Plan Review Details - Permit 07090657
Plan Review Stops For Permit 07090657
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-21 Cont ID  
Sent By jwitmer Date 2007-11-21 Time 09:31 Rev Time 1.66
Received By jwitmer Date 2007-11-21 Time 09:31 Sent To  
Notes
2007-11-21 09:32:26INSTALL A NITROGEN INFLATION STATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-20 Cont ID  
Sent By jwitmer Date 2007-10-20 Time 11:43 Rev Time 0.55
Received By jwitmer Date 2007-10-20 Time 11:29 Sent To  
Notes
2007-10-20 12:07:11BUILDING PLAN REVIEW
 PERMIT: 07090657
 ADD: 3201 ELECTRONIC WAY
 CONT: ROBLING ARCHITECTURE CONSTRUCTION, INC
 TEL: (561)662-0000
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS.
  
 2) SHEET A-1.0 UNDER BUILDING DATA INDICATES THE SBCCI
 CODE, PLEASE REFER TO THE PLANS SUBMITTED UNDER THE
 2004 FBC WITH 2007 REVISIONS.
  
 3)SHEET E-1.0 THE ENGINEER OF RECORD HAS USED A OUT
 OF DATE SEAL. RULE 61G15-23.001(1) F.A.C.
 THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS HAS
 CLEANED UP THE APPEARANCE
 OF THE SEAL BY ELIMINATING OBSOLETE CONTENT AND
 CHANGING THE WORD
 "CERTIFICATE" TO "LICENSE". A GRACE PERIOD RAN THROUGH
 DEC. 31,2005.
  
 PURSUANT TO SECTION 471.025 F. S. , THE BOARD HEREBY
 ESTABLISHES AS INDICATED
 BELOW THE FORMS OF EMBOSSING IMPRESSION SEALS WHICH ARE
 ACCEPTABLE TO THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8" IN DIAMETER. ALL
 ENGINEERS MUST BE
 UTILIZING SEALS AS ILLUSTRATED IN THIS RUKE NO LATER
 THAN JANUARY 1, 2006.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-26 Cont ID  
Sent By dpalmer Date 2007-11-26 Time 12:06 Rev Time 0.00
Received By dpalmer Date 2007-11-26 Time 12:06 Sent To  
Notes
2007-11-26 12:07:21REDLINED PLANS.
  
 NO CONDUCTOR SIZES, OR OCP LISTED ON PANEL SCHEDULE.
 MUST MEET 240.4 AND 310.16
 VIF.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-15 Cont ID  
Sent By dpalmer Date 2007-10-15 Time 16:49 Rev Time 0.00
Received By dpalmer Date 2007-10-15 Time 16:24 Sent To  
Notes
2007-10-15 16:49:44**** DENIED ****
  
  
  
 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT
 CODES ARE STATED ON PLANS.
 PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER
 DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A
 MINIMUM.
 PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE
 REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE
 FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS
 FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
  
 2) NOTE: PLEASE SEE THE SEAL WHICH IS BEING USED BY THE
 ENGINEER IS NO LONGER VALID IN THE STATE OF FLORIDA.
 PLEASE SEE RULING DATED FEBRUARY OF 2004 WHICH REQUIRED
 ALL SEALS FOR ENGINEERS WITH THE WORDING OF
 *CERTIFICATE* TO BE CHANGED TO *LICENSE*.
 61G15-23.001.
 PLEASE KNOW AN EXTENSION WAS GIVEN TO A DATE OF
 DECEMBER 31ST, 2005 HOWEVER PLANS MAY NOT USE THIS SEAL
 AFTER THIS DATE. ANY QUESTIONS SHOULD BE DIRECTED TO
 THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS AS THIS
 RULING WAS CHANGED OVER THREE YEARS AGO.
 PLEASE OBTAIN NEW SEAL AND ADJUST FOR NOTES #2 AND #3.
  
 3) NOTE: PLEASE SEE FS 471.025 AS THIS AND FAC
 61G15-23.002 REQUIRES THE ENGINEER TO DATE PLANS WHEN
 SIGNING AND SEALING DOCUMENTS. THE PLANS WERE NOT
 DATED.
  
 4) NOTE: PLEASE SEE THE EQUIPMENT AS SUBMITTED AND
 SHOWN ON PLANS DO NOT INDICATE ANY LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY. NRTL.
 PLEASE SEE 110.3, 90.7
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR
 REVIEW.
 THIS IS FOR EQUIPMENT ON A-2.3
  
 5) NOTE: PLEASE BE SURE TO PROVIDE ELECTRICAL
 INFORMATION FOR EQUIPMENT ON SHEETS FOR VOLTAGE
 CONNECTIONS.
 PANEL IS BEING NOTED AS 277/480V AND UNTIL MANUFACTURES
 SPECS/CUT SHEETS CAN BE REVIEWED SIZING OF CIRCUITS,
 LOADS ETC CAN NOT BE CONFIRMED.
 ELECTRICAL PLANS DO NOT INDICATE SIZE OF CIRCUITS, OVER
 CURRENT PROTECTION, CONDUCTOR ETC.240.4, 310.16 ETC
 PLAN SHEET A-1.1 SHOWS ONE NEW RECEPTACLE BEING
 INSTALLED WHICH DOES NOT SEEM TO BE WHAT IS NEEDED
 BASED ON EQUIPMENT AS SHOWN. IS THIS A 277/480V
 RECEPTACLE? PLEASE SPECIFY TYPE. (NEMA RATING/NUMBER).
 ELECTRICAL PANEL SCHEDULE DOES NOT SHOW THE NEW
 CIRCUIT(S). 408.4
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
  
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 16:15 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 16:15 Sent To  
Notes
2007-11-20 15:52:23TO "COMM" BD#5
2007-11-06 16:16:02WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-01 Cont ID  
Sent By tgordon Date 2007-11-01 Time 14:46 Rev Time 0.00
Received By tgordon Date 2007-09-24 Time 14:59 Sent To  
Notes
2007-10-15 10:42:11TO "COMM" BD#30
2007-09-24 14:59:21WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-26 Cont ID  
Sent By tgordon Date 2007-11-26 Time 14:23 Rev Time 0.30
Received By tgordon Date 2007-11-26 Time 14:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-01 Cont ID  
Sent By tgordon Date 2007-11-01 Time 14:37 Rev Time 0.30
Received By tgordon Date 2007-11-01 Time 14:37 Sent To  
Notes
2007-11-01 14:44:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE BUILDING AND ELECTRICAL REVIEW NOTES, PLEASE
 CORRECT.
  
 2) PLEASE LIST PIPING MATERIALS BEING USED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]