Plan Review Details - Permit 07090662
Plan Review Stops For Permit 07090662
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 15:18 Rev Time 0.00
Received By adarroug Date 2007-12-10 Time 15:18 Sent To P
Notes
2007-12-10 15:19:21TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 13:48 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 13:48 Sent To P
Notes
2007-11-19 13:48:34TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-26 Cont ID  
Sent By adarroug Date 2007-10-26 Time 15:16 Rev Time 0.00
Received By adarroug Date 2007-10-26 Time 15:16 Sent To P
Notes
2007-10-26 15:16:29TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-09 Cont ID  
Sent By mperson Date 2007-10-09 Time 14:11 Rev Time 0.00
Received By mperson Date 2007-09-24 Time 16:48 Sent To  
Notes
2007-09-24 16:48:58TO "P" BOX

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-01-10 Cont ID  
Sent By mperson Date 2008-01-10 Time 09:21 Rev Time 0.00
Received By mperson Date 2008-01-10 Time 09:21 Sent To  
Notes
2008-01-10 09:47:28 
  
 ****************PROVISO****************
 909.1 WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE
 VENTED BY A WET VENT. THE WET VENT SHALL BE CONSIDERED
 THE VENT FOR THE FIXTURES AND SHALL EXTEND FROM THE
 CONNECTION OF THE DRY VENT ALONG THE DIRECTION OF THE
 FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE
 DRAIN CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY
 THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
2008-01-10 09:22:29NOTE: RESTAMP (PER LUIS MARTINEZ NO FEE)

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-12-13 Cont ID  
Sent By mperson Date 2007-12-13 Time 13:16 Rev Time 0.00
Received By mperson Date 2007-12-13 Time 13:16 Sent To PC
Notes
2007-12-13 13:21:03****************PROVISO***************
 909.1 WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE
 VENTED BY A WET VENT. THE WET VENT SHALL BE CONSIDERED
 THE VENT FOR THE FIXTURES AND SHALL EXTEND FROM THE
 CONNECTION OF THE DRY VENT ALONG THE DIRECTION OF THE
 FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE
 DRAIN CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY
 THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-12-03 Cont ID  
Sent By mperson Date 2007-12-03 Time 15:19 Rev Time 0.00
Received By mperson Date 2007-12-03 Time 15:19 Sent To PC
Notes
2007-12-03 16:15:16PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 07 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 3RD TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE STILL
 REQUIRED FOR PLUMBING PLAN REVIEW TO MEET CODE
 COMPLIANCE FROM THE PREVIOUS PLAN REVIEWS:
  
 1. OK, COMMENT ADDRESSED
  
 2. OK, COMMENT ADDRESSED.
  
 3. OK, COMMENT ADDRESSED.
  
 4. OK, COMMENT ADDRESSED.
  
 5. OK, COMMENT ADDRESSED.
  
 6. OK, COMMENT ADDRESSED.
  
 7. OK, COMMENT ADDRESSED.
  
 8. OK, COMMENT ADDRESSED.
  
 9. OK, COMMENT ADDRESSED.
  
 10. THE RESUBMITTED EXISTING FLOOR PLAN OR THE NEW
 FLOOR PLAN ARE NOT INDICATING A DRINKING FOUNTAIN. PER
 TABLE *403.1(2), 1 PER 100 IS REQUIRED FOR BUILDINGS
 FOR THE TRANSACTION OF BUSINESS AND SHALL BE
 ACCESSIBLE. PLEASE INDICATE THAT THERE IS AN EXISTING
 DRINKING FOUNTAIN AND ITS LOCATION OR INDICATE THAT A
 NEW ONE WILL BE PROVIDED WITH THE FOLLOWING INFORMATION
 ON THE RESUBMITTED PLANS. IF A NEW ONE IS REQUIRED THE
 PLUMBING FOR THE NEW DRINKING FOUNTAIN WILL NEED TO BE
 ON THE RESUBMITTED SANITARY AND WATER RISER DIAGRAMS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 *****RESPONSE NOTED ON PLANS: HOWEVER THE RESUBMITTED
 PLANS ARE INDICATING A WATER COOLER, NOT A DRINKING
 FOUNTAIN. PER *410.1 APPROVAL. IN OTHER OCCUPANCIES,
 WHERE DRINKING FOUNTAINS ARE REQUIRED, BOTTLED WATER
 DISPENSERS SHALL BE PERMITTED TO BE SUBSTITUTED FOR NOT
 MORE THAN 50 PERCENT OF THE REQUIRED DRINKING
 FOUNTAINS. INTERPRETATION IS 1 ACCESSIBLE DRINKING
 FOUNTAIN IS REQUIRED PER THE ABOVE REQUIREMENTS AND ITS
 REQUIRED SANITARY AND WATER NEED TO BE INDICATED ON THE
 RESUBMITTED SANITARY AND WATER ISOMETRIC RISER
 DIAGRAMS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-06 Cont ID  
Sent By mperson Date 2007-11-06 Time 16:25 Rev Time 0.00
Received By mperson Date 2007-11-05 Time 16:25 Sent To PC
Notes
2007-11-05 17:00:59DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE ON THE
 RESUBMITTED PLANS:
  
 1. RESUBMITTED ISOMETRIC WATER RISER DIAGRAM IN PENCIL
 IS UNACCEPTABLE. PLEASE RESUBMIT IN PEN. PER *106.1.3
 QUALITY OF BUILDING PLANS.
  
 2. THERE WAS ONLY ONE BELLA PEDICURE SPAS SCHEMATIC IN
 THE RESUBMITTAL.
 PER *106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
  
 3. THE WASTE FOR THE PEDICURE SPAS MUST DRAIN
 DOWNSTREAM OF THE EXISTING WET VENT BATHROOM. PER
 FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 4. PER DISCUSSION WITH ACTING CHIEF PLUMBING INSPECTOR
 LARRY WAGNER THE WASTE PIPE AND THE WASTE STACK FOR THE
 PEDICURE SPAS WILL NEED TO BE 3" AND THE TRAP WILL NEED
 TO BE 2" WITH A STANDPIPE, PER *422 HEALTH CARE
 FIXTURES AND EQUIPMENT, *406.3 WASTE CONNECTION, AND
 802.4 STANDPIPES.
  
 5. CLEANOUTS ARE REQUIRED FOR THE PEDICURE SPAS PER
 THE FOLLOWING:
  
 (A) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 **NOTE: CLEANOUT FOR THE PEDICURE SPAS SHALL BE THREE
 INCH (3").
  
 (B) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **NOTE: CLEANOUT FOR THE PEDICURE SPAS SHALL BE FOUR
 FEET ABOVE FINNISH FLOOR (4' A.F.F.).
  
 6. VACUUM BREAKERS ARE REQUIRED FOR THE HOT AND COLD
 WATER TO THE PEDICURE SPAS. VACUUM BREAKERS SHALL BE
 INSTALLED A MINIMUM OF 6 INCHES ABOVE THE FLOOD LEVEL
 RIM OF THE FIXTURE OR DEVICE IN ACCORDANCE WITH SECTION
 *608. THE FLOOD LEVEL RIM OF HOSE CONNECTIONS SHALL BE
 THE MAXIMUM HEIGHT AT WHICH ANY HOSE IS UTILIZED.
 PLEASE INDICATE THESE ON THE RESUBMITTED WATER RISER
 DIAGRAM.
  
 7. RESUBMITTED PLANS INDICATE EXISTING BACKFLOW
 PREVENTERS. PER *607.3.2 WHERE A BACKFLOW PREVENTION
 DEVICE IS INSTALLED ON A WATER SUPPLY SYSTEM UTILIZING
 WATER HEATING EQUIPMENT SUCH THAT THERMAL EXPANSION
 CONTROL CAUSES AN INCREASED PRESSURE, A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED. PLEASE
 INDICATE THIS ON THE RESUBMITTED WATER RISER DIAGRAM.
  
 8. PER *606.1(7) A FULL OPEN VALVE IS REQUIRED ON THE
 WATER SUPPLY PIPE TO EVERY WATER HEATER. PLEASE
 INDICATE THIS ON THE RESUBMITTED WATER RISER DIAGRAM.
  
 9. PLEASE CLEARLY INDICATE ON THE RESUBMITTED PLANS IF
 THE NEW WATER HEATER IS GAS OR ELECTRIC. *PER *106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 10. THE RESUBMITTED EXISTING FLOOR PLAN OR THE NEW
 FLOOR PLAN ARE NOT INDICATING A DRINKING FOUNTAIN. PER
 TABLE *403.1(2) ONE IS REQUIRED FOR BUILDINGS FOR THE
 TRANSACTION OF BUSINESS AND THEY MUST BE ACCESSIBLE.
 PLEASE INDICATE THAT THERE IS AN EXISTING DRINKING
 FOUNTAIN AND ITS LOCATION OR INDICATE THAT A NEW ONE
 WILL BE PROVIDED WITH THE FOLLOWING INFORMATION ON THE
 RESUBMITTED PLANS. IF A NEW ONE IS REQUIRED THE
 PLUMBING FOR THE NEW DRINKING FOUNTAIN WILL NEED TO BE
 ON THE RESUBMITTED SANITARY AND WATER RISER DIAGRAMS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-09 Cont ID  
Sent By mperson Date 2007-10-09 Time 11:42 Rev Time 0.00
Received By mperson Date 2007-10-09 Time 11:42 Sent To PC
Notes
2007-10-09 14:11:27DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
 ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. VALUE OF THE PROPOSED WORK IS TO LOW PER FBC-2004,
 CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
 NOTE: ONLINE SEARCH OF PEDICURE CHAIRS INDICATES COST
 PER ONE CHAIR AT $2100.00 NOT TO MENTION THE COST OF
 THE KITCHEN SINK AND WATER HEATER PLUS LABOR AND
 MATERIALS. ADJUST THE COST AND PAY THE DIFFERENCE PRIOR
 TO THE RESUBMITTAL.
  
 2. SUBMIT (TWO COPIES) OF MINIMUM OF 1/8 INCH SCALE OF
 THE EXISTING FLOOR PLAN LAYOUT OF BUILDING AND ANOTHER
 WITH THE PROPOSED LAYOUT OF THE PEDICURE CHAIRS AND
 KITCHEN SINK PER FBC-2004 CHAPTER 1, SECTION 106.1.3.
  
 3. NEW PROPSED KITCHEN SINK NEEDS TO BE ACCESSIBLE AND
 AN ELEVATION DETAIL IS REQUIRED WITH THE FOLLOWING
 INFORMATION:
  
 **SINKS
 A} 11-4.24.2 HEIGHT: 34 INCHES MAX TO RIM.
 B} 11-4.24.3 KNEE CLEARANCE: 27 INCHES HIGH, 30 INCHES
 WIDE, 19 INCHES DEEP.
 C} 11-4.24.4 SINK DEPTH: 6-1/2 INCHES DEEP.
 D} 11-4.24.5 CLEAR FLOOR SPACE: 30 INCHES X 48 INCHES.
 (INDICATE CLEAR FLOOR SPACE ON PROPOSED LAYOUT FLOOR
 PLAN)
 E} 11-4.24.6 EXPOSED PIPES AND SURFACES: PROTECTION
 REQUIRED.
 F} 11-4.24.7 FAUCETS: LEVER-OPERATED, PUSH-TYPE,
 TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED ARE
 ACCEPTABLE.
  
 4. PER FBC-2004 CHAPTER 1, SECTION106.3.5.1.3 PLEASE
 INDICATE THE FOLLOWING INFORMATION PER THE FOLLOWING
 SUBSECTIONS:
  
 (3) ISOMETRIC WATER RISER DIAGRAM INDICATING PIPE
 SIZES, VALVE LOCATIONS, BACKFLOW PREVENTION (BACKFLOW
 PREVENTOR LOCATION AND VACUUM BREAKERS FOR NEW PEDICURE
 CHAIRS)
  
 (5) WATER HEATER SIZE AND LOCATION ON FLOOR PLAN.
  
 (8) BACKFLOW PREVENTER LOCATION ON SITE PLAN.
  
 (10) LOCATION OF THE WATER SUPPLY LINE.
  
 5. CLEARLY INDICATE ON THE RESUBMITTED PLANS THAT THE
 PROPOSED AIR ADMITTANCE VALVES ARE COMPLIANT WITH
 FBC-2004 WITH 05 & 06 REV. SECTION 917.3.1 LOCATION OF
 BRANCH: THE HORIZONTAL BRANCH DRAIN SHALL CONNECT TO
 THE DRAINAGE STACK OR BUILDING DRAIN A MAXIMUM OF FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK.
  
 6. 1. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved