.
 PLEASE SEE 1013.2.
  
 36) SHEETA8.2 INDICATES A WINDOW DESIGNATION W-8 AS
 WELL AS ON THE ELEVATIONS AND THE ROOF PLAN A2.1 BOTH
 INDICATE WHAT APPEARSTO BE A ROOF LINE THAT DOES NOT
 APPEAR ON SHEET S1-3.0, A DISCREPANCY THAT NEEDS
 CLARIFICATION. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-21 Cont ID  
Sent By jwitmer Date 2007-10-21 Time 14:04 Rev Time 3.33
Received By jwitmer Date 2007-10-21 Time 14:04 Sent To  
Notes
2007-10-21 14:17:51500 BANYAN BLVD
 CITY PARKING GARAGE
 OCT. 22/ 2007
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07090764
 ADD: 500 BANYAN BLVD
 CONT: CATALFUMO
 TEL: (561)307-4746
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIEDWPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS, PLEASE SEE SHEET
 T-1& LS0.0 APPLICABLE CODES.
  
 1E) PLEASE SEE SHEET T-1 UNDER APPLICABLE CODES (2)(E)
 UPDATE THE STANDARD ASCE 7-98,SEE SECTION 1609.1.1 &
 CHAPTER 35 REFRENECE STANDARDS.
  
 2) NOTE, IMPACT FEE STAMP AND RADON FEES WERE PAID
 UNDER FOUNDATION PERMIT # 07070220.
  
 3)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY FL S S. 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED. ALTHOUGH
 THERE IS A ON GOING FOUNDATION PERMIT, A SECOND
 AGREEMENT WILL BE REQUIRED SINCE THESE ARE STAND ALONE
 PERMITS.
  
 4) NOTEICE TO CONTRACTOR:109.3.10* IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE APPLICABLE
 PROPERTY OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO
 THE APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING
 STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS,EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 6) PLEASE REVIEW ALL SHEETS ARCHITTECTAL AND
 ENGINEERING SHEETS FOR THE REQUIRED ADDRESSIN THE
 TITLEBLOCK. FLORIDA ADMINISTRATIVE CODE 61G15-23.002 &
 61G1-16.004 , FBC 2004,
 110.1.2 & 106.5. NOTE SHEET S1 HAS 401 CLEMATIS ST ON
 SHEET.
  
 7) LS.1 VERSES A6.1 DETAIL# 01 THE RETAIL STORES 1.101
 & 1.102 BOTH INDICATE A 2 HR RATED WALL BETWEEN THE
 PARKING GARAGE AND RETAIL AREAS, A6.1 DOES NOT HAVE ANY
 WALL TAGS IDENTIFYING TYPES OF WALLS NOR RATING. FBC
 106.1.2 ADDITIONAL INFORMATION REQUIRED, TABLE 302.3.2
 & 706.3.6 & 708.1.
  
 8)LS.1 VERSES A6.1 DETAIL# 01 THE RETAIL STORES BOTH
 DO NOT INDICATE WALL RATINGS NOR WALL TAGS FOR THE
 TENANT SEPERATION WALLS BETWEEN THE TWO UNITS.FIRE
 PARTITIONS 708.1(5).
  
 9)PLANS FAIL TO PROVIDE THE OCCUPANCY SEPERATION
 BETWEEN THE RETAIL AREAS AND THE S2 STORAGE OCCUPANCY
 ON THE 2ND FLOOR, 711.3 FIRE RESISTANCERATINGS, SHEET
 A5-0.2 INDICATES THE USE OF
 HOLLOW CORE SLAB FOR A RATED ASSEMBLY PLEASE SEE
 721.2.2.1.1 FOR THE EQUIVALANT THICKNESS VALUE FOR TYPE
 OF SLABALSO SEE TABLE 721.2.2.1.
  
 10) SHEET A5-D.1 INDICATES THE USE OF T-JOIST FLOOR
 SYSTEM PLEASE PROVIDE THE HOURLY FIRE RATING FOR SUCH
 FLOOR SYSTEM , 721.2.2.1.2 / TABLE 721.2.2.1.
  
 11)LS.1 VERSES A6.1 DETAIL# 01 THE GENERATOR ROOM,
 LS.1 INDICATES A 2HR RATED WALL BETWEEN THE S2 STORAGE
 AND THE GENERATOR, SHEET A6.1 IT APPEARS THERE IS A
 LOUVER IN THIS WALL.
 SEE 702 FIRE DAMPERS, &716.3.1 FIRE PROTECTION
 RATING. FIRE DAMPERS SHALL HAVE THE MINIMUM FIRE
 PROTECTION RATING SPECIFIED IN TABLE 716.3.1 FOR THE
 TYPE OF PENETRATION.
  
 12) LS.1 VERSES A6.1 DETAIL# 01 THE EMERGENCY POWER
 SUPPLY ROOM # 1.106. LS.1 INDICATES A TWO HOUR RATED
 WALL WHERE AS THE DOOR SCHEDULE ON A-8.1 DOES NOT SHOW
 ANY FIRE RATING AT ALL.
 PLEASE SEE SECTION 715.3 AND TABLE 715.3.
  
 13) A6.1 DETAIL# 01 DOES NOT INDICATE WALL TAGS FOR THE
 2 HR RATED WALL SEPERATING THE S2 OCCUPANCY FROM THE
 SEPERATED USE ROOMS GENERATOR, ELECTRIC ROOM , ETC,
 PLEASE PROVIDE ADDITIONAL INFORMATION 106.1.2 & TABLE
 715.3 REQUIRED WALL RATINGS, MAIN ELECTRIC ROOM NFPA
 13:8.14.0, GENERATOR ROOM NFPA 110.7.2.2 & MAIN
 ELECTRIC ROOM NFPA 13.8.14.10.
  
 14)A6.1 DETAIL# 01 STORAGE ROOM 1.108 PLEASE PLACE
 WALL IDENTIFICATION TAGS ON COMMON WALLS TO THE S2
 ENCLOSED PARKING GARAGE WALLS. PLANS APPEAR TO HAVE
 OPENINGS IN THE EAST END OF THE STORAGE ROOM WALL, ARE
 THEY ENCLOSED OR RATED? WHAT TYPE OF STORAGE IS THIS S1
 OR S2? 106.1.2 ADDITIONAL INFORMATION REQUIRED.SECTION
 302.1.
  
 15) A6.1 DETAIL# 02 STORAGE ROOM 1.109 PLEASE INDICATE
 AS TO WHAT TYPE OF ITEMS ARE TO PLACED IN STORAGE
 CREATING EITHER A S1 OR S2 OCCUPANCY? SECTION302.1 .
  
 16) A6.1 DETAIL# 03 THE ELEVATOR MACHINE ROOM #
 2.003.1AND ROOM 2.005L DOESN'T INDICATE ANY WALL
 IDENTIFICATION TAGS NOR DOES THE DOOR SCHEDULE INDICATE
 A FIRE RATING ON DOOR# 2-003.1A SHEET A8.1.
 3006.4 MACHINE ROOMS AND MACHINERY SPACES. ELEVATOR
 MACHINE ROOMS AND MACHINERY SPACES SHALL BE ENCLOSED
 WITH CONSTRUCTION HAVING A FIRE-RESISTANCE RATING NOT
 LESS THAN THE REQUIRED RATING OF THE HOISTWAY ENCLOSURE
 SERVED BY THE MACHINERY.
  
 17) PLEASE PROVIDE COMPLIANCE WITH, 3002.4 ELEVATOR CAR
 TO ACCOMMODATE AMBULANCE STRETCHER . IN BUILDINGS FOUR
 STORIES IN HEIGHT OR MORE, AT LEAST ONE ELEVATOR SHALL
 BE PROVIDED FOR FIRE DEPARTMENT EMERGENCY ACCESS TO ALL
 FLOORS. SUCH ELEVATOR CAR SHALL BE OF SUCH A SIZE AND
 ARRANGEMENT TO ACCOMMODATE A 24-INCH BY 76-INCH (610 MM
 BY 1930 MM) AMBULANCE STRETCHER IN THE HORIZONTAL, OPEN
 POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL
 SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE).
 THE SYMBOL SHALL NOT BE LESS THAN 3 INCHES (76 MM) HIGH
 AND SHALL BE PLACED INSIDE ON BOTH SIDES OF THE
 HOISTWAY DOOR FRAME.
  
 18)3003.6.1 VENTS. HOISTWAYS OF ELEVATORS SERVING
 MORE THAN 3 FLOORS SHALL BEPROVIDED WITH MEANS OF
 VENTING SMOKE AND HOT GASES TO THE OUTER AIR IN CASE OF
 FIRE.
  
 19)3003.6.2 VENTS SHALL BE LOCATED BELOW THE FLOOR OR
 FLOORS AT THE TOP OF THE HOISTWAY, AND SHALL BE EITHER
 DIRECTLY TO THE OUTER AIR OR THROUGH NONCOMBUSTIBLE
 DUCTS TO THE OUTER AIR.
  
 20) A6.1 DETAILS 02 AND 03 BOTH INDICATE THE VERTICAL
 EXIT ENCLOSURES AND ELEVATOR HOIST WAYS AGAIN THERE ARE
 NO WALL TYPE IDENTIFICATION TAGS INDICATING THESE WALLS
 ARE 2 HR RATED WALLS AND OF WHAT TYPE OF CONSTRUCTION.
 THE LIFE SAFETY PLAN DOES IDENTIFY THEM AS TWO HR RATED
 BUT WHAT TYPE OF CONSTRUCTION. 707.4.
  
 21) PLEASE PROVIDE INFORMATION ON THE SPIRAL STAIRWAY,
 RISERS, TREAD DEPTH, HEAD ROOM ETC, 1009.9.1.
  
 22) DELETED.10-26-07
 23) SHEET A2.1 DETAIL# 02 PLEASE PROVIDE WHAT TYPE OF
 MATERIAL THE ARCHITECTURAL TRIM IS DEPICTED IN THIS
 PICTURE? AND HOW WILLIT BE ATTACHED TO THE STRUCTURE.
 1406.2.2.
  
 24)PLEASE PROVIDE INFORMATION FOR CODE COMPLIANCE ON
 VAN ACCESSIBILITY AND IN COMPLIANCE WITH 11-4.6.3 VAN
 ACCESSIBLITY REQUIREMENTS
  
 25) SHEET A3.2 PROVIDE THE WIND LOAD INFORMATION
 (CALCULATIONS) FOR THE ROOFTOP LIGHT POLES. ASCE 7-02.
  
 26) A4.3 INDICATES VARIOUS PRECAST PILASTER DETAILS BUT
 THERE IS NO DETAILS FOR INSTALLATION PLEASE PROVIDE
 METHOD OF ATTACHMENT, 1405.6/ 1405.7/ 1405.9 .
  
 27)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 ALL OF THE PRODUCT APPROVALS ARE STAMPED WITH
 THORTON-TOMASETTIS' SHOP DRAWING STAMP THAT THEY WERE
 REVIEWED. THE ISSUE THAT IS NOT COMMONLY KNOWN THAT THE
 OLDER MIAMI-DADE
 NOA'S THAT WERE TESTED BEFORE THE 2004 FBC MAY OR MAY
 NOT MEET THE CURRENT 2004 FBC. 1605.3.1.1 LOAD
 REDUCTIONS. BEFORE THE 2004 FBC THE MANUFACTURERS WERE
 ALLOWED TO TAKE
 1.33 STEEL INCREASES AND DID SO WITH THERE FASTENERS.
 THE NEWER MIAMI-DADE REPORTS AND THE OLDER REPORTS THAT
 ARE BEING UPDATED ARE BEING REVIEWED FOR THE ANCHOR
 CONNECTIONS. THE
 STATEMENTIS SHOWN UNDER C CALCULATION, REVISED
 ANCHOR CALCULATIONS THAT HAVE BEEN REVIEWED UNDER THE
 2004 FBC WILL STATE THE ANCHOR CALCULATIONS HAVE BEEN
 REVIEWED TO THE 2004 FBC.
 PLEASE REVIEW THE INGERSOLL- RAND AND THE TRAINER GLASS
 FOR THE ANCHOR CONNECTIONS MEETING 1605.3.1.1/ 2004
 FBC. THIS MAY AFFECT THE PRESSURES LISTED IN THE
 REPORT.
  
 28) SHEET S0.30 PROVIDES THE ELEVATIONS WITH THE
 ILLUSTRATED INTERIOR ZONES AS WELL AS THE END ZONES,
 THE PLANS DO FAIL TO PROVIDE THE ZONE LOCATION AND
 ASSOCIATEDPRESSURES FOR THE DOORS LOCATED ON THE ROOF
 TOP STAIR TOWERS. PLEASE PROVIDE THIS ADDITIONAL
 INFORMATION TO REVIEW FOR WIND PRESSURES. 1609. 6.1.2.
  
 29A)THE EVALUATION REPORT FROM INGERSOLL-RAND REPORT#
 S07-001 IS A COPY AND NEEDS TO BE AN ORIGINAL (3) FOR
 THRESHOLD BUILDING) SIGNED AND SEALED REPORTS. 29B)
 THIS REPORT INDICATESUNDER PRODUCT COMPARISON TO BE A
 INSWING DOOR WHERE AS UNDER EVALUATION FOR A POSITIVE
 WIND APPLICATION THE WIND LOAD APPLIED TO THE DOOR
 PANEL WOULD BE DISTRIBUTED AROUND THE FRAME EQUALLY,
 THIS WOULD REQUIRE THE DOOR & FRAME TO BE INSTALLED IN
 A OUTSWING INSTALLATION. PLEASE CORRECT STATEMENTS.
 29C) PLEASE PROVIDE CALCULATIONS INDICATING THE
 EXTRAPOLATION OF PRESSURES OR INTERPALATION OF
 PRESSURES, DEPENDING ON REPORT.
 29D) IT APPEARS THAT A LOCAL PRODUCT APPROVAL WILL BE
 REQUIRED, PLEASE FILL OUT FORM FOR A LOCAL PRODUCT
 APPROVAL FOR WEST PALM BEACH, SEE FORM ATTACHED.
  
 30) THE PRODUCT APPROVAL FOR TRAINER GLASS WILL REQUIRE
 FLORIDA APPROVAL COVERSHEETS, PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE STATE
 WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A
 COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE 9B-72.
  
 31) LOUVERS,THE PRODUCT APPROVAL THST WAS SUBMITTED
 FORAMERICAN WARMING AND VENTILATING UNDER FL# 5121 IS
 NOT THE REPORT THAT WASSPSECED ON SHEET A8.2 / W-12,
 NOTE THERE IS A
 W-13 AND NO REPORT NUMBER SPECIFIED?
  
 32) ROOFING, NO ROOFING REPORT WAS SUBMITTED EVEN
 THOUGH THERE IS A ROOFER SIGNER ON THE PERMIT
 APPLICATION.
 THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH THE
 FOLLOW ITEMS:
 __XX_ CONTRACTOR DID NOT PROVIDE PRODUCT APPROVAL
 REPORT.
 __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO
 BE USED.
 __XX_ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE
 2&3___ .
 __XX_ THE SYSTEM PROVIDED STATESLIMITATION# 7,
 SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISEDFASTENER SPACING,
 PREPARED , SIGNEDAND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOFCONSULTANT MAY BE
 SUBMITTED.
 __XX_ BE AWARE OF : THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCEDFASTENING ALLOWED.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2008-10-03 Cont ID  
Sent By dpalmer Date 2008-10-03 Time 13:06 Rev Time 1.00
Received By dpalmer Date 2008-10-03 Time 13:06 Sent To  
Notes
2008-10-03 13:06:59REV FOR CHNAGING DESIGNATION FOR *FUTURE RETAIL*

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2008-09-29 Cont ID  
Sent By dpalmer Date 2008-09-29 Time 14:11 Rev Time 0.00
Received By dpalmer Date 2008-09-29 Time 13:40 Sent To PC
Notes
2008-09-29 14:12:12REVISED COORDINATION STUDY.
 COMMENT #2 FROM PREVIOUS REVIEW WILL STILL NEED TO BE
 ADDRESSED BEFORE FINAL/CO.

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2008-09-29 Cont ID  
Sent By dpalmer Date 2008-09-29 Time 09:29 Rev Time 0.00
Received By dpalmer Date 2008-09-29 Time 09:29 Sent To PC
Notes
2008-09-29 09:29:46** DENIED **
  
 1) NOTE: PLEASE COORDINATE THE SELECTIVE COORDINATION
 STUDY WITH LATEST REVISED RISER ON FILE.
 PLEASE SEE SDP SWITCHBOARD WHICH INDICATES FOUR 125 AMP
 BREAKERS TO ELEVATOR EQUIPMENT. EVEN IF ONLY ONE OF
 THESE IS LEGALLY REQUIRED THE OTHER THREE MAY AFFECT
 THE COORDINATION OF THE SYSTEM.
 PLEASE VERIFY.
 700.27, 701.18, 240.12
  
 2) NOTE: PLEASE SEE THE LATEST ELECTRICAL RISER AS THIS
 INDICATES A 100 MCB FOR 10GH, YET COORDINATION STUDY
 SHOWS 60 AMP MCB. PLEASE SEE PANEL SCHEDULE AS THE
 LATEST REVISED PANEL SCHEDULE SHOWS THIS AS A 100AMP
 MAIN LUG ONLY PANEL.
 AS THE 10GH IS OF THE OPTIONAL STAND-BY SYSTEM, THIS IS
 NOT REQUIRED TO BE PART OF THE COORDINATION STUDY
 HOWEVER PLANS WILL NEED TO MATCH BEFORE CO. IF THIS
 WERE THE ONLY COMMENT A TCO COULD BE GRANTED AS THIS
 PARTICULAR PANEL IS NOT LIFE SAFETY OR LEGALLY
 REQUIRED.
  
 IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE TO
 CONTACT THIS OFFICE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2008-09-25 Cont ID  
Sent By btrobaug Date 2008-09-25 Time 09:16 Rev Time 0.00
Received By btrobaug Date 2008-09-25 Time 09:15 Sent To PC
Notes
2008-09-25 09:16:30 
 EXIT LIGHT REVISION./WRT.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2008-08-12 Cont ID  
Sent By dpalmer Date 2008-08-12 Time 10:22 Rev Time 0.00
Received By dpalmer Date 2008-08-12 Time 10:22 Sent To PC
Notes
2008-08-12 10:22:41 
 **DENIEDREVISION**
  
 ** PLEASE SEE SOME ITEMS FROM REVIEW DATED 6/25 ARE
 STILL IN NEED OF ADDRESSING.
  
 1) NOTE:PLEASE SEE PREVIOUS REVIEW WHICH STATED THE
 REVISED ENERGY CALCULATIONS WERE NEEDED DUE TO LIGHTING
 ETC BEING REVISED ON PLANS. THE RESPONSE LETTER
 MENTIONS TO SEE REVISED CALCULATIONS. HOWEVER PLEASE
 SEE THE PACKAGE AS ONLY THE CERTIFICATION SHEETS ALONG
 WITH SUMMARY SHEETS WERE SUBMITTED. PLEASE SEE SHEET
 TWO WHICH STATES THE INPUT DATA REPORT MUST BE
 SUBMITTED ALONG WITH COMPLIANCE REPORT. AS NO INPUT
 DATA REPORT WAS SUBMITTED A REVIEW OF THE SPECIFIC
 ITEMS ON PLANS CAN NOT BE REVISED AT THIS TIME.
 PLEASE BE SURE ALL REVISED LIGHTING ON PLANS ALONG WITH
 ALL OTHER COMPONENTS OF BUILDING REFLECTS THE INPUT
 DATA REPORT.
 13-400.3B, 13-415.2, 13-415.2.ABC.1.1, .1.2, AND .1.3.
  
 ** PLEASE SEE THE *CERTIFICATION SHEET* WHICH REQUIRES
 THE SIGNING, SEALING DATING AND OTHER INFORMATION TO BE
 COMPLETED. AS THESE DOCUMENTS ARE ALSO PART OF
 INFORMATION SENT TO THE STATE, THE CERTIFICATION SHEET
 NEEDS TO BE COMPLETED. SIGNING AND SEALING THE COVER
 SHEET DOES NOT PROVIDE THE INFORMATION ON THE
 CERTIFICATION SHEETS.
 13-103.1, FS 471.025
  
 2) NOTE: AS NOTED ON PREVIOUS REVIEW WHY WAS THE
 PHOTO-METRICS BEING SUBMITTED IF LIGHTING WAS NOT BEING
 REVISED? THE RESPONSE MENTIONS *INDUCTION LIGHTING *
 ETC.
 PLEASE BE SURE THERE IS COORDINATION BETWEEN ALL
 REVISED LIGHTING PLANS, PHOTO-METRICS AND CALCULATIONS
 AS NOTED ABOVE.
 FOR EXAMPLE:
 PLEASE SEE THE QUARTZ LIGHT FIXTURES AS NOTED ON
 PHOTO-METRICS ARE NOT THE SAME AS THE FIXTURES LISTED
 ON FIXTURE LEGEND FOR MANUFACTURE, WATTAGE ETC
  
 FOR EXAMPLE:
 PLEASE TAKE A LOOK AT THE FIXTURE DESIGNATIONS AND
 COORDINATED ANY CHANGES AS NEEDED.
  
  
 3) NOTE: PLEASE KNOW AT THIS TIME THERE ARE NO COMMENTS
 ON SHEETS 2.1,2.2,4.1,5.1 AND 6.1 HOWEVER BASED ON
 OTHER COMMENTSTHESE MAY OR MAY NOT BE REVISED.
 IF NO REVISIONS ARE MADE PLEASE BE SURE TO SUBMIT THESE
 SHEETS BACK WHEN OTHER CORRECTIONS.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-07-08 Cont ID  
Sent By dpalmer Date 2008-07-08 Time 15:25 Rev Time 0.00
Received By dpalmer Date 2008-07-08 Time 15:25 Sent To  
Notes
2008-07-08 15:25:48** DENIEDREVISIONS **
  
 1) NOTE: PLEASE COORDINATE THE COMMENTS FROM REV #5
 PREVIOUSLY SUBMITTED AND REVIEWED FOR ELECTRICAL
 6/26/08. THESE REVISIONS WERE SUBMITTED BEFORE COMMENTS
 FROM 6/26 WERE GENERATED.
 PLEASE ALSO SEE COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT PLANS, LAYOUT ETC.
 THIS IS FOR SHEETS E3.1 AND 4.1
  
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-06-25 Cont ID  
Sent By dpalmer Date 2008-06-25 Time 11:53 Rev Time 0.00
Received By dpalmer Date 2008-06-24 Time 17:01 Sent To  
Notes
2008-06-25 11:54:59** DENIEDREVIEW **
  
  
  
 1)NOTE: PLEASESEE SHEET E1.1 WHICH STATES REVISIONS
 DUE TO PERMIT COMMENTS HOWEVERTHERE IS NO RECORD OF
 ANY COMMENTS.
 PLEASE COORDINATE PLANS OR PROVIDE A RESPONSE FOR
 REVISED ITEMS TO CLARIFY.
 106.5, 106.1.1
  
 2) NOTE: PLEASE SEE THE STORAGE ROOM WHICH HAS NOW BEEN
 CHANGED TO THE *METER STORAGE* HOWEVER IS ALSO NOW A
 WORK SHOP OF SORTS.
 THIS ROOM HAS NOW BEEN AIR CONDITIONED WHICH WILL
 REQUIRE THE ENERGY CALCULATIONS TO BE REVISED. PLEASE
 SEE SHEET 3.1 WHICH DOES NOT HAVE THE REVISED ROOM
 LAYOUT.
 PLEASE COORDINATE PLANS.
 FBC 106.5,106.1.1,106.1.2
 FBC CHAPTER 13, 13-400.3.B.
  
 3) NOTE: PLEASE SEE SHEET E3.1 WHICH STATES A REVISION
 #5. THE ONLY REV #5 ON SHEET WAS UNDER ONE OF THE SCALE
 DETAILS. THIS SCALE DETAIL SHOWING 1/4INCH = 1FTIS
 THE SAME AS PREVIOUS PLANS WHICH INDICATED A REV #4
 WITH THE SAME LOCATION CONTAINING A CLOUD FOR REVISING
 THE SCALE.
 A REVISED PLAN ALONG WITH CLOUDS OR TRIANGLES SHOWING
 THE REVISED ITEMS NEEDS TO BE SUBMITTED. PLEASE KNOW
 ANY REVISIONS MAY ALSO BE NOTED IN A LETTER INFORMING
 THE REVIEWER OF CHANGE. THE LETTER IS NOT REQUIRED
 HOWEVER IS HELPFUL IN THE REVIEW PROCESS.
 FBC 106.1.1, 106.1.2, 106.5 FOR COORDINATION AND
 CLARITY OF RECORD PLANS.
  
 4) NOTE: THE RISER HAS BEEN REVISED AND COORDINATE WITH
 PANEL SCHEDULES ETC ARE NEEDED.
 PLEASE SEE 1EGH SHOWS THIS PANEL FED FROM EDP HOWEVER
 EDP NO LONGER EXISTS.
 PLEASE SEE SDP SHOWS BEING FED FROM EM ATS HOVER BASED
 ON THE RISER THIS IS NO LONGER FED FROM THE EM ATS.
 408.4
 FBC 106.1.1, 106.1.2, 106.5 FOR COORDINATION AND
 CLARITY OF REVISED PLANS.
  
 5) NOTE: PLEASE SE THE MGP SHOWS SOME SORT OF
 DISCONNECTING MEANS ON RISER FOR FEEDERS FROM THE
 GENERATOR. BASED ON THE MGP PANEL SCHEDULE THIS IS A
 MAIN LUG ONLY PANEL.
 AS SHOWN ALL BREAKERS ON LOAD SIDE OF THE GENERATOR
 BREAKERS ARE NOW DISCONNECTS FOR THE GENERATOR
 FEEDERS.
  
 PLEASE BE SURE TO CLARIFY THE DISCONNECT SHOWN ON THE
 RISER CIRCLED IN RED ON ONE SET.
 PLEASE LABEL WITH NOTES FOR SIGNAGE THAT THE BREAKERS
 ON THE GENERATOR ARE NOW THE NEW DISCONNECTS FOR THE
 EMERGENCY POWER. THIS IS BASED ON THE RISER AS SHOWN.
 IF EQUIPMENT CHANGES OR THERE IS ACTUALLY A DISCONNECT
 WHICH IS NOT LABELED, THEN THIS COMMENT MAY CHANGE.
 PLEASE CALL TO GO OVER COMMENT.
 PLEASE VERIFY IF THE MGP MEETS SWITCHBOARD OR PANEL
 BOARD. PLEASE SEE COMMENTARY OF 700.9B BELOW.
 FBC 106.1.1, 106.1.2 FOR CLARITY AND COORDINATION. NEC
 230.2E, 700.9B (FOR MGP) , 700.8, 701.9, 702.8
  
 6) NOTE: PLEASE KNOW AS REDLINED ON ORIGINAL PLANS: NO
 LOW VOLTAGE PERMITS HAVE BEEN APPLIED FOR OR ISSUED FOR
 THE LOW VOLTAGE SYSTEMS SHOWN ON PLANS.
 THIS IS GIVEN FOR INFORMATION SO PERMIT CAN BE APPLIED
 FOR BEFORE SCOPE OF WORK COMMENCES.
  
 7) NOTE: PLEASE VERIFY WHY PHOTO-METRICS FOR ENTIRE
 BUILDIGN ARE BEING SUBMITTED. IF LIGHTING PLANS ARE NOT
 BEING REVISED FORAREAS AS SHOWN THEN REVISED
 PHOTO-METRICS ARE NOT NEEDED.
  
  
 **WHERE AN ALTERNATE POWER SOURCE SUPPLIES A
 SWITCHBOARD FROM A SINGLE FEEDER OR FEEDERS IN
 PARALLEL, THAT SWITCHBOARD MAY FURTHER DISTRIBUTE AND
 PROVIDE POWER FOR THE EMERGENCY, LEGALLY REQUIRED, AND
 OPTIONAL STANDBY SYSTEMS.
 SWITCHBOARDS PROVIDE THE PHYSICAL SEPARATION
 REQUIREMENTS OF BOTH SYSTEM AND WIRING FROM A COMMON
 POWER SOURCE. THIS PHYSICAL SEPARATION CANNOT OCCUR
 WITHIN A PANELBOARD ENCLOSURE BECAUSE OF ITS OPEN
 DESIGN. INDIVIDUAL OVERCURRENT SECTIONS CAN SUPPLY
 EMERGENCY, LEGALLY REQUIRED, AND OPTIONAL STANDBY
 TRANSFER SWITCHES.**
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-04-14 Cont ID  
Sent By dpalmer Date 2008-04-14 Time 16:30 Rev Time 0.00
Received By dpalmer Date 2008-04-14 Time 16:30 Sent To  
Notes
2008-04-14 16:31:13OWNER AGENT TO SIGN ENERGY CALCULATIONS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-04-01 Cont ID  
Sent By dpalmer Date 2008-04-01 Time 19:54 Rev Time 0.00
Received By dpalmer Date 2008-04-01 Time 19:54 Sent To  
Notes
2008-04-01 19:54:58** DENIED4TH REVIEW**
  
 ** PLEASE SEE THERE ARE COMMENTS FROM THE PREVIOUS
 REVIEWS WHICH ARE STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE THE FIRST TWO REVIEWS REQUESTED THE
 ENERGY CALCULATIONS TO BE SUBMITTED AND NOT UNTIL THE
 THIRD REVIEW WERE THESE DOCUMENTS SUBMITTED. THE THIRD
 REVIEW WAS THE FIRST TIME THIS OFFICE WAS TO REVIEW
 PLANS AND CALCULATIONS. THERE WERE COMMENTS WITH
 RESPECT TO THE TWO COMPLETELY DIFFERENT SETS OF
 CALCULATIONS SUBMITTED. THERE WERE ALSO COMMENTS WITH
 RESPECT THAT ALL INFORMATION CONTAINED ON THE PLANS
 NEEDS TO COORDINATE WITH THE INPUT DATA REPORT. SOME
 EXAMPLES WERE GIVEN ON BOTH SETS OF CALCULATIONS
 PREVIOUSLY SUBMITTED FOR THE THIRD REVIEW. PLEASE SEE
 THAT PLANS AND LIGHTING ON THE CALCULATIONS STILL DO
 NOT COORDINATE. PLEASE SEE THERE ARE FIXTURES ON PLANS
 WHICH DO NOT CONTAIN DESIGNATION OR ARE NOT THE SAME AS
 PLACED IN THE INPUT DATA REPORT. THE INPUT DATA REPORT
 WILL BE NOTED AS IDR FOR THE REMAINDER OF THIS
 COMMENT.
 THIS OFFICE WILL GIVE SOME EXAMPLES ONCE AGAIN:
 EXAMPLE:
 PLEASE SEE THE PLANS AND DESIGNATIONS ON FIXTURES FOR
 ROOF TOP FLOODS. (ALSO NOTED AS 20FT POLES) WHAT IS THE
 WATTAGE ON THESE FIXTURES? PLEASE TAKE A LOOK AT THE
 IDR AS THESE FIXTURES COULD NOT BE IDENTIFIED.
 EXAMPLE:
 PLEASE SEE THE IDR WHICH CONTAINS 800W FIXTURES YET THE
 PLANS NOR THE FIXTURE LEGEND SHOW ANY 800W FIXTURES.
 EXAMPLE:
 PLEASE SEE THE IDR WHICH CONTAINS 4000W FIXTURES YET
 THE PLANS NOR THE FIXTURE LEGEND SHOW ANY 4000W
 FIXTURES.
 EXAMPLE: PLEASE SEE THE IDR REPORT INDICATES 169 W AND
 168W FIXTURES, ARE THESE THE *C-EM* FIXTURES? EXAMPLE:
 PLEASE SEE THE FIXTURE *A*, THESE ARE NOTED ON THE
 FIXTURE LEGEND AS 150W/VA RATED FIXTURES, YET THE *AE*
 FIXTURES ARE NOTED ON FIXTURE LEGEND AS *Q100* AND THE
 MANUFACTURES CATALOG INFORMATION STATES 150W. WHICH
 ONES ARE THESE AND PLEASE SEE THE TOTAL AMOUNT OF *A*
 AND *AE* FIXTURES ON PLANS COMPARED TO THE IDR.
 EXAMPLE:
 PLEASE TAKE A LOOK AT THE FIXTURE *B* AND *BE*. EACH OF
 THESE FIXTURES ARE SHOWN RATED ON MANUFACTURE CATALOG
 INFORMATION AS 200VA RATED, HOWEVER BASED ON THE
 FIXTURE LEGEND THE *B* IS SHOWN WITH A 200PMH AND THE
 *BE* FIXTURES ARE SHOWN LIKE THE *AE* FIXTURES WITH A
 Q-100. WHAT ARE THESE? HOW ARE THESE ARE ALL FIGURED
 INTO THE IDR? THE IDR DOES SHOW SOME 100W FIXTURES
 HOWEVER ONLY FOUR.
 EXAMPLE:
 PLEASE SEE IN ZONE #2 WHICH SHOWS 9-32W FIXTURES ON THE
 IDR HOWEVER THE AMOUNT OF THESE FIXTURES BASED ON PLANS
 IS HIGHER. PLEASE TAKE A LOOK AT THE LIGHTING ON THE
 SHEET E1.1 FOR THE ELEVATOR MACHINE ROOMS. THESE SAME
 ROOMS ON THE SHEET E2.2 SHOW MORE FIXTURES THAN ON E1.1
 AND ALSO THESE FIXTURES IN THESE ROOMS ARE LABELED AS
 *B* FIXTURES. HOW ARE THESE NOW *B* FIXTURES IF THE *B*
 FIXTURES ON THE FIXTURE LEGEND ARE 200W MH? PLEASE ALSO
 CORRELATE THE AMOUNT OF FIXTURES.
 EXAMPLE:
 PLEASE SEE THE FIXTURES FOR IN ZONE #4 (OFFICE). PLEASE
 SEE THE AMOUNT OF 64W FIXTURES ON PLANS IS HIGHER THAN
 THE IDR WHICH SHOWS ONLY ONE OF THESE FIXTURES.
 EXAMPLE:
 PLEASE SEE THE TYPE OF FIXTURE BULBS SHOULD COORDINATE
 WITH PLANS. ALL FIXTURES ARE NOTED ON THE IDR AS THE
 FOLLOWING: FLUORESCENT OR METAL HALIDE, HOW IS THIS
 POSSIBLE?
 EXAMPLE:
 PLEASE SEE THE LIGHTING CONTROL METHODS ON THE IDR
 STATES *CENTRAL CONTROL* FOR ALL PARKING LEVEL
 LIGHTING. HOW IS THIS POSSIBLE? ROOF TOP/OUT-DOOR
 LIGHTING WHICH WILL NOT BE INSIDE THE ENCLOSED GARAGE
 WHICH IS GREATLY AFFECT BY DAYLIGHT SHALL BE TURNED OFF
 AS REQUIRED PER 13-415.1.ABC.1.4. SOME OF THE LIGHTING
 ON PLANS DOES THIS AND THE IDR DOES SHOW PHOTO-SENSOR
 CONTROL FOR EXTERIOR LIGHTS ONLY. IN EITHER CASE, THE
 LIGHTING ON PLANS IS NOT ON CONTROL BY CENTRAL
 STATION.
 EXAMPLE:
 PLEASE SEE THE PLANS DOES INCLUDE AN ELECTRIC WATER
 HEATER, HOWEVER THE IDR IS *BLANK*. HOW IS THIS
 POSSIBLE?
 EXAMPLE:
 PLEASE SEE THE PLANS CALL FOR FIXTURES *H* FOR THE
 EXTERIOR AND A NUMBER UNDER THE FIXTURE LEGEND AS A
 *T5C40*. THE ONLY INFORMATION ON A *T5C40* IS THIS IS A
 175W MH BULB, YET THE IDR DOES NOT CONTAIN AN 175W
 BULBS ON THE IDR. PLEASE SEE THE LOAD ON CIRCUIT
 *INGH-15* DOES NOT CORRESPOND TO WHETHER OR NOT THESE
 ARE 40W FIXTURES OR 175W FIXTURES. PLEASE BE SURE TO
 ADJUST ANY LOAD CALCULATIONS ONCE DETERMINED. PLEASE
 SEE FBC 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
 13-400.3.B, 13-415.1.B, 13-412 ETC
  
  
 ** THESE ARE SOME EXAMPLES*
 PLEASE BE SURE TO GO THROUGH ALL LIGHTING ON PLANS;
 PLEASE BE SURE TO GO THROUGH ALL CALCULATIONS AND THE
 IDR. PLEASE BE SURE TO ADJUST PHOTO-METRICS ONCE
 COORDINATION IS COMPLETED.
 IT IS IMPORTANT TO NOTE THAT ALL INFORMATION ON THE IDR
 NEEDS TO COORDINATE WITH PLANS NOT ONLY THE COMMENTS
 MADE FOR ELECTRICAL. HOW IS IT POSSIBLE THAT THE IDR
 DOES NOT CONTAIN MANY OTHER DESIGN ASPECTS FOR OTHER
 TRADES SUCH AS BUILDING COMPONENTS?
  
 2) NOTE: THIS IS ONLY BEING NOTED: THE FIXTURES IN
 STAIRS SHOWN AS D AND DDE CONTAIN 3-32W BULBS?
  
 3) NOTE: PLEASE BE SURE THE CERTIFICATION SHEET
 CONTAINS THE SIGNATURE FROM THE OWNER'S
 REPRESENTATIVE.
 FBC 13-103.1
  
 4) NOTE: PLEASE SEE NOTICE IS NOW BEING GIVEN TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 THIS IS ONLY A NOTICE AT THIS TIME. THE FIRST TWO
 REVIEWS REQUESTED THE CALCULATIONS.
 THE CALCULATIONS HAVE NOW ONLY BEEN REVIEWED TWICE,
 PLEASE BE SURE ALL PLANS AND CALCULATIONS COORDINATE ON
 THE FOLLOWING REVIEW.
 ONE COPY OF PLANS AND THE CALCULATIONS SUBMITTED MAY BE
 RETAINED BY THIS OFFICE.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-02-16 Cont ID  
Sent By dpalmer Date 2008-02-16 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2008-02-16 Time 16:08 Sent To  
Notes
2008-02-16 16:08:26** DENIED 3RDREVIEW **
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 ARE NOT CODE COMPLIANT. THE TWO PREVIOUS REVIEWS
 REQUESTED ENERGY CALCULATIONS AND THIS IS THE FIRST
 TIME THESE ARE BEING SUBMITTED FOR REVIEW.
 NOW TWO COMPLETELY SEPARATE SETS ARE BEING SUBMITTED.
 ONE FOR THE ADMINISTRATIVE OFFICE SPACE.
 ONE FOR THE PARKING GARAGE.
 PLEASE SEE THAT THE CALCULATIONS TO BE SUBMITTED ARE
 FOR ONE BUILDING AND STRUCTURE. THE FOLLOWING WILL BE
 BROKEN UP INTO SECTIONS FOR NOTES AND THE INPUT DATA
 REPORT WILL BE NOTED AS IDR.
  
 A) PLEASE SEE THE CALCULATIONS WHICH WERE SUBMITTED FOR
 THE ADMINISTRATIVE OFFICE SPACES ARE SHOWING ONLY TWO
 INTERIOR LIGHT FIXTURES. TO BE EXACT THEY SHOW 2-35
 WATT FIXTURES WITH A TOTAL OF 70WATTS ON THE SUMMARY
 SHEETS AS WELL AS THE IDR. THESE CALCULATIONS ARE
 SUBMITTED AND SIGNED AND SEALED BY MR. WU.
 HOW IS THIS POSSIBLE WHEN THE PLANS SHOW DOZENS OF
 FIXTURES IN THESE SAME OFFICES??
 PLEASE SEE 13-400.3.B, 13-415.1.B, 13-415.2
  
 B) PLEASE SEE THE CALCULATIONS FOR WHICH ARE REQUIRED
 TO HAVE THE CERTIFICATION SHEET FILLED OUT IS NOT
 DONE.
 PLEASE KNOW AS THIS SHEET IS SENT INTO THE STATE FOR
 AUDITING ALONG WITH THE COVER SHEET ALL INFORMATION ON
 THE CERTIFICATION SHEET ALONG WITH BEING SIGNED, DATED
 AND SEALED NEEDS TO BE DONE.
 PLEASE BE SURE THE OWNER AGENT IS FILLED OUT AND
 SIGNED.
 FBC 13-103.1.1.1, FS 471.025, FAC 61G15-23.002
  
 C) PLEASE SEE THE IDR REPORT FOR EXTERIOR SUBMITTED FOR
 GARAGE NEEDS TO BE COORDINATE WITH THE ELECTRICAL
 PLANS.
 PLEASE SEE FOR EXAMPLE: EXTERIOR IDR WHICH ONLY SHOWS
 26-H FIXTURES WHICH IS OK, HOWEVER WHERE ARE THE
 J-FIXTURES?
 PLEASE SEE THE INTERIOR LIGHTING OF THE PARKING GARAGE
 DOES NOT MATCH WITH THE COUNT OF FIXTURES, THE WATTAGE
 OF FIXTURES AND THE METHOD OF CONTROL.
 FOR EXAMPLE:PLEASE SEE THE IDR DOES NOT CONTAIN ANY
 150W OR 100W FIXTURES, YET THE FIXTURE LEGEND CONTAINS
 THESE.
 FOR EXAMPLE: PLEASE SEE THE IDR SHOWS 16-300W FIXTURES,
 HOWEVER THE FIXTURE LEGEND DOES NOT SHOW ANY 300W
 FIXTURES.
 FOR EXAMPLE: THE IDR SHOWS METHODS OF CONTROL AS
 DAYLIGHTINGON/OFF W/ OCCUPANCY SENSORS, PROGRAMMABLE
 ETC HOWEVER BASED ON PLANS AND KNOWN TO THIS OFFICE
 MANY OF THESE LOCATIONS ARE MANUAL ON/OFF, PHOTO-SENSOR
 CONTROL, OR OCCUPANCY SENSOR WITHOUT DAYLIGHTING.
  
 D) PLEASE KNOW A NOTE WHICH WAS NOT MENTIONED BUT GIVEN
 FOR INFORMATION. IF ANY LIGHTING IS DONE FROM AN
 ASTRONOMICAL TIME CLOCK, BATTERY BACK OF CONTROLS IS
 REQUIRED FOR TEN HOURS. THIS IS ONLY NOTED AS PLANS
 INDICATE PHOTO-SENSOR CONTROLS FOR LIGHTING CONTROL
 PANEL. 13-415.1.ABC.1.4
  
 ** PLEASE COORDINATE ENERGY CALCULATIONS AND SUBMIT
 ONLY ONE. ** THERE ARE OTHER FIXTURES WHICH NEED
 COORDINATION.
  
 2) NOTE: PLEASE SEE OFFICE AREAS WHICH SHOW ALL
 LIGHTING BEING CONTROLLED BY SENTRY SWITCHING AND OVER
 RIDES.
 IN MEETING HELD BEFORE PLANS WERE RESUBMITTED THE
 COMMENT WITH RESPECT TO EMERGENCY LIGHTING FOR EGRESS
 TO CONTROLS WAS BROUGHT UP. IF AN OCCUPANT IS LOCATED
 IN ANY AREA OF THESE OFFICES (EGRESS PATHS) AND TIME
 SWEEPS LIGHTING OFF, AN OCCUPANT WOULD BE IN TOTAL
 DARKNESS IN ORDER TO FIND THEIR WAY TO AN OVER RIDE.
 THIS OFFICE WILL REQUIRE OCCUPANCY SENSORS OF SOME TYPE
 FOR MINIMUM EGRESS TO OVER RIDES AS STATED IN THE
 FOLLOWING SECTIONS OF THE FBC AND LIFE SAFETY CODES.
 **PLEASE SEE FBC 1006.1.2 AND NFPA-101 7.8.1.2.2 WITH
 RESPECT TO AUTOMATED DEVICES IN EGRESS PATHS. THIS IS
 PERMITTED BY BOTH CODES HOWEVER THE COVERAGE OF SUCH
 UNITS SHALL BE SUFFICIENT FOR ALL AREAS, THE DEVICES
 ARE REQUIRED TO BE 15MINS OF TIME FOR ON AND SHALL ALSO
 BE FAIL SAFE ON.
 PLEASE KNOW AS MENTIONED ON PREVIOUS PROJECTS WITH
 RESPECT TO FBC AND CHAPTER 13 THIS AHJ DOESHAVE AN
 ISSUE WITH NIGHT LIGHTS AS LONG AS THE LIGHTING BEING
 LEFT ON DOES NOT EXCEED THE MINIMUM LEVELS OF 1FT
 CANDLES WITHIN REASON FOR EGRESS AREAS.
 AS SHOWN AT THIS TIME, AN OCCUPANT ON STAIRS WOULD BE
 OK AS A NIGHT LIGHT WAS DESIGNATED AND ADDED TO PLANS.
 PLEASE SEE SOME OTHER EGRESS PATHS MAY NOT HAVE ANY
 AMBIENT LIGHTING FROM OUTSIDE OR OTHER AREAS TO PROVIDE
 NEEDED MINIMUM.
 PLEASE INCLUDE OCCUPANCY DEVICES OR OTHER MEANS.
 ** PLEASE KNOW THIS MAY BE PART OF A PROVISO IN ORDER
 TO NOT HAVE TO REPRINT SHEETS HOWEVER COMMENT NUMBER 1
 ABOVE WILL KEEP FROM ISSUANCE AT THIS TIME.
  
 ** MAY CALL TO GO OVER.
  
 ** A CALL WAS PLACED TO THE ENGINEERS OFFICE AS OF
 REVIEW AND LEFT VOICEMAIL.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-26 Cont ID  
Sent By dpalmer Date 2007-12-26 Time 14:04 Rev Time 0.00
Received By dpalmer Date 2007-12-25 Time 13:01 Sent To  
Notes
2007-12-26 14:04:50 
 *** DENIED2ND REVIEW***
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM THE
 PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE AS STATED ON PREVIOUS REVIEW THERE WERE
 ITEMS NOT YET SUBMITTED FOR REVIEW WHICH COULD CREATE
 NEW COMMENTS. THIS WILL ALSO REMAIN AS THERE ARE NEW
 ITEMS ONLY NOW BEING SUBMITTED FOR THE FIRST REVIEW
 ALONG WITH ITEMS WHICH HAVE STILL NOT BEEN SUBMITTED.
 REVIEW COMMENTS CAN ONLY BE MADE ON PLANS AND
 DOCUMENTATION PROVIDED.
  
  
 1) NOTE:THIS NOTE REMAINS AS THERE ARE STILL CODES
 REFLECTED ON PLANS WHICH ARE NOT CURRENT OR LATEST
 ADOPTED EDITIONS AS PREVIOUSLY NOTES: FOR EXAMPLE:
 PLEASE SEE LS0.0 WHICH SHOWS THE 2002 NEC/ NFPA-70.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE
 THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC
 FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE
 ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2002 NFPA-110
 2003 NFPA-20
  
 ** PLEASE SEE FOR EXAMPLE THE T-1 SHEET WHICH CONTAINS
 CODE WHICH IS NOT ACCURATE OR NO LONGER ADOPTED BY THE
 STATE.
 PLEASE SEE THE 2002 NEC NOTED, PLEASE SEE A 2004
 NFPA-101 WAS NOTED AND 2003 REVISIONS TO THE FBC.
 PLEASE SEE SOME OF THE CODE ON LS SHEET HAS BEEN
 UPDATED HOWEVER LS SHEET STILL INDICATES SOME CODE NO
 LONGER IN ADOPTION.
 ** MANY OF THESE ARE OK ON ELECTRICAL PLANS.
  
 2) NOTE: PLEASE SEE THE PERMIT APPLICATIONS SUBMITTED
 AS PREVIOUSLY NOTED WERE NOT CORRECTED. PLEASE SEE THE
 DUPLICATE APPLICATION WHICH HAS CONTRACTORS SIGNED
 STILL NEEDS TO BE NOTARIZED.
 THIS WAS NOTED ON PREVIOUS REVIEW NOTE #34.
  
 3) NOTE: PLEASE SEE FPL VAULT IS STILL SHOWING POWER
 BEING FED INTO THIS ROOM WHICH IS NOT PERMITTED PER FPL
 VAULT STANDARDS AND VAULT SPECIFICATIONS. PLEASE SEE
 E2.1, REDLINED SET FOR THIS ENLARGED ROOM LAYOUT.
 ** PREVIOUS NOTE #6 **
  
 4) NOTE:PLEASE SEE SHEET E2.1, WHAT IS THE MSBE-3
 DESIGNATION ON THE PLANS AT THE FIRE PUMP ROOM?
 IT IS UNCLEAR WHAT THIS IS AT THIS TIME.
  
 5) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR
 EGRESS PATHS WHICH MEET THE MINIMUM LIGHTING LEVELS AS
 REQUIRED PER NFPA-101 7.8 AND 7.9.
 PLEASE SEE 7.8.1.3, 7.9.2.2
 THE RESPONSE LETTER MENTIONS THIS WILL BE DONE AT A
 LATER DATE; HOWEVER THIS IS REQUIRED AT THIS TIME TO
 MEET THE MINIMUM FOR LIFE SAFETY.
 PLEASE SEE THE LIGHT FIXTURES SHOWN ON PLANS DO NOT
 CORRELATE WITH THE FIXTURE LEGEND.FOR EXAMPLE: PLEASE
 SEE B-EM WHICH IS NOT LISTED.
 PLEASE PROVIDE INFORMATION ON THE HID FIXTURES FOR BACK
 UP AND TIME RESPONSE AS THESE ARE LIFE SAFETY FIXTURES.
 HOW WILL THE FIXTURE PROVIDE REQUIRED LIGHTING IN THE
 TIME GIVEN IF THESE ARE HID?
 PLEASE SEE THE LIGHTING IN STAIRS STILL SHOW A STANDARD
 FIXTURE WITH NO BATTERY BACK UP OF ANY KIND. BATTERY
 BACK UP FOR THE 1FT CANDLE MINIMUM WILL BE REQUIRED.
 PLEASE SEE THE ROOMS ARE PREVIOUSLY SPECIFIED WILL
 REQUIRE BATTERY BACK UP FIXTURES OF SOME KIND. THE REST
 OF THE RESPONSE STATES A COMMENT ABOUT THE STAIRS.
 THE SECTION WITH RESPECT TO THE SPIRAL STAIR HAS BEEN
 REMOVED AND REQUIRED EGRESS WAS CONFIRMED WITH THE
 BUILDING REVIEWER.
 LS 101 7.8, 7.9 AND SECTIONS GIVEN IN PREVIOUS REVIEW
 NOTES BELOW.
 ** PREVIOUS REVIEW NOTES**
 MOST OF THESE WERE SUBMITTED HOWEVER PLEASE SEE THE
 MINIMUM AVERAGE ON SHEETS FOR NORMAL DO NOT MEET THE
 MINIMUM LEVELS.
 PLEASE SEE THE FOLLOWING LOCATIONS ARE REQUIRED TO
 CONTAIN SOME SORT OF BATTERY BACK UP LIGHTING FIXTURE.
 THE STAIR TOWERS WILL REQUIRE A BATTERY BACK UP FIXTURE
 OF SOME TYPE TO MEET THE MINIMUM OF 1FT CANDLE LEVEL
 UNDER EMERGENCY.7.8.2.1, 7.9.2.2
 PLEASE SEE THE OTHER LOCATIONS WILL BE THE GENERATOR
 ROOM, FIRE PUMP ROOM, MAIN ELECTRICAL ROOM, EMERGENCY
 MAIN ELECTRICAL ROOM, AND THE ELEVATOR EQUIPMENT ROOMS.
 (SOME OF THESE MAY ALREADY SHOW A BATTERY BACK UP
 FIXTURE, BUT MOST DO NOT).
 700.12F.
 PLEASE SEE 700.16 FOR THESE SAME ROOMS.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE #8 WITH RESPECT TO
 THE WIND LOADS ON ROOF TOP POLES WITH THE EFFECTIVE
 PROJECTED AREA. THE LIGHT POLE DETAIL ON SHEET 7.1 DOES
 NOT CORRELATE WITH THE AMOUNT OF LIGHTING FIXTURES
 SHOWN ON POLES ON E1.2.
 RESPONSE MENTIONS CALCULATIONS SUBMITTED, HOWEVER THE
 LOCATION IN BINDER WHICH IS LABELED FOR POLE
 CALCULATIONS IS EMPTY??
 PLEASE KNOW THE ROOF TOP LIGHTING POLES WILL BE
 REQUIRED TO HAVE STRUCTURAL WIND LOAD CALCULATIONS AND
 WILL BE REVIEWED BY THE BUILDING REVIEWER.
 ** THIS IS NOTED FOR INFORMATION.
  
 7) NOTE:PLEASE SEE PREVIOUS NOTE #10. THE CODE
 SECTIONS GIVEN WERE FOR REQUIRED DEDICATED CIRCUITS.
 PLEASE SEE THE RESPONSE MENTIONS THIS WAS DONE.
 PLEASE SEE THE FOLLOWING FOR A COUPLE OF EXAMPLES:
 PLEASE SEE E1.1, AS CIRCUIT 1EGL-1 STILL FEEDS ELEVATOR
 PITS ON NORTH SIDE AS WELL AS SOUTH SIDE ELEVATOR
 PITS.
 PLEASE SEE CIRCUIT 1EGH-19 AS THIS CIRCUIT IS SHOWN ON
 E2.2 AS FEEDING BOTH ROOMS ON NORTH AND SOUTH SIDE
 ELEVATOR ROOMS.
 PLEASE SEE THE FOLLOWING COMMENT AND THE NOTE FROM
 PREVIOUS REVIEW.
  
 8) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #13. SAME
 COMMENT.
 RESPONSE MENTIONS TO SEE E1.1 AND DETAIL 01 AND ALSO
 SAYS TO SEE E0.1?
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 620.23 AS THE EXPLANATORY NOTE IN THE
 HANDBOOK FOR ELEVATOR PIT LIGHTING REQUIRES A 5FT
 CANDLE LIGHTING LEVEL.
 PLEASE SEE THE FOLLOWING WHICH WAS EXTRACTED FOR THIS
 SECTION ON THE NEC.
 *ASME A17.1-2004, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX)
 AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE
 EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.*
  
 9) NOTE: PLEASE SEE LIGHTING SYSTEM IN OFFICES AS SOME
 AREAS DO NOT SHOW CONTROL/COMPLETED SYSTEM. PLEASE SEE
 SHEET E6.1 FOR EXAMPLE AS THE LCP IS BASICALLY BLANK.
 WHAT IS THIS?
 PLEASE SEE ALL AREAS PER CODE NOT DONE.
 PLEASE SEE NOTES FROM PREVIOUS REVIEW EVEN GAVE
 EXAMPLES AND SPECIFIC ROOMS SUCH AS RETAIL SPACES, YET
 NO CHANGES WERE MADE.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND 1.3.
  
 10) NOTE: PLEASE SEE MISSING ENERGY CALCULATIONS/
 LIGHTING PERFORMANCE CALCULATIONS PER 13-415.2 AND
 13-415.2.ABC.1.3 ETC. RESPONSE MENTIONS TO SEE ATTACHED
 CALCULATIONS HOWEVER THIS REVIEWER HAS GONE THROUGH ALL
 BOOKS AS SUBMITTED. PLANS DO NOT SHOW MINIMUM
 COMPLIANCE FOR MAXIMUM LIGHTING LEVELS FOR INTERIOR OR
 EXTERIOR LIGHTING.
 PLEASE SEE SOME AREAS OF THIS BUILDING WILL HAVE
 CONDITIONED SPACE.
  
 11) NOTE: PLEASE SEE PREVIOUS NOTE #17.
 PLEASE PROVIDE COMPLETED INFORMATION FOR FIRE PUMP AND
 LOCKED ROTOR OVER CURRENT PROTECTION AND AMPERAGES. THE
 NOTE HERE FROM PREVIOUS REVIEW IS BASICALLY THE SAME.
 THE RESPONSE MENTIONS THESE ITEMS WERE REVISED AND
 ADJUSTED HOWEVER PLEASE SEE RISER SHEET E5.1. ??
 PLEASE SEE FP SHEET FP0.1 AS THIS SHEET STILL SHOWS THE
 SAME INFORMATION FROM PREVIOUS REVIEW WHICH DOES NOT
 CORRELATE WITH ELECTRICAL SHEETS NOR DOES IT COORDINATE
 WITH THE FIRE PUMP SUBMITTALS.
 PLEASE ADJUST PLANS AND IF THERE IS ANY QUESTION ON
 WHAT IS MEANT FROM THE TYPED COMMENT, PLEASE CALL TO GO
 OVER.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NEC 695.4B1, 9.3.2.2.3.2(A), (B) ETC PLEASE
 SEE THE ELECTRICAL PLANS INDICATE A DISCONNECT WITH
 OVER CURRENT PROTECTION AHEAD OF THE FIRE PUMP
 CONTROLLER WHICH WILL ALSO CONTAIN OVER CURRENT
 PROTECTION.
 PLEASE KNOW THERE MAY NOT BE OVER CURRENT PROTECTION ON
 THE LINE SIDE OF THE FIRE PUMP CONTROLLER. THE TYPICAL
 LISTED FIRE PUMP CONTROLLER CONTAINS THE LOCKED ROTOR
 CURRENT SETTING FOR THE SELECTED PUMP AND ASSEMBLY.
 10.4.4.1 NFPA-20
 PLEASE ALSO SEE THE FIRE PUMP IS BEING SHOWN AS 60 HP
 ON FP SHEETS AND 75HP ON ELECTRICAL SHEETS.
 PLEASE SEE PROVIDE INFORMATION ON WHAT TYPE OF BREAKERS
 ARE ON THE SECONDARY EMERGENCY SIDE FOR FIRE PUMP
 POWER. AS THE FIRE PUMP IS BEING FED THROUGH A TOTAL OF
 THREE BREAKERS ON THE EMERGENCY SIDE, THESE MAY CREATE
 AN ISSUE WITH SELECTIVE COORDINATION.
 PLEASE SEE THESE BREAKERS ARE TYPICALLY MAGNETIC TYPE.
 PLEASE SEE NEC 695 AND NFPA-20CHAPTER 9 AND 10.
  
 12) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #22. THE
 RESPONSE STATES *THIS HAS BEEN VERIFIED WITH FPL AND
 CAN BE GRANTED*.
 PLEASE KNOW THAT FPL HAS NO AUTHORITY OVER SERVICES
 GRANTED BY THE NEC AND ARTICLE 230.2. THE NOTE WAS HOW
 DOES THIS SEPARATE SERVICE SHOWN MEET THE NEC AND 230.2
 NOT WHAT FPL WILL OR WILL NOT DO.
 PLEASE KNOW THIS SEPARATE SERVICE AS SHOWN IS NOT
 GRANTED.
  
 13) NOTE: NO ACTION NEEDED, ONLY A RESPONSE FOR LETTER
 RESPONSE FROM DESIGNER.
 PLEASE SEE PREVIOUS NOTE #27, THE REQUEST WAS TO
 COMPLETE EDP1 SCHEDULE FOR FEEDERS ETC FOR THE
 ELEVATORS AND BASE DISCONNECTS.THE NOTE/REQUEST WAS
 NOT FOR THE FINAL OVER CURRENT PROTECTION FROM THE
 DISCONNECT(S) TO THE ELEVATOR MOTORS.
 THE EDP1 SCHEDULE WAS BLANK ON PREVIOUS PLANS. THANK
 YOU FOR COMPLETING INFORMATION.
  
 14) NOTE: PLEASE SEE PREVIOUS NOTE #24 AS THE FIXTURES
 ON ROOF-TOP LIGHT POLES AND FIXTURE LEGEND DOES NOT
 CORRELATE.
 PLEASE SEE E1.2 FOR EXAMPLE AS THERE ARE FIXTURES ON
 PLANS WHICH ARE NOT ON THE FIXTURE LEGEND.
 PLEASE GO THROUGH CIRCUITING, FIXTURES, FIXTURE
 SCHEDULE, LIGHT POLE DETAILS ETC AND COORDINATE ALL.
 PLEASE SEE NOTE ABOVE WITH RESPECT TO OTHER PARKING
 GARAGE FIXTURES WHICH DO NOT COORDINATE WITH OTHER
 LOCATIONS.
 ** PLEASE COMPLETE.
 LS 101 7.8, 7.9, FBC 13-415.2.ABC.1.3, NEC 408.4,
 310.16, 240.4 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 15) NOTE: PLEASE SEE THE GENERATOR SPECS SUBMITTED
 INDICATE A LOAD BANK WHICH WILL NOT BE PART OF THE
 GENERATOR UNIT AND WILL BE REQUIRED TO BE MOUNTED
 SEPARATELY. PLEASE SEE THE PLANS AS THE ELECTRICAL
 RISER DIAGRAM AND PLANS DO NOT SHOW ANY BREAKER, ANY
 LOCATION, ANY CONDUCTORS ETC.
 ** PLEASE SEE SUBMITTAL IN SPEC BOOKS FOR A UNIT WHICH
 NOTES BEING PART OF THE GENERATOR?
 PLEASE COMPLETE RISER AND ADJUST AS NEEDED.
 240.4, 310.16, 215.5, 110.3, 90.7 ETC
 FBC 106.1.2 FOR COORDINATION.
  
  
 16) NOTE: PLEASE SEE PREVIOUS NOTE #29.
 RESPONSE MENTIONS THIS WAS DONE, HOWEVER COULD NOT
 LOCATE ON RISER.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 230.2E, 700.8 ETC AS ALL MAINS ARE REQUIRED
 TO BE LABELED.
 PLEASE SEE 230.2 AS THE POWER FOR THE EMERGENCY SERVICE
 EQUIPMENT IS BEING TAPPED FROM THE NORMAL ELECTRICAL
 SERVICE. IF THERE ARE ANY CHANGES PLEASE BE SURE TO
 LABEL ALL MAINS ACCORDINGLY.
 PLEASE SEE COMMENT ABOVE WITH RESPECT TO RETAIL SERVICE
 PROPOSED.
  
 17) NOTE: PLEASE SEE PREVIOUS NOTE #31 WITH RESPECT TO
 COMPLETION OF RETAIL SERVICE CONDUCTORS ETC. AS THE
 RISER WILL BE CHANGING AND THE INFORMATION WAS NOT
 SHOWN ON REVISED RISER FOR TAPPED CONDUCTORS ETC, THEN
 PLEASE SEE 310.16, 240.4 , 250.6, ETC
  
 18) NOTE: PLEASE SEE FLORIDA STATUTES WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-12-25 14:30:472007-12-25 14:30:47
  
 REVIEW IN PROGRESS
2007-12-25 13:01:052007-12-25 13:01:05
  
 ONE SET IN ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-20 Cont ID  
Sent By dpalmer Date 2007-10-20 Time 18:59 Rev Time 0.00
Received By dpalmer Date 2007-10-19 Time 17:06 Sent To  
Notes
2007-10-20 18:58:562007-10-20 18:58:56
  
 *** DENIED***
  
 **THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION.
  
 CITY PARKING GARAGE.
 500 BANYAN BLVD.
  
 ** PLEASE SEE THERE ARE ITEMS WHICH WERE NOT SUBMITTED
 FOR REVIEW OR WHICH WILL REQUIRE CHANGE ON PLANS WHICH
 MAY GENERATE NEW COMMENTS ON THE FOLLOWING REVIEW.
 THESE COMMENTS ARE BASED ON PLANS AND DOCUMENTATION
 PROVIDED.
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2002 NFPA-110
 2003 NFPA-20
  
 ** PLEASE SEE FOR EXAMPLE THE T-1 SHEET WHICH CONTAINS
 CODE WHICH IS NOT ACCURATE OR NO LONGER ADOPTED BY THE
 STATE.
 PLEASE SEE THE 2002 NEC NOTED, PLEASE SEE A 2004
 NFPA-101 WAS NOTED AND 2003 REVISIONS TO THE FBC.
 PLEASE SEE SOME OF THE CODE ON LS SHEET HAS BEEN
 UPDATED HOWEVER LS SHEET STILL INDICATES SOME CODE NO
 LONGER IN ADOPTION.
 ** MANY OF THESE ARE OK ON ELECTRICAL PLANS.
  
 2) NOTE: PLEASE SEE SHEET T-1 WHICH CONTAINS
 *WHITE-OUT* ON SHEETS COVERING FIRE ALARM ON LEGEND.
 PLEASE SEE THE FIRE ALARM PLANS ARE NEEDED AND REQUIRED
 WITH THE BASE BUILDING PLANS FOR REVIEW.
 PLEASE KNOW EVEN THOUGH THE FA IS UNDER SEPARATE PERMIT
 PLEASE SUBMIT THESE AT THIS TIME TO SHOW BASE DESIGN
 INTENT AND PROTECTION.
 PLEASE SEE FBC 11-4.28.1, .2, AND .3(4) AS THE MINIMUM
 DEVICE LOCATIONS AND LEVELS FOR ADA COMPLIANCE.
  
 3) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEET
 FOR THE GENERATOR, FIRE PUMP, FIRE PUMP CONTROLLER, ATS
 AND SUB-BASE FUEL TANK.
 PLEASE SEE OTHER COMMENTS BELOW WHICH WILL AFFECT THE
 DOCUMENTS AND INFORMATION AS SHOWN ON PLANS. 110.3,
 90.7OF NEC,NFPA-20 ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 4) NOTE:PLEASE SEE FBC ADMIN SECTION 109.3.6,
 109.3.6.4.4 WHICH REQUIRES THE STATEMENT FOR THRESHOLD
 PROJECTS ON ALL ARCH AND ENG SHEETS.
 THIS WAS DONE ON THE ARCHITECTS SHEETS HOWEVER NOT
 ALL.
 " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 OF THE FLORIDA STATUTES".
 THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON
 PLANS.
  
 5) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR
 EGRESS PATHS WHICH MEET THE MINIMUM LIGHTING LEVELS AS
 REQUIRED PER NFPA-101 7.8 AND 7.9.
 PLEASE SEE 7.8.1.3, 7.9.2.2
 MOST OF THESE WERE SUBMITTED HOWEVER PLEASE SEE THE
 MINIMUM AVERAGE ON SHEETS FOR NORMAL DO NOT MEET THE
 MINIMUM LEVELS.
 PLEASE ALSO SEE FOR EXAMPLE THE SPIRAL STAIRS LOCATED
 IN OFFICE LOCATIONS.
 PLEASE SEE THE FOLLOWING LOCATIONS ARE REQUIRED TO
 CONTAIN SOME SORT OF BATTERY BACK UP LIGHTING FIXTURE.
 THE STAIR TOWERS WILL REQUIRE A BATTERY BACK UP FIXTURE
 OF SOME TYPE TO MEET THE MINIMUM OF 1FT CANDLE LEVEL
 UNDER EMERGENCY.7.8.2.1, 7.9.2.2
 PLEASE SEE THE OTHER LOCATIONS WILL BE THE GENERATOR
 ROOM, FIRE PUMP ROOM, MAIN ELECTRICAL ROOM, EMERGENCY
 MAIN ELECTRICAL ROOM, AND THE ELEVATOR EQUIPMENT ROOMS.
 (SOME OF THESE MAY ALREADY SHOW A BATTERY BACK UP
 FIXTURE, BUT MOST DO NOT).
 700.12F.
 PLEASE SEE 700.16 FOR THESE SAME ROOMS.
  
 6) NOTE: PLEASE SEE THE PLANS FOR LIGHTING AND POWER
 INDICATES ELECTRICAL LIGHTING AND RECEPTACLE IN THE FPL
 VAULT WHICH IS NOT PERMITTED PER FPL. THIS ROOM IS ALSO
 FPL LEGAL EASEMENT AREA AND IS NOT CONSIDERED PART OF
 THE GARAGE BUILDING.
  
 7) NOTE: PLEASE SEE THE ADDRESS OF THIS STRUCTURE WAS
 GIVEN AS 500 BANYAN BLVD.
 PLEASE ADJUST ALL TITLE BLOCKS TO INCLUDE THE ADDRESS.
 PLEASE BE SURE TO SEE THAT THERE ARE SEVERAL LOCATIONS
 ON PLANS WHICH MENTIONS THE *CLEMATIS ST GARAGE*
 INCLUDING TITLE BLOCKS.
 IF THE ADDRESS IS ASSIGNED AS BANYAN BLVD, PLEASE
 ADJUST. (ANY REQUEST FOR LOCATION DESIGNATION CHANGE
 NEEDS TO GO THROUGH ADDRESSING REVIEWER).
 FAC 61G15-23.002, 61G1-16.004
 FBC 110.1.2, 106.5, ETC ADMIN SECTION.
  
 8) NOTE: PLEASE KNOW THE ROOF TOP LIGHTING POLES WILL
 BE REQUIRED TO HAVE STRUCTURAL WIND LOAD CALCULATIONS
 AND WILL BE REVIEWED BY THE BUILDING REVIEWER.
 ** THIS IS NOTED FOR INFORMATION.
  
 9) NOTE: PLEASE SEE THE EXHAUST FANS ON E1.1 ARE NOT
 SHOWN ON ENLARGED PLANS FOR THE SAME ROOM.
 FBC 106.1.2 FOR COORDINATION.
  
 10) NOTE: PLEASE SEE 620.22-620.24 AS THE REQUIRED
 DEDICATED CIRCUITS NEEDS TO BE FOR EACH ELEVATOR
 EQUIPMENT ROOM.
 PLEASE SEE THE PLANS CURRENTLY SHOW THE SAME CIRCUITS
 FOR BOTH ROOMS WHICH IS NOT PERMITTED.
  
 11) NOTE: PLEASE SEE 110.26C AS THE DOOR SWINGS ON
 ELECTRICAL ROOM DOORS MAY NOT SWING IN. PLEASE BE SURE
 TO ADJUST ON ELECTRICAL SHEETS AND BE SURE TO GIVE
 INFORMATION TO OTHER DESIGNERS FOR COORDINATION OF ALL
 SHEETS FOR ALL TRADES.
  
 12) NOTE: PLEASE CONTACT THE STATE OF FLORIDA GOVERNING
 ELEVATOR EQUIPMENT ROOMS. IT HAS COME TO THE ATTENTION
 ON THIS OFFICE THAT SEVERAL LOCATIONS WHEN BEING
 INSPECTED BY THE STATE FOR ELEVATOR CERTIFICATION ARE
 BEING REQUIRED TO HAVE THE EQUIPMENT ROOM AIR
 CONDITIONED. THIS IS NOT IN THE ELECTRICAL CODE.
  
 13) NOTE: PLEASE SEE 620.23 AS THE EXPLANATORY NOTE IN
 THE HANDBOOK FOR ELEVATOR PIT LIGHTING REQUIRES A 5FT
 CANDLE LIGHTING LEVEL.
 PLEASE SEE THE FOLLOWING WHICH WAS EXTRACTED FOR THIS
 SECTION ON THE NEC.
 *ASME A17.1-2004, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX)
 AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE
 EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.*
  
 14) NOTE: PLEASE CLARIFY THE LIGHTING CONTROL SYSTEM
 BEING PROPOSED FOR THE ENTIRE PARKING GARAGE. PLEASE
 VERIFY WITH THE CITY IF THE GARAGE AREA WHICH DO NOT
 INCLUDE ROOMS AND OFFICES IS GOING TO BE A 24HR
 OPERATION.
 IF THIS IS 24 HR OPERATION AND USE, THEN NO LIGHTING
 CONTROL SYSTEM WOULD BE SHOWN FOR MANY OF THESE
 LIGHTING FIXTURES.
 PLEASE SE THERE ARE AREAS IN WHICH THE LIGHTING
 CONTROLS FOR DURING DAYLIGHT HOURS ARE IN QUESTION. IF
 THE LIGHTING LEVELS INSIDE THE GARAGE DURING THE DAY
 FALL BELOW MINIMUM SAFETY LEVELS FOR EGRESS, WHAT WILL
 TURN THE LIGHTING ON?
 PLEASE SEE THE CIRCUITING WILL NEED TO BE ADJUSTED
 ALONG WITH ANY LIGHTING CONTROLS.
 AS THERE ARE SEVERAL UNANSWERED QUESTIONS ON THIS NOTE,
 THIS MAY NEED TO BE GONE OVER WITH CITY STAFF OTHER
 THAN PLAN REVIEW. PLANS REVIEW WILL BE FOR MINIMUM
 LIGHTING LEVELS AND CONTROLS OF THOSE LEVELS. PLEASE
 SEE 13-415.1.ABC.1, 13-415.1.ABC.1.4 ETC
  
 15) NOTE: PLEASE SEE THAT MORE INFORMATION WILL BE
 NEEDED FOR LIGHTING IN OFFICES AND DUE TO THE
 ADJUSTMENTS POSSIBLY WITH NOTE #14 ABOVE, THE OFFICES,
 MEETINGS ROOMS ETC MAY NEED TO BE GONE OVER. PLEASE SEE
 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE MISSING
 LIGHTING CONTROLS IN RETAIL AREAS.
  
 16) NOTE: PLEASE SEE MISSING ENERGY CALCULATIONS,
 LIGHTING PERFORMANCE CALCULATIONS PER 13-415.2 AND
 13-415.2.ABC.1.3 ETC.
 PLEASE SEE COMMENTS FROM MECHANICAL REVIEWER WHICH
 WILL BE FORTH COMING.
 PLEASE SEE SOME AREAS OF THIS BUILDING WILL HAVE
 CONDITIONED SPACE.
  
 17) NOTE: PLEASE PROVIDE COMPLETED INFORMATION FOR FIRE
 PUMP AND LOCKED ROTOR OVER CURRENT PROTECTION AND
 AMPERAGES.
 PLEASE SEE NEC 695.4B1, 9.3.2.2.3.2(A), (B) ETC PLEASE
 SEE THE ELECTRICAL PLANS INDICATE A DISCONNECT WITH
 OVER CURRENT PROTECTION AHEAD OF THE FIRE PUMP
 CONTROLLER WHICH WILL ALSO CONTAIN OVER CURRENT
 PROTECTION. PLEASE KNOW THERE MAY NOT BE OVER CURRENT
 PROTECTION ON THE LINE SIDE OF THE FIRE PUMP
 CONTROLLER. THE TYPICAL LISTED FIRE PUMP CONTROLLER
 CONTAINS THE LOCKED ROTOR CURRENT SETTING FOR THE
 SELECTED PUMP AND ASSEMBLY. 10.4.4.1 NFPA-20 PLEASE
 ALSO SEE THE FIRE PUMP IS BEING SHOWN AS 60 HP ON FP
 SHEETS AND 75HP ON ELECTRICAL SHEETS.
 PLEASE SEE PROVIDE INFORMATION ON WHAT TYPE OF BREAKERS
 ARE ON THE SECONDARY EMERGENCY SIDE FOR FIRE PUMP
 POWER. AS THE FIRE PUMP IS BEING FED THROUGH A TOTAL OF
 THREE BREAKERS ON THE EMERGENCY SIDE, THESE MAY CREATE
 AN ISSUE WITH SELECTIVE COORDINATION.
 PLEASE SEE THESE BREAKERS ARE TYPICALLY MAGNETIC TYPE.
 PLEASE SEE NEC 695 AND NFPA-20CHAPTER 9 AND 10.
  
 18) NOTE: PLEASE PROVIDE THE MINIMUM FUEL TIMES FOR
 EMERGENCY GENERATOR AND FUEL FOR FIRE PUMP. NFPA-20
 9.6.2.2. (8HRS PLUS OTHER LOADS)
  
 19) NOTE: PLEASE SEE THE RISER INDICATES THE NORMAL
 FEED FROM FPL TO THE EMERGENCY SIDE OF THE FIRE PUMP
 CONTROLLER/ATS.
 PLEASE SEE THIS APPEARS TO BE A MISPRINT AND WILL NEED
 TO BE REVISED.
 FBC 106.1.2 FOR COORDINATION.
 NEC 695.1
  
 20) NOTE: PLEASE SEE GROUNDING DETAIL FOR GENERATOR
 DOES NOT ACCURATELY REFLECT THE SERVICE EQUIPMENT. FBC
 106.1.2 FOR COORDINATION,
 230.2, 230.70, 250.50 ETC
  
 21) NOTE: PLEASE SEE AS THE RISER, PANELS AND EQUIPMENT
 NEED COORDINATION THERE ARE SOME ITEMS WHICH CAN NOT BE
 CONFIRMED AT THIS TIME.
 PLEASE SEE FOR EXAMPLE:
 A) THE RISER INDICATES THE MSB AS A 1200AMP WITH WHAT
 APPEARS TO BE A 800AMP BREAKER, HOWEVER THE MSB PANEL
 INDICATES THIS AS A 1200AMPS MAIN LUG ONLY DISTRIBUTION
 BOARD.
  
 B) PLEASE SEE 240.13, AND 230.95 CAN NOT BE CONFIRMED
 IF REQUIRED OR NOT.
  
 C) PLEASE SEE 250.30, 250.20 AND WHETHER OR NOT A
 4-POLE ATS IS REQUIRED CAN NOT BE CONFIRMED.
  
 D) PLEASE SEE 230.70, 230.71 ETC CAN ALSO NOT ME
 CONFIRMED. IF THIS MSB DOES NOT CONTAIN A MAIN, IT DOES
 NOT MEET EITHER OF THESE TWO SECTIONS OF CODE ALONG
 WITH SEVERAL OTHERS INCLUDING 240.4 AND 310.16
  
 THESE ARE SOME OF THE ITEMS WHICH NEED TO BE
 COORDINATED AND ADJUSTED ON PLANS.
  
 22) NOTE: PLEASE CLARIFY WHERE/HOW THE ADDITIONAL
 SERVICE FOR RETAIL CAN BE GRANTED PER 230.2.
  
 23) NOTE: PLEASE ADJUST AND PLACE ON THE LIGHTING
 PROTECTION PLANS. PLEASE KNOW ANY SYSTEM SHALL BE MEET
 NFPA-780. (UNDER SEPARATE PERMIT)
  
 24) NOTE: PLEASE CLARIFY FIXTURE SC ON LEGEND AND ON
 PLANS.
 PLEASE SEE THE CIRCUITING TO 5TH FLOOR LIGHTING WHICH
 IS CIRCUITED TO 1NGH-11 IS THE SAME AS THE CIRCUIT FOR
 WHAT APPEARS TO BE FEEDING THESE SC FIXTURES ON ROOF ON
 E6.1.
 PLEASE SEE ON PLANS ONLY ONE LOCATION SHOWS THE FIXTURE
 SC YET THE SYMBOL FOR THIS SAME FIXTURE APPEARS TO BE
 FOR OTHER FIXTURES BUT THEY ARE NOT LABELED OR
 IDENTIFIED.
 PLEASE COMPLETE, ADJUST AND COORDINATE.
 FBC 106.1.2.
 408.4, 310.16, 240.4 ETC
  
 25) NOTE: PLEASE PROVIDE INFORMATION FOR FAIL SAFE
 OPERATION OF GATES.
 PLEASE SEE COMMENTS FROM FIRE MARSHAL WITH RESPECT TO
 OPERATION OF THESE GATES UNDER THE LOSS OF POWER.
 PLEASE SEE POSSIBLE CHAPTER 7 OF THE LS CODE.
 THIS IS ONLY BEING NOTED AS ANY CHANGES AND COMMENTS
 FROM OTHER TRADES SUCH AS BUILDING FOR CHAPTER 10 OF
 THE FBC AND CHAPTER 7 OF NFPA-101 WILL AFFECT THE
 ELECTRICAL PLANS.
  
 26) NOTE: PLEASE SEE THE SHEET E4.1 WHICH CONTAINS THE
 LOW VOLTAGE SYSTEMS/CONDUIT LOCATIONS IS LABELED AND
 IDENTIFIED AS LIGHTING PLANS AND DETAILS.
 FBC 106.1.2 FOR COORDINATION.
  
 27) NOTE: PLEASE SEE THE FEEDERS ON EDP1 IS NOT
 COMPLETE AT THIS TIME FOR MCC, AND ELEVATORS 1-4.
 PLEASE COMPLETE INFORMATION FOR THE SIZE OF THE
 ELEVATOR MOTORS SO THAT THE FEEDERS CAN BE SHOWN AND
 DETERMINED FOR CODE COMPLIANCE.
 PLEASE SEE THAT THE BASE OVER CURRENT PROTECTION AT THE
 ELEVATOR DISCONNECTS/CONTROLLERS ARE NOT REQUIRED AT
 THIS TIME UNLESS KNOWN. IF THIS INFORMATION IS KNOWN AT
 THIS TIME, THEN THIS WILL ALLEVIATE PLANS FROM HAVING
 TO BE REVISED AT A LATER DATE. AT SOME POINT IN TIME
 THE PLANS WILL BE REQUIRED TO SHOW AND INDICATE ALL OF
 THESE.
 PLEASE SEE NEC 620.1,240.4, 310.16, 408.4 ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 28) NOTE: PLEASE SEE THE MAIN MEANS OF DISCONNECT FOR
 THE FEEDERS FROM THE GENERATOR APPEARS TO BE FED
 THROUGH AND *BACK-FED* BREAKER IN MSBE.
 PLEASE NOTE REJECTION CLIP IF THIS IS INDEED THE CASE.
 PLEASE SEE FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 29) NOTE: PLEASE SEE 230.2E, 700.8 ETC AS ALL MAINS ARE
 REQUIRED TO BE LABELED.
 PLEASE SEE 230.2 AS THE POWER FOR THE EMERGENCY SERVICE
 EQUIPMENT IS BEING TAPPED FROM THE NORMAL ELECTRICAL
 SERVICE. IF THERE ARE ANY CHANGES PLEASE BE SURE TO
 LABEL ALL MAINS ACCORDINGLY.
 PLEASE SEE COMMENT ABOVE WITH RESPECT TO RETAIL SERVICE
 PROPOSED. AT THIS TIME THIS ADDITIONAL SERVICE AS SHOWN
 NOTED ON NOTE #22 ABOVE IS NOT GRANTED. EACH OF THOSE
 TENANT/RETAIL DISCONNECTS WOULD HAVE BEEN MAINS.
  
 30) NOTE: PLEASE SEE NOTE ABOVE WITH RESPECT TO
 LIGHTING CONTROLS AND EXTERIOR LIGHTING CONTROLS PER
 13-415.1.ABC.1.4.
 PLEASE CLARIFY HOW ALL LIGHTING ON FA?ADE IS BEING
 CONTROLLED.
 PLEASE SEE SOME OF THIS IS SHOWN BEING CONTROLLED FROM
 A PHOTO-CELL AS WELL AS A LIGHTING CONTROL PANEL. SEE
 CIRCUITING ON SCHEDULE.
 PLEASE SEE FBC 106.1.2 FOR COORDINATION.
  
 31) NOTE: PLEASE SEE NO INFORMATION FOR CONDUITS,
 CONDUCTORS, TAPS ETC ON THE RETAIL SERVICE EQUIPMENT IS
 SHOWN.
 PLEASE COMPLETE.
 PLEASE BE SURE TO SEE COMMENT #22 ETC FOR SERVICE.
  
 32) NOTE: PLEASE SEE NO GROUNDING ELECTRODE SYSTEM IS
 BEING SHOWN FOR THE SAME RETAIL SERVICE.
 250.50.
  
 33) NOTE: PLEASE SEE SELECTIVE COORDINATION IS NEEDED
 TO BE SHOWN FOR THE LIFE SAFETY ITEMS PER 240.12
  
 34) NOTE: PLEASE SEE TWO PERMIT APPLICATIONS WERE
 SUBMITTED AT TWO DIFFERENT TIMES ON THE SAME DAY. THE
 PERMIT APPLICATION WHICH DOES CONTAIN ALL OF THE
 SIGNATURES FOR SUB CONTRACTORS NEEDS TO BE NOTARIZED ON
 THE BACK WHERE THE CONTRACTORS AUTHORIZED AGENT IS
 SIGNED ON. THIS CAN BE DONE WHEN PLANS ARE RESUBMITTED.
 THE ORIGINAL APPLICATION WHICH WAS SUBMITTED WILL
 BECOME VOID.
 THIS CAN BE DONE AT ANY TIME BEFORE RESUBMISSION OF
 PLANS. IF THERE ARE ANY QUESTIONS, OR IF THE AUTHORIZED
 AGENT IS IN THE OFFICE, THIS CAN BE DONE AT THAT TIME.
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 ** PLEASE KNOW AS THERE ARE MANY CHANGES AND ITEMS NOT
 SUBMITTED; PLEASE BE AWARE OF ANY POSSIBLE COMMENTS
 WHICH HAVE NOT BEEN MADE AT THIS TIME.
 PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-20 08:02:17 
  
 IN ELEC FOR REVIEW. 1-SET ONLY, AND 1-BOOK.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2008-04-04 Cont ID  
Sent By rchokshi Date 2008-04-04 Time 09:24 Rev Time 0.00
Received By rchokshi Date 2008-04-04 Time 09:24 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2008-02-28 Cont ID  
Sent By rchokshi Date 2008-02-28 Time 13:39 Rev Time 0.00
Received By rchokshi Date 2008-02-28 Time 13:31 Sent To  
Notes
2008-02-28 13:39:43***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
  
 1.YOU NEED TO PROVETHAT YOUR FINISHED FLOOR IS HIGH
 ENOUGH TO TAKE ALL WORST FLOOD CONDITION.THEREFORE,
 PLEASE SHOW ON STORM WATER CALCULATTION THAT YOUR FF
 ELEVATION IS HIGH ENOUGH ANDHAVE CONSIDERED FLOOD
 ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA TO
 DETERMINE THE FIRST FLOOR ELEVATION, PARKING LOT
 ELEVATION, CROWN OF THE ROAD ELEVATION, SIDEWALK ETC.
 ALSO, PLEASE SHOW WORST CROWN OF THE ROAD ELEVATION ON
 THE DRAWINGS. PLEASE PROVIDE A COPY OFSTORM WATER
 CALS TO 1000 45TH STREET ENGINEERING FOR THEIR APPROVAL
 BEFORE WE APPROVE.
  
 PLEASE RESPOND EACH OF THE ABOVE ITEMSIN DETAIL TO
 EXPEDITE YOUR PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-12-28 Cont ID  
Sent By rchokshi Date 2007-12-28 Time 13:54 Rev Time 0.00
Received By rchokshi Date 2007-12-28 Time 12:56 Sent To  
Notes
2007-12-28 13:54:20***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 OUR RESPONSE: WE LOOKEDAN NOI APPLICATION COPY YOU
 FILED.JUST A NOI APPLICATION YOU FILED NOT ENOUGH.
 YOU NEED TO GET A LETTER FROM FDEP THAT YOU HAVE PAID
 FEES & FILED PAPERS FOR NOI.
  
 2.PLEASE SHOW ON STORM WATER CALCULATTION THAT YOUR
 FF ELEVATION IS HIGH ENOUGH ANDHAVE CONSIDERED FLOOD
 ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA TO
 DETERMINE THE FIRST FLOOR ELEVATION, PARKING LOT
 ELEVATION, CROWN OF THE ROAD ELEVATION, SIDEWALK ETC.
 ALSO, PLEASE SHOW WORST CROWN OF THE ROAD ELEVATION ON
 THE DRAWINGS.
  
 3. STORM WATER CALS MUST BE APPROVED FROM 1000 45TH
 STREETENG OFFICE BEFORE WE ISSUE A PERMIT.
  
 4. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH OF THE ABOVE ITEMSIN DETAIL TO
 EXPEDITE YOUR PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-10-24 Cont ID  
Sent By rchokshi Date 2007-10-24 Time 13:48 Rev Time 0.00
Received By rchokshi Date 2007-10-24 Time 13:18 Sent To  
Notes
2007-10-24 13:48:29***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWINGSDUMPSTER LOCATION ON DWG,
 LOCATION MUST BE ACCESSIBLE FOR PICKUP TRUCK. YOUR NOTE
 ON SHEET C-10, SAYS "DUMPSTER AND RECEPTACLES WILL BE
 MANUALLY ROLLED OUT........." YOU NEED TO GET AN
 APPROVAL FROM CITY'S SANITATION DEPT FOR PICKUP.
 3. PLEASE SHOW ON STORM WATER CALCULATTION THAT YOUR FF
 ELEVATION IS HIGH ENOUGH ANDHAVE CONSIDERED FLOOD
 ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA TO
 DETERMINE THE FIRST FLOOR ELEVATION, PARING LOT
 ELEVATION, CROWN OF THE ROAD ELEVATION, SIDEWALK ETC.
 ALSO, PLEASE SHOW WORST CROWN OF THE ROAD ELEVATION ON
 THE DRAWINGS.
 4. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS.
 5. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS,
 6.IN YOURCALCULATION FOR EXFILTRATION TRENCHES, PER
 SFWMD YOU NEED TOTAKE WORST ONE EITHER 1" OVER ENTIRE
 AREA OR 2.5" CRITERIA FOR % OF IMPERVIOUS AREA. SO,
 PLEASE RECALCULATE LENGTH OF EXFILTRATION TRENCH. ALSO,
 PLEASE SHOW DRY DETENTION/WET DETENTION AREAS IN STORM
 WATER CALS I YOU HAVE THEM.
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES
 BEFORE WE ISSUE PERMIT.
 9. POLLUTION PREVENTION DETAILS:CLOTHES USED FOR SILT
 FENCE ETC., HEIGHT OF FENCE SHOULD BE HIGH(5' OR MORE)
 ENOUGH PER FDEP TO STOP DUSTPARTICLES.
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH OF THE ABOVE ITEMSIN DETAIL TO
 EXPEDITE YOUR PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2008-10-08 Cont ID  
Sent By mawillia Date 2008-10-08 Time 16:47 Rev Time 0.00
Received By mawillia Date 2008-10-08 Time 16:14 Sent To B
Notes
2008-10-08 16:46:50*****REVISION, DATED 9/16/08, APPROVED*****
  
 REVISED PLAN SHEETS LS0.0, LS.0 THRU LS.2, E3.1, FA1.1,
 AND FP1.1 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2008-09-23 Cont ID  
Sent By mwennerg Date 2008-09-23 Time 14:42 Rev Time 0.00
Received By mwennerg Date 2008-09-23 Time 14:42 Sent To  
Notes
2008-09-23 14:43:18REVISED SHEETS LS-1 AND LS-2 DATED 9/2/08.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-07-10 Cont ID  
Sent By mwennerg Date 2008-07-10 Time 10:39 Rev Time 0.00
Received By mwennerg Date 2008-07-10 Time 10:39 Sent To  
Notes
2008-07-10 10:40:22REVISION DATED 6/13/08 STAMPED LS-1 AND LS-3

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2008-06-26 Cont ID  
Sent By mawillia Date 2008-06-26 Time 18:49 Rev Time 0.00
Received By mawillia Date 2008-06-26 Time 18:19 Sent To  
Notes
2008-06-26 18:18:45*****REVISION,DATED 4/28/08,PARTIAL APPROVED*****
  
 REVISED PLAN SHEETS LS.1 AND LS.3 WERE STAMPED,
 INITIALED, AND DATED;HOWEVER E3.1 STILL NEEDS TO BE
 FIRE STAMPED
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-04-08 Cont ID  
Sent By mawillia Date 2008-04-08 Time 14:50 Rev Time 0.00
Received By mawillia Date 2008-04-08 Time 13:29 Sent To  
Notes
2008-04-08 14:50:21*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; PLAN SHEETS C-16, LS.0 THRU LS.3, A4.2,
 A9.1, E3.1, FA0.1 THRU FA1.2, AND FP0.1 THRU FP3.1 WERE
 STAMPED, INITIALED, AND DATED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-03-12 Cont ID  
Sent By mawillia Date 2008-03-12 Time 15:08 Rev Time 0.00
Received By mawillia Date 2008-03-12 Time 14:48 Sent To  
Notes
2008-03-12 15:04:57*****UNSAT*****
  
 THE FOLLOWING COMMENT TAKEN FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEEDS TO BE ADDRESSED.CAPS BEHIND THE
 COMMENTS MAY BE USED AS GUIDELINES TO ADDRESS THE
 COMMENT.
  
  
 07.A TEMPORARY STANDPIPE SYSTEM IS REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.COULD NOT LOCATE THIS NOTATATION ON SHEET
 LS0.0 AS PER YOUR RESPONSE LETTER
  
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-01-04 Cont ID  
Sent By mawillia Date 2008-01-04 Time 11:27 Rev Time 0.00
Received By mawillia Date 2008-01-04 Time 09:34 Sent To  
Notes
2008-01-04 11:27:15*****UNSAT*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED.CAPS BEHIND
 THE COMMENTS MAY BE USED AS GUIDELINES TO ADDRESS THE
 COMMENT.
  
  
 07.A TEMPORARY STANDPIPE SYSTEM IS REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.ADD COMMENT TO SHEET LS0.0
  
 17.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.ADD
 COMMENT TO SHEET FP0.1
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-15 Cont ID  
Sent By mawillia Date 2007-11-15 Time 16:53 Rev Time 0.00
Received By mawillia Date 2007-11-15 Time 12:53 Sent To  
Notes
2007-11-15 16:53:43*****DENIED*****
  
 01.THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 02.ON SHEET T-1, MAKE REFERENCE TO NFPA 101 - 2003
 EDITION, NOT 2004.
  
 03.ON SHEET T-1, INCLUDE THE STANDARD FOR PARKING
 STRUCTURES NFPA 88A - 2002 EDITION.
  
 04.DOORWAYS AND OTHER OPENINGS IN FIRE WALLS AND FIRE
 PARTITIONS SHALL BE PROTECTED WITH APPROVED FIRE DOORS
 INSTALLED IN ACCORDANCE WITH NFPA 80, STANDARD FOR FIRE
 DOORS AND WINDOWS.
  
 05.CLEAR AISLE SPACE SHALL BE MAINTAINED TO PERMIT
 READY ACCESS TO, AND THE USE OF, FIRE-FIGHTING
 EQUIPMENT.
  
 06.FLOORS SHALL BE KEPT CLEAN AND FREE OF OIL AND
 GREASE.
  
 07.A TEMPORARY STANDPIPE SYSTEM IS REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 08.ON SHEET LS.O, PROVIDE DISTANCE (IN FEET) OF THE
 ADJACENT FIRE HYDRANT LOCATED AT CLEMATIS AND ROSEMARY
 TO THE PROPOSED STRUCTURE.
  
 09.ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTER'S EMERGENCY REQUIREMENTS OF ASME A17.1.
  
 10.ELEVATOR WARNING SIGNS (DO NOT USE IN EVENT OF
 FIRE) SHALL BE REQUIRED.
  
 11.PLEASE PROVIDE EMERGENCY LIGHTING FACILITIES FOR
 THE MEANS OF EGRESS AREAS FOR THIS STRUCTURE.
  
 12.DISPLAY/ILLUSTRATE THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS CLEMATIS
 STREET.AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL
 BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 STROKE.
  
 13.ON SHEET A4.3, ILLUSTRATE THAT THE DOUBLE DETECTOR
 VALVE ASSEMBLY IS TO CHAINED AND LOCKED.
  
 14.ON SHEET E0.1, REFERENCE IS TO MADE TO NFPA 13 -
 2002 EDITION, NOT 1999.
  
 15.KNOX LOCKING CAPS ARE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTIONS (FDC).FOR A APPLICATION,
 CONTACT WEST PALM BEACH FIRE PREVENTION AT
 561-804-4724.
  
 16.SEPARATE PLAN AND PERMIT WILL BE REQUIRED FO THE
 FIRE SPRINKLER SYSTEM INSTALLATION.
  
 17.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.
  
 18.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS FOR THE EXITS, EXIT AISLE CORRIDORS, AND
 OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-11-26 Cont ID  
Sent By adarroug Date 2008-11-26 Time 10:18 Rev Time 0.00
Received By adarroug Date 2008-11-26 Time 10:18 Sent To B
Notes
2008-11-26 10:18:58TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-09-26 Cont ID  
Sent By adarroug Date 2008-09-26 Time 14:49 Rev Time 0.00
Received By adarroug Date 2008-09-26 Time 14:48 Sent To M
Notes
2008-09-26 14:49:21TO "M" BOX/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-09-26 Cont ID  
Sent By adarroug Date 2008-09-26 Time 14:42 Rev Time 0.00
Received By adarroug Date 2008-09-26 Time 14:42 Sent To E
Notes
2008-09-26 14:42:51TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-09-25 Cont ID  
Sent By adarroug Date 2008-09-25 Time 16:36 Rev Time 0.00
Received By adarroug Date 2008-09-25 Time 16:36 Sent To B
Notes
2008-09-25 16:37:20TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-09-22 Cont ID  
Sent By adarroug Date 2008-09-22 Time 13:09 Rev Time 0.00
Received By adarroug Date 2008-09-22 Time 13:09 Sent To  
Notes
2008-09-22 13:12:01TO "COMM" BD#45--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-09-12 Cont ID  
Sent By adarroug Date 2008-09-12 Time 09:40 Rev Time 0.00
Received By adarroug Date 2008-09-12 Time 09:40 Sent To B
Notes
2008-09-12 09:40:25TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-09-10 Cont ID  
Sent By adarroug Date 2008-09-10 Time 09:13 Rev Time 0.00
Received By adarroug Date 2008-09-10 Time 09:13 Sent To  
Notes
2008-09-10 09:13:55TO "COMM" BD#33

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 11:06 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 11:06 Sent To E
Notes
2008-08-21 11:06:46TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-07-30 Cont ID  
Sent By adarroug Date 2008-07-30 Time 08:42 Rev Time 0.00
Received By adarroug Date 2008-07-30 Time 08:42 Sent To B
Notes
2008-07-30 08:42:52TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-07-22 Cont ID  
Sent By adarroug Date 2008-07-22 Time 16:39 Rev Time 0.00
Received By adarroug Date 2008-07-22 Time 16:39 Sent To  
Notes
2008-07-22 16:39:37TO "COMM" BD#16--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 08:51 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 08:51 Sent To  
Notes
2008-06-17 08:53:21TO "COMM" BD#31

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-29 Cont ID  
Sent By adarroug Date 2008-05-29 Time 16:45 Rev Time 0.00
Received By adarroug Date 2008-05-29 Time 16:45 Sent To  
Notes
2008-05-29 16:47:36TO "COMM" BD#40

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-10 Cont ID  
Sent By adarroug Date 2008-04-10 Time 16:12 Rev Time 0.00
Received By adarroug Date 2008-04-10 Time 16:12 Sent To  
Notes
2008-04-10 16:13:22TO "COMM" BD#6--PLANS ON RACK--7ROLLS AND 1
 BOX---EXPEDITED---

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-28 Cont ID  
Sent By adarroug Date 2008-03-28 Time 15:52 Rev Time 0.00
Received By adarroug Date 2008-03-28 Time 15:52 Sent To  
Notes
2008-03-28 15:55:47TO "COMM" BD#26/PLANS ON RACK--7 ROLLS, 1
 BOX--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-11 Cont ID  
Sent By adarroug Date 2008-02-11 Time 13:30 Rev Time 0.00
Received By adarroug Date 2008-02-11 Time 13:30 Sent To  
Notes
2008-02-15 15:58:37TO "COMM" BD#51/PLANS BY "RBROWN" OFFICE.7 ROLLS, 1
 BOX
2008-02-11 13:30:43WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-18 Cont ID  
Sent By adarroug Date 2007-12-18 Time 11:29 Rev Time 0.00
Received By adarroug Date 2007-12-18 Time 11:29 Sent To  
Notes
2007-12-18 11:29:39TO "COMM" BD#47/PLANS ON RACK-3 ROLLS AND 1 BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-15 Cont ID  
Sent By mawillia Date 2007-11-15 Time 12:53 Rev Time 0.00
Received By mawillia Date 2007-09-28 Time 13:20 Sent To  
Notes
2007-10-17 15:04:35TO "COMM" BD#50--PLANS ON RACK/3 ROLLS AND BINDERS
2007-09-28 13:22:30WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2008-10-02 Cont ID  
Sent By rregueir Date 2008-10-02 Time 14:36 Rev Time 0.00
Received By rregueir Date 2008-10-02 Time 14:36 Sent To  
Notes
2008-10-02 14:36:26REVISED M1.1 AND M2.1

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2008-10-01 Cont ID  
Sent By   Date 2008-10-01 Time   Rev Time 0.00
Received By   Date 2008-10-01 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2008-10-01 Cont ID  
Sent By   Date 2008-10-01 Time   Rev Time 0.00
Received By   Date 2008-10-01 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2008-09-22 Cont ID  
Sent By rregueir Date 2008-09-22 Time 11:10 Rev Time 0.00
Received By rregueir Date 2008-09-22 Time 11:09 Sent To B
Notes
2008-09-22 11:10:01REVISED ENERGY CALCULATIONS.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2008-08-07 Cont ID  
Sent By rregueir Date 2008-08-07 Time 16:21 Rev Time 0.00
Received By rregueir Date 2008-08-07 Time 13:54 Sent To  
Notes
2008-08-07 16:21:07PAGE M1.1 REV 4, PAGE M2.1 REV 5

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2008-07-03 Cont ID  
Sent By rregueir Date 2008-07-03 Time 16:25 Rev Time 0.00
Received By rregueir Date 2008-07-03 Time 16:14 Sent To  
Notes
2008-07-03 16:25:07REVIEW #: REVISION 4
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. DATA CLOSET 2.201A IS BEING CONVERTED INTO A RETURN
 AIRR PLENUM BY INSTALLING THE AHU FOR THE
 CONFERENCE/TRAINING ROOM IN THERE. PROVIDE
 DOCUMENTATION SHOWING ALL DATA EQUIPMENT AND ALL
 ASSOCIATED MATERIALS EXPOSED WITHIN THIS PLENUM TO BE
 NONCOMBUSTIBLE OR HAS A FLAME SPREAD INDEX OF NOT MORE
 THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50
 WHEN TESTED IN ACCORDANCE WITH ASTM E84 PER FBCM
 606.2.1.
  
 2. THE DOOR ON DATA CLOSET 2.201A IS SHOWN ON DOOR
 SCHEDULE TO BE MADE OF WOOD. THIS DOOR MUST ALSO BE IN
 COMPLIANCE WITH FBCM 606.2.1.
  
 3. IS CLOSET 2.204A ALSO TO BE A PLENUM? IF SO, THIS
 DOOR IS ALSO SHOWN ON DOOR SCHEDULE TO BE WOOD. THIS
 DOOR MUST BE IN COMPLIANCE WITH FBCM 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-06-20 Cont ID  
Sent By rregueir Date 2008-06-20 Time 15:16 Rev Time 0.00
Received By rregueir Date 2008-06-20 Time 14:30 Sent To  
Notes
2008-06-20 15:17:30REVISION #3 PAGES M0.1, M1.1, M2.1

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-04-11 Cont ID  
Sent By rregueir Date 2008-04-11 Time 14:25 Rev Time 0.00
Received By rregueir Date 2008-04-11 Time 14:19 Sent To  
Notes
2008-04-11 14:26:07MECHANICAL PORTION OF ENERGY CALCULATIONS OK.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-04-11 Cont ID  
Sent By rregueir Date 2008-04-11 Time 14:18 Rev Time 0.00
Received By rregueir Date 2008-04-03 Time 14:04 Sent To  
Notes
2008-04-11 14:18:56PENDING SUCCESSFUL REVIEW OF ENERGY CALCULATIONS BY ALL
 INTERESTED TRADES.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-03-11 Cont ID  
Sent By rregueir Date 2008-03-11 Time 15:31 Rev Time 0.00
Received By rregueir Date 2008-03-10 Time 17:39 Sent To  
Notes
2008-03-11 15:31:54ALL PREVIOUS REVIEW COMMENTS HAVE BEEN ADDRESSED,
 MECHANICAL PAGES WILL BE STAMPED. THE REVIEW WILLL
 REMAIN IN FAIL STATUS PENDING SATISFACTORY COMPLETION
 OF ENERGY CALCULATIONS.
  
 THE NEWLY SUBMITTED ENERGY CALCULATIONS ARE NOT
 ACCEPTABLE. THERE HAVE BEEN TWO SEPARATE SETS OF
 CALCULATIONS SUBMITTED. ONE SET IS METHOD A AND COVERS
 BOTH THE CONDITIONED AND UNCONDITIONED PORTIONS OF THE
 BUILDING. THE OTHER SET IS METHOD B AND ONLY COVERS ONE
 PORTION OF THE CONDITIONED SPACE IN THE BUILDING. IT IS
 NOT CLEAR WHY THE BUILDING IS BEING SPLIT FOR TWO
 DIFFERENT CALCULATIONS, YET ONE SECTION OF THE BUILDING
 IS INCLUDED IN BOTH CALCULATIONS (OFFICE AREA?).
  
 BASED ON THE FACT THAT THERE ARE UNFINISHED PORTIONS OF
 THE CONDITIONED SPACE, THE APPROPRIATE METHOD TO USE TO
 DEMONSTRATE CODE COMPLIANCE WOULD BE METHOD B OR METHOD
 C FOR THE ENTIRE BUILDING, INCLUDING ALL ENERGY
 UTILIZING SYSTEMS ON ONE REPORT. PLEASE CORRECT AND
 RESUBMIT. ONCE ALL DISCIPLINES HAVE FOUND THE ENERGY
 CALCULATIONS TO BE ACCURATELY COMPLETED AND VIA THE
 CORRECT METHOD, THIS REVIEW STATUS WILL BE CHANGED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-01-03 Cont ID  
Sent By rregueir Date 2008-01-03 Time 16:36 Rev Time 0.00
Received By rregueir Date 2008-01-03 Time 07:57 Sent To  
Notes
2008-01-03 16:36:26REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. LS.1 AND LS.2: ONLY TWO OF THE 8 REFERENCES TO ?OPEN
 PARKING GARAGE? ON THESE PAGES HAVE BEEN CORRECTED. THE
 OTHER SIX ARE STILL INCORRECT. PLEASE CORRECT ALL
 REFERENCES TO AN OPEN PARKING GARAGE. FBC 406.2.1.
  
 2. M1.1: EF-2 LOCATION IS NOT SHOWN AS BEING PROTECTED
 BY BOLLARDS ON PG A1.1 OR M1.1. PLEASE SHOW THIS FAN TO
 BE PROTECTED FROM MECHANICAL DAMAGE IN ACCORDANCE WITH
 FBC, M 304.5. ALSO, EF-20 IS SHOWN IN THE WALL BETWEEN
 THE FIRE PUMP ROOM AND THE STORAGE ROOM AS WELL AS AT
 COLUMN LINE C. WHICH IS CORRECT? HOW WILL THIS PROVIDE
 THE REQUIRED VENTILATION FOR THE FIRE PUMP ROOM?
  
 3 & 4: OK
  
 5. OK EXCEPT, SEE COMMENT #2 REGARDING EF 20.
  
 6 - 9: OK
  
 10. IT IS NOT POSSIBLE TO ASCERTAIN THE DESIGN INTENT
 RELATED TO OCCUPANCY TYPES AND REQUIRED OCCUPANCY
 SEPARATIONS RELATED TO THIS BUILDING AS THE ENTIRE
 GARAGE IS BEING CALLED ?S2 INCIDENTAL USE? ON PG LS0.0.
 THE S2 OCCUPANCY IS NOT INCIDENTAL TO THE USE OF THE
 BUILDING. IT IS THE PRIMARY USE AND OCCUPANCY OF THE
 BUILDING. THERE ARE OTHER OCCUPANCIES WHICH MAY BE
 CONSIDERED INCIDENTAL OR ACCESSORY TO THE PRIMARY
 OCCUPANCY, BUT EITHER WAY A FIRE RATED SEPARATION
 BETWEEN THESE SPACES IS REQUIRED, INCLUDING THE TYPE B
 OCCUPANCY AREAS IN ACCORDANCE WITH FBC 302.1.1 AND
 302.2 AND 302.3.
  
 THE EXHAUST DUCT PENETRATIONS IN THIS AREA WILL REQUIRE
 OPENING PROTECTIVES IN ACCORDANCE WITH FBC 607.5 OR
 607.1.1. SHOW COMPLIANCE WITH THESE SECTIONS AND
 COORDINATE WITH ARCHITECTURAL AND LIFE SAFETY PLANS.
  
 11 & 12: OK
  
 13. TOILET ROOMS 1.205 AND 1.206 BOTH RECEIVE SUPPLY
 AIR FROM AHU #3. ALL AIR SUPPLIED TO SUCH SPACES SHALL
 BE EXHAUSTED IN ACCORDANCE WITH FBC, M 403.2.1(3). IF
 THE LIGHT SWITCHES ARE OFF AND AHU #3 IS RUNNING, HOW
 WILL THE AIR BEING SUPPLIED TO THESE SPACES BE
 EXHAUSTED IN ACCORDANCE WITH THIS SECTION? THE
 REQUIREMENTS OF401.3 AND 403.2.1(3) SHALL BE MET FOR
 THESE SPACES.
  
 14 - 17: OK
  
 18. OK PENDING BUILDING PLAN REVIEW.
  
 19. OK
  
 20. M4.1: DETAIL 03 SHOWS A SECONDARY DRAIN OFF A
 SECONDARY DRAIN PAN TIED INTO THE PRIMARY DRAIN LINE.
 THIS IS NOT AN ACCEPTABLE MEANS OF AUXILIARY OR
 SECONDARY DRAIN PROTECTION. SEE FBC, M 307.2.3 FOR A
 LIST OF APPROVED METHODS AND SHOW COMPLIANCE.
  
 21. MOTORIZED DAMPERS HAVE NOT BEEN SHOWN IN THE O.A.
 DUCT ON PLANS FOR AHU-1 OR AHU-2. SHOW COMPLIANCE WITH
 FBC 13-409.1.ABC.3.3. GRAVITY OPERATED DAMPERS
 (BACKDRAFT DAMPERS) ARE ACCEPTABLE ON BATHROOM EXHAUST
 DUCTS.
  
 22. OK
  
 23. NO ENERGY CODE COMPLIANCE FORM COULD BE FOUND IN
 THIS SUBMITTAL.
  
 24 ? 26: OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By rregueir Date 2007-10-29 Time 17:54 Rev Time 0.00
Received By rregueir Date 2007-10-25 Time 20:20 Sent To  
Notes
2007-10-29 15:15:34REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG LS.0 DECLARES AN ENCLOSED PARKING GARAGE, BUT
 LS.1 AND LS.2 ARE SHOWING AN OPEN PARKING GARAGE.
 CORRECT ALL REFERENCES, SHOWING THIS TO BE AN ENCLOSED
 PARKING GARAGE. FBC 406.2.1
  
 2. PG M1.1: EF-1, EF-2, EF-20 AND RELATED DUCTWORK,
 WHAT IS THEIR ELEVATION? APPLIANCES LOCATED IN PUBLIC
 GARAGES OR OTHER AREAS FREQUENTED BY MOTOR VEHICLES,
 SHALL BE INSTALLED A MINIMUM OF 8 FEET ABOVE THE FLOOR.
 WHERE MOTOR VEHICLES EXCEED 6 FEET IN HEIGHT AND ARE
 CAPABLE OF PASSING UNDER AN APPLIANCE, APPLIANCES SHALL
 BE INSTALLED A MINIMUM OF 2 FEET HIGHER ABOVE THE FLOOR
 THAN THE HEIGHT OF THE TALLEST VEHICLE UNLESS THE
 APPLIANCES ARE PROTECTED FROM MOTOR VEHICLE IMPACT AND
 INSTALLED IN ACCORDANCE WITH NFPA 88B. FBC,M 304.5
  
 3. PG M1.1: EF-11 IN STORAGE ROOM 1.108 IS SHOWN TO
 DISCHARGE INSIDE THE ENCLOSED PARKING GARAGE. THE AIR
 REMOVED BY EVERY MECHANICAL EXHAUST SYSTEM SHALL BE
 DISCHARGED OUTDOORS AT A POINT WHERE IT WILL NOT CAUSE
 A NUISANCE AND FROM WHICH IT CANNOT AGAIN BE READILY
 DRAWN IN BY A VENTILATING SYSTEM IN ACCORDANCE WITH
 FBC,M 501.2. AN ENCLOSED PARKING GARAGE IS NOT
 OUTDOORS. SHOW COMPLIANCE WITH THIS SECTION.
  
 4. PG M0.1: FAN SCHEDULE CALLS FOR EF-12 IN STORAGE
 ROOM 1.109. HOWEVER, EF-12 IS NOT SHOWN ON PG M1.1 AND
 PG M1.2 SHOWS EF-11 IN THIS ROOM. COORDINATE ALL FLOOR
 PLANS AND SCHEDULES. FBC,M 501.1 AND FBC 106.1.1. ALSO,
 EF-12 IN ROOM 1.109 IS DISCHARGING INTO THE ENCLOSED
 PARKING GARAGE. THE AIR REMOVED BY EVERY MECHANICAL
 EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS AT A POINT
 WHERE IT WILL NOT CAUSE A NUISANCE AND FROM WHICH IT
 CANNOT AGAIN BE READILY DRAWN IN BY A VENTILATING
 SYSTEM IN ACCORDANCE WITH FBC,M 501.2. AN ENCLOSED
 PARKING GARAGE IS NOT OUTDOORS. SHOW COMPLIANCE WITH
 THIS SECTTION.
  
 5. PG M1.1: EF-20 ON 1ST FLOOR, EF-21 ON 2ND FLOOR,
 EF-5A AND EF-22 ON 3RD FLOOR ARE NOT SHOWN TO BE
 PROTECTED FROM MECHANICAL DAMAGE. SHOW THESE FANS TO BE
 PROTECTED FROM VEHICLE IMPACT OR OTHER MECHANICAL
 DAMAGE IN ACCORDANCE WITH FBC,M 303.4 AND 304.5.
  
 6. PG M1.2: EF-23 ON 4TH FLOOR AND EF-24 ON 5TH FLOOR
 ARE NOT SHOWN TO BE PROTECTED FROM MECHANICAL DAMAGE.
 SHOW THESE FANS TO BE PROTECTED FROM VEHICLE IMPACT OR
 OTHER MECHANICAL DAMAGE IN ACCORDANCE WITH FBC,M 303.4
 AND 304.5.
  
 7. PG M2.1: KEY NOTE #3, WILL 7 FT BE AT LEAST 2 FT
 ABOVE THE HEIGHT OF THE TALLEST VEHICLE IN THE GARAGE?
 SHOW COMPLIANCE WITH FBC,M 304.5.
  
 8. PG M2.1 DETAIL 02: L-13 O.A INTAKE LOUVER IS
 ADJACENT TO THE PARKING GARAGE ENTRANCE. MECHANICAL
 OUTSIDE AIR INTAKE OPENINGS SHALL BE LOCATED A MINIMUM
 OF 10 FEET FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 SUCH AS STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS
 IN ACCORDANCE WITH FBC,M 401.5.1. SHOW A LOCATION FOR
 THE O.A. INTAKE WHICH IS IN COMPLIANCE WITH THIS
 SECTION.
  
 9. PG M2.1 DETAIL 02: EF-13, 14 AND 16, ARE THESE
 EXHAUST OUTLETS DISCHARGING ONTO WALKWAYS? SHOW
 COMPLIANCE WITH FBC,M 401.5.2. ALSO, EF-16 SHALL
 DISCHARGE DIRCTLY TO THE OUTDOORS IN ACCORDANCE WITH
 FBC,M 501.2.
  
 10. PG M2.1 DETAIL 02: EF 13, 14 AND 16 EXHAUST DUCTS,
 IF THE WALL SEPARATING OFFICES FROM THE PARKING GARAGE
 ARE REQUIRED TO BE FIRE RESISTANCE RATED (SEE BUILDING
 REVIEW COMMENTS), SHOW HOW DUCT PENETRATIONS OF RATED
 WALL ASSEMBLIES ARE TO BE PROTECTED IN ACCORDANCE WITH
 FBC,M 607.5 OR 607.1.1.
  
 11. PG M2.1 DETAIL 02: EF-17 IS DISCHARGING INTO AN
 ENCLOSED PARKING GARAGE. THE AIR REMOVED BY EVERY
 MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS
 AT A POINT WHERE IT WILL NOT CAUSE A NUISANCE AND FROM
 WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM IN ACCORDANCE WITH FBC,M 501.2. AN
 ENCLOSED PARKING GARAGE IS NOT OUTDOORS. SHOW
 COMPLIANCE WITH THIS SECTTION. ALSO, SEE COMMENT #10
 ABOVE REGARDING OPENING PROTECTION IN RATED WALL
 ASSEMBLIES.
  
 12. PG M2.1 DETAIL 01: EF-11 (OR EF-12, ACCORDING TO
 THE FAN SCHEDULE) IS DISCHARGING INTO AN ENCLOSED
 PARKING GARAGE. THE AIR REMOVED BY EVERY MECHANICAL
 EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS AT A POINT
 WHERE IT WILL NOT CAUSE A NUISANCE AND FROM WHICH IT
 CANNOT AGAIN BE READILY DRAWN IN BY A VENTILATING
 SYSTEM IN ACCORDANCE WITH FBC,M 501.2. AN ENCLOSED
 PARKING GARAGE IS NOT OUTDOORS. SHOW COMPLIANCE WITH
 THIS SECTTION. ALSO, SEE COMMENT #10 ABOVE REGARDING
 OPENING PROTECTION IN RATED WALL ASSEMBLIES.
  
 13. PG M2.1 DETAIL 02: EF-13 AND EF-14, WHAT IS THE
 METHOD OF CONTROL FOR THESE FANS? ALL AIR SUPPLIED TO
 THESE SPACES SHALL BE EXHAUSTED IN ACCORDANCE WITH
 FBC,M 403.2.1(3). THEY MAY BE INTERLOCKED WITH AHU-2,
 RUN CONTINUOUS OR BE PROVIDED WITH TRANSFER AIR FOR
 MAKE-UP OF EXHAUST. ALSO, VENTILATION SHALL BE PROVIDED
 DURING OCCUPANCY IN ACCORDANCE WITH FBC,M 401.3.
  
 14. PG M2.1 DETAIL 02: OFFICE 1.210, THERE IS NO RETURN
 SHOWN IN THE CEILING FOR THIS HABITABLE ROOM. SHOW
 COMPLIANCE WITH FBC,M 601.4. ALS, PLEASE SEE THE
 FOLLOWING COMMENT REGARDING RETURN AIR FLOW ABOVE THE
 CEILING.
  
 15. PG M2.1 DETAILS 02 AND 04: FLOOR PLANS SHOW PLENUM
 CEILINGS WITH FREE-FLOW RETURNS BACK TO AHU'S. HOWEVER,
 WALL TYPES AS SHWON ON PG A5-D.1 AND A6.1 SHOW
 PARTITIONS FROM FLOOR TO DECK IN MOST AREAS. HOW WILL
 RETURN AIR FLOW BACK TO AHU'SWHEN BLOCKED BY
 PARTITIONS? CHOW COMPLIANCE WITH FBC,M 601.4. NOTE: IF
 PARTITION TYPES ARE CHANGED, DUCTS FOR EF'S 13, 14 AND
 16 SHOULD NOT BE EXPOSED TO PLENUM IN ACCORDANCE WITH
 FBC,M 601.3.
  
 16. PG M2.1 DETAIL 02 AND 04: AHU'S 3 AND 4 ON 1ST
 FLOOR SHARE A COMMON RETURN PLENUM AND ARE REQUIRED TO
 HAVE FAN SHUT-DOWN BY SMOKE DETECTOR IN ACCORDANCE WITH
 FBC,M 606.2.2. THE SAME CONDITION OCCURS ON 2ND FLOOR
 WITH AHU'S 5 AND 6. SHOW COMPLIANCE WITH THIS SECTION
 IN THESE AREAS. NOTE: DUCT SMOKE DETECTORS SHALL BE
 CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IF ONE IS
 REQUIRED BY CODE. FBC,M 606.4.1
  
 17. PG M2.1 DETAIL 03: AHU'S 1 AND 2 ARE EACH OVER 2000
 CFM AND REQUIRE FAN SHUT-DOWN BY SMOKE DETECTOR IN
 ACCORDANCE WITH FBC,M 606.2.1. SHOW COMPLIANCE WITH
 THIS SECTION. NOTE: DUCT SMOKE DETECTORS SHALL BE
 CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IF ONE IS
 REQUIRED BY CODE. FBC,M 606.4.1
  
 18. PG M2.1 DETAIL 03: THE 12X10 O.A. DUCT IS PASSING
 THROUGH A TENANT SEPARATION WALL BETWEEN THE TWO
 MERCANTILE UNITS. IF THIS WALL REQURES A FIRE
 RESISTANCE RATING (SEE BUILDING REVIEW COMMENTS) PLEASE
 SHOW OPENING PROTECTIVES AT THIS PENETRATION IN
 ACCORDANCE WITH FBC,M 607.5.
  
 19. PG M2.1 DETAIL 03: THE 24X24 VERTICAL O.A. DUCT IS
 SHOWN PENETRATING A RATED FLOOR/CEILING ASSEMBLY (SEE
 BUILDING REVIEW COMMENTS). SHOW THIS PENETRATION TO BE
 PROTECTED IN ACCIRDANCE WITH FBC,M 607.6.
 NOTE: COORDINATE ANY CHANGES IN FLOOR PLANS BETWEEN
 ARCHITECTURAL AND MECHANICAL DESIGNERS TO ENSURE ALL
 PENETRATIONS OF RATED ASSEMBLIES ARE PROTECTED IN
 ACCORDANCE WITH FBC,M SEC.607 AND FBC CH.7.
  
 20. PG M2.1 DETAILS 02 AND 04: WHAT IS THE SIZE OF THE
 O.A. BRANCH DUCTS FEEDING AHU'S 3 AND 5? HOW WILL THIS
 DUCT BE TIED TO THE AHU'S SINCE THIS IS AN OPEN RETURN
 CEILING? PROVIDE HANGING DETAIL FOR AHU'S SHOWING DUCT
 CONNECTIONS, HOW UNITS ARE HING AND ATTACHED TO
 STRUCTURE AS WELL AS THE MEANS OF AUXILIARY DRAIN
 PROTECTION. FBC,M 301.1, 307.2.3, 603.1, FBC 106.1.2
  
 21. PG M2.1 DETAIL 02,03,04: AHU 1-6 OUTSIDE AIR DUCTS
 FOR VENTILATION SHALL BE DESIGNED TO BE CAPABLE OF
 REDUCING THE SUPPLY OF OUTDOOR AIR TO THE MINIMUM
 VENTILATION RATES REQUIRED BY SECTION 6.1.3 OF ASHRAE
 62. SYSTEMS MAY BE DESIGNED TO SUPPLY OUTSIDE AIR
 QUANTITIES EXCEEDING MINIMUM LEVELS, BUT THEY SHALL BE
 CAPABLE OF OPERATING AT NO MORE THAN MINIMUM LEVELS
 THROUGH THE USE OF RETURN DUCTS, MANUALLY OR
 AUTOMATICALLY OPERATED CONTROL DAMPERS, FAN VOLUME
 CONTROLS, OR OTHER DEVICES IN ACCORDANCE WITH FBC
 13-409.1.ABC.1.1. ALSO, BOTH OUTDOOR AIR SUPPLY AND
 EXHAUST SYSTEMS SHALL BE EQUIPPED WITH MOTORIZED
 DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS
 OR SPACES SERVED ARE NOT IN USE. VENTILATION OUTSIDE
 AIR DAMPERS SHALL BE CAPABLE OF AUTOMATICALLY SHUTTING
 OFF DURING PREOCCUPANCY BUILDING WARMUP, COOLDOWN, AND
 SETBACK, EXCEPT WHEN VENTILATION REDUCES ENERGY COSTS
 (E.G., NIGHT PURGE) OR WHEN VENTILATION MUST BE
 SUPPLIED TO MEET CODE REQUIREMENTS. FBC
 13-409.1.ABC.3.3.
  
 22. PG M0.1 AND M2.1: AC SYSTEMS 1-6 SHALL BE EQUIPPED
 WITH AUTOMATIC SHUTDOWN CONTROLS IN ACCORDANCE WITH FBC
 13-407.1.ABC.2.4.1. SHOW COMPLIANCE WITH THIS SECTION.
  
 23. PROVIDE ENERGY CALCULATIONS IN THE FORM OF AN
 APPROVED ENERGY CODE COMPLIANCE FORM IN ACCORDANCE WITH
 FBC 13-101.1.1 AND 13-103.2.
  
 24. BUILDING CAVITIES WHICH WILL BE USED AS RETURN AIR
 PLENUMS (CEILING SPACES) SHALL BE LINED WITH AN AIR
 BARRIER AND SEALED IN ACCORDANCE WITH SECTION
 410.1.ABC.3.7 AND SHALL BE INSULATED IN ACCORDANCE WITH
 SECTION 410.1.ABC.2. SEE FBC 13-410.1.ABC.3.6.
  
 25. PG M4.1: PROVIDE WALL MOUNTING DETAIL FOR DUCTLESS
 SPLIT SYSTEMS TW-1 THROUGH TW-7, SHOWING WALL BRACKET,
 ANCHORING, REQUIRED CLEARANCES FOR SRVICE AND PROPER
 AIRFLOW AS REQUIRED BY MANUFACTURER'S INSTRUCTIONS IN
 ACCORDANCE WITH FBC,M 304.1 AND FBC 106.1.2.
  
 26. PG M4.1: DETAIL 5 SHOWS A CONDENSER INSTALLED ON A
 BUILT-UP ROOF SYSTEM. THIS DETAIL IS NOT APPLICABLE TO
 THIS PROJECT. PG M1.2 6TH FL PLAN SHOWS CONDENSERS
 INSTALLED ON THE TOP LEVEL OF THE PARKING STRUCTURE.
 SHOW HOW THESE UNITS ARE TO BE SECURED TO THE STRUCTURE
 TO MEET WIND LOAD REQUIREMENTS IN ACCORDANCE WITH FBC,M
 301.13 AND FBC CH.16.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 10 Status P Date 2008-10-27 Cont ID  
Sent By kstevens Date 2008-10-27 Time 12:00 Rev Time 0.00
Received By kstevens Date 2008-10-27 Time 12:00 Sent To  
Notes
2008-10-27 12:00:58REVISION OK -- SHT IR-1

Review Stop P PLUMBING
Rev No 9 Status P Date 2008-09-24 Cont ID  
Sent By kstevens Date 2008-09-24 Time 16:48 Rev Time 0.00
Received By kstevens Date 2008-09-24 Time 16:48 Sent To  
Notes
2008-09-24 16:49:01REVISION OK -- SHT P1.1.

Review Stop P PLUMBING
Rev No 8 Status P Date 2008-07-29 Cont ID  
Sent By kstevens Date 2008-07-29 Time 12:19 Rev Time 0.00
Received By kstevens Date 2008-07-29 Time 12:19 Sent To  
Notes
2008-07-29 12:21:02REVISIONS APPROVED--SHTS P1.1, P2.1 & P3.2

Review Stop P PLUMBING
Rev No 7 Status P Date 2008-07-14 Cont ID  
Sent By kstevens Date 2008-07-14 Time 14:53 Rev Time 0.00
Received By kstevens Date 2008-07-14 Time 14:53 Sent To  
Notes
2008-07-14 14:55:27REVISIONS OK--SHTS P2.1 & P3.2

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-06-26 Cont ID  
Sent By kstevens Date 2008-06-26 Time 12:32 Rev Time 0.00
Received By kstevens Date 2008-06-26 Time 12:32 Sent To  
Notes
2008-06-26 12:39:23REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P1.1 REVISIONS ARE REQUIRED FOR THE STORM &
 CONDENSATE RISER DIAGRAMS TO REFLECT CHANGES TO THESE
 SYSTEMS. PLEASE INDICATE HOW THE CONDENSATE CONNECTS TO
 THE STORM AT COL LINE 2.1/H-J AND COL LINE 3-2.1/C-D.
 REVISIONS FOR RISER DIAGRAMS SHALL BE SUBMITTED WHEN
 SHT P1.1 SO CONNECTIONS CAN BE APPROVED WITH FLOOR PLAN
 CHANGES. SECTIONS 106.1.1, 106.1.3, 106.3.5.1.3 314.2.1
 &1101.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-06-26 Cont ID  
Sent By kstevens Date 2008-06-26 Time 12:31 Rev Time 0.00
Received By kstevens Date 2008-06-18 Time 12:31 Sent To  
Notes
2008-06-26 12:32:31REVISIONS OK--SHTS P2.1 & P3.1

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-04-01 Cont ID  
Sent By kstevens Date 2008-04-01 Time 14:27 Rev Time 0.00
Received By kstevens Date 2008-04-01 Time 14:27 Sent To  
Notes
2008-04-01 14:28:12IRRIGATION PERMIT REQUIRED.--RPZV BACKFLOW REQUIRED
 DOWNSTREAM OF THE METER AND INSTALLED BY LICENSED
 PLUMBING CONTRACTOR.

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-02-21 Cont ID  
Sent By kstevens Date 2008-02-21 Time 14:35 Rev Time 0.00
Received By kstevens Date 2008-02-19 Time 18:54 Sent To  
Notes
2008-02-21 14:38:33DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. SHTS IR.1 & IR.2 ARE REQUIRED TO SEALED WITH AN
 EMBOSSED TYPE SEAL THAT WILL IMPRESS ALL REQUIRED
 INFORMATION ON EACH SHEET. A STAMP SEAL IS NOT
 APPROVED. SECTION 106.1. FAC 61G1-16.001 & 61G1-16.002
 INDICATE THE REQUIREMENTS OF THE SEAL. PLEASE COMPLY.
 FS 481.306.
 ****RESPONSE NOTED, BUT THE REQUIREMENTS FOR THE SEAL
 INDICATE THAT THE SEAL BE "APPROXIMATELY 2 INCHES IN
 DIAMETER". THE OLD SEALS WERE APPROXIMATELY 1-1/2" AND
 THESE ARE NOT APPROVED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-27 Cont ID  
Sent By kstevens Date 2007-12-27 Time 10:04 Rev Time 0.00
Received By kstevens Date 2007-12-26 Time 16:53 Sent To  
Notes
2007-12-27 10:42:05DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT IR.1 SHOW THE LOCATION OF THE WATER SOURCE. IF
 IT IS POTABLE WATER FROM THE CITY, SHOW THE WATER METER
 LOCATION AND THE RPZV BACKFLOW LOCATION.THE NOTE
 "CONNECT TO EXISTING SYSTEM". WHAT EXISTING SYSTEM?
 PLEASE SHOW ALL PIPING FOR THE COMPLETE SYSTEM.(METER
 2 LOCATION IS INDICATED. IS THERE ANOTHER METER?).
 PLEASE CLARIFY. SECTIONS 106.1.1 & 106.1.2.
  
 2. SHT IR.1 SOME INFORMATION ON THE SHEET IS NOT
 LEGIBLE. PLEASE MAKE ALL INFORMATION LEGIBLE. SECTION
 106.1.1.
  
 3. SHT IR.1 SHOWS CONTROLLER B,AND THE LEGEND
 INDICATES A RAIN SENSOR ONE PER EACH CONTROLLER. PLEASE
 CLARIFY. IS THERE MORE THAN ONE CONTROLLER. IF SO
 PLEASE INDICATE THE LOCATION OF EACH CONTROLLER.
 SECTION 106.1.1.
  
 4. SHTS IR.1 & IR.2 ARE REQUIRED TO SEALED WITH AN
 EMBOSSED TYPE SEAL THAT WILL IMPRESS ALL REQUIRED
 INFORMATION ON EACH SHEET. A STAMP SEAL IS NOT
 APPROVED. SECTION 106.1. FAC 61G1-16.001 & 61G1-16.002
 INDICATE THE REQUIREMENTS OF THE SEAL. PLEASE COMPLY.
 FS 481.306.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-26 Cont ID  
Sent By kstevens Date 2007-10-26 Time 17:50 Rev Time 0.00
Received By kstevens Date 2007-10-25 Time 17:50 Sent To  
Notes
2007-10-26 18:48:02DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT T-1 WHITE OUT NOT APPROVED ON SIGNED SEALED
 PLANS. SECTION 106.1.3.
  
 2. SHT T-1 THE SHEET INDEXSHOWS SHEETS LP-0, LP-1,
 LP-2, LP-3 & IRR-1 & IRR-2, BUT THESE SHEETS WERE NOT
 SUBMITTED. PLEASE CORRELATE INDEX WITH SHEETS
 SUBMITTED. SECTION 106.1.1.
  
 3. SURVEY SHEET. THE ADDRESS IN THE TITLE BLOCK DOES
 NOT REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE
 DBPR WEBSITE. PLEASE UPDATE THE TITLE BLOCK OR THE DBPR
 WEBSITE PRIOR TO RESUBMITTING FOR REVIEW. FAC
 61G1-16.004(1), 61G15-23.002(2) & FS 472.025.
  
 4. SHT A2.1 DETAIL 05 SCUPPER SHOWS AN 8" OVERFLOW
 OPENING OPPOSITE THE SCUPPER OPENING FROM THE ROOF.
 THIS SEEMS LIKE THE WATER WILL DRAIN OUT THIS OPENING
 AS WELL AS DRAIN DOWN THE DOWNSPOUT. PLEASE CLARIFY.
 SECTION 106.1.2 & SECTION 1106.
  
 5. SHT A5-D.2 DETAIL 01 IDENTIFY THE DETAIL. NO DETAIL
 TITLE INDICATED. WHAT IS THE DRAIN FOR? PLEASE CLARIFY.
 SECTION 106.1.1 & TABLE 1106.3.
  
 6. SHT A9.1 DETAIL 02. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
  
 7. SHTS P1.1 & P1.2 PLANS SHALL BE DRAWN TO A MINIMUM
 1/8TH SCALE. SECTION 106.1.3.
  
 8. SHTS P1.1 & P1.2 SHOW ALL RWL RISER DESIGNATIONS FOR
 EACH FLOOR. THIS WILL AID IN FOLLOWING THE RISERS THRU
 THE BUILDING AND DECREASE REVIEW TIME. SECTION
 106.1.2.
  
 9. SHT P1.1 SHOW THE SECONDARY ROOF DRAINS/OVERFLOW
 SCUPPERS FOR THE LOWER ROOF AT THE SOUTH SIDE OF THE
 BUILDING. SECTION 1107 & ALL SUBSECTIONS.
  
 10. SHT P1.2 DETAIL 03 SHOWS A LOWER ROOF ON THE SOUTH
 SIDE OF THE BUILDING, BUT NO PIPING IS SHOWN TO THE
 ROOF DRAINS. PLEASE CLARIFY. SECTION 106.1.1 & TABLE
 1106.3.
  
 11. SHT P3.2 RWL-3 MINIMUM 8" PIPE REQUIRED ON THE
 HORIZONTAL (9288SF). TABLE 1106.3.
  
 12. SHT P3.2 RWL-2 MINIMUM 8"PIPE REQUIRED ON THE
 HORIZONTAL (9288SF). TABLE 1106.3.
  
 13. SHT P3.2 RWL-1 MINIMUM 12"PIPE REQUIRED ON THE
 HORIZONTAL (23214SF). TABLE 1106.3.
  
 14. SHT P3.2 RWL-1 RISER DOES NOT REFLECT THE FLOOR
 PLAN. AREA DRAINS ARE SHOWN ON THE RIGHT SIDE OF THE
 RISER ON THE FLOOR PLAN AND THE OFFSET AT THE BASE OF
 THE RISER IS NOT SHOWN. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 106.1.1.
  
 15. SHT P3.2 THE CONDENSATE SHALL RUN SEPARATELY TO THE
 CATCH BASIN, NOT DISCHARGE INTO THE STORM RISER
 DIAGRAM. PLEASE CONNECT THE CONDENSATE TO THE STORM.
 SECTION 1106.3 & TABLE 1106.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-12-04 Cont ID  
Sent By mflis Date 2008-12-04 Time 16:04 Rev Time 0.00
Received By mflis Date 2008-12-04 Time 16:04 Sent To  
Notes
2008-12-04 16:04:42ZONING REVIEW: PASSED
  
 ** REVISION OF ENTRY ISLANDS AT BANYAN BLVD
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 3 Status P Date 2008-10-22 Cont ID  
Sent By mflis Date 2008-10-22 Time 08:38 Rev Time 0.00
Received By mflis Date 2008-10-22 Time 08:38 Sent To  
Notes
2008-10-22 08:38:49ZONING REVIEW (FOR LANDSCAPE): PASSED
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status P Date 2007-12-21 Cont ID  
Sent By mflis Date 2007-12-21 Time 13:40 Rev Time 0.00
Received By mflis Date 2007-12-21 Time 13:40 Sent To  
Notes
2007-12-21 13:42:25ZONING REVIEW: PASSED
  
 OLD COMMENTS:
  
 1) OK
 2) OK - GRILLES WERE ADDED.
 3) OK - SEPARATE PERMIT
 4) OK - SEPARATE PERMIT
 5) OK - ARCH INDICATED THESE WERE BELOW-GRADE UTILITY
 BOXES AND WOULD NOT INTERFERE WITH PEDESTRIAN ACCESS
 6) OK
 7) OK
 8) OK
 9) OK
 10) OK
 11) OK
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-24 Cont ID  
Sent By mflis Date 2007-10-24 Time 17:22 Rev Time 0.00
Received By mflis Date 2007-10-24 Time 17:22 Sent To  
Notes
2007-10-25 08:35:45ZONING REVIEW: FAILED
  
 1) PLEASE SUBMIT EXTERIOR MATERIAL AND PAINT COLOR
 SELECTIONS TO CITY FOR APPROVAL.
 2) ON A4 - 2, DOWNTOWN ACTION COMMITTEE CHAIR REQUESTED
 A GRILLE BE USED IN ARCH INSET AREAS ABOVE STOREFRONT
 ALONG CLEMATIS (TO MATCH GRILLES ON QUADRILLE FACADE).
 ARCHITECT SAID THIS WOULD BE OK. PLEASE CONFIRM GRILLES
 WILL BE ADDED.
 3) SIGNAGE SHALL BE REVIEWED UNDER SEPARATE PERMIT.
 4) AWNINGS SHALL BE REVIEWED UNDER SEPARATE PERMIT.
 5) METER BOXES APPEAR TO BE LOCATED IN SIDEWALK ALONG
 EASTER SIDE OF SITE. PLEASE CONFIRM AND RELOCATE
 AGAINST BUILDING SO THEY DO NOT IMPEDE PEDESTRIAN
 MOVEMENT.
 6) BIKE RACK COUNT AND LOCATIONS SHOULD BE REVIEWED IN
 CONSULTATION WITH CITY STAFF. THESE WILL NEED TO BE
 INDICATED IN PLAN.
 7) PARKING ADMIN OFFICES AND EQUIPMENT LOCATIONS TO BE
 REVIEWED BY S. OLLEY. PLEASE CONFIRM.
 8) LANDSCAPE PLANS TO BE REVIEWED UPON RESUBMILLAL OF
 PERMIT.
 9) AWNING ALONG QUADRILLE ELEVATION ONLY SHOW FROM SIDE
 VIEW ON CLEMATIS AND BANYAN ELEVATION DRAWINGS. PLEASE
 SHOWN ON QUADRILLE ELEVATION.
 10) PLEASE CONFIRM THERE IS ENOUGH CLEARANCE FOR
 PEDESTRIANS TO EXIT/ENTER GARAGE WITHOUT WALKING IN
 DRIVE LANES ALONG CLEMATIS STREET SIDE. PLANS AND
 ELEVATIONS INDICATE APPROXIMATELY 3'-6" OF WIDTH IN PED
 PASSAGES. PLEASE CONFRIM.
 11) DASHED LINES ARE SHOWN ABOVE ELEVATOR/STAIRS IN
 A1.2/02 - NOT SURE WHAT THIS IS SHOWNING. PLEASE
 CLARIFY.
  
 MATT FLIS - 822-1445