Plan Review Details - Permit 07090685
Plan Review Stops For Permit 07090685
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-07 Cont ID  
Sent By amorse Date 2008-02-07 Time 18:01 Rev Time 0.00
Received By amorse Date 2008-02-07 Time 18:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-31 Cont ID  
Sent By amorse Date 2007-12-31 Time 12:10 Rev Time 0.00
Received By amorse Date 2007-12-31 Time 12:10 Sent To PC
Notes
2007-12-31 12:30:36 
 DENIED
  
  
 THE FOLLOWING COMMENT WAS NOT ADDRESSED FROM 1ST
 REVIEW:
  
 7)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
 *****PRODUCT APPROVALS AND SHOP DRAWINGS SHALL BE
 REVIEWED AND APPROVED BY PERSONS RESPONSIBLE FOR THE
 DRAWINGS*****
  
 NEW REVIEW COMMENTS
  
 1)PHOTO COPIED, STAMPED OR REPRODUCED SIGNATURES ARE
 NOT ACCEPTABLE PER 471.025 F.S.
 SOIL REPORTS AND TRUSS DRAWINGS ARE REQUIRED TO CARRY
 ORIGINAL SIGNATURES
  
 2)TRUSS DRAWING PLAN SHALL INCLUDE WIND DESIGN DATA
 AND LOADS AS REQUIRED BY DESIGNER OF RECORD. INDIVIDUAL
 TRUSS SHEETS ARE NOT REQUIRED TO BE SIGNED AND SEALED
 INDIVIDUALLY SO LONG AS A SIGNED AND SEALED INDEX SHEET
 LISTING TRUSSES IS INCLUDED. PLEASE NOTE THAT THESE
 DRAWINGS CAN BE GIVEN TO THE INSPECTOR AT ROOF FRAMING
 INSPECTION.
  
 3)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS WITH REVISIONS AND INCLUDE 1 COPY OF
 THE OLD PAGES ONLY FOR REFERENCE. PLEASE RE-SUBMIT ANY
 PAGES WITH THE IMPACT FEE STAMP
 *****PLEASE NOTE THAT BOTH NEW SETS ARE INCOMPLETE,
 SHEETS A/3,A/4,A/8 AND A/9 FROM OLD SETS NEED TO BE
 INSERTED INTO NEW SETS AND BOTH IMPACT FEE SHEETS ADDED
 FOR THE STAMP ONLY*****
  
 4)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING, THE NOTICE IS
 VOID
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-25 Cont ID  
Sent By amorse Date 2007-10-25 Time 14:16 Rev Time 0.00
Received By amorse Date 2007-10-25 Time 14:16 Sent To PC
Notes
2007-10-25 14:30:41 
  
 DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $418.21 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 3)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION
  
 4)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE
 OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2
 COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER
 R401.4 FBC RES.
  
 5)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 6)ALONG WITH LANDSCAPE PLAN PROVIDE A SITE PLAN THAT
 SHOWS DRAINAGE IN COMPLIANCE WITH THE REQUIREMENTS OF
 R403.1 FBC RES.
  
 7)THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 8)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 9)NO PRODUCT APPROVALS WERE SUBMITTED FOR LINTELS,
 METAL ROOFING IF USED AND CONNECTORS AND STRAPS. IN LUE
 OF PRODUCT APPROVALS STRAPS/CONNECTORS MAY BE LISTED IN
 A SCHEDULE ON THE DRAWINGSCOMPLETE WITH THE STATEWIDE
 PRODUCT APPROVAL NUMBERS OR SUBMIT SIMPSON TIES
 COMPLETE FLORIDA INDEX WITH CONNECTORS TO BE USED
 HIGHLIGHTED
  
 10)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 11)THE FOLLOWING COMMENTS ARE REQUIRED FOR THE OFFICE
 AREA AS IT IS CONSIDERED TO BE A BEDROOM, EMERGENCY
 EGRESS PER R310 FBC: MIN. NET CLEAR OPENING OF 5 SQ.FT.
 ON GRADE FLOOR. THE MIN.NET CLEAR HEIGHT SHALL BE 24"
 AND THE NET CLEAR WIDTH SHALL BE 20" AND PROVIDE SMOKE
 ALARMS TO THE INTERIOR AND EXTERIOR OF THIS ROOM AND TO
 EXISTING BUILDING PER R313.1.1 FBC RES.
  
 12)PROVIDE SIZE AND AMOUNT OF ATTIC VENTILATION THAT
 MEETS THE REQUIREMENTS OF R806.2 FBC RES.
  
 13)ADDITIONS ARE NEW CONSTRUCTION AS SUCH SHALL
 COMPLY WITH THE ACCESSIBILITY REQUIREMENTS OF THE FBC
 RES.PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER
 R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90 DEGREES
  
 14) PROVIDE MIN ROOF SHEATHING ATTACHMENT PER
 R803.2.3.1 FBC RES. PLEASE NOTE THAT THIS HAS CHANGED
 WITH THE 2006 AMENDMENT TO 4" O/C FIELD AND EDGES IN
 ZONE 3
  
 15)BUILDING ELEVATION TO INCLUDE MEAN ROOF HEIGHT
  
 16)PROVIDE NOTE FOR SHOWER DOORS TO BE SAFETY GLAZING
 PER R308.4 FBC RES.
  
 17)SHOW MIN INSULATION BETWEEN THE CONDITIONED AND
 UNCONDITIONED FLOOR/CEILING SPACE FROM LIVING ROOM TO
 BALCONY ABOVE
  
 18)DRAWINGS TO CORRECTLY REFLECT TYPE OF ROOFING
 PLANS STATE METAL AND PRODUCT APPROVALS ARE FOR TILE
  
 19)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES
 ONLY FOR REFERENCE
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-28 Cont ID  
Sent By dpalmer Date 2008-01-28 Time 14:31 Rev Time 0.00
Received By dpalmer Date 2008-01-28 Time 14:31 Sent To M
Notes
2008-01-28 14:47:20REDLINED PLANS.
  
 ALL RECESSED LIGHTING SHALL BE PER FBC
 13-606.1.ABC.1.2.4

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-20 Cont ID  
Sent By dpalmer Date 2007-12-20 Time 14:51 Rev Time 0.00
Received By dpalmer Date 2007-12-20 Time 14:51 Sent To M
Notes
2007-12-20 14:51:23** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME OF THE NOTES FROM PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW
 NOTES DUE TO CHANGES MADE TO PLANS WHICH WERE NOT ON
 PREVIOUS PLANS.
  
  
 1) NOTE: PLEASE SEE FBC R313 FOR SMOKE ALARMS REQUIRED
 TO MEET NFPA-72 11.5.1.1INSIDE AND OUTSIDE ALL
 EXISTING SLEEPING ROOMS.
 PLEASE SHOW AND INDICATE THESE IN THE EXISTING DWELLING
 EITHER NEW TO BE INSTALLED OR EXISTING MEETING CURRENT
 CODE.
 THIS NOTE WAS ON PREVIOUS REVIEW.
  
 2) NOTE: PLEASE SEE THE RISER DIAGRAM HAS COMPLETELY
 BEEN REVISED AND CHANGED FROM PREVIOUS PLANS.
 PLEASE SEE THERE ARE SEVERAL ITEMS SHOWN ON LOAD
 CALCULATIONS HOWEVER ARE NOT LISTED ON PANEL SCHEDULE.
 FOR EXAMPLE: PLEASE SEE DISHWASHER, WASHER, DRYER,
 SMALL APPLIANCE, ETC ETC WHICH ARE NOT LISTED ON THE
 PANEL SCHEDULE.
 PLEASE LIST.
 PLEASE KNOW THE MINIMUM OVER CURRENT PROTECTION, AND
 CONDUCTOR SIZES NEED TO BE VERIFIED AT THIS TIME FROM
 NEW PANEL.
 240.4, 310.16
 PLEASE SEE NEC 408.4 AS THIS REQUIRES ALL CIRCUITS TO
 BE IDENTIFIED ON PANEL SCHEDULE FOR ROOMS AND AREAS IN
 WHICH THEY FEED.
  
 3) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS, THE NOTE MENTIONS AT THE BOTTOM OF PANEL
 SCHEDULE HOWEVER AS NOTED ABOVE ON NOTE #2, THIS NEEDS
 TO BE LISTED FOR CIRCUITS. THIS ITEM COULD BE REDLINED
 FOR REVISION BEFORE FINAL HOWEVER MAY BE REVISED AT
 THIS TIME.
 THIS WAS NOTED ON PREVIOUS REVIEW.
  
 4) NOTE: PLEASE KNOW FOR INFORMATIONAL PURPOSE AND
 REQUIRED BY CODE ALL RECESSED LIGHTS NEED TO MEET FBC
 13-606.1.ABC.1.2.4 FOR TRANSFER OF AIR FROM CONDITIONED
 SPACE.
  
 ** PLEASE KNOW SOME OF THESE ITEMS COULD HAVE BEEN
 RED-LINED HOWEVER NOT ALL. PLANS ARE COMING BACK FOR
 COMMENTS FROM ZONING PLEASE ADDRESS AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-27 Cont ID  
Sent By dpalmer Date 2007-09-27 Time 07:53 Rev Time 0.00
Received By dpalmer Date 2007-09-26 Time 16:05 Sent To M
Notes
2007-09-27 07:53:562007-09-27 07:53:56
  
 ** DENIED**
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THE PLANS ARE MISSING INDICATING
 LOCATIONS FOR NEW AND/OR EXISTING SMOKE ALARMS PER FBC
 R313 AND NFPA-72 11.5.1.1, 11.8.3.
 PLEASE SEE THE FIRST FLOOR OF THE NEW ADDITION IS
 MISSING A SMOKE ALARM ALSO IN THE VICINITY LEADING TO
 THE FLOOR ABOVE.
 PLEASE KNOW THE OFFICE IS CONSIDERED AN ADAPTABLE
 SLEEPING ROOM THIS WILL ALSO REQUIRE SMOKE ALARMS
 INSIDE AND OUTSIDE THIS ROOM.
 PLEASE SEE THE SMOKE DETECTION DEVICE IS REQUIRED TO BE
 WITHIN 3FT OG THE PEAK ON THE SLOPED CEILING OR WITHIN
 12INCHES FOR HIGHEST POINT ON FLAT OR TRAY CEILINGS.
 PLEASE SEE MINIMUM DISTANCES FROM CEILING FANS AS
 STATED IN NFPA-72 11.8.3.
 PLEASE KNOW THAT THE PLANS ARE SHOWING *SD* AND LEGEND
 STATES SMOKE DETECTORS. PLEASE VERIFY THIS AS BY
 NFPA-72 DEFINITIONS A SMOKE DETECTOR IS ONLY A DEVICE
 WHICH DETECTS AND DOES NOT SOUND AN ALARM. THE PLANS
 WOULD THEN NEED TO INDICATE THE HORN DEVICES ALONG WITH
 A FIRE ALARM PANEL. IF THIS IS THE INTENT PLEASE
 COMPLETE PLANS ACCORDINGLY. IF THESE ARE MEANT TO BE SA
 FOR SMOKE ALARMS WHICH ARE A DEVICE WHICH DETECTS AND
 SOUNDS AN ALARM PLEASE ADJUST SYMBOL AND LEGEND.
  
 3) NOTE: PLEASE SEE RISER MENTIONS NEW SERVICE, HOWEVER
 EXISTING METER. PLEASE INDICATE THE SIZE/AMPERAGE OF
 THIS METER.
 PLEASE SEE THE RISER IS MISSING ALL CONDUCTORS FROM
 METER TO GUTTER, GUTTER TO MAINS ETC.
 THIS SERVICE IS BEING SHOWN AS 225AMPS. PLEASE VERIFY.
 PLEASE COMPLETE RISER.
 240.4, 310.16
  
 4) NOTE: PLEASE SEE THE PLANS DO NOT INDICATE THE
 LOCATIONS OF ALL SERVICE EQUIPMENT ALONG WITH THE
 LOCATION OF NEW PANEL.
 PLEASE SEE 230.70, 230.71, 230.72, 230.76 AND 230.76
 FOR MAINS AND GROUPING.
 PLEASE SEE 110.26, 240.24, FOR LOCATIONS WHICH NEED TO
 MEET THESE SECTIONS ALONG WITH OTHER SECTIONS OF THE
 NEC.
 PLEASE KNOW AS THE LOCATIONS OF EQUIPMENT HAVE NOT BEEN
 SHOWN, REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT
 THIS TIME.
  
 5) NOTE: PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR
 SIZE IS TOO SMALL FOR THE SERVICE AS SHOWN.
 PLEASE SEE 250.66.
  
 6) NOTE: PLEASE SEE MISSING COMPLETE GROUNDING
 ELECTRODE SYSTEM PER 250.50.
 PLEASE SEE MISSING NEW FOOTER STEEL REQUIRED AND OTHER
 ELECTRODES.
  
 7) NOTE: PLEASE SEE MISSING AIC RATING(S) FOR NEW
 SERVICE EQUIPMENT PER 110.9.
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE MISSING CONDENSING UNIT ON PLANS
 ALONG WITH REQUIRED DISCONNECT PER 440.11 AND MISSING
 GFI RECEPTACLE PER 210.63 AND 210.8A3
  
 9) NOTE: PLEASE SEE MISSING REQUIRED LISTED ARC FAULT
 PROTECTED CIRCUITS PER 210.12 FOR *ALL* OUTLETS IN
 DWELLING SLEEPING ROOMS.
  
 10) NOTE: PLEASE SEE MISSING THE REQUIRED DEDICATED
 BATH(S) CIRCUIT(S) PER 210.52D AND 210.11C3. PLEASE
 KNOW THESE MUST BE 20AMP AND #12. PLEASE ADJUST PANEL
 SCHEDULE.
  
 11) NOTE: PLEASE SE THE CLOSET LIGHT DOES NOT MEET THE
 MINIMUM CLEARANCE REQUIREMENTS PER 410.8.
 THIS IS FOR OFFICE CLOSET.
  
 12) NOTE: PLEASE 220.83B FOR LOAD CALCULATIONS AND
 ADJUST.
 PLEASE SEE 422.13 AS THE LOAD TO BE FIGURED FOR THE
 WATER HEATER IS TO BE SHOWN AT 125%. THIS WAS CHANGED
 IN THE 2005 NEC AS THIS IS NOW CONSIDERED A CONTINUOUS
 LOAD.
 PLEASE VERIFY SMALL APPLIANCE CIRCUITS PER 210.52B,
 210.11C1, 220.53 (SHOWN AS PORTABLE?)
 PLEASE ADJUST LOAD CALCULATIONS.
  
 13) NOTE: PLEASE SEE THE RISER IS MISSING THE EQUIPMENT
 GROUNDING CONDUCTORS FROM NEW MAIN TO NEW PANEL PER
 250.110, 250.122.
  
 14) NOTE: PLEASE SEE 210.52 AS THERE ARE SEVERAL
 MISSING RECEPTACLES PER 2FT OF WALL SPACE. SOME OF
 THESE LOCATIONS ARE REDLINED ON ONE SET OF PLANS.
 PLEASE SEE 2FT, 6FT, AND 12FT RULE.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS MISSING FROM
 PLANS A FULL AND COMPLETE REVIEW FOR CODE COMPLIANCE
 COULD NOT BE DONE AT THIS TIME. PLEASE KNOW THERE MAY
 VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-27 06:54:342007-09-27 06:54:34
  
 IN ELEC FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-11-24 Cont ID  
Sent By adarroug Date 2008-11-24 Time 16:14 Rev Time 0.00
Received By adarroug Date 2008-11-24 Time 16:14 Sent To P
Notes
2008-11-24 16:14:39TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-28 Cont ID  
Sent By tgordon Date 2008-05-28 Time 13:19 Rev Time 0.00
Received By tgordon Date 2008-05-28 Time 13:19 Sent To M
Notes
2008-05-28 13:19:49TO MECH. BOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-24 Cont ID  
Sent By adarroug Date 2008-01-24 Time 10:48 Rev Time 0.00
Received By adarroug Date 2008-01-24 Time 10:48 Sent To Z
Notes
2008-01-24 10:49:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-14 Cont ID  
Sent By adarroug Date 2007-12-14 Time 16:46 Rev Time 0.00
Received By adarroug Date 2007-12-14 Time 16:46 Sent To Z
Notes
2007-12-14 16:46:32TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-10-25 Time   Rev Time 0.00
Received By adarroug Date 2007-09-25 Time 09:57 Sent To  
Notes
2007-09-25 09:58:21TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-28 Cont ID  
Sent By tgordon Date 2008-05-28 Time 13:52 Rev Time 0.30
Received By tgordon Date 2008-05-28 Time 13:52 Sent To  
Notes
2008-05-28 13:53:27REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-01-28 Cont ID  
Sent By tgordon Date 2008-01-28 Time 16:02 Rev Time 0.20
Received By tgordon Date 2008-01-28 Time 16:02 Sent To P
Notes
2008-01-28 16:03:06REVIEWED AND STAMPED ON 12-20-07.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-20 Cont ID  
Sent By tgordon Date 2007-12-20 Time 16:40 Rev Time 0.30
Received By tgordon Date 2007-12-20 Time 16:39 Sent To P
Notes
2007-12-20 16:41:44*** PROVISO ***
 1) PROVIDE FOR RETURN AIR TO OFFICE, PER 2004 FBC/R
 M1602.4.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-15 Cont ID  
Sent By tgordon Date 2007-10-15 Time 08:39 Rev Time 0.30
Received By tgordon Date 2007-10-15 Time 08:39 Sent To P
Notes
2007-10-15 08:44:42PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.2.
  
 2) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1.
  
 3) PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004
 FBC CITY OF WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-01-13 Cont ID  
Sent By lwagner Date 2009-01-13 Time 08:40 Rev Time 0.00
Received By lwagner Date 2009-01-13 Time 08:34 Sent To  
Notes
2009-01-13 08:42:11PLUMBING REVISION ON SHEET E1 OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-02-06 Cont ID  
Sent By jleech Date 2008-02-06 Time 13:47 Rev Time 0.00
Received By jleech Date 2008-02-06 Time 13:47 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-10-20 Cont ID  
Sent By jleech Date 2007-10-20 Time 13:43 Rev Time 0.00
Received By jleech Date 2007-10-20 Time 13:40 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-01-28 Cont ID  
Sent By choops Date 2008-01-28 Time 09:44 Rev Time 0.00
Received By choops Date 2008-01-28 Time 09:44 Sent To E
Notes
2008-01-28 09:44:46***APPROVED - RESUB #2***
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 2 Status F Date 2007-12-19 Cont ID  
Sent By choops Date 2007-12-19 Time 10:05 Rev Time 0.00
Received By choops Date 2007-12-19 Time 10:04 Sent To E
Notes
2007-12-19 10:09:17***FAILED - RESUB #1***
  
  
 1)AS THE UPDATED LANDSCAPE PLAN PROVIDED IS ALSO ON A
 SHEET THAT CONTAINS INFORMATION REGARDING SETBACKS
 WHICH NEEDS TO BE A SIGNED/SEALED SHEET, AND THE NEWLY
 PROVIDED SHEETS WERE NOT SIGNED AND SEALED,NEW
 SIGNED/SEALED UPDATED SHEETS SHALL BE PROVIDED.
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-26 Cont ID  
Sent By choops Date 2007-09-26 Time 13:47 Rev Time 0.00
Received By choops Date 2007-09-26 Time 13:46 Sent To E
Notes
2007-09-26 14:04:57***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF ALL SUBMITTED
 PLANS (SURVEYS).
  
 2)INDICATE HEIGHT ON ELEVATIONS FROM GRADE TO THE
 MIDPOINT OF THE ROOF'S PITCH.
  
 3)SHOW ANY PROPOSED A/C EQUIPMENT (IF ANY) WITH
 SETBACK DIMENSIONS FROM PROPERTY LINES.
  
 4)AS THE PROPOSED RENOVATION EXCEEDS 50% OF THE
 IMPROVEMENT VALUE OF THE HOME, LANDSCAPING SHALL BE
 BROUGHT TO COMPLIANCE WITH SECTION 94-442 OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS(ZLDRS), PURSUANT TO
 SECTION 94-441(C) OF THE ZLDRS.PLEASE PROVIDE A
 LANDSCAPE PLANS SHOWING COMPLIANCE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING