Plan Review Details - Permit 07090742
Plan Review Stops For Permit 07090742
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-20 Cont ID  
Sent By rmcdouga Date 2007-12-20 Time 07:39 Rev Time 0.00
Received By rmcdouga Date 2007-12-20 Time 07:01 Sent To  
Notes
2007-12-20 07:40:28PROCESS PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-19 Cont ID  
Sent By rmcdouga Date 2007-11-19 Time 17:37 Rev Time 0.00
Received By rmcdouga Date 2007-11-19 Time 17:37 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-01 Cont ID  
Sent By rmcdouga Date 2007-10-01 Time 17:19 Rev Time 0.00
Received By rmcdouga Date 2007-09-28 Time 11:46 Sent To  
Notes
2007-10-01 17:54:362004 FBC W/2007 REVISIONS
 NSFR
  
 DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE INFORMATION IN REGARDS TO THE SURROUNDING
 TERRAIN. NOTE THAT THE DEFINITION FOR EXPOSURE C HAS
 CHANGED EFFECTIVE DECEMBER 8, 2006 (2006 AMENDMENTS TO
 THE FBC), FBC1609.4, FBC R301.2.1.4.
 IF THERE IS EXPOSURE C TYPE TERRAIN IN ANY QUADRANT
 FOR A DISTANCE OF MORE THAN 600 FEET THE STRUCTURE
 SHALL BE DESIGNED TO EXPOSURE C. NOTE: THE COMPONENT
 AND CLADDING PRESSURES WILL NEED TO BE INCREASED TO
 EXPOSURE C VALUES, WHICH MAY AFFECT THE PRODUCT
 APPROVALS.
  
 3) A ONE HOUR FIRE RATED GLASS BLOCK ASSEMBLY WILL BE
 REQUIRED AT THE ZERO LOT LINE PER R302.1. PLEASE
 SPECIFY ON THE PLANS.
  
 4) SUBMIT PRODUCT APPROVALS, MANUFACTURER'S
 SPECIFICATIONS AND LISTING FOR THE ONE HOUR FIRE RATED
 GLASS BLOCK ASSEMBLY THAT WILL BE USED.
  
 5) SHOW COMPLIANCE WITH FBC R401.3 DRAINAGE.
  
 6) IN THE WINDOW SCHEDULE ON SHEET A-4.0, 2" X 4"
 MULLIONS ARE SPECIFIED. SUBMIT PRODUCT APPROVALS FOR
 THESE MULLS AS REQUIRED BY FAC RULE 9B-72 OR REVISE THE
 PLAN.
  
 7) THE PRODUCT APPROVAL FOR THE IMPACT SLIDING GLASS
 DOOR FL251-R5 HAS BEEN REVISED AS THE NOA EXPIRED ON
 11/9/05. SUBMIT THE NEW FL251-R7 AND CURRENT NOA.
  
 8) SPECIFY WHICH FASTENERS LISTED IN THE ICC ROOF TILE
 PRODUCT APPROVAL WILL BE USED TO ATTACH THE TILES.
 CIRCLE THE NUMBER AND TYPE ON THE PRODUCT APPROVAL.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-12-04 Cont ID  
Sent By btrobaug Date 2007-12-04 Time 08:56 Rev Time 0.00
Received By btrobaug Date 2007-12-04 Time 06:26 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-19 Cont ID  
Sent By btrobaug Date 2007-11-19 Time 07:47 Rev Time 0.00
Received By btrobaug Date 2007-11-19 Time 06:36 Sent To P
Notes
2007-11-19 07:47:51 
  
 APPLICATION #07090742
 ELECTRICAL PLAN REVIEW
 6793 SPARROW HAWK DRIVE
 11/19/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 ALL COMMENTS RELATE TO SHEET A-3.0, UNLESS OTHERWISE
 NOTED.
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW.
  
 4} IN THE "ELECTRICAL LEGEND" FOR AFI RECEPTACLES THE
 2002 NEC IS INCORRECTLY REFERENCED. THE 2005 NEC IS THE
 CURRENT EDITION ADOPTED BY THE STATE. *HAND DRAWN
 CHANGES TO THE PLAN ARE UNACCEPTABLE AS IT CANNOT BE
 DETERMINED THAT THE CHANGES WERE MADE WITH THE
 KNOWLEDGE OR CONSENT OF THE DESIGNER OF RECORD. 106.1.3
 FBC AS AMENDED.
  
 5} IF THE PVC CONDUIT FEED FROM PANEL "A" TO PANEL "B"
 IS EXPOSED TO PHYSICAL DAMAGE PER 352.10(F) SCHEDULE 80
 WOULD BE REQUIRED. THE SCHEDULE 80 WOULD NEED TO BE
 INCREASED TO 1 1/4" TO MEET MINIMUM SIZE FOR FILL
 REQUIREMENTS OF ARTICLE 352.22. *HAND DRAWN CHANGES TO
 THE PLAN ARE UNACCEPTABLE AS IT CANNOT BE DETERMINED
 THAT THE CHANGES WERE MADE WITH THE KNOWLEDGE OR
 CONSENT OF THE DESIGNER OF RECORD. 106.1.3 FBC AS
 AMENDED.
  
 7} THE ARCHITECTS SEAL IS INDISCERNIBLE, ALL SHEETS.
 SEE 61G1-16.001 FAC. *THE INFORMATION ON THE SEAL STILL
 CANNOT BE READ.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-27 Cont ID  
Sent By btrobaug Date 2007-09-27 Time 14:24 Rev Time 0.00
Received By btrobaug Date 2007-09-27 Time 10:23 Sent To M
Notes
2007-09-27 14:23:51 
  
 APPLICATION #07090742
 ELECTRICAL PLAN REVIEW
 6793 SPARROW HAWK DRIVE
  
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET A-3.0, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER
 THAN THE AVAILABLE FAULT.
  
 2} THE 13000VA HEAT CALCULATION GIVEN IN PANEL "A" DOES
 NOT CORRELATE TO THE 10000 VA LOADS SHOWN IN THE PANEL
 SCHEDULE OR IN THE MECHANICAL SPECIFICATIONS.
  
 3} THE 6' GROUND ROD INDICATED ON THE RISER DIAGRAM IS
 NOT IN COMPLIANCE WITH 250.53(G) "THE ELECTRODE SHALL
 BE INSTALLED SUCH THAT AT LEAST 2.44 M (8 FT) OF LENGTH
 IS IN CONTACT WITH THE SOIL".
  
 4} IN THE "ELECTRICAL LEGEND" FOR AFI RECEPTACLES THE
 2002 NEC IS INCORRECTLY REFERENCED. THE 2005 NEC IS THE
 CURRENT EDITION ADOPTED BY THE STATE.
  
 5} IF THE PVC CONDUIT FEED FROM PANEL "A" TO PANEL "B"
 IS EXPOSED TO PHYSICAL DAMAGE PER 352.10(F) SCHEDULE 80
 WOULD BE REQUIRED. THE SCHEDULE 80 WOULD NEED TO BE
 INCREASED TO 1 1/4"TO MEET MINIMUM SIZE FOR FILL
 REQUIREMENTS OF ARTICLE 352.22.
  
 6} THE ELECTRICAL NOTES ON SHEET D-1 INDICATE #12
 CONDUCTORS WILL BE THE MINIMUM SIZE FOR THIS PROJECT,
 THE PANEL SCHEDULE FOR PANEL "A" LISTS SEVERAL #14
 CONDUCTORS FOR BRANCH CIRCUITS. PLEASE CORRELATE SAME.
  
 7} THE ARCHITECTS SEAL IS INDISCERNIBLE, ALL SHEETS.
 SEE 61G1-16.001 FAC.
  
 8} THE SIGNATURE OF THE REVIEWER FOR GFA CANNOT BE READ
 DUE TO THE LOCATION IN THE COMPLIANCE BLOCK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-14 Cont ID  
Sent By adarroug Date 2008-04-14 Time 12:04 Rev Time 0.00
Received By adarroug Date 2008-04-14 Time 12:04 Sent To E
Notes
2008-04-14 12:04:54TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 11:56 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 11:56 Sent To Z
Notes
2007-12-19 11:56:55TO "Z" BOX/RESUB--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-03 Cont ID  
Sent By adarroug Date 2007-12-03 Time 16:07 Rev Time 0.00
Received By adarroug Date 2007-12-03 Time 16:07 Sent To E
Notes
2007-12-03 16:08:10TO "Z" BOX/RESUB--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-16 Cont ID  
Sent By adarroug Date 2007-11-16 Time 15:52 Rev Time 0.00
Received By adarroug Date 2007-11-16 Time 15:52 Sent To Z
Notes
2007-11-16 15:53:18TO "CHOOPS" DESK/RESUB--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-01 Cont ID  
Sent By rmcdouga Date 2007-10-01 Time 17:20 Rev Time 0.00
Received By rmcdouga Date 2007-09-27 Time 09:04 Sent To  
Notes
2007-09-27 09:04:47TO "CHOOPS" DESK/PRIVATE PROVIDER

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-26 Cont ID  
Sent By tgordon Date 2007-11-26 Time 08:36 Rev Time 0.45
Received By tgordon Date 2007-11-26 Time 08:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-28 Cont ID  
Sent By tgordon Date 2007-09-28 Time 09:09 Rev Time 1.00
Received By tgordon Date 2007-09-28 Time 09:09 Sent To P
Notes
2007-09-28 09:49:02PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 11B STATES THE AIR HANDLER
 IS INSTALLED IN THE INTERIOR, BUT THE PLANS SHOW THE
 AIR HANDLER TO BE INSTALLED IN THE ATTIC, THE TWO MUST
 COINCIDE. SEE F.B.C. 106.1.1CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS. PLEASE CORRECT.
  
 2) COOLING LOAD CALCULATIONS SHOW SYSTEM ONE TOTAL
 COOLING BTU'S TO BE 34,112, MECHANICAL PLANS SHOW
 SYSTEM ONE TO BE 46,500 TOTAL BTU'S. PER F.B.C.
 13-607.1.ABC.1.1 THE PLANS MAY ONLY CALL FOR 15% MORE
 TOTAL COOLING BTU'S THEN THE COOLING LOAD CALCULATIONS,
 PLEASE CORRECT. (SEE ATTACHED ARI SHEET THAT SHOWS A 3
 TON SYSTEM MAYMEET THIS REQUIREMENT).
  
 3) COOLING LOAD CALCULATIONS SHOW SYSTEM TWO TOTAL
 COOLING BTU'S TO BE 20,318, MECHANICAL PLANS SHOW
 SYSTEM TWO TO BE 29,200 TOTAL BTU'S. PER F.B.C.
 13-607.1.ABC.1.1 THE PLANS MAY ONLY CALL FOR 15% MORE
 TOTAL COOLING BTU'S THEN THE COOLING LOAD CALCULATIONS,
 PLEASE CORRECT. (SEE ATTACHED ARI SHEET THAT SHOWS A 2
 TON SYSTEM MAYMEET THIS REQUIREMENT).
  
 4) SEE MECHANICAL PLAN EQUIPMENT SCHEDULE, MODEL
 NUMBERS FOR THE CONDENSER UNITS COULD NOT BE FOUND IN
 THE ARI DIRECTORY, PLEASE CORRECT AND PROVIDE A ARI
 REFERENCE SHEET, SEE W.P.B AMEND. 106.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-19 Cont ID  
Sent By jleech Date 2007-11-19 Time 08:39 Rev Time 0.00
Received By jleech Date 2007-11-19 Time 08:39 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-28 Cont ID  
Sent By jleech Date 2007-09-28 Time 10:01 Rev Time 0.00
Received By jleech Date 2007-09-28 Time 10:00 Sent To B
Notes
2007-09-28 10:24:04DENIED;
 RISER DIAGRAM DOES NOT MATCH FLAT DRAWING.
 A) BATH #2 SHOWER IS PART OF THE BATHROOM GROUP
 ON RISER DIAGRAM PART OF THE 1/2 BATH ON FLOOR PLAN
 WITH OWN VENT.
 B) KITCHEN, RISER DIAGRAM SHOWS A LOOP VENT,
 FLAT DRAWING DOES NOT.
 C) MASTER BATH RISER DIAGRAM DOES NOT MATCH FLAT
 DRAWING
 RISER DIAGRAM SHOWS 2" AT BASE OF WAHER STACK WITH A 3"
 VENT THOUGH ROOF.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2007-12-19 Cont ID  
Sent By choops Date 2007-12-19 Time 13:52 Rev Time 0.00
Received By choops Date 2007-12-19 Time 13:52 Sent To B
Notes
2007-12-19 13:53:08***APPROVED - RESUB #3***
  
  
  
 SENT TO "B" - RMC

Review Stop Z ZONING
Rev No 3 Status F Date 2007-12-03 Cont ID  
Sent By choops Date 2007-12-03 Time 16:40 Rev Time 0.00
Received By choops Date 2007-12-03 Time 16:40 Sent To E
Notes
2007-12-03 16:43:43***FAILED - RESUB #2***
  
  
 REPEAT COMMENTS:
  
 1)PURSUANT TO SECTION 94-482(A) OF THE ZLDRS:
 REQUIRED PARKING MAY BE LOCATED IN A FRONT YARD;
 HOWEVER, THE LESSER OF 1,000 SQUARE FEET OR 75 PERCENT
 OF THE FRONT YARD AREA MUST BE LANDSCAPED. PARKING
 AREAS LOCATED IN THE FRONT YARD SHALL BE SURFACED WITH
 A SMOOTH, NONDUSTING SURFACE IN COMPLIANCE WITH
 SUBSECTION 33-485(E).PLEASE PROVIDE ALL DIMENSIONS
 AND SQUARE FOOTAGE OF PROPOSED DRIVEWAY, INCLUDING ANY
 WALKWAYS.ALSO INDICATE IF APPROACH IS TO BE INCLUDED
 IN THE SCOPE OF WORK FOR THIS PERMIT, AS THIS WILL
 REQUIRE A REVIEW FROM THE CITY'S ENGINEERING DEPT.
 PROPOSED DRIVEWAY (SHOWN ON SURVEY) EXCEEDS MAXIMUM
 SQUARE FOOTAGE ALLOWABLE...792 SQ.FT. IS THE MAXIMUM
 ALLOWABLE.
  
 2)PLEASE PROVIDE AN APPROVED EASEMENT CONSENT FORM
 FROM THE CITY OF WEST PALM BEACH DEPARTMENT OF PUBLIC
 UTILITIES (1ST FLOOR, CITY HALL) TO APPROVE THE
 PROPOSED PRIVACY WALL AT THE SOUTH.
  
 3)INDICATE ELEVATION (HEIGHT) DIMENSIONS FROM GRADE
 TO THE MIDPOINT OF THE ROOF'S PITCH (ON SHEET A-4.0).
  
