Plan Review Details - Permit 07090648
Plan Review Stops For Permit 07090648
Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2008-10-08 Cont ID  
Sent By jwitmer Date 2008-10-08 Time 12:22 Rev Time 0.77
Received By jwitmer Date 2008-10-10 Time 12:22 Sent To PC
Notes
2008-10-10 12:24:37BUILDING PLAN REVIEW
 PERMIT: 07090648
 ADD: 700 S ROSEMARY AVE# 100
 CONT: IN MOTION BUILDERS, INC.
 TEL: (954)698-0900
 MARCH 18/2008
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION DATED 10-08-08 REVIEW
  
 ACTION: BUILDING PROVISO
  
 32"X32" "B" LABELED FIRE RATED DOOR LOCATED WITH
 STAIRWELL LANDING FROM RESTROOM. THIS STAIR CANNOT BE
 PART OF A VERTICAL EXIT OR EXIT PASSAGE WAY.
 1019.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 AND ELECTRICAL RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M 2 ). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712 . THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2008-09-30 Cont ID  
Sent By jwitmer Date 2008-09-30 Time 14:51 Rev Time 0.77
Received By jwitmer Date 2008-09-30 Time 14:51 Sent To  
Notes
2008-10-08 07:45:05BUILDING PLAN REVIEW
 PERMIT: 07090648
 ADD: 700 S ROSEMARY AVE# 100
 CONT: IN MOTION BUILDERS, INC.
 TEL: (954)698-0900
 MARCH 18/2008
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION DATED 10-08-08 REVIEW
  
 ACTION: BUILDING PROVISO
  
 32"X32" "B" LABELED FIRE RATED DOOR LOCATED WITH
 STAIRWELL LANDING FROM RESTROOM. THIS STAIR CANNOT BE
 PART OF A VERTICAL EXIT OR EXIT PASSAGE WAY.
 1019.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 AND ELECTRICAL RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M 2 ). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712 . THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
2008-09-30 14:56:33BUILDING PLAN REVIEW
 PERMIT: 07090648
 ADD: 700 S ROSEMARY AVE# 100
 CONT: IN MOTION BUILDERS, INC.
 TEL: (954)698-0900
 MARCH 18/2008
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION DATED 9-10-08 REVIEW
 ACTION: DENIED
  
 32"X32" "B" LABELED FIRE RATED DOOR LOCATEDED WITH
 STAIRWELL LANDING FROM RESTROOM.
 1019.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 AND ELECTRICAL RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M 2 ). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712 . THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-09-04 Cont ID  
Sent By jwitmer Date 2008-09-04 Time 13:27 Rev Time 0.00
Received By jwitmer Date 2008-09-04 Time 13:28 Sent To PC
Notes
2008-09-04 13:30:07SHEET S1SK-3, SK-4, SK-8 & SK-9
 SHEET S4 SK-3-4 SK-6-7 & SK-13-14

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-09-04 Cont ID  
Sent By jwitmer Date 2008-09-04 Time 13:05 Rev Time 0.77
Received By jwitmer Date 2008-09-04 Time 13:05 Sent To PC
Notes
2008-09-04 13:07:10SHEET S5.0 RE-ISSUED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-08-25 Cont ID  
Sent By jwitmer Date 2008-08-25 Time 13:06 Rev Time 0.77
Received By jwitmer Date 2008-08-25 Time 13:06 Sent To PC
Notes
2008-08-25 13:08:04REVISION:
 A2.1 FOR SUSPENDED CEILING HANGING DETAIL
 A6.2 SCREW ATTACHMENT FOR WOOD BUCKS

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-07-21 Cont ID  
Sent By jwitmer Date 2008-07-21 Time 11:03 Rev Time 0.77
Received By jwitmer Date 2008-07-21 Time 11:03 Sent To  
Notes
2008-07-21 11:05:39S0.0 REISSUED 5-22-08

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-05-10 Cont ID  
Sent By jwitmer Date 2008-05-10 Time 09:54 Rev Time 1.75
Received By jwitmer Date 2008-05-10 Time 09:54 Sent To  
Notes
2008-05-10 09:58:39BUILDING PLAN REVIEW
 PERMIT: 07090648
 ADD: 700 S ROSEMARY AVE# 100
 CONT: IN MOTION BUILDERS, INC.
 TEL: (954)698-0900
 MAY 10/2008
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 PASSED FOR INTERIOR WORK ONLY!

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-04-21 Cont ID  
Sent By jwitmer Date 2008-04-21 Time 12:51 Rev Time 3.33
Received By jwitmer Date 2008-04-21 Time 12:51 Sent To  
Notes
2008-04-28 11:18:534-25-08
 COMMENT 1F)IN REVIEWING THIS COMMENT WITH THE
 BUILDING OFFICIAL, NEIL HAS DIRECTED THAT THIS COMMENT
 IS IRRELEVENT AND NOT BE INCLUDED IN THIS REVIEW. THE
 CBC WOULD BE ABLE TO HAVE THE CGC AS A SUB-CONTRACTOR
 AND THE ENGINEERING FIRM COULD CONTRACT WITH THE CBC .
2008-04-21 13:15:05BUILDING PLAN REVIEW
 PERMIT: 07090648
 ADD: 700 S ROSEMARY AVE# 100
 CONT: IN MOTION BUILDERS, INC.
 TEL: (954)698-0900
 MARCH 18/2008
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1A)NOTE, INFORMATIONAL, WHEN RESUBMITTING PLANS
 PLEASE INDICATE THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B) NOTE INFORMATIONAL, PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) NOTE INFORMATIONAL, 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D )NOTE INFORMATIONAL, FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION. 2)SHEET T1.1,CODE ANALYSIS PLEASE UPDATE
 THE 2004 TO THE 2007 FBC, BUILDING WITH 2007
 REVISIONS.
  
 1E) PARTIALLY COMPLIED, THEEXTERIOR WORK THAT COULD
 NOT BE COMPLETED UNDER A CBC LICENSE DOES NOT ONLY
 APPLY TO THE CANOPY BUT THE EXTERIOR GLAZING AND DOOR
 SYSTEMS SINCE THE PRESSURES ASSOCIATED WITH THE DOOR
 AND WINDOW SYSTEM DO EFFECT THE STRUCTURAL INTEGRITY OF
 THE BUILDING. THE CGC WOULD ALSO NEED TO INCORPORATE
 THE INSTALLATION OF THE EXTERIOR COMPONENTS UNDER THE
 CGC LICENSURE. PLEASE ADD THIS WORK TO THE PERMIT
 APPLICATION UNDER THE DESCRIPTION OF PROJECT.
  
 1F)THE SECOND LICENSING ISSUE IS THE WINGERTER
 LABORTIES THAT WILL BE COMPLETING THE THRESHOLD
 INSPECTIONS WILL NEED TO CONTRACT THROUGH THE CGC, NOT
 THE CBC, PLEASE CHANGE OUT THE WINGERTER LABORATORIES
 COVER SHEET,(3) COPIES OF RAISED SIGNED AND SEALED
 COVER SHEETS, THE MENTION OF IN MOTION BUILDERS SHOULD
 TRUELY REFLECT THE NEW CGC AND IT WOULD BE WITHIN THE
 CGC'S LICENSE SCOPE OF WORK.
  
 2-9) COMPLIED.
  
 10-16) COMPLIED.
 17) ***FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES (FOR THRESHOLD BUILDINGS (3 COPIES) OF
 PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
  
 17A-G) COMPLIED.
  
 17H) ROOFING ASSEMBLIES W / INSULATION,NONE OF THE
 SUB-SYSTEMS WERE HIGHLIGHTED INDICATING WHICH SYSTEM
 WAS TO BE INSTALLED. 2ND ISSUE ISALL SUB-SYSTEMS WILL
 REQUIRE RAS 117 CALCULATIONS FOR THE REQUIRED ENHANCED
 FASTENING, PLEASE PROVIDE 3 COPIES OF THE ENHANCED
 FASTENING SCHEDULE FOR ZONES 2 & 3. TABLE 1609.2.1(2) *
 TABLE 1609.2.1(4). TO BE REVIEWED BY CAPRI THEN
 SUBMITTED TO THE CITY.
  
 18-19) COMPLIED.
  
 20) COMPLIED.
  
 21-22) COMPLIED.
  
 23) THIS COMMENT DIDN'T APPEAR ON THE COMMENT RESPONCE
 SHEET, SHEET A6.3 PLEASE PROVIDE PRODUCT INFORMATION ON
 THE STUCCO TAPE TO BE USED ON STC-1 WALLS? ADDITIONAL
 INFORMATION REQUIRED.
  
 24) BUILDING PROVISO:A6.4 DETAIL # 2 & S5.0 FOR A
 BRUSHED ALUMINUM CANOPY, THIS WILL REQUIRE SHOP
 DRAWINGS, TO BE UNDER A SEPARATE PERMIT. THIS STRUCTURE
 DOES NOT MEET THE REQUIREMENTS OF 3105, MUST MEET THE
 140 MPH PROVISIONS OF 1609.6.2.1(2) & 1609.2.1(4) THIS
 CAN BE SUBMITTED FOR REVIEW TO CAPRIFOR REVIEW THEN
 TO WPB CONSTRUCTION SEERVICES DEPARTMENT.
  
 25)COMPLIED.
  
 26-27) COMPLIED.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-03-18 Cont ID  
Sent By jwitmer Date 2008-03-18 Time 16:30 Rev Time 3.33
Received By jwitmer Date 2008-03-17 Time 16:30 Sent To  
Notes
2008-03-18 11:04:38BUILDING PLAN REVIEW
 PERMIT: 07090648
 ADD: 700 S ROSEMARY AVE# 100
 CONT: IN MOTION BUILDERS, INC.
 TEL: (954)698-0900
 MARCH 18/2008
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1A) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. 2)SHEET
 T1.1,CODE ANALYSIS PLEASE UPDATE THE 2004 TO THE 2007
 FBC, BUILDING WITH 2007 REVISIONS.
  
 1E) NEW COMMENT, PLANS INDICATE A NEW COVERED PATIO
 AREA BUT THE PERMIT APPLICATION
 (DUPLICATE) INDICATES ?ONLY INTERIOR WORK? WHICH IS
 CORRECT? THIS GREATLY AFFECTS THE SCOPE OF WHAT WORK
 WILL BE ACCOMPLISHED UNDER THIS PERMIT AND REVIEW.
 SINCE THE FIRST 2 REVIEWS WERE REVIEWED WITH THE
 COVERED PATIO ADDITION AS PART OF THE PERMIT SCOPE THIS
 REVIEW WILL ALSO INCLUDE THIS SAME SCOPE OF WORK. IF
 THE EXTERIOR COVERED PATIO IS NOT PART OF THIS PERMIT
 IT SHOULD NOT SHOW UP ON THE PLANS.
  
 2-9) COMPLIED.
  
 10) STRUCTURAL CALCULATIONS WERE RESUBMITTED,
 STRUCTURAL DESIGN CALCULATIONS ARE MISSING A SIGNED AND
 SEALED INDEX SHEET INDICATING WHAT WORK IS COVERED IN
 THIS REPORT.. FL S S 471.025.
  
 11A) COMPLIED.
  
 11B) 3RD REQUEST FROM PREVIOUS AUDITS,*** WPB AMENDMENT
 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY S. 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT
 HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR PROGRAM
 AT (561) 805-6711 FOR FURTHER INFORMATION BEFORE THE
 PERMIT MAY BE ISSUED.
  
 11C) 3RD REQUEST FROM PREVIOUS AUDITS,*** W.P.B.
 AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 12) 3RD REQUEST FROM PREVIOUS AUDITS,*** THE STRUCTURAL
 SHEET S0.0 FOUNDATION DESIGN INDICATES THERE TO BE A
 GEOTECHNICAL SOILS ENGINEER SHALL VERIFY THAT THE SOILS
 OF THE DESIGN BEARING CAPACITY HAVE BEEN ENCOUNTERED.
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 13-16) COMPLIED.
  
 17) 3RDD REQUEST FROM PREVIOUS AUDITS,*** FL BLD CODE
 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2 COPIES (FOR
 THRESHOLD BUILDINGS (3 COPIES) OF PRODUCT TESTING
 REPORTS ,MISSING REPORTS ARE AS FOLLOWS:
  
 17A) FIXED WINDOWS, STOREFRONT, FL COVERSHEET ONLY
 SUBMITTED
 PLANS CALL FOR LARGE MISSILE IMPACT RATED GLAZING, THE
 FL# 6001.1
 IS FOR NON-RATED SYSTEM REQUIRING STORM SHUTTERS OR
 ROLL DOWN SYSTEM
  
 17B) GLAZED EXTERIOR SWING DOOR, SINGLE AND PAIRS FL
 COVERSHEET SUBMITTED, NON-IMPACT
  
 17C) DOORS W/ SIDELIGHTS, FL COVERSHEET
 ONLY SUBMITTED, PLANS CALL FOR LARGE MISSILE IMPACT
 RATED GLAZING, THE FL# 7237.1 & 7237.2 IS FOR NON-RATED
 IMPACT SYSTEM REQUIRING STORM SHUTTERS OR ROLL DOWN
 SYSTEM ,
 THE ROLL-DOWN SYSTEM IS NOT FOUND IN THE SECTION
 DETAILS, THERE ARE HEATERS FOUND IN SOME OF THESE
 AREAS.
  
 17D) FOLDING DOOR SYSTEM FL COVERSHEET ONLY SUBMITTED.
 FL 6859.1 IMPACT RATED, A +/-
 75 PSF BUT IN NON WIND BORNE DEBRIS REGION.
  
 17D) FOLDING WALL SYSTEM FL 2947.2FL COVERSHEET
 SUBMITTED. .NANA WALL SYSTEM- FBC 2001 FBC NOT 2004FBC,
 SEE RESTRICTIONS PLANS INDICATE 13?-0? OPENINGS WITH 4
 EQUAL PANELS, RESTRICTION SIZE IS LIMITED TO 3?-0?. SEE
 REPORT NOT SUBMITTED!!!
  
 17E) HURRICANE SHUTTER, HORIZONTAL ROLLER, FL
 COVERSHEET ONLY SUBMITTED, PLANS INDICATE LARGE MISSILE
 ON THE EGRESS DOOR BUT THE FL NUMBERS SUBMITTED ARE FOR
 NON-RATED GLAZING BLOCKING REQUIRED EXITS WITH STORM
 SHUTTER OR ROLL DOWN SHUTTER SYSTEMS.
  
 17F) TRUSS ANCHOR TYPE HARDWARE, FL COVERSHEET
 SUBMITTED, OK WILL USE VALUES FROM CATALOG
 NO 1/3RD STEEL INCREASES TAKEN COLUMN.
  
 17G) LOUVER, FL COVERSHEET SUBMITTED THE REPORT NOT
 SUBMITTED WILL SHOW THIS TO BE A NON-
 RATED WALL LOUVER, SEE 1609.1.4(5).
  
 17H) ROOFING ASSEMBLIES W / INSULATION, FL COVERSHEET
 SUBMITTED ONLY, THE REPORT NOT SUBMITTED WILL INDICATE
 THAT THIS SYSTEM IS TO BE USED FOR APPLICATION TO A
 PLYWOOD DECK.
 BOTH THE ARCHITECTURAL AND STRUCTURAL SHEETS INDICATE
 THE USE OF A METAL DECK, PLEASE SEE
 PLANS FOR DETAILS.
  
 18) 3RD REQUEST FROM PREVIOUS AUDITS,*** PRODUCT
 APPROVALS SUBMITTED WITH PERMIT APPLICATION AFTER
 OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A
 COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE 9B-72.
  
 19) 3RD REQUEST FROM PREVIOUS AUDITS,*** WPB ADMIN CODE
 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2)*** THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 20)3RD REQUEST FROM PREVIOUS AUDITS,*** SHEET EX1.1
 INDICATES POINTS WHERE THE EXIT IS 3?-8? BUT THE WIDTH
 OF THE EGRESS PATH MAY BE AS LITTLE AS 30? IN SOME
 AREAS, PLEASE PROVIDE THE EGRESS PATH SHOWING THE FULL
 44? WHERE IT SERVES AN OCCUPANT LOAD GREATER THAN 50
 AND 36? WHERE REQUIRED FOR LESS THAN 50. 1024.9.1.1 THE
 MINIMUM WIDTH OF AISLES SERVING SEATING AT TABLES SHALL
 BE 44 INCHES (1118 MM). EXCEPTION: THIRTY-SIX INCHES
 (914 MM) WHERE SERVING AN OCCUPANT LOAD OF NOT MORE
 THAN 50.
  
 THERE ARE STILL AREAS ON THE EGRESS PLAN THAT WILL NOT
 MEET THE MINIMUM CLEARANCES PENCILED IN AREAS OF
 CONCERN.
  
 21-23) COMPLIED.
  
 24) BUILDING PROVISO: A6.4 DETAIL # 2 & S5.0 FOR A
 BRUSHED ALUMINUM CANOPY, THIS WILL REQUIRE SHOP
 DRAWINGS, TO BE UNDER A SEPARATE PERMIT. THIS STRUCTURE
 DOES NOT MEET THE REQUIREMENTS OF 3105, MUST MEET THE
 140 MPH PROVISIONS OF 1609.6.
  
 25) COMPLIED.
  
 NEW COMMENTS, 3RD REVIEW:
  
 26) THE NEW SHEET A8.1 DOES NOT HAVE THE STAMP FROM
 CAPRI INDICATING CODE COMPLIANCE.
  
 27) THE NEW SHEET A8.1 THE DESIGN PROFESSIONAL JAMES R
 LENCIONI, ARCHITECT PUT THE EXPIRATION DATE OF HIS
 LICENSE ON THIS SHEET NOT THE DATE IT WAS DRAWN OR
 CHANGES MADE.
  
 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 XX - STATE DATE PREPARED
 XX - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL -
 INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 NOTE:
 *** CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED THREE OR
 MORE TIMES FOR REPEATED FAILURE TO CORRECT A CODE
 VIOLATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-01 Cont ID  
Sent By jwitmer Date 2008-02-01 Time 10:29 Rev Time 3.33
Received By jwitmer Date 2008-02-01 Time 09:20 Sent To  
Notes
2008-02-01 10:46:36KONA GRILL
 700 S ROSEMARY AVE SUITE# 100
  
 BUILDING PLAN REVIEW
 PERMIT: 07090648
 ADD: 700 S ROSEMARY AVE# 100
 CONT: IN MOTION BUILDERS, INC.
 TEL: (954)698-0900
 FEB. 01/08
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT
 STATEMENT ---
 PLEASE DO
 NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. 2)SHEET
 T1.1,CODE ANALYSIS PLEASE UPDATE THE 2004 TO THE 2007
 FBC, BUILDING WITH 2007 REVISIONS.
  
 2-9) COMPLIED.
  
 10) STRUCTURAL CALCULATIONS WERE NOT RESUBMITTED,
 STRUCTURAL DESIGN CALCULATIONS ARE MISSING TITLE BLOCK
 INFORMATION AS WELL AS NOT HAVING AN INDEX OF HOW MANY
 SHEETS ARE IN THIS REPORT. FL S S 471.025.
  
 11A) COMPLIED.
  
 11B) 2ND REQUEST, WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT HAROLD PISKURA MANAGER
 OF THE SPECIAL INSPECTOR PROGRAM AT (561) 805-6711 FOR
 FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 11C) 2ND REQUEST,W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED
 AND SEALED BY THE ARCHITECT OR ENGINEER OF RECORD
 CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 12) 2ND REQUEST, THE STRUCTURAL SHEET S0.0 FOUNDATION
 DESIGN INDICATES THERE TO BE A GEOTECHNICAL SOILS
 ENGINEER SHALL VERIFY THAT THE SOILS OF THE DESIGN
 BEARING CAPACITY HAVE BEEN ENCOUNTERED. 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6
 .
  
 13-16) COMPLIED.
  
 17)2ND REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES
 (FOR THRESHOLD BUILDINGS (3 COPIES) OF PRODUCT TESTING
 REPORTS ,MISSING REPORTS ARE AS FOLLOWS:
 17A) FIXED WINDOWS, STOREFRONT
 17B) GLAZED EXTERIOR SWING DOOR, SINGLE AND PAIRS 17C)
 DOORS W/ SIDELIGHTS
 17D) FOLDING DOOR SYSTEM
 17E) HURRICANE SHUTTER, HORIZONTAL ROLLER
 17F) TRUSS ANCHOR TYPE HARDWARE
 17G) LOUVER
 17H) ROOFING ASSEMBLIES W / INSULATION
  
 18) 2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 19) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 20) 2ND REQUEST, SHEET EX1.1 INDICATES POINTS WHERE THE
 EXIT IS 3?-8? BUT THE WIDTH OF THE EGRESS PATH MAY BE
 AS LITTLE AS 30? IN SOME AREAS, PLEASE PROVIDE THE
 EGRESS PATH SHOWING THE FULL 44? WHERE IT SERVES AN
 OCCUPANT LOAD GREATER THAN 50 AND 36? WHERE REQUIRED
 FOR LESS THAN 50. 1024.9.1.1 THE MINIMUM WIDTH OF
 AISLES SERVING SEATING AT TABLES SHALL BE 44 INCHES
 (1118 MM). EXCEPTION: THIRTY-SIX INCHES (914 MM) WHERE
 SERVING AN OCCUPANT LOAD OF NOT MORE THAN 50.
  
 21-23) COMPLIED.
  
 24) BUILDING PROVISO:A6.4 DETAIL # 2 & S5.0 FOR A
 BRUSHED ALUMINUM CANOPY, THIS WILL REQUIRE SHOP
 DRAWINGS, TO BE UNDER A SEPARATE PERMIT. THIS STRUCTURE
 DOES NOT MEET THE REQUIREMENTS OF 3105, MUST MEET THE
 140 MPH PROVISIONS OF 1609.6.
  
 25) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-25 Cont ID  
Sent By jwitmer Date 2007-09-25 Time 18:51 Rev Time 4.55
Received By jwitmer Date 2007-09-25 Time 18:51 Sent To  
Notes
2007-09-25 21:04:28 
 KONA GRILL
 700 S ROSEMARY AVE SUITE# 100
  
 BUILDING PLAN REVIEW
 PERMIT: 07090648
 ADD: 700 S ROSEMARY AVE# 100
 CONT: IN MOTION BUILDERS, INC.
 TEL: (954)698-0900
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) --- VERY IMPORTANT
 STATEMENT ---
 PLEASE DO
 NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. 2)SHEET
 T1.1,CODE ANALYSIS PLEASE UPDATE THE 2004 TO THE 2007
 FBC, BUILDING WITH 2007 REVISIONS.
  
 3) SHEET T1.1 TYPE OF BUILDING, PLANS INDICATE THIS TO
 BE A TYPE IIB PLEASE CORRECT TO A TYPE IB, PLEASE NOTE
 THAT 700 S ROSEMARY IS CONSIDERED A MIXED USE BUILDING
 THE PARKING GARAGE IS 5 STORIES AND IS CONSIDERED PART
 OF THE MERCANTILE AND A2 RESTAURANTS FOUND IN THIS
 BUILDING. THE LOCATION OF THE ELEVATORS AND STAIRWAY
 ARE OVER 30? WIDE CREATING ONE LARGE BUILDING.
 DEFINITIONS:WALKWAY , COVERED. A ROOFED, UNOBSTRUCTED
 WALKWAY CONNECTING BUILDINGS AND USED AS A MEANS OF
 TRAVEL BY PERSONS AND WHERE LESS THAN 50 PERCENT OF THE
 PERIMETER IS ENCLOSED AND THE MAXIMUM WIDTH
 PERPENDICULAR TO THE DIRECTION OF TRAVEL IS LESS THAN
 30 FEET (9144 MM). PLEASE CORRECT THE MINIMUM BUILDING
 TYPE.
  
 4) SHEET T1.1 SINCE THE MINIMUM BUILDING TYPE HAS
 INCREASED THE FIRE RESISTANCE RATINGS WILL ALSO
 INCREASE, SEE TABLE 603.
  
 5) SHEET T1.1 PLEASE CORRECT THE CODE ANALYSIS THIS IS
 NOT A SINGLE STORY BUILDING AND A 300% INCREASE CAN NOT
 BE TAKEN, MULTI-STORY BUILDING AND ONLY A 200% INCREASE
 CAN BE TAKEN. 506.3.
  
 6) THE ARCHITECTURAL SHEETS ARE MISSING THEIR
 CERTIFICATE OF AUTHORIZATION FOR ARIA GROUP ARCHITECTS
 INC. 481.219 F.S.CERTIFICATE OF AUTHORIZATION.THE
 TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
  
 7) THE ARCHITECTURAL SHEETS IN THE TITLE BLOCK THE
 ARCHITECT OF RECORD WHICH SEALED THE PLANS HADN?T
 PLACED THE PRINTED NAME OF THE DESIGN PROFESSIONAL.
 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE
 NUMBER
 XX- STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 XX - STATE DATE PREPARED- INCLUDE AN ORIGINAL SIGNATURE
 AND DATED SEAL, IN THE SET BEING
 REVIEWED ONLY THE TOP SHEET OF THE
 ARCHITECTURAL SHEETS HAS A DATE ON THEM.
 XX - INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING
 THE PLANS.
  
 8) SHEET S0.0 HART, GAUGLER & ASSOCIATES, INC. IS
 MISSING THEIR CERTIFICATE OF AUTHORIZATION. 471.023
 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK
 FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER. ADD THE NUMBER TO
 EACH SHEET.
  
 9) SHEET S0.0 THE ENGINEER OF RECORD HAS NOT:
 61G15-23.002(2)FL. ADMIN. CODE.
 PLANS SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL
 INCLUDE EITHER THE NAME, ADDRESS AND LICENSE NUMBER OF
 THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE
 ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS
 THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S.
 AND 471.023 F.S.).
  
 10) STRUCTURAL DESIGN CALCULATIONS ARE MISSING TITLE
 BLOCK INFORMATION AS WELL AS NOT HAVING AN INDEX OF HOW
 MANY SHEETS ARE IN THIS REPORT. FL S S 471.025
  
 11) ARCHITECTURAL AS WELL AS STRUCTURAL PLANS INDICATE
 STRUCTURAL WORK TO BE ACCOMPLISHED UNDER THIS PERMIT.
 NOTE THIS BUILDING BEING A 5 STORY STRUCTURE WILL
 REQUIRE A THRESHOLD
 INSPECTION PLAN AND A THRESHOLD INSPECTOR.
  
 11A)FL S. S. 553.71(7) " THRESHOLD BUILDING"
 MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCYCLASSIFICATION AS DEFINED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS. 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE
 A SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS
 ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURALINSPECTION PLAN
 PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THEENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 11B) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S. 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 11C)W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 12) THE STRUCTURAL SHEET S0.0 FOUNDATION DESIGN
 INDICATES THERE TO BE A GEOTECHNICAL SOILS ENGINEER
 SHALL VERIFY THAT THE SOILS OF THE DESIGN BEARING
 CAPACITY HAVE BEEN ENCOUNTERED. 1802.2.1 QUESTIONABLE
 SOIL. WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 13) S0.0 WIND DESIGN DOES NOT INDICATE IF THIS IS TAKEN
 FROM TABLE 1609.6 OR ASCE 7-02, NOTE AGAIN THIS IS A 5
 STORY BUILDING NOT A SINGLE STORY BUILDING?
  
 14)SHEET S0.0 INDICATES VARIOUS STANDARDS, EXAMPLE
 ACI 318 MOST RECENT EDITION, PLEASE SEE CHAPTER 35
 WHICH LIST ALL THE STANDARDS AND YEARS THAT ARE
 REFERENCED IN THE 2004 FBC.
  
 15) S0.0 ALSO HAS STANDARDS FOR THE HIGH VELOCITY
 HURRICANE ZONE WHICH ARE UNENFORCEABLE EXCEPT DADE &
 BROWARD COUNTIES PLEASE REMOVE.
 16) S0.0 INSPECTIONS REQUIRED, PLEASE UPDATE TO A
 THRESHOLD INSPECTION PLAN AS PER FL S S 553.7(71).
  
 17)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES
 (FOR THRESHOLD BUILDINGS (3 COPIES) OF PRODUCT TESTING
 REPORTS ,MISSING REPORTS ARE AS FOLLOWS:
 17A) FIXED WINDOWS, STOREFRONT
 17B) GLAZED EXTERIOR SWING DOOR, SINGLE AND PAIRS 17C)
 DOORS W/ SIDELIGHTS
 17D) FOLDING DOOR SYSTEM
 17E) HURRICANE SHUTTER, HORIZONTAL ROLLER
 17F) TRUSS ANCHOR TYPE HARDWARE
 17G) LOUVER
 17H) ROOFING ASSEMBLIES W / INSULATION
  
 18) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
  
 19) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 20) ) SHEET EX1.1 INDICATES POINTS WHERE THE EXIT IS
 3?-8? BUT THE WIDTH OF THE EGRESS PATH MAY BE AS LITTLE
 AS 30? IN SOME AREAS, PLEASE PROVIDE THE EGRESS PATH
 SHOWING THE FULL 44? WHERE IT SERVES AN OCCUPANT LOAD
 GREATER THAN 50 AND 36? WHERE REQUIRED FOR LESS THAN
 50. 1024.9.1.1 THE MINIMUM WIDTH OF AISLES SERVING
 SEATING AT TABLES SHALL BE 44 INCHES (1118 MM).
 EXCEPTION: THIRTY-SIX INCHES (914 MM) WHERE SERVING AN
 OCCUPANT LOAD OF NOT MORE THAN 50.
  
 21) SHEET A6.2 INDICATES A NEW CANOPY WITH WOOD BEAMS
 AND DECKING. PLEASE REFER BACK TO COMMENT # 3
 CLASSIFYING THIS BUILDING AS A TYPE 1B, SEE TABLE 601
 ROOF CONSTRUCTION FOOTNOTE ?C?, COMBUSTIBLE
 WOOD COMPONENTS AND DECKING WILL NOT BE ACCEPTED,
 UNLESS A 4 HOUR FIRE WALL IS INTRODUCED CREATING A
 SEPARATE BUILDING. THERE MAY BE OTHER ISSUES THEN WITH
 THE MEP PLANS AS WELL AS FIRE SPRINKLER AND FIRE
 ALARM.
  
 22)SHEET A6.3 INDICATES IN VARIOUS DETAILS THE USE OF
 PLYWOOD SUB-SHEATHINGWITHIN EXTERIOR NON-LOAD BEARING
 WALLS. SEE SECTION 603 .1.1(1.2)FIRE RETARDANT
 ?TREATED WOOD SHALL BE PERMITTED.
  
 23)SHEET A6.3 PLEASE PROVIDE PRODUCT INFORMATION ON
 THE STUCCO TAPE TO BE USED ON STC-1 WALLS? ADDITIONAL
 INFORMATION REQUIRED 106.1.2.
  
 24)BUILDING PROVISO:A6.4 DETAIL # 2 & S5.0 FOR A
 BRUSHED ALUMINUM CANOPY, THIS WILL REQUIRE SHOP
 DRAWINGS, TO BE UNDER A SEPARATE PERMIT. THIS STRUCTURE
 DOES NOT MEET THE REQUIREMENTS OF 3105, MUST MEET THE
 140 MPH PROVISIONS OF 1609.6.
  
 25) SHEET A3.1/A6.2 BOTH INDICATE A CANOPY WITH ROOF
 SLOPE AND A DETAIL WITH A CURB OF APPROXIMATELY 3?, IS
 THERE TO BE ROOF DRAINS SCUPPERS AND OR OVER FLOWS?
 ADDITIONAL INFORMATION REQUIRED
 106.1.2*/ 1503.4 & 1503.6.
  
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2008-12-22 Cont ID  
Sent By dpalmer Date 2008-12-22 Time 10:17 Rev Time 0.00
Received By dpalmer Date 2008-12-22 Time 10:17 Sent To PC
Notes
2008-12-22 10:18:33REVISED PLAN, AUDITED.

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2008-12-01 Cont ID  
Sent By dpalmer Date 2008-12-01 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2008-12-01 Time 11:36 Sent To PC
Notes
2008-12-01 11:36:26** FAILED AUDIT**
  
  
 1) NOTE: NO COMPLIANCE AFFIDAVITS SUBMITTED. FS 553.791
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2008-09-04 Cont ID  
Sent By dpalmer Date 2008-09-04 Time 14:26 Rev Time 0.00
Received By dpalmer Date 2008-09-04 Time 14:26 Sent To PC
Notes
2008-09-04 14:27:05REVISIONS DATED 6/19/08 SUBMITTED 8/27

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-09-04 Cont ID  
Sent By dpalmer Date 2008-09-04 Time 14:25 Rev Time 0.00
Received By dpalmer Date 2008-09-04 Time 14:25 Sent To PC
Notes
2008-09-04 14:26:19REVISIONS DATED 5/30/08 SUBMITTED 8/27

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-07-31 Cont ID  
Sent By dpalmer Date 2008-07-31 Time 08:09 Rev Time 0.00
Received By dpalmer Date 2008-07-31 Time 08:09 Sent To PC
Notes
2008-07-31 08:09:31** DENIEDAUDIT **
  
  
 1) NOTE: PLEASE SUBMIT THE COMPLIANCE AFFIDAVITS AS
 REQUIRED UNDER FS 553.791. PLEASE SEE THAT ONLY ONE WAS
 LOCATED IN PACKAGE FOR ELECTRICAL REVISIONS DATED
 5/30/08 HOWEVER THERE ARE ELECTRICAL REVISIONS IN SETS
 DATED 6/19/08.
 PLEASE SUBMIT ORIGINAL LETTERS.
  
  
 ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE
 NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-05-16 Cont ID  
Sent By dpalmer Date 2008-05-16 Time 08:31 Rev Time 0.00
Received By dpalmer Date 2008-05-16 Time 08:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-05-12 Cont ID  
Sent By dpalmer Date 2008-05-12 Time 13:11 Rev Time 0.00
Received By dpalmer Date 2008-05-12 Time 13:11 Sent To  
Notes
2008-05-12 13:11:20** DENIED/TEMPORARY FAILED STATUS**
  
 1) NOTE:ALL THREE SETS OF PLANS DO NOT CONTAIN THE
 AFFIDAVITS FOR SHEETS WHICH WERE NOT REVISED. THE NEW
 AFFIDAVITS FOR NEW REVISED SIGNED AND SEALED SHEETS
 WERE THE ONLY ONES ATTACHED TO PLANS.
 PLEASE OBTAIN THREE COMPLETE SETS OF AFFIDAVITS AND
 ATTACH TO PLANS. THIS WILL BE FOR ALL TRADES.THIS
 INFORMATION WAS FORWARDED TO OTHER TRADES ALONG WITH
 ASSISTANT BUILDING OFFICIAL MR. ROBERT BROWN. FS
 553.791
  
 2) NOTE: PLEASE SEE SHEET F-1.1 STILL SHOWS THE WEST
 PATIO WITH FIRE SPRINKLERS WHICH ARE NOT INCLUDED IN
 SCOPE OF WORK.
 THIS WAS GIVEN TO FIRE MARSHAL AND TO ASSISTANT
 BUILDING OFFICIAL MR. ROBERT BROWN FOR CONTRACTOR TO
 OBTAIN REVISED PLANS WHICH COORDINATE WITH OTHER SHEETS
 AND PLANS IN SETS.
  
 3) NOTE: ELECTRICAL PLANS NEED THE THIRD SET, SIGNED,
 DATED, SEALED, REVIEWED FROM PRIVATE PROVIDER ETC.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-04-18 Cont ID  
Sent By dpalmer Date 2008-04-18 Time 18:21 Rev Time 0.00
Received By dpalmer Date 2008-04-18 Time 18:21 Sent To  
Notes
2008-04-18 18:21:30** DENIED 4TH AUDIT **
  
  
 ** PLEASE SEE NEW COMMENTS FOR AUDIT DUE TO COMPLETELY
 NEW DOCUMENTS NOW SUBMITTED WHICH ARE NOT THE SAME AS
 PREVIOUS SUBMITTED DOCUMENTS.
 PLEASE SEE NOTES BELOW. THESE ARE REQUIRED BY FLORIDA
 STATUES AND SHALL CORRECTED AND COMPLETE BEFORE PERMIT
 MAY BE ISSUED.
  
 1) NOTE: PLEASE BE SURE TO SUBMIT ALL DOCUMENTS INTO
 TWO SETS. PLEASE DO NOT SUBMIT ALL DOCUMENTS INTO ONE
 BOOK.
 FBC 106.1.3, 106.1. ADMIN SECTION OF THE FLORIDA
 BUILDING CODE FOR COORDINATION OF PLANS AND DOCUMENTS.
  
 2) NOTE: PLEASE KNOW THE TWO SUBMITTED *NOTICE TO
 BUILDING OFFICIAL* LETTERS AS REQUIRED PER FS 553.791
 ARE BOTH IN FACT *COLORED PHOTO-COPIES* AND ARE NOT
 ORIGINAL.
 PLEASE KNOW THAT ORIGINALS NOTARIZED AND COORDINATED
 WITH THE PLAN REVIEW AFFIDAVITS WILL BE REQUIRED.
  
 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 DO NOT CONTAIN ANY REQUIRED STAMPS OR SIGNATURES BY THE
 PRIVATE PROVIDER AS REQUIRED PER FS 553.791. PLEASE BE
 SURE TO SUBMIT NEW ENERGY CALCULATIONS TO THE PRIVATE
 PROVIDER TO REVIEW FOR CODE COMPLIANCE WITH REVISED
 PLANS.
 PLEASE BE SURE THESE ARE COORDINATED WITH ALL SUBMITTED
 DOCUMENTS AND SUBMIT TWO COMPLETED NEW SETS OF ENERGY
 CALCULATIONS FOR MINIMUM DOCUMENTS REQUIRED PER FBC
 106.1
  
 4) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS
 SHOWING THE ACCURATE SCOPE OF WORK. PLANS/SETS ARE NOT
 COMPLETE AND ARE MISSING SHEET(S).
 PLEASE SEE ONE SET CONTAINS A SHEET E2.2 WHICH WAS
 SIGNED, DATED AND SEALED BY THE ELECTRICAL ENGINEER ON
 2/21/08. THIS SHEET ON ONE OF THE SETS IS STILL SHOWING
 THE OUTSIDE ROOF COVERED EATING AREA WHICH IS NOT ON
 OTHER SHEETS IN SETS.
 PLEASE KNOW THAT THIS SHEET E2.2 IS NOT REVISED NOR IS
 THERE A SHEET E2.2 IN THE FIRST REVISED SET. THIS OTHER
 SET IS MISSING SHEET E2.2 ALL TOGETHER. COVER SHEET
 T1.1 CLEARLY STATES THERE SHOULD BE AN E2.2 IN BOTH
 SETS. BOTH SHOULD BE REVISED TO ACCURATELY DEPICT THE
 LATEST REVISED FLOOR PLANS ALONG WITH ELECTRICAL SCOPE
 OF WORK.
 PLEASE ALSO SEE ONE SET IS MISSING SHEET E5.1 WHICH IS
 ALSO SHOWN ON COVER SHEET T1.1. THE SECOND SET DOES
 CONTAIN THIS SHEET E5.1 WHICH WAS SIGNED, SEALED AND
 DATED 2-21-08.
 ** PLEASE COORDINATE ALL PLANS AND DOCUMENTS.
  
 5) NOTE: PLEASE SEE FLORIDA STATUTES 471.025 AND
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002 WHICH REQUIRES
 THE DESIGNER OF RECORD TO SIGN, DATE AND SEAL ALL PLANS
 RELEVANT TO THAT LICENSED DESIGNERS SCOPE OF WORK.
 PLEASE SEE THE REVISED ELECTRICAL SHEETS ARE NOW COMING
 IN WITH A COMPLETELY NEW SIGNATURE THAN THOSE SHOWN ON
 PREVIOUS PLANS AS WELL AS SOME OF THE SHEETS IN THESE
 SETS ALSO DO NOT CORRELATE.
 THIS NEW SIGNATURE DOES NOT COORDINATE WITH THE
 SIGNATURE GIVEN TO THIS OFFICE ON PREVIOUS PROJECTS BY
 SIGNATURE VERIFICATION LETTER WHICH WAS SIGNED, DATED,
 SEALED AND NOTARIZED. ALL SHEETS AND DOCUMENTS WILL NOW
 BEE RETAINED BY THIS REVIEWER. THIS OFFICE MAY HAVE NO
 CHOICE BUT TO TURN SAID PLANS AND DOCUMENTS OVER TO THE
 FLORIDA BOARD OF ENGINEERS FOR REVIEW.
 THE DESIGNER OF RECORD MAY APPEAR IN PERSON WITH PHOTO
 IDENTIFICATION TO SIGN, DATE AND SEAL REVISED PLANS
 WHICH WILL BE NEEDED AS CURRENT SHEETS ARE BEING
 RETAINED BY THIS OFFICE.
  
 6) NOTE: PLEASE SEE THE PRIVATE PROVIDER INFORMATION
 LISTED ON THE NOTICE TO BUILDING OFFICIAL AND PRIVATE
 PROVIDER AFFIDAVIT DOES NOT CORRELATE. THE NOTICE TO
 BUILDING OFFICIAL STATES MR. MORGAN DICKINSON P.E. WITH
 AN ADDRESS LOCATED TAMPA, FLORIDA. HOWEVER THE PRIVATE
 PROVIDER AFFIDAVITS STATE THE PRIVATE PROVIDER AS MR.
 OSVALDO AREVALO P.E..
 PLEASE COORDINATE ALL DOCUMENTS AND INFORMATION. FS
 553.791
 FBC 106.1, 106.3.5 ADMIN SECTION OF THE FLORIDA
 BUILDING CODE FOR MINIMUM CONSTRUCTION DOCUMENTS
 REQUIRED AND COORDINATION OF INFORMATION.
  
 7) NOTE: PLEASE BE SURE THE JURISDICTION AS LISTED ON
 THE COVER OF THE ENERGY CALCULATIONS ACTUALLY LISTS THE
 JURISDICTION IN WHICH THE SCOPE OF WORK IS TAKING
 PLACE.
 PLEASE SEE THESE SHEETS LIST PALM BEACH COUNTY AND NOT
 THE CITY OF WEST PALM BEACH.
 13-400.3.B, 13-415.2
 FBC 106.1, 106.3.5 FOR COORDINATION OF CONSTRUCTION
 DOCUMENTS AND PLANS FOR RECORD.
  
 8) NOTE: PLEASE SEE ALL THREE PREVIOUS AUDITS WITH
 RESPECT TO THE LIGHTING ON PLANS WHICH NEED TO
 COORDINATE WITH THE SUBMITTED INPUT DATA REPORT ON THE
 ENERGY CALCULATIONS.
 13-400.3.B, 13-415.2, 13-415.2.ABC.1.1, .1.2, .1.3. THE
 BELOW IS ONCE AGAIN SOME EXAMPLES OF LIGHTING WHICH IS
 LOCATED ON PLANS AND LISTED ON FIXTURE LEGEND WHICH ARE
 NOT IN THE IDR. THIS IS NOT AN EXHAUSTED LIST OF ALL
 LIGHT FIXTURES WHICH MAY NOT COORDINATE. THE AUDIT IS
 TO SHOW WHERE MINIMUM CODE COMPLIANCE IS NOT MET AND
 EXAMPLES ARE GIVEN AS A BENEFIT ONLY.
 FOR EXAMPLE:
 PLEASE SEE THE EXTERIOR LIGHTING ON THE IDR. THERE ARE
 FIXTURE LOCATIONS FOR TYPE NN FIXTURES ON WEST
 ELEVATION; THE COUNT ON PLANS IS THE SAME AS THE IDR
 HOWEVER THE VA RATING USED IN THE IDR IS LOWER THAN
 THAT STATED ON THE FIXTURE LEGEND. THE NN FIXTURE IS
 LISTED AS 50W ON LEGEND HOWEVER WITH 75W BALLAST. THE
 SHEET A2.2 WHICH IS REFERENCED IN NOTE #1 ON LIGHTING
 LEGEND SPECIFICALLY MENTIONS TO SEE ARCHITECTURAL PLANS
 FOR ACTUAL FIXTURES AND LOCATIONS. IF YOU GO TO SHEET
 A2.2 THE SHEET DOES SHOW FIXTURES *NN* HOWEVER THE
 ARCHITECT?S FIXTURE LEGEND SPECIFICALLY STATES THE *NN*
 FIXTURES ARE * NOT USED*. ONCE AGAIN AS STATED ON
 PREVIOUS REVIEW PLEASE COORDINATE ALL LIGHTING ON
 ARCHITECTURAL PLANS WITH THAT OF THE LIGHTING AND
 FIXTURES ON ELECTRICAL PLANS. THE PREVIOUS REVIEWS
 SPECIFICALLY GAVE CODE SECTIONS 13-415.2.ABC.1.1, .1.2
 AND .1.3.
 THE MINIMUM INPUT REQUIRED INTO THE IDR IS THAT IF THE
 BALLAST OUTPUT, MAXIMUM FIXTURE VA RATING ETC. THIS IS
 NOT THE VA OR WATTAGE OF BULB INSTALLED IS IT THE
 MAXIMUM RATING OF A FIXTURE OR THE BALLAST OUTPUT. AN
 EXAMPLE WAS GIVEN ON PREVIOUS REVIEW.
 FOR EXAMPLE:
 PLEASE SEE THE FIXTURE LEGEND WHICH SHOWS TYPE *QQ*
 FIXTURES FOR EXTERIOR. WHAT ARE THESE? DOES THE PLANS
 OR IDR CONTAIN A MISPRINT? IF SO PLEASE ALSO SEE THE
 TYPE *QQ* FIXTURES LISTED AS EXTERIOR SCONCES ARE
 100W/VA FIXTURES. THESE SAME FIXTURE ARE NOTED AS NOT
 USED ON SHEET A2.2 SO PLANS AND IDRDO NOT
 COORDINATE.
 FOR EXAMPLE:
 AS NOTED ABOVE FOR FIXTURES *NN* ON ARCHITECTURAL SHEET
 A2.2 WHICH WERE NOT SHOWN OR LABELED AS *NOT USED*
 PLEASE ALSO SEE THERE ARE SEVERAL FIXTURES ON
 ELECTRICAL LIGHTING PLANS SHEET E1.1 WHICH ARE NOT
 LOCATED ON SHEET A2.2. SOME OF THESE ARE FIXTURES SUCH
 AS EM8 AND EM4 ARE ON ELECTRICAL HOWEVER NOT ON
 ARCHITECTURAL.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-03-12 Cont ID  
Sent By dpalmer Date 2008-03-12 Time 18:06 Rev Time 0.00
Received By dpalmer Date 2008-03-12 Time 18:06 Sent To  
Notes
2008-03-12 18:06:53** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING.EXAMPLES WERE GIVEN ON
 PREVIOUS REVIEW HOWEVER NOT ALL ITEMS AS MENTIONED.
 PLEASE SEE SOME EXAMPLES ARE GIVEN ONCE AGAIN.
  
 ** PLEASE ALSO SEE THERE ARE SOME NEW COMMENTS BASED ON
 DOCUMENTS SUBMITTED AND/OR CHANGES MADE TO PLANS OR
 DOCUMENTS SUBMITTED. REVIEW COMMENTS CAN ONLY BE MADE
 ON PLANS AND DOCUMENTS REVIEWED.
 IN EITHER CASE THE COMMENTS NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SEE THE PLANS STILL SHOW A PERMANENT
 STRUCTURE FOR OUTSIDE EATING ON THE WEST SIDE WHICH BY
 GOING OVER WITH ERIC SCHNEIDER FROM ZONING, THIS
 STRUCTURE MAY NOT BE BUILT AS SHOWN. THIS WILL AFFECT
 ALMOST ALL DOCUMENTS AND PLANS INCLUDING ARCHITECTURAL,
 ELECTRICAL, AND PERFORMANCE CALCULATIONS.
  
 2) NOTE: PLEASE SEE SUBMITTED PLANS AND ALL DOCUMENTS
 WERE GONE THROUGH AND AS NOTED ON PREVIOUS REVIEW
 COMMENT #1, THE OWNER AFFIDAVIT WAS NOT SUBMITTED IN
 PACKAGE.
 PLEASE SEE FS 553.791(4)( C)
  
 3) NOTE: PLEASE SEE ONE SHEET OF THE PRIVATE PROVIDER
 BUILDING COMPLIANCE FOR MECHANICAL CONTAINS A NOTARY
 STAMP AND SIGNATURE OF THIS SHEET HOWEVER THE SHEET
 WHICH IS REQUIRED TO BE SIGNED BY THE REVIEWER IS NOT
 SIGNED AND IS BLANK?
 PLEASE SEE FS 553.791 AS THIS IS REQUIRED TO BE SIGNED
 BY THE PLANS EXAMINER AND A NOTARY UNDER FS 117.05 MAY
 NOT NOTARIZE A BLANK PAGE WHERE A SIGNATURE IS
 REQUIRED.
  
 4) NOTE: PLEASE SEE RESPONSE FROM THE DESIGNER FOR
 SIGNATURE MENTIONS THE TOP SIGNATURE IS THE ONE TO USE
 HOWEVER LETTER IS SIGNED WITH ANOTHER SIGNATURE ALL
 TOGETHER.THE LETTER MAY NOT LIST MULTIPLE SIGNATURES
 AND NEEDS TO STATE THIS IS THE LEGAL SIGNATURE. THE
 LETTER WILL BE PLACED IN SIGNATURE FILE.
 FS 471.025
  
 5) NOTE: PLEASE SEE COMMENTS BELOW WITH RESPECT TO
 ARCHITECTURAL PLANS FOR LIGHTING AND ELECTRICAL PLANS
 FOR LIGHTING WHICH DO NOT CORRELATE. PLEASE SEE SHEET
 A2.2 SPECIFICALLY WHICH DOES NOT SHOW THE REVISED
 LIGHTING FOR EMERGENCY LIGHTS, EXIT LIGHTS WHICH MANY
 WERE ADDED AND SOME WERE REMOVED OR RELOCATED. ONE
 EXAMPLE GIVEN: SEE THE AREA IN KITCHEN JUST TO THE LEFT
 OF THE LIQUOR STORAGE ROOM #121 WHICH ON ELECTRICAL
 PLANS THE EXIT LIGHT WAS REMOVED.
 PLEASE SEE THE NEW UPDATED ARCHITECTURAL SHEETS NOW
 CONTAIN COMPLETELY DIFFERENT SIGNATURES THAN THE
 PREVIOUSLY SUBMITTED PLANS?
 PLEASE SEE THE PRINTED LICENSE NUMBER OF THE ARCHITECT
 WHICH MAY SIMPLY BE ADDED TO TITLE BLOCKS ON ANY SHEETS
 WHICH DO NOT NEED TO BE RE-PRINTED. THIS IS GIVEN AS A
 NEW COMMENT DUE TO THE A-SHEETS NOT CORRELATING WITH
 ELECTRICAL. THIS WAS A COMMENT FROM OTHER TRADES ON
 PREVIOUS REVIEW(S) AND IS GIVEN FOR INFORMATION AND IS
 REQUIRED EVEN IF COMMENT IS NOT MADE BY OTHER
 TRADE(S).
  
 6) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO
 EGRESS LIGHTING REQUIRED TO MEET MINIMUM LEVELS PER THE
 LIFE SAFETY CODE. 7.8 AND 7.9. THE RESPONSE MENTIONS
 THIS WILL BE THE RESPONSIBILITY OF THE CONTRACTOR AND
 WILL NEED TO PERFORM READINGS OF LIGHTING LEVELS AT THE
 END OF THE PROJECT. THIS IS NOT ACCEPTABLE AS THIS IS
 NOT THE RESPONSIBILITY OF THE CONTRACTOR AND IS THE
 RESPONSIBILITY OF THE DESIGN PROFESSIONAL. PLEASE SEE
 FLORIDA ADMINISTRATIVE CODE 61G15-33.004 WITH RESPECT
 TO MINIMUM RESPONSIBILITIES OF THE ENGINEER.
 IF THE LIGHTING IN AREAS OF CONCERNS WERE NOT ON
 DIMMING PANELS AND ALL A PART OF NORMAL LIGHTING AS
 SHOWN ON PLANS THIS WOULD NOT BE OF CONCERN. THEFACT
 THAT THE PLANS CONTAINS LIGHTING ON DIMMING PANELS AND
 THERE IS NO INFORMATION ON A STARTING LIGHTING LEVEL
 POINT AND NO INFORMATION ON THE MINIMUM LEVEL IN WHICH
 EGRESS LIGHTING IN ALL PATHS WILL BE DIMMED TO, THIS
 SHALL BE ADDRESSED AT THIS TIME.
 PLEASE PROVIDE INFORMATION ON LEVELS, DIMMING ETC.
 PLEASE SEE7.8.1.3, 7.8.1.4 WHICH REQUIRES 1FT CANDLE
 MINIMUM NO DESIGNATED AREA TO FALL BELOW 2.2 LUX OR .02
 FT CANDLES WITH THE FAILURE OF ANY ONE UNIT. PLEASE SEE
 SOUTHEAST CORNER OF DINING AREA FOR ONE EXAMPLE AS THE
 LEVELS SHOWN ON PHOTO-METRIC PLANS FOR THAT AREA ARE
 ALREADY LOW AND APPEARS IT WILL FALL BELOW MINIMUM AS
 ONLY ONE UNIT IS SHOWN ON PLANS FOR THAT AREA.
  
 7) NOTE: PLEASE SEE RESPONSE TO PREVIOUS REVIEW NOTE
 WHICH MENTIONED VERSION 3.0 OF FLA-COMM COULD NOT BE
 USED WAS AS FOLLOWS AND IS QUOTED FROM DESIGNER'S
 RESPONSE:
 *
 BUILDING OFFICIALS: ENERGY GAUGE SUMMIT VERSION 3.0 AND
 3.1 SATISFIES THE REQUIREMENTS IN 13-400.3.A AND
 13-400.3.B (GENERATED BY FLA/COM-2004 COMPUTER PROGRAM,
 VERSION 2.5).*
 *
 PLEASE SEE THIS IS EXACTLY THE WORDING ON THE STATE
 WEBSITE. PLEASE READ WHAT THE STATEMENT SAYS, THE
 VERSION 3.0 AND 3.1 *ENERGY GAUGE SUMMIT* GENERATED BY
 THE FLA/COM 2004 COMPUTER PROGRAM, * VERSION 2.5*.
 THESE MEANS IT IS STILL THE VERSION 2.5 AS TITLED IN
 PROGRAM AND YOU WILL SEE THE ENERGY GAUGE SUMMIT 3.0 OR
 3.1 ON THE LAST LINE OF SHEET.
 NOW THE SUBMITTED CALCULATIONS DO SHOW THE 2.5 HOWEVER
 SAYS ENERGY GAUGE SUMMIT 3.14.
 THE MECHANICAL REVIEW STATED IN THE PREVIOUS REVIEW
 THAT METHOD *B* WAS NOT AN OPTION FOR MECHANICAL REVIEW
 AND TO ADDRESS NOTE #17.
 PLEASE SEE THE PREVIOUS ELECTRICAL REVIEWS GAVE
 SECTIONS 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3 FOR
 PRESCRIPTIVE REQUIREMENTS.
 PLEASE SEE THAT NOT ALL LIGHTING ON PLANS COORDINATE
 WITH THE LIGHTING ON FIXTURE SCHEDULE ALONG WITH
 LIGHTING IN THE INPUT DATA REPORT.
 EXAMPLE: WOMEN AND MEN BATH ROOMS, DIMMING PANELS
 CLEARLY SHOW VANITY LIGHTING IN THESE AREAS YET NOT IN
 THE IDR.
 EXAMPLE: MECHANICAL ROOM WHICH IS NOTED AS ROOM 129 ON
 PLANS WHICH IS BEING ASSUMED AS THE ROOM WHICH IS
 LABELED AS STORAGE ON IDR.
 EXAMPLE: FIXTURE U, WHICH FIXTURE LEGEND STATES 75W
 TRANSFORMER MONO-POINT USE.
 EXAMPLE: UMBRELLA LIGHTS ON DIMMING PANEL CIRCUIT 24.
 WHAT ARE THESE FIXTURES, WHERE ARE THEY IN THE IDR, HOW
 ARE THEY FIGURED?
 THESE CALCULATIONS MAY ONLY BE FOR ELECTRICAL LIGHTING
 AND MAY NOT TRADE OFF ANY OTHER ITEMS SUCH AS BUILDING
 SYSTEMS ETC.
 THIS SECTION13-101.1.3 APPLIES TO RENOVATIONS WHICH
 THIS DOES NOT FALL UNDER AND ONLY 13-415.2 APPLIES AND
 ITS ADOPTED SECTIONS THERETO.
 PLEASE EXPLAIN HOW THE EFFECTIVE WATTAGE IS LESS THAN
 DESIGN AND DESIGN IS HIGHER THAN THE ALLOWANCE. PLEASE
 EXPLAIN HOW THE DESIGN WATTAGE ON COMPLIANCE SUMMARY
 SHEET IS NOT THE SAME AS DESIGN WATTAGE ON LIGHTING
 COMPLIANCE SHEET.
 PLEASE SEE SECTION ABOVE AS THIS IS NOT A TRADE OFF FOR
 OTHER COMPONENTS.
 ** AS NOTED ON PREVIOUS REVIEW, PLEASE GO OVER ALL
 LIGHTING ON PLANS, PLEASE BE SURE THE SPECIFIC
 REQUIREMENTS OF 13-415.2.ABC.1.1, .1.2 AND .1.3 ARE
 MET.
 ** PLEASE SEE AS MENTIONED ON THE PREVIOUS REVIEW
 PLEASE BE SURE THE OWNER AGENT IS SIGNED ON THE
 CERTIFICATION SHEETS. THIS DOES NOT MEAN THE NAME SHALL
 BE TYPE WRITTEN ON SHEETS, THIS REQUIRES A SIGNATURE.
 PLEASE BE SURE AS MENTIONED ON PREVIOUS REVIEW THE
 CERTIFICATION SHEET CONTAINS THE SIGNATURE AND SEAL
 FROM THE DESIGN PROFESSIONAL.13-103.1., FBC 106.1.2
 ADMIN SECTION.
  
 8) NOTE: PLEASE SEE COMPLIANCE FOR 13-415.1.ABC.1.1,
 .1.2 AND .1.3 HAVE NOT BEEN ACHIEVED FOR ALL LIGHTING
 AS REQUIRED.
 THERE ARE LOCATIONS ON PLANS WHICH STILL ONLY SHOW A
 STANDARD METHOD OF CONTROL WHEN THE CODE REQUIRES
 AUTOMATED SHUT OFF. SOME AREAS WERE GIVEN AS EXAMPLES
 ON PREVIOUS REVIEW AND NOTED AS ALSO SEE OTHER AREAS.
 PLEASE SEE PREVIOUS NOTE WITH RESPECT TO SOME OF THE
 FIXTURES NOTED WHICH WERE NOT INCLUDED IN THE IDR. ONE
 FOR EXAMPLE WAS FIXTURE *P* WHICH WAS GIVEN. PLEASE SEE
 HOST AREA WHICH SHOWS FIXTURE *P* ABOVE ARE WHICH
 CONTAINS A STANDARD DIMMING SWITCH AND DOES NOT GO TO
 ANY CIRCUITING, CONTROLS, DIMMING PANEL ETC? THE PLANS
 DO CONTAIN NOTES #9 AND #10 HOWEVER THEY MENTION TO SEE
 E2.1 FOR CONTINUATION HOWEVER 2.1 DOES NOT PROVIDE ANY
 CONTROL OR CIRCUITING INFORMATION. PLEASE EXPLAIN AND
 SHOW HOW THE OCCUPANT CAN SEE ALL LIGHTING WHICH IS
 BEING CONTROLLED AS THIS PROPOSED CONTROL IS AT ONE
 LOCATION. HOW WILL SYSTEM MEET IDENTIFICATION AND PILOT
 LIGHTS REQUIRED?
 PLEASE SEE BAR RELAY PANEL MENTIONS THIS BEING A RELAY
 PANEL HOWEVER THE CIRCUITS IN THIS PANEL ARE SHOWN FROM
 PANEL L1 AND NO OVER RIDES OR TIMES COULD BE FOUND.
 EXAMPLE: PLEASE SEE PLANS STILL INDICATE LIGHTING IN
 MEN'S AND WOMEN'S BATHROOM WITH NO SEPARATE SPACE OVER
 RIDE CONTROLS. SOME LIGHTING WAS NOW PLACED ON
 OCCUPANCY SENSORS HOWEVER SEE DIMMING PANEL WHICH STILL
 LIST LIGHTS IN BOTH OF THESE LOCATIONS.
 ** PLEASE VERIFY LISTING OF MARLIN PANELS AND MATRIX
 CONTROLLERS. AS THE SYSTEM ON PLANS WAS NOT COMPLETE
 SOME RESEARCH OF SYSTEM COMPONENTS WAS DONE AND EVEN AS
 EACH MAY BE LISTED, COULD NOT LOCATE THESE AS A LISTED
 ASSEMBLY OR SYSTEM. PLEASE PROVIDE TECHNICAL SPECS/CUT
 SHEETS FOR THIS PER 110.3, 90.7. THESE ARE NOW BEING
 REQUESTED AS THE INFORMATION FOR LABELING, PILOT LIGHTS
 ETC HAS NOT BEEN CLEAR ALONG WITH CONTROLS.
  
 9) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WITH RESPECT
 TO TRACK LIGHTING LOADS AND HOW THEY WERE FIGURED INTO
 SERVICE PER 220.43B. THE DIMMING PANELS NOW SHOW THE VA
 PER TWO FT HOWEVER THE LOADS ARE STILL SHOWN AT 1.0
 FACTOR. ARE THESE NOT CONTINUOUS LOADS?
 125%, 215.3, 230.42 ETC PLEASE ADJUST.
  
 10) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO
 FLORIDA STATUES 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE. AT THIS TIME AS REQUIRED
 UNDER FLORIDA STATUTES, THIS OFFICE HAS ASSESSED THE
 FEE AS REQUIRED WHICH IS REQUIRED TO BE PAID BEFORE THE
 PLANS MAY BE RESUBMITTED. PLEASE BE SURE TO GO OVER
 COMMENTS, IF THERE ARE ANY QUESTIONS PLEASE CONTACT
 THIS OFFICE/REVIEWER TO GO OVER COMMENTS.
 PLEASE SEE THE FEE OF $18, 600 WILL BE DUE UPON
 RESUBMITTING OF PLANS.
 ** ONE SET OF ELECTRICAL PLANS ALONG WITH ONE COPY OF
 THE ENERGY CALCULATIONS SUBMITTED ARE BEING RETAINED BY
 THIS OFFICE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-03-11 19:37:58 
  
 ** REVIEW WILL GO INTO A FAILED STATUS. NOTES TO FOLLOW
 ONCE COMPLETED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-30 Cont ID  
Sent By dpalmer Date 2008-01-30 Time 14:58 Rev Time 0.00
Received By dpalmer Date 2008-01-30 Time 14:58 Sent To  
Notes
2008-01-31 15:27:03** NOTE ADDED **
 1/31
  
  
 1) NOTE: IT HAS BEEN CONFIRMED WITH FIRE MARSHAL THAT
 AN EXIT SIGN WILL BE REQUIRED AT DELIVERY DOOR FOR
 KITCHEN PERSONNEL.
 LS 101 7.8,7.9
2008-01-30 14:58:50** DENIED 2ND REVIEW **
  
 ** PLEASE SEE THERE ARE STILL SOME COMMENTS FROM
 PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SUBMIT THE REQUIRED FEE OWNER AFFIDAVIT
 WHICH IS REQUIRED PER FS 553.791(4)(C).
  
 2) NOTE: PLEASE SEE SIGNATURE LETTER SUBMITTED FOR THE
 ENGINEER CONTAINS TWO DIFFERENT SIGNATURES OF THE
 RESPONSIBLE ENGINEER OF RECORD.
 PLEASE SEE FS 471.025 WHICH SIGNATURE IS THE LEGAL
 ORIGINAL SIGNATURE FOR ENGINEER OF RECORD?
 PLEASE CALL TO GO OVER.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #17 WITH
 RESPECT TO LIGHTING ON BATH ROOMS BEING NOTED TO BE
 CONTROLLED BY DIMMING PANEL. THE RESPONSE WAS THE
 EMERGENCY LIGHT FIXTURE IS CIRCUITED TO THE HOT/LINE
 SIDE OF THE LOCAL CIRCUIT WHICH IS OK. PLEASE SEE THE
 PREVIOUS REVIEW COMMENT WAS NOT FOR THE EMERGENCY
 LIGHTING AND CIRCUITING, IT WAS FOR THE LEVELS OF
 LIGHTING UNDER NORMAL CONDITIONS. PLEASE SEE THE CODE
 SECTION WHICH WAS GIVEN ON PREVIOUS REVIEW WAS LS 101
 7.8 WHICH IS FOR MINIMUM LIGHTING LEVELS UNDER NORMAL
 CONDITIONS. THIS IS NOT FOR THE EMERGENCY (BATTERY BACK
 UP) LIGHT FIXTURE.
 PLEASE SEE THE LIGHTING LEVELS FOR EGRESS IN, AROUND
 AND EXITING BATHROOMS MAY NOT FALL BELOW 1FT CANDLE
 AVERAGE AT ALL EGRESS WALKING SURFACES.
 THIS COMMENT IS ALSO FOR OTHER EGRESS PATHS AS
 DESIGNATED AS GENERAL LIGHTING ON DIMMER PANEL MAY NOT
 FALL BELOW MINIMUM 1FT CANDLE LEVEL. PLEASE INDICATE
 HOW THIS IS BEING DONE.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT # 14 WITH
 RESPECT TO LIGHTING CONTROLS REQUIRED IN SEPARATE
 SPACES AND AN EXAMPLE WAS NOTED *SUCH AS BATHROOMS*.
 THE RESPONSE MENTIONS THE PARTITIONS INSIDE THE
 BATHROOMS AND CONTROLS ARE NOT REQUIRED AS THESE
 PARTITIONS DO NOT GO ALL THE WAY TO THE CEILING. PLEASE
 SEE 13-415.1.ABC.1.1 AND .1.2. THE PREVIOUS COMMENT WAS
 NOT FOR THE STALL AREAS IN THE BATHROOMS. THIS WAS FOR
 THE *BATHROOMS* AS THEY ARE CONSIDERED SEPARATE SPACES
 FROM OTHER OPEN AREAS WITH LIGHTING CONTROLS.
 PLEASE SEE THIS AND ANY OTHER AREAS.
 PLEASE SEE THIS PREVIOUS REVIEW NOTE ALSO CONTAIN A
 NOTICE ABOUT THE OCCUPANT BEING ABLE TO VISUALLY SEE
 ALL LIGHTING IN WHICH IS BEING OVER RIDDEN. PLEASE SEE
 THE RESPONSE LETTER ONLY RESPONDED TO PARTITIONS IN
 BATHROOMS. PLEASE CLARIFY HOW THE OCCUPANT FROM EACH
 OVER RIDE/ ENTRANCE LOCATION CAN VISUALLY SEE THE
 LIGHTING WHICH IS BEING CONTROLLED OR MEETING THE
 EXCEPTION IN SAME SECTION AS PREVIOUSLY NOTED. THIS
 WOULD REQUIRE PILOT LIGHTS ETC CLEARLY LABELED.
  
 5) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT # 15 WITH
 RESPECT TO CHAPTER 13 AND ENERGY CALCULATIONS
 SUBMITTED.
 PLEASE KNOW THE PREVIOUS SUBMITTED METHOD WAS *A* WHICH
 IS NOW CHANGED TO METHOD *B* WHICH IS ACCEPTABLE
 HOWEVER PLEASE SEE FBC 13-400.3.B AS THE VERSION
 SUBMITTED IS NOT THE VERSION AS ADOPTED UNDER THE FBC.
 PLEASE SEE THE SECTION AS NOTED WHICH REFERENCES
 VERSION 2.5/400.B-04R.
 PLEASE SEE THE FOLLOWING SECTIONS TO THIS SAME NOTE:
 PLEASE SEE THE INPUT DATA REPORT WILL BE NOTED AS IDR
 ON THE FOLLOWING NOTES.
  
 A) ONCE AGAIN PLEASE CORRELATE ALL LIGHTING ON PLANS
 WITH THE IDR. PLEASE SEE SOME EXAMPLES WERE GIVEN ON
 PREVIOUS REVIEW HOWEVER THEY WERE NOT ALL.
 PLEASE SEE FOR EXAMPLE: THE EXTERIOR LIGHTING SHOWN ON
 PLANS DOES NOT COORDINATE WITH THE IDR FOR EXTERIOR
 LIGHTS. PLEASE SEE FIXTURES *H*, *BB*, *EM4*, ETC.
 PLEASE SEE FOR EXAMPLE: THE FIXTURES WHICH ARE NOTED AS
 INTERIOR LIGHTING WHEN THEY ARE LOCATED OUTSIDE. HOW IS
 THIS POSSIBLE?
 PLEASE SEE THE FIXTURES NOTED AS *EM4* ON PLANS ARE
 FIXTURES USED AS PART OF THE GENERAL LIGHTING WHICH ARE
 NOT EXEMPT.
 PLEASE ALSO SEE THE LIGHTING ON PLANS FOR INTERIOR
 FIXTURES DO NOT CORRELATE WITH THE IDR AND FIXTURE
 LEGEND. FOR EXAMPLE: SEE MISSING VA INPUTS FOR FIXTURES
 *P*, SEE MISSING VA REQUIRED FOR TRACK LIGHTING AS
 PREVIOUS NOTED, SEE ENTRY E1 FIXTURES AND COUNTS ON
 THESE IN HOST AREAS ETC
  
 THERE ARE SEVERAL INSTANCES ON PLANS AS NOTED WHICH
 NEED COORDINATION. PLEASE KNOW AS THE LOCATION
 DESIGNATIONS ON PLANS DO NOT CORRELATE WITH THE IDR AND
 BASED ON THE FACT NOT ALL LIGHTING IS FIGURED INTO THE
 IDR A COMPLETE REVIEW OF ALL ITEMS CAN NOT BE DONE AT
 THIS TIME.MECHANICAL ROOM, OTHER ROOM ON PLANS NEAR
 TOILET VESTIBULE NOT LABELED.
 PLEASE SEE 13-415.1.B, 13-415.2, 13-415.2.ABC.1.3,
 13-415.2.ABC.1.2 (TRACK LIGHTING FOR LINE VOLTAGE AND
 LOW VOLTAGE) ETC.
  
 6) NOTE: PLEASE SEE THE CERTIFICATION SHEET CONTAINS A
 SIGNATURE FOR THE PERSON WHO *PREPARED* CALCULATIONS
 HOWEVER DOES NOT LIST ANY INFORMATION FOR THIS PERSON.
 PLEASE LIST INFORMATION AS LICENSED PE IN THE STATE OF
 FLORIDA. PLEASE SEE 13-103.1, FAC 61G15-23.002,
 FS471.025.
 THE COVER SHEET CONTAINS SIGNATURES AND SEALS FROM TOW
 OTHER DESIGNERS HOWEVER THIS INFORMATION SHOULD BE ON
 THE CERTIFICATION SHEET AS STATED.
  
 7) NOTE: PLEASE SEE PREVIOUS NOTE #12 WITH RESPECT TO
 LOADS FOR TRACK LIGHTING. PLEASE SEE RESPONSE MENTIONS
 LOAD WAS ADDED TO PANELS ON E4.1 HOWEVER COULD NOT
 LOCATE ON PLANS, PANELS OR ANY LOAD CALCULATIONS HOW
 THESE LOADS WERE DERIVED PER 220.43B.
  
 8) NOTE: PLEASE SEE FIXTURES EM4 ON SOUTH SIDE OF ENTRY
 VESTIBULE WILL BE REQUIRED TO BE CIRCUITED TO THE LOCAL
 BRANCH CIRCUIT FEEDING OTHER *Q* FIXTURES IN THAT AREA
 PER 700.12F.
 PLEASE SEE THEY ARE CURRENTLY SHOWN COMING FROM SOUTH
 PATIO CIRCUIT.
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
 PLEASE KNOW ONE SET OF ELECTRICAL PLANS ALONG WITH ONE
 SET OF ENERGY CALCULATIONS ARE BEING RETAINED BY THIS
 OFFICE.
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-01-29 20:16:33ON SET IN ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-24 Cont ID  
Sent By dpalmer Date 2007-09-24 Time 17:57 Rev Time 0.00
Received By dpalmer Date 2007-09-24 Time 17:57 Sent To  
Notes
2007-09-24 17:57:212007-09-24 17:57:21
  
  
 ** DENIED**
  
 KONA GRILL
  
  
 1) NOTE: PLEASE STATE THE FOLLOWING RELEVANT CODES ON
 PLANS.
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLANS INDICATE THE 2004 FLORIDA ELECTRICAL CODE.
  
 2) NOTE: PLEASE SEE MISSING REQUIRED INFORMATION ON
 TITLE BLOCKS FOR ARCHITECTURAL FIRM. PLEASE SEE MISSING
 PRINTED INFORMATION ALONG WITH MISSING LICENSE
 INFORMATION.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004.
 PLEASE ALSO SEE FLORIDA STATUES 481.219 FOR MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER ALSO KNOWN AS FIRM
 LICENSE NUMBER.
 PLEASE BE SURE THE PRINTED NAME IS ALSO STATED.
 ** THIS IS REQUIRED FOR ALL SHEETS WHICH CONTAIN THE
 TITLE BLOCKS FOR ARIA GROUP ARCHITECTS INC. INFORMATION
 ON REQUIREMENTS MAY ALSO BE FOUND THROUGH THE STATE OF
 FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION OR FLORIDA BOARD OF ARCHITECT'S LEGAL
 COUNSEL TO THE BOARD.
  
 3) NOTE: PLEASE SEE ARCHITECTURAL AND OTHER SHEETS SUCH
 AS *G* SHEETS WHICH WERE NOT DATED WHEN SIGNED AND
 SEALED.
 PLEASE SEE ONLY THE FIRST SHEET IN SET WAS SIGNED,
 DATED AND SEALED AS REQUIRED PER FS 481.221
  
 4) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS ALSO AS
 THE *S* SHEETS ARE MISSING THE REQUIRED TITLE BLOCK
 INFORMATION FOR THE ENGINEERING FIRM.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND
 FLORIDA STATUTES 471.023 FOR THE REQUIRED CERTIFICATE
 OF AUTHORIZATION NUMBER. (ALSO KNOWN AS ENGINEERING
 BUSINESS NUMBER)
 THIS REQUIRES PRINTED NAME, PRINTED LICENSE NUMBER OF
 THE DESIGNER AS WELL.
  
 5) NOTE: PLEASE SEE ELECTRICAL SHEETS AS WELL AS ALL
 MEP SHEETS WHICH ARE MISSING REQUIRED INFORMATION ON
 TITLE BLOCKS PER THE FAC 61G15-23.002 AND FS 471.023.
 THIS IS THE SAME INFORMATION AS STATED ABOVE IN NOTE
 #4.
 TITLE BLOCKS TO INCLUDE PRINTED NAME OF DESIGNER,
 PRINTED LICENSE NUMBER AND CA/EB LICENSE NUMBER FOR
 FIRM.
 *** THIS IS REQUIRED FOR ALL MEP SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE(S). IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE. INFORMATION ON REQUIREMENTS MAY ALSO BE FOUND
 THROUGH THE STATE OF FLORIDA DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION OR FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS.
  
 6) NOTE: PLEASE BE SURE TO PROVIDE THE UNIT/SUITE
 NUMBER ON TITLE BLOCKS FOR PROJECT. THE BUILDING
 ADDRESS IS ALREADY ON SHEETS, HOWEVER NEEDS TO CONTAIN
 UNIT NUMBER.
 FAC 61G1-16.004, 61G15-23.002, FBC ADMINISTRATIVE
 SECTION 110.1.2, 106.1.2.
  
 7) NOTE: PLEASE KNOW EVEN AS THE REQUIRED FIRE ALARM
 SYSTEM WILL BE UNDER A SEPARATE PERMIT THE BASE BUILD
 OUT PLANS ARE STILL REQUIRED TO SHOW THE MINIMUM
 DEVICES AND DEVICE LEVELS FOR THE FLORIDA BUILDING CODE
 CHAPTER 11 FOR ADA.
 PLEASE SEE 11-4.28.1, .2 AND .3(4) AS THE MINIMUM
 LEVELS ARE TO BE STATED ON PLANS.
 THE SYMBOL LEGEND AND F SHEETS DO INDICATE LEVELS
 HOWEVER MANY DEVICES DO NOT MEET THE MINIMUM LEVELS.
 PLEASE KNOW IF MULTIPLE LOCATIONS ARE INDEED USING A
 DEVICE WITH LESS THAN THE MINIMUM THEN PLEASE PROVIDE
 POINT BY POINT CALCULATIONS ON THE MINIMUM LIGHTING
 LEVELS FOR CANDELA LEVELS.
 PLEASE ADJUST FOR THE MINIMUM LEVELS AS REQUIRED IN
 SECTIONS ABOVE.
  
 8) NOTE: PLEASE SEE THE COLOR CODING AS STATED ON SHEET
 E5.1 FOR 277/480V NEEDS TO BE BROWN, PURPLE, AND
 YELLOW.
 PLEASE KNOW THE NEC ONLY PROVIDE THE IDENTIFICATION OF
 *ORANGE* FOR HIGH-LEG SYSTEMS. AS THIS SYSTEM DOES NOT
 CONTAIN A HIGH-LEG AND ALONG WITH THE FACT THE LOCAL
 COLOR CODING USED IN THIS EXISTING BUILDING IS THE
 COLOR CODING AS NOTED ABOVE ANY NEW CONDUCTORS WILL
 REQUIRE THE SAME IDENTIFICATION. PLEASE ADJUST NOTE.
 NEC 90.4.
  
 9) NOTE: PLEASE SEE THE RISER CONTAINS AN
 IDENTIFICATION AS EX FROM THE FPL TRANSFORMER TO THE
 BUILDING SERVICE MAIN. THE EX ON THE RISER NOTES
 MENTIONS THESE ARE *FEEDERS*. PLEASE CLARIFY THIS
 IDENTIFICATION AS THE CONDUCTORS AHEAD OF ANY SERVICE
 MAIN ARE IN FACT *SERVICE ENTRANCE CONDUCTORS* AND
 WOULD CONTAIN IDENTIFICATION ACCORDINGLY.
 NEC 100, 215, ETC
 FBC 106.1.2 ADDITIONAL INFORMATION.
  
 10) NOTE: PLEASE SEE THE CONDUCTORS FROM THE SECONDARY
 SIDE OF THE TRANSFORMER TO THE LDP ARE NOT LARGE
 ENOUGH.
 PLEASE SEE 240.21C2, 240.4, 310.16 AND 110.14
 ** THE CODE DOES PERMIT OVER CURRENT PROTECTION TO THE
 NEXT STANDARD AS LISTED IN 240.6 IN MANY INSTANCES
 HOWEVER NOT ON THE SECONDARY SIDE OF THE TRANSFORMERS
 AS THEY ARE REQUIRED TO TERMINATE IN OVER CURRENT
 PROTECTION WHICH LIMITS THE LOAD ON THE CONDUCTORS.
  
 11) NOTE: PLEASE SEE PANEL *CC* WHICH IS NOTED ON RISER
 AS BEING FED BY 80AMP OVER CURRENT PROTECTION ON THE
 CIRCUIT SCHEDULE, HOWEVER THE RISER INDICATES 125AMP
 OVER CURRENT PROTECTION ON PANEL LDP WHICH DOES NOT
 CORRELATE.
 PLEASE COORDINATE AND ADJUST PLANS.
 FBC 106.1.2, 106.1.3 ADMIN FOR COORDINATION.
  
 12) NOTE: PLEASE CLARIFY WHERE AND HOW TRACK LIGHTING
 LOADS FOR THE LOAD CALCULATIONS HAVE BEEN FIGURED PER
 220.43B.
  
 13) NOTE: PLEASE SEE 210.8B2 AS PROTECTION OF ALL
 RECEPTACLES IN KITCHENS ARE REQUIRED TO CONTAIN GFCI
 PROTECTION. THIS IS FOR ALL 15 AND 20AMP RECEPTACLES
 WHETHER OR NOT THEY ARE FEEDING THE COUNTER SPACES. THE
 PLANS DO INDICATE A NOTE WHICH MENTIONS THIS HOWEVER
 THERE ARE NUMEROUS CIRCUITS ON PANEL SCHEDULES WHICH DO
 NOT INDICATE THE DESIGNATION FOR GF TYPE BREAKERS WHICH
 IS NOTED ON LEGEND ON PANEL SCHEDULE.
 PLEASE SEE SOME ARE NOTED AS GFEP FOR GROUND FAULT
 EQUIPMENT PROTECTION HOWEVER PLEASE KNOW THAT THE CLASS
 OF GROUND FAULT PROTECTION IS NOT THAT FOR EQUIPMENT
 BUT FOR PERSONNEL.
 PLEASE SEE FOR EXAMPLE A FEW CIRCUITS MISSING REQUIRED
 PROTECTION:
 KP1-16, KP1-31, KP2-22, KP2-15. THIS IS ONLY A FEW AS
 NOTED FOR EXAMPLE.
  
 14) NOTE: PLEASE SEE MISSING SOME INFORMATION FOR
 COMPLIANCE TO FBC CHAPTER 13.
 THERE IS NOT ENOUGH INFORMATION FOR LIGHTING CONTROLS
 AT THIS TIME.
 PLEASE SEE MISSING INFORMATION FOR LIGHTING CONTROLS OF
 MAIN DINING AREAS AND OTHER SEPARATE SPACES PER
 13-415.1.ABC .1.1, .1.2 AND .1.3.
 PLEASE SEE SOME OCCUPANCY DEVICES ARE SHOWN FOR SOME
 AREAS AND TWO CONTACTORS ARE SHOWN FOR SOME EXTERIOR
 LIGHTING AND KITCHEN PREP AREAS HOWEVER MISSING
 INFORMATION AND CONTROLS FOR OTHER SPACES INCLUDING
 SEPARATE SPACES WHICH CONTAIN FLOOR TO CEILING HEIGHT
 PARTITIONS (BATHROOMS) AND ACCENT LIGHTING.
 PLEASE PROVIDE LOCATIONS FOR ALL DEVICES OR SYSTEMS.
 SECTION 13-415.1.ABC.1.1, .1.2 REQUIRES THE OCCUPANT TO
 SEE THE LIGHTING IN WHICH IS BEING OVER RIDDEN OR
 CONTROLLED. THERE IS AN EXCEPTION AND IF USING THE
 EXCEPTION FOR PILOT LIGHTS ETC PLEASE INDICATE AND
 PROVIDE DETAIL.
 PLEASE PROVIDE SCHEDULING OF SYSTEM OR INFORMATION ON
 OTHER DEVICES.
 PLEASE BE SURE TO PROVIDE ALL MAXIMUM OVER RIDE TIMES
 ON OTHER DEVICES INSTALLED. THIS WAS DONE FOR THE
 DEVICES ALREADY ON PLANS.
  
 15) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.B,
 13-415.1.C, 13-415.2.
 A)PLEASE SEE MECHANICAL REVIEW COMMENTS ALSO WITH
 RESPECT TO THE *METHOD* OF CALCULATIONS BEING
 SUBMITTED. PLEASE CLARIFY HOW *A* IS BEING USED WHEN
 THIS IS NOT A WHOLE BUILDING.
 METHOD *A* CLEARLY STATES *WHOLE BUILDING METHOD*.
  
 B) PLEASE COORDINATE ALL LIGHTING ON THE ENERGY
 CALCULATIONS SPECIFICALLY THE INPUT DATA REPORT WITH
 THE PLANS.
 PLEASE SEE 13-415.2.ABC.1.2 FOR REQUIRED MINIMUM
 LOADS/FIGURES TO BE USED FOR TRACK LIGHTING. PLEASE SEE
 THE MINIMUM FOR LINE VOLTAGE TRACK IS BASED ON THE
 NUMBER OF FIXTURES AT THE WATTAGE OF EACH OR THE TOTAL
 LINEAR FT OF TRACK AT 30VA PER FT, WHICH EVER IS
 GREATER.
 PLEASE ALSO SEE THE ANY LOW VOLTAGE TRACK IS BASED ON
 THE AVAILABLE VA OF THE TRANSFORMER.
 PLEASE BE SURE TO COMPLETE PLANS WITH ALL INFORMATION
 EACH OF THE TRANSFORMERS.
 PLEASE SEE THE PLANS SEEM TO INDICATE A *T* IN A SQUARE
 BOX FOR WHAT IS BEING ASSUMED AS THE LOW VOLTAGE
 TRANSFORMERS. PLEASE CLARIFY THIS AS THE SYMBOL LEGEND
 ON THE MEP1.0 SHEET DOES NOT CONTAIN THIS DESIGNATION.
 C) PLEASE COORDINATE ALL OTHER LIGHTING FIXTURES,
 WATTAGE AND METHOD OF CONTROLS ON THE INPUT DATA
 REPORT. THE FIXTURE LEGEND ON PLANS INDICATES A CERTAIN
 WATTAGE AND THE IDR INDICATES ANOTHER.
 EXAMPLE, PLEASE SEE TYPE N-2 FIXTURE ON E1.1 WHICH IS
 SHOWN LISTED FOR THE OFFICE, MECHANICAL ROOM AND LIQUOR
 STORAGE. THIS SAME FIXTURE N-2 IS LISTED AS 96VA/WATTS
 ON THE FIXTURE LEGEND ON SHEET E4.1, AND YET THE IDR
 LIST THIS SAME FIXTURE AS 84VA AND 64VA? PLEASE SEE TWO
 DIFFERENT VA LISTINGS FOR THE SAME FIXTURE. (MECHANICAL
 ROOM/OFFICE)
 PLEASE SEE THIS IS ONLY ONE LOCATION IN QUESTION.
 PLEASE BE SURE TO SEE PART *B* OF THIS COMMENT ABOVE AS
 THE TRACK LIGHTING LOADS ON THE CALCULATIONS WILL NEED
 ADJUSTING.
  
 D) PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ARE
 REQUIRED TO FILL OUT WITH COMPLETED INFORMATION ON THE
 CERTIFICATION SHEETS ALONG WITH BEING SIGNED, DATED AND
 SEALED BY THE RESPECTIVE RESPONSIBLE DESIGNERS OF
 RECORD.
 PLEASE SEE NEITHER COPY SUBMITTED CONTAIN THIS REQUIRED
 INFORMATION ON THE *CERTIFICATION SHEET* AS REQUIRED.
 PLEASE SEE ONLY ONE COPY ACTUALLY CONTAINED ANY
 SIGNATURES AND SEALS. IN FACT THE SECOND SET OF
 CALCULATIONS WERE *PHOTO-COPIES* OF THE FIRST SET.
 PLEASE SEE FLORIDA BUILDING CODE 13-101.1.1.1, FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES
 471.025.
 PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED ON
 SHEET.
  
 16) NOTE: PLEASE PROVIDE THE MINIMUM DESIGNATED EGRESS
 PATHS AND MINIMUM PHOTO-METRIC LEVELS FOR THESE SAME
 EGRESS DESIGNATION PATHS AS REQUIRED PER NFPA-101 7.8
 AND 7.9.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-33.004.
 FBC ADMIN SECTION106.1.2, 106.3.5.1.2
  
 17) NOTE: PLEASE CLARIFY LIGHTING NOTE #2 WITH RESPECT
 TO *DIMMING* LIGHTING IN BATHROOMS.
 LS 101 7.8.
 FBC 106.1.2
  
 18) NOTE: PLEASE CLARIFY HOW PANEL *CC* MEETS 110.26,
 110.11, 240.24D, 110.3, 90.7.
 PLEASE PROVIDE MORE INFORMATION ON CLEARANCES FOR
 EQUIPMENT AND IF THIS PANEL IS LOCATED NEAR FLOOR WHICH
 IN A KITCHEN WOULD PLACE THIS PANEL NOT ONLY IN A WET
 AREA BUT ALSO NEAR DETERIORATING FACTORS IF NOT LISTED
 FOR THE LOCATION OR ENVIRONMENT INSTALLED.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
  
 19) NOTE: PLEASE CLARIFY HOW THE LOAD IN THE PANEL
 SCHEDULE ON SHEET E3.1 IS LOWER THAN THE LOAD ON THE
 EQUIPMENT PLANS FOR THE SAME PANEL.
 PLEASE COORDINATE.
 240, 408.4, 220, 215, ETC.
 FBC 106.1.2 COORDINATION.
  
 20) NOTE: PLEASE KNOW AS FOR INFORMATIONAL PURPOSE
 ONLY. ALL LOW VOLTAGE SYSTEMS SUCH AS PHONE, CATV, AND
 DATA ETC ARE REQUIRED TO BE UNDER SEPARATE PERMITS. THE
 PLANS MAY CONTAIN THIS LOW VOLTAGE INFORMATION AND ANY
 LV PERMIT APPLICATIONS MAY REFERENCE THE BASE PLANS
 ONCE ISSUED FOR PERMIT.
 ANY LOW VOLTAGE NOT INCLUDED ON BASE BUILD OUT PLANS
 WILL REQUIRE SEPARATE PLANS.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE DO NOT
 HESITATE IN CONTACTING THIS REVIEWER.
  
 21) NOTE: PLEASE KNOW AS PLANS ARE *PROVIDE PROVIDER*
 STAMPED AND REVIEWED PER FS553.791, PLANS MAY NOT BE
 STAMPED WITH *REDLINES* OR *PROVISOS* FOR CONDITIONS OF
 PERMIT ISSUANCE.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2008-10-16 Cont ID  
Sent By mawillia Date 2008-10-16 Time 13:22 Rev Time 0.00
Received By mawillia Date 2008-10-16 Time 13:09 Sent To  
Notes
2008-10-16 13:22:32*****REVSION, PROVISO*****
  
 REVISED PLAN SHEET A1.1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-07-30 Cont ID  
Sent By mwennerg Date 2008-07-30 Time 15:48 Rev Time 0.00
Received By mwennerg Date 2008-07-30 Time 15:48 Sent To  
Notes
2008-07-30 15:48:58REVISION DATED 5/30/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-05-16 Cont ID  
Sent By mwennerg Date 2008-05-16 Time 15:05 Rev Time 0.00
Received By mwennerg Date 2008-05-16 Time 15:05 Sent To  
Notes
2008-05-16 15:06:14PLANS STAMPED, SIGNED AND DATED FOR CAPT. WILLIAMS

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-04-21 Cont ID  
Sent By mawillia Date 2008-04-21 Time 15:11 Rev Time 0.00
Received By mawillia Date 2008-04-21 Time 14:23 Sent To  
Notes
2008-04-21 14:54:41*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED, HOWEVER THE APPROPIATE PLAN SHEETS TO
 BE FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-03-19 Cont ID  
Sent By mawillia Date 2008-03-19 Time 18:33 Rev Time 0.00
Received By mawillia Date 2008-03-19 Time 17:02 Sent To  
Notes
2008-03-19 17:05:58*****DENIED*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 06.PLEASE PROVIDE FLAME SPREAD DETAILS FOR THE ENTRY
 CANOPY.
  
 07.A DOOR NORMALLY REQUIRED TO BE KEPT CLOSED SHALL
 BE SELF-CLOSING OR AUTOMATIC CLOSING IN ACCORDANCE WITH
 7.2.1.8.2 OF NFPA 101.
  
 09.SPECIFY INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS.INTERIOR WALL AND CEILING FINISH
 MATERIALS SHALL BE CLASS A OR CLASS B IN GENERAL
 ASSEMBLY AREA HAVING AN OCCUPANT LOADS OF MORE THAN
 300.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE APPROPIATE PLAN SHEET
 OR IN THE SPECIFICATIONS) EACH COMMENT WAS ADDRESSED
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-02-05 Cont ID  
Sent By mwennerg Date 2008-02-05 Time 13:55 Rev Time 0.00
Received By mwennerg Date 2008-02-05 Time 13:55 Sent To  
Notes
2008-02-05 14:00:19***DENIED***
  
 1) OK
  
 2) OK
  
 3) OK
  
 4) OK
  
 5) OK
  
 6) PLEASE PROVIDE INFORMATION FOR THIS PLAN REVIEW.
  
 7) UNDERSTOOD. PLEASE PROVIDE APPLICABLE INFORMATION IN
 DOOR SCHEDULE.
  
 8) OK
  
 9) PLEASE SEE PREVIOUS COMMENT REGARDING MINIMUM
 INTERIOR FINISH CLASSIFICATION FOR WALLS AND CEILING.
 REFER TO NFPA 101, SEC. 12.3.3.3.
  
 10) OK
  
 11) OK
  
 12) OK
  
 13) OK
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-04 Cont ID  
Sent By mawillia Date 2007-10-04 Time 19:39 Rev Time 0.00
Received By mawillia Date 2007-10-04 Time 12:16 Sent To  
Notes
2007-10-04 14:29:10*****DENIED*****
  
  
 01.THE SUITE NUMBER SHALL BE INCLUDED WITH THE
 PROJECT SITE ADDRESS LOCATED IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.ADD TO CODE ANALYSIS UNDER APPLICABLE
 CODES (SHEET T1.1).
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY
 AS NECESSARY FOR SAFE OPERATION.
  
 05.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 SOUTH ROSEMARY AVENUE, DISPLAY THE SUITE NUMBER.AS
 PER WEST PALM BEACH CODE, TENANT SPACE NUMBERS SHALL BE
 NO LESS THA 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
 06.PLEASE PROVIDE FLAME SPREAD DETAILS FOR THE ENTRY
 CANOPY.
  
 07.A DOOR NORMALLY REQUIRED TO BE KEPT CLOSED SHALL
 BE SELF-CLOSING OR AUTOMATIC CLOSING IN ACCORDANCE WITH
 7.2.1.8.2 OF NFPA 101.
  
 08.COMMERCIAL COOKING EQUIPMENT SHALL BE IN
 ACCORDANCE WITH NFPA 96.SEPARATE PLANS AND PERMIT
 WILL BE REQUIRED FOR THE HOOD INSTALLATION AS WELL AS
 THE HOOD SUPPRESSION SYSTEM.
  
 09.SPECIFY INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS.INTERIOR WALL AND CEILING FINISH
 MATERIALS SHALL BE CLASS A OR CLASS B IN GENERAL
 ASSEMBLY AREA HAVING AN OCCUPANT LOAD S OF MORE THAN
 300.
  
 10.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF
 CLASS I OR CLASSII.
  
 11.THE 2002 EDITION NFPA 13 SHALL BE BE REFERENCED
 FOR THE FIRE SPRINKLER INSTALLATION AND/RE-MODEL.
  
 12.THE 2002 EDITION OF NFPA 72 SHALL BE REFERENCED
 FOR THE INSTALLATION/RE-MODEL OF THE FIRE ALARM
 SYSTEM.
  
 13.AS PER LOCAL REQUIREMENTS, DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM.AMEND FIRE ALARM
 GENERAL NOTE 6 ON SHEET F1.1 AND ALSO THE FIRE ALARM
 SEQUENCE OF OPERATIONS ON SHEET F2.1 SECTION 16C 2-3.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLAN OR IN THE
 SPECIFICATIONS) EACH COMMENT WAS ADDRESSED
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2009-02-02 Cont ID  
Sent By kstevens Date 2009-02-02 Time 17:30 Rev Time 0.00
Received By kstevens Date 2009-02-02 Time 17:30 Sent To  
Notes
2009-02-02 17:33:13REVISIONS OK -- SHTS P2.1 & P3.1.

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2009-01-22 Cont ID  
Sent By kstevens Date 2009-01-22 Time 18:54 Rev Time 0.00
Received By kstevens Date 2009-01-22 Time 18:53 Sent To  
Notes
2009-01-22 18:54:51REVISIONS OK -- SHTS P2.1 & P3.1.

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2008-12-19 Cont ID  
Sent By kstevens Date 2008-12-19 Time 10:19 Rev Time 0.00
Received By kstevens Date 2008-12-19 Time 10:19 Sent To  
Notes
2008-12-19 10:19:45DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
  
 1. SHT P2.1 THE REVISIONS ON FILE FOR PUBLIC RECORD
 SHOW REVISIONS 07/25/07, 1, 3, 11/12/07, 4, 5, 6,
 REVISION 7 (DATED 4/7/08), 4/29/08, 5/22/08 & 9 DATED
 5/30/08 BUT THE SHEET SUBMITTED FOR REVISION HAS
 DELETED THE REVISION NUMBERS 7 & 9 FROM THE REVISION
 INDEX AND ADDED 2 REVISION DATED 6/19/08 & 10/20/08
 (INDICATED AS #SK-P1 BUT NOT FOUND). IN ORDER TO REVIEW
 THE REVISIONS, EACH REVISION AFTER REVISION 7 SHALL BE
 INDICATED WITH A REVISION NUMBER AND EACH REVISION
 SHALL BE CLOUDED ON THE FLOOR PLAN AND A REVISION
 NUMBER INDICATED ON EACH CLOUDED REVISION. REVISION 7
 NUMBER SHALL BE INDICATED ON THE REVISION INDEX FOR
 DATE 4/7/08. SECTION 106.1.3.
 FBC-2004 106.1.3 QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 2. SHT P2.1 THE GAS PIPING IS INCORRECT FOR THE 3/4"
 PIPE WITH 68 CFH. PER TABLE 402.4(1) 1" PIPE IS
 REQUIRED. -- THE GAS PIPING IS INCORRECT FOR THE 1 PIPE
 WITH 106 CFH. PER TABLE 402.4(1) 1-1/4" IS REQUIRED.
 THIS IS FOR THE GAS PIPING CHANGED AT THE PATIO
 HEATERS.
  
 3. SHT P3.1 THE REVISIONS ON FILE FOR PUBLIC RECORD
 SHOW REVISIONS 07/25/07, 1, 3, 11/12/07, 4, 5, 6 &
 REVISION 7 (DATED 4/7/08, BUT THE SHEET SUBMITTED FOR
 REVISION HAS DELETED THE REVISION NUMBER 7 FROM THE
 REVISION INDEX AND ADDED 5 REVISIONS DATED 4/29/08,
 5/22/08, 5/30/08, 6/19/08 & 10/20/08 (INDICATED AS
 #SK-P1 BUT NOT FOUND). IN ORDER TO REVIEW THE
 REVISIONS, EACH REVISION AFTER REVISION 7 SHALL BE
 INDICATED WITH A REVISION NUMBER AND EACH REVISION
 SHALL BE CLOUDED ON THE FLOOR PLAN AND A REVISION
 NUMBER INDICATED ON EACH CLOUDED REVISION. REVISION 7
 NUMBER SHALL BE INDICATED ON THE REVISION INDEX FOR
 DATE 4/7/08. SECTION 106.1.3.
 FBC-2004 106.1.3 QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 4. SHT P3.1 SHT P2.1 THE GAS PIPING IS INCORRECT FOR
 THE 3/4" PIPE WITH 68 CFH. PER TABLE 402.4(1) 1" PIPE
 IS REQUIRED. -- THE GAS PIPING IS INCORRECT FOR THE 1
 PIPE WITH 106 CFH. PER TABLE 402.4(1) 1-1/4" IS
 REQUIRED. THIS IS FOR THE GAS PIPING CHANGED AT THE
 PATIO HEATERS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-05-09 Cont ID  
Sent By kstevens Date 2008-05-09 Time 09:57 Rev Time 0.00
Received By kstevens Date 2008-05-09 Time 09:57 Sent To  
Notes
2008-06-03 10:31:30IF GAS PIPING TO BE WELDED, THEN THE WELDING PROCEDURE
 AND WELDERS CERTIFICATIONS ARE REQUIRED AT THE TIME OF
 APPLICATION.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-01-28 Cont ID  
Sent By kstevens Date 2008-01-28 Time 14:20 Rev Time 0.00
Received By kstevens Date 2008-01-28 Time 14:20 Sent To  
Notes
2008-04-23 14:21:39DