Plan Review Stops For Permit 07090742 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-12-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-12-20 |
Time |
07:39 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-12-20 |
Time |
07:01 |
Sent To |
|
|
Notes |
2007-12-20 07:40:28 | PROCESS PLANS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-11-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-11-19 |
Time |
17:37 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-11-19 |
Time |
17:37 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-10-01 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-10-01 |
Time |
17:19 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-09-28 |
Time |
11:46 |
Sent To |
|
|
Notes |
2007-10-01 17:54:36 | 2004 FBC W/2007 REVISIONS | | NSFR | | | | DENIED BY BUILDING | | | | 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) PROVIDE INFORMATION IN REGARDS TO THE SURROUNDING | | TERRAIN. NOTE THAT THE DEFINITION FOR EXPOSURE C HAS | | CHANGED EFFECTIVE DECEMBER 8, 2006 (2006 AMENDMENTS TO | | THE FBC), FBC1609.4, FBC R301.2.1.4. | | IF THERE IS EXPOSURE C TYPE TERRAIN IN ANY QUADRANT | | FOR A DISTANCE OF MORE THAN 600 FEET THE STRUCTURE | | SHALL BE DESIGNED TO EXPOSURE C. NOTE: THE COMPONENT | | AND CLADDING PRESSURES WILL NEED TO BE INCREASED TO | | EXPOSURE C VALUES, WHICH MAY AFFECT THE PRODUCT | | APPROVALS. | | | | 3) A ONE HOUR FIRE RATED GLASS BLOCK ASSEMBLY WILL BE | | REQUIRED AT THE ZERO LOT LINE PER R302.1. PLEASE | | SPECIFY ON THE PLANS. | | | | 4) SUBMIT PRODUCT APPROVALS, MANUFACTURER'S | | SPECIFICATIONS AND LISTING FOR THE ONE HOUR FIRE RATED | | GLASS BLOCK ASSEMBLY THAT WILL BE USED. | | | | 5) SHOW COMPLIANCE WITH FBC R401.3 DRAINAGE. | | | | 6) IN THE WINDOW SCHEDULE ON SHEET A-4.0, 2" X 4" | | MULLIONS ARE SPECIFIED. SUBMIT PRODUCT APPROVALS FOR | | THESE MULLS AS REQUIRED BY FAC RULE 9B-72 OR REVISE THE | | PLAN. | | | | 7) THE PRODUCT APPROVAL FOR THE IMPACT SLIDING GLASS | | DOOR FL251-R5 HAS BEEN REVISED AS THE NOA EXPIRED ON | | 11/9/05. SUBMIT THE NEW FL251-R7 AND CURRENT NOA. | | | | 8) SPECIFY WHICH FASTENERS LISTED IN THE ICC ROOF TILE | | PRODUCT APPROVAL WILL BE USED TO ATTACH THE TILES. | | CIRCLE THE NUMBER AND TYPE ON THE PRODUCT APPROVAL. | | | | - ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-12-04 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-12-04 |
Time |
08:56 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-12-04 |
Time |
06:26 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-11-19 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-11-19 |
Time |
07:47 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-11-19 |
Time |
06:36 |
Sent To |
P |
|
Notes |
2007-11-19 07:47:51 | | | | | APPLICATION #07090742 | | ELECTRICAL PLAN REVIEW | | 6793 SPARROW HAWK DRIVE | | 11/19/07 | | WEST PALM BEACH, FL. | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE | | NOTED. | | | | ALL COMMENTS RELATE TO SHEET A-3.0, UNLESS OTHERWISE | | NOTED. | | | | THESE COMMENTS ARE FROM THE PREVIOUS REVIEW. | | | | 4} IN THE "ELECTRICAL LEGEND" FOR AFI RECEPTACLES THE | | 2002 NEC IS INCORRECTLY REFERENCED. THE 2005 NEC IS THE | | CURRENT EDITION ADOPTED BY THE STATE. *HAND DRAWN | | CHANGES TO THE PLAN ARE UNACCEPTABLE AS IT CANNOT BE | | DETERMINED THAT THE CHANGES WERE MADE WITH THE | | KNOWLEDGE OR CONSENT OF THE DESIGNER OF RECORD. 106.1.3 | | FBC AS AMENDED. | | | | 5} IF THE PVC CONDUIT FEED FROM PANEL "A" TO PANEL "B" | | IS EXPOSED TO PHYSICAL DAMAGE PER 352.10(F) SCHEDULE 80 | | WOULD BE REQUIRED. THE SCHEDULE 80 WOULD NEED TO BE | | INCREASED TO 1 1/4" TO MEET MINIMUM SIZE FOR FILL | | REQUIREMENTS OF ARTICLE 352.22. *HAND DRAWN CHANGES TO | | THE PLAN ARE UNACCEPTABLE AS IT CANNOT BE DETERMINED | | THAT THE CHANGES WERE MADE WITH THE KNOWLEDGE OR | | CONSENT OF THE DESIGNER OF RECORD. 106.1.3 FBC AS | | AMENDED. | | | | 7} THE ARCHITECTS SEAL IS INDISCERNIBLE, ALL SHEETS. | | SEE 61G1-16.001 FAC. *THE INFORMATION ON THE SEAL STILL | | CANNOT BE READ. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-09-27 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-09-27 |
Time |
14:24 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-09-27 |
Time |
10:23 |
Sent To |
M |
|
Notes |
2007-09-27 14:23:51 | | | | | APPLICATION #07090742 | | ELECTRICAL PLAN REVIEW | | 6793 SPARROW HAWK DRIVE | | | | WEST PALM BEACH, FL. | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | ALL COMMENTS RELATE TO SHEET A-3.0, UNLESS OTHERWISE | | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | OTHERWISE NOTED. | | | | 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | EQUAL TO OR GREATER | | THAN THE AVAILABLE FAULT. | | | | 2} THE 13000VA HEAT CALCULATION GIVEN IN PANEL "A" DOES | | NOT CORRELATE TO THE 10000 VA LOADS SHOWN IN THE PANEL | | SCHEDULE OR IN THE MECHANICAL SPECIFICATIONS. | | | | 3} THE 6' GROUND ROD INDICATED ON THE RISER DIAGRAM IS | | NOT IN COMPLIANCE WITH 250.53(G) "THE ELECTRODE SHALL | | BE INSTALLED SUCH THAT AT LEAST 2.44 M (8 FT) OF LENGTH | | IS IN CONTACT WITH THE SOIL". | | | | 4} IN THE "ELECTRICAL LEGEND" FOR AFI RECEPTACLES THE | | 2002 NEC IS INCORRECTLY REFERENCED. THE 2005 NEC IS THE | | CURRENT EDITION ADOPTED BY THE STATE. | | | | 5} IF THE PVC CONDUIT FEED FROM PANEL "A" TO PANEL "B" | | IS EXPOSED TO PHYSICAL DAMAGE PER 352.10(F) SCHEDULE 80 | | WOULD BE REQUIRED. THE SCHEDULE 80 WOULD NEED TO BE | | INCREASED TO 1 1/4"TO MEET MINIMUM SIZE FOR FILL | | REQUIREMENTS OF ARTICLE 352.22. | | | | 6} THE ELECTRICAL NOTES ON SHEET D-1 INDICATE #12 | | CONDUCTORS WILL BE THE MINIMUM SIZE FOR THIS PROJECT, | | THE PANEL SCHEDULE FOR PANEL "A" LISTS SEVERAL #14 | | CONDUCTORS FOR BRANCH CIRCUITS. PLEASE CORRELATE SAME. | | | | 7} THE ARCHITECTS SEAL IS INDISCERNIBLE, ALL SHEETS. | | SEE 61G1-16.001 FAC. | | | | 8} THE SIGNATURE OF THE REVIEWER FOR GFA CANNOT BE READ | | DUE TO THE LOCATION IN THE COMPLIANCE BLOCK. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-04-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-14 |
Time |
12:04 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-14 |
Time |
12:04 |
Sent To |
E |
|
Notes |
2008-04-14 12:04:54 | TO "BTROBAUG" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-12-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-19 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-19 |
Time |
11:56 |
Sent To |
Z |
|
Notes |
2007-12-19 11:56:55 | TO "Z" BOX/RESUB--PRIVATE PROVIDER-- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-12-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-03 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-03 |
Time |
16:07 |
Sent To |
E |
|
Notes |
2007-12-03 16:08:10 | TO "Z" BOX/RESUB--PRIVATE PROVIDER-- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-11-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-16 |
Time |
15:52 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-16 |
Time |
15:52 |
Sent To |
Z |
|
Notes |
2007-11-16 15:53:18 | TO "CHOOPS" DESK/RESUB--PRIVATE PROVIDER-- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-10-01 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-10-01 |
Time |
17:20 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-09-27 |
Time |
09:04 |
Sent To |
|
|
Notes |
2007-09-27 09:04:47 | TO "CHOOPS" DESK/PRIVATE PROVIDER |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2007-11-26 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-11-26 |
Time |
08:36 |
Rev Time |
0.45 |
Received By |
tgordon |
Date |
2007-11-26 |
Time |
08:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-09-28 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-09-28 |
Time |
09:09 |
Rev Time |
1.00 |
Received By |
tgordon |
Date |
2007-09-28 |
Time |
09:09 |
Sent To |
P |
|
Notes |
2007-09-28 09:49:02 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) ENERGY CALCULATIONS LINE 11B STATES THE AIR HANDLER | | IS INSTALLED IN THE INTERIOR, BUT THE PLANS SHOW THE | | AIR HANDLER TO BE INSTALLED IN THE ATTIC, THE TWO MUST | | COINCIDE. SEE F.B.C. 106.1.1CONSTRUCTION DOCUMENTS | | SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE | | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS | | OF THIS CODE AND RELEVANT LAWS. PLEASE CORRECT. | | | | 2) COOLING LOAD CALCULATIONS SHOW SYSTEM ONE TOTAL | | COOLING BTU'S TO BE 34,112, MECHANICAL PLANS SHOW | | SYSTEM ONE TO BE 46,500 TOTAL BTU'S. PER F.B.C. | | 13-607.1.ABC.1.1 THE PLANS MAY ONLY CALL FOR 15% MORE | | TOTAL COOLING BTU'S THEN THE COOLING LOAD CALCULATIONS, | | PLEASE CORRECT. (SEE ATTACHED ARI SHEET THAT SHOWS A 3 | | TON SYSTEM MAYMEET THIS REQUIREMENT). | | | | 3) COOLING LOAD CALCULATIONS SHOW SYSTEM TWO TOTAL | | COOLING BTU'S TO BE 20,318, MECHANICAL PLANS SHOW | | SYSTEM TWO TO BE 29,200 TOTAL BTU'S. PER F.B.C. | | 13-607.1.ABC.1.1 THE PLANS MAY ONLY CALL FOR 15% MORE | | TOTAL COOLING BTU'S THEN THE COOLING LOAD CALCULATIONS, | | PLEASE CORRECT. (SEE ATTACHED ARI SHEET THAT SHOWS A 2 | | TON SYSTEM MAYMEET THIS REQUIREMENT). | | | | 4) SEE MECHANICAL PLAN EQUIPMENT SCHEDULE, MODEL | | NUMBERS FOR THE CONDENSER UNITS COULD NOT BE FOUND IN | | THE ARI DIRECTORY, PLEASE CORRECT AND PROVIDE A ARI | | REFERENCE SHEET, SEE W.P.B AMEND. 106.2. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2007-11-19 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-11-19 |
Time |
08:39 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-11-19 |
Time |
08:39 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-09-28 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-09-28 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-09-28 |
Time |
10:00 |
Sent To |
B |
|
Notes |
2007-09-28 10:24:04 | DENIED; | | RISER DIAGRAM DOES NOT MATCH FLAT DRAWING. | | A) BATH #2 SHOWER IS PART OF THE BATHROOM GROUP | | ON RISER DIAGRAM PART OF THE 1/2 BATH ON FLOOR PLAN | | WITH OWN VENT. | | B) KITCHEN, RISER DIAGRAM SHOWS A LOOP VENT, | | FLAT DRAWING DOES NOT. | | C) MASTER BATH RISER DIAGRAM DOES NOT MATCH FLAT | | DRAWING | | RISER DIAGRAM SHOWS 2" AT BASE OF WAHER STACK WITH A 3" | | VENT THOUGH ROOF. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2007-12-19 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-12-19 |
Time |
13:52 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-12-19 |
Time |
13:52 |
Sent To |
B |
|
Notes |
2007-12-19 13:53:08 | ***APPROVED - RESUB #3*** | | | | | | | | SENT TO "B" - RMC |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2007-12-03 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-12-03 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-12-03 |
Time |
16:40 |
Sent To |
E |
|
Notes |
2007-12-03 16:43:43 | ***FAILED - RESUB #2*** | | | | | | REPEAT COMMENTS: | | | | 1)PURSUANT TO SECTION 94-482(A) OF THE ZLDRS: | | REQUIRED PARKING MAY BE LOCATED IN A FRONT YARD; | | HOWEVER, THE LESSER OF 1,000 SQUARE FEET OR 75 PERCENT | | OF THE FRONT YARD AREA MUST BE LANDSCAPED. PARKING | | AREAS LOCATED IN THE FRONT YARD SHALL BE SURFACED WITH | | A SMOOTH, NONDUSTING SURFACE IN COMPLIANCE WITH | | SUBSECTION 33-485(E).PLEASE PROVIDE ALL DIMENSIONS | | AND SQUARE FOOTAGE OF PROPOSED DRIVEWAY, INCLUDING ANY | | WALKWAYS.ALSO INDICATE IF APPROACH IS TO BE INCLUDED | | IN THE SCOPE OF WORK FOR THIS PERMIT, AS THIS WILL | | REQUIRE A REVIEW FROM THE CITY'S ENGINEERING DEPT. | | PROPOSED DRIVEWAY (SHOWN ON SURVEY) EXCEEDS MAXIMUM | | SQUARE FOOTAGE ALLOWABLE...792 SQ.FT. IS THE MAXIMUM | | ALLOWABLE. | | | | 2)PLEASE PROVIDE AN APPROVED EASEMENT CONSENT FORM | | FROM THE CITY OF WEST PALM BEACH DEPARTMENT OF PUBLIC | | UTILITIES (1ST FLOOR, CITY HALL) TO APPROVE THE | | PROPOSED PRIVACY WALL AT THE SOUTH. | | | | 3)INDICATE ELEVATION (HEIGHT) DIMENSIONS FROM GRADE | | TO THE MIDPOINT OF THE ROOF'S PITCH (ON SHEET A-4.0). | | | | NEW COMMENT: | | | | 1)TWO COPIES OF ALL PLANS SHALL BE SUBMITTED | | (LANDSCAPE PLAN). | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | TECHNICIAN | | (561)805-6720 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2007-11-16 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-11-16 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-11-16 |
Time |
16:34 |
Sent To |
E |
|
Notes |
2007-11-16 16:35:57 | ***FAILED - RESUB #1*** | | | | | | REPEAT COMMENTS: | | | | 1)PURSUANT TO SECTION 94-482(A) OF THE ZLDRS: | | REQUIRED PARKING MAY BE LOCATED IN A FRONT YARD; | | HOWEVER, THE LESSER OF 1,000 SQUARE FEET OR 75 PERCENT | | OF THE FRONT YARD AREA MUST BE LANDSCAPED. PARKING | | AREAS LOCATED IN THE FRONT YARD SHALL BE SURFACED WITH | | A SMOOTH, NONDUSTING SURFACE IN COMPLIANCE WITH | | SUBSECTION 33-485(E).PLEASE PROVIDE ALL DIMENSIONS | | AND SQUARE FOOTAGE OF PROPOSED DRIVEWAY, INCLUDING ANY | | WALKWAYS.ALSO INDICATE IF APPROACH IS TO BE INCLUDED | | IN THE SCOPE OF WORK FOR THIS PERMIT, AS THIS WILL | | REQUIRE A REVIEW FROM THE CITY'S ENGINEERING DEPT. | | PROPOSED DRIVEWAY EXCEEDS MAXIMUM SQUARE FOOTAGE | | ALLOWABLE...792 SQ.FT. IS THE MAXIMUM ALLOWABLE. | | | | 2)PLEASE PROVIDE AN EASEMENT CONSENT FORM FROM THE | | CITY OF WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES | | (1ST FLOOR, CITY HALL) TO APPROVE THE PROPOSED PRIVACY | | WALL AT THE SOUTH. | | | | 3)INDICATE ELEVATION (HEIGHT) DIMENSIONS FROM GRADE | | TO THE MIDPOINT OF THE ROOF'S PITCH (ON SHEET A-4.0). | | | | NEW COMMENT: | | | | 1)AS THERE IS NO LANDSCAPE PLAN WITH THIS | | RESUBMITTAL, A LANDSCAPE PLAN SHOWING COMPLIANCE WITH | | SECTION 94-442 OF THE CITY OF WEST PALM BEACH ZONING | | AND LAND DEVELOPMENT REGULATIONS SHALL BE SUBMITTED. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | TECHNICIAN | | (561)805-6720 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-09-27 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-09-27 |
Time |
09:36 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-09-27 |
Time |
09:36 |
Sent To |
E |
|
Notes |
2007-09-27 09:47:54 | ***FAILED*** | | | | | | 1)PURSUANT TO SECTION 94-305(B)(4) OF THE ZONING AND | | LAND DEVELOPMENT REGULATIONS (ZLDRS):MECHANICAL | | EQUIPMENT MAY NOT PROJECT MORE THAN FOUR FEET INTO A | | SETBACK.PLEASE INDICATE SETBACK DIMENSIONS FROM | | PROPOSED MECHANICAL EQUIPMENT TO THE PROPERTY LINES. | | | | 2)PURSUANT TO SECTION 94-482(A) OF THE ZLDRS: | | REQUIRED PARKING MAY BE LOCATED IN A FRONT YARD; | | HOWEVER, THE LESSER OF 1,000 SQUARE FEET OR 75 PERCENT | | OF THE FRONT YARD AREA MUST BE LANDSCAPED. PARKING | | AREAS LOCATED IN THE FRONT YARD SHALL BE SURFACED WITH | | A SMOOTH, NONDUSTING SURFACE IN COMPLIANCE WITH | | SUBSECTION 33-485(E).PLEASE PROVIDE ALL DIMENSIONS | | AND SQUARE FOOTAGE OF PROPOSED DRIVEWAY, INCLUDING ANY | | WALKWAYS.ALSO INDICATE IF APPROACH IS TO BE INCLUDED | | IN THE SCOPE OF WORK FOR THIS PERMIT, AS THIS WILL | | REQUIRE A REVIEW FROM THE CITY'S ENGINEERING DEPT. | | | | 3)PLEASE PROVIDE AN EASEMENT CONSENT FORM FROM THE | | CITY OF WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES | | TO APPROVE THE PROPOSED PRIVACY WALL AT THE SOUTH. | | | | 4)INDICATE ELEVATION (HEIGHT) DIMENSIONS FROM GRADE | | TO THE MIDPOINT OF THE ROOF'S PITCH. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | TECHNICIAN | | (561)805-6720 |
|
|