 NEW COMMENT:
  
 1)TWO COPIES OF ALL PLANS SHALL BE SUBMITTED
 (LANDSCAPE PLAN).
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2007-11-16 Cont ID  
Sent By choops Date 2007-11-16 Time 16:35 Rev Time 0.00
Received By choops Date 2007-11-16 Time 16:34 Sent To E
Notes
2007-11-16 16:35:57***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 1)PURSUANT TO SECTION 94-482(A) OF THE ZLDRS:
 REQUIRED PARKING MAY BE LOCATED IN A FRONT YARD;
 HOWEVER, THE LESSER OF 1,000 SQUARE FEET OR 75 PERCENT
 OF THE FRONT YARD AREA MUST BE LANDSCAPED. PARKING
 AREAS LOCATED IN THE FRONT YARD SHALL BE SURFACED WITH
 A SMOOTH, NONDUSTING SURFACE IN COMPLIANCE WITH
 SUBSECTION 33-485(E).PLEASE PROVIDE ALL DIMENSIONS
 AND SQUARE FOOTAGE OF PROPOSED DRIVEWAY, INCLUDING ANY
 WALKWAYS.ALSO INDICATE IF APPROACH IS TO BE INCLUDED
 IN THE SCOPE OF WORK FOR THIS PERMIT, AS THIS WILL
 REQUIRE A REVIEW FROM THE CITY'S ENGINEERING DEPT.
 PROPOSED DRIVEWAY EXCEEDS MAXIMUM SQUARE FOOTAGE
 ALLOWABLE...792 SQ.FT. IS THE MAXIMUM ALLOWABLE.
  
 2)PLEASE PROVIDE AN EASEMENT CONSENT FORM FROM THE
 CITY OF WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES
 (1ST FLOOR, CITY HALL) TO APPROVE THE PROPOSED PRIVACY
 WALL AT THE SOUTH.
  
 3)INDICATE ELEVATION (HEIGHT) DIMENSIONS FROM GRADE
 TO THE MIDPOINT OF THE ROOF'S PITCH (ON SHEET A-4.0).
  
 NEW COMMENT:
  
 1)AS THERE IS NO LANDSCAPE PLAN WITH THIS
 RESUBMITTAL, A LANDSCAPE PLAN SHOWING COMPLIANCE WITH
 SECTION 94-442 OF THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS SHALL BE SUBMITTED.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-27 Cont ID  
Sent By choops Date 2007-09-27 Time 09:36 Rev Time 0.00
Received By choops Date 2007-09-27 Time 09:36 Sent To E
Notes
2007-09-27 09:47:54***FAILED***
  
  
 1)PURSUANT TO SECTION 94-305(B)(4) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS):MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN FOUR FEET INTO A
 SETBACK.PLEASE INDICATE SETBACK DIMENSIONS FROM
 PROPOSED MECHANICAL EQUIPMENT TO THE PROPERTY LINES.
  
 2)PURSUANT TO SECTION 94-482(A) OF THE ZLDRS:
 REQUIRED PARKING MAY BE LOCATED IN A FRONT YARD;
 HOWEVER, THE LESSER OF 1,000 SQUARE FEET OR 75 PERCENT
 OF THE FRONT YARD AREA MUST BE LANDSCAPED. PARKING
 AREAS LOCATED IN THE FRONT YARD SHALL BE SURFACED WITH
 A SMOOTH, NONDUSTING SURFACE IN COMPLIANCE WITH
 SUBSECTION 33-485(E).PLEASE PROVIDE ALL DIMENSIONS
 AND SQUARE FOOTAGE OF PROPOSED DRIVEWAY, INCLUDING ANY
 WALKWAYS.ALSO INDICATE IF APPROACH IS TO BE INCLUDED
 IN THE SCOPE OF WORK FOR THIS PERMIT, AS THIS WILL
 REQUIRE A REVIEW FROM THE CITY'S ENGINEERING DEPT.
  
 3)PLEASE PROVIDE AN EASEMENT CONSENT FORM FROM THE
 CITY OF WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES
 TO APPROVE THE PROPOSED PRIVACY WALL AT THE SOUTH.
  
 4)INDICATE ELEVATION (HEIGHT) DIMENSIONS FROM GRADE
 TO THE MIDPOINT OF THE ROOF'S PITCH.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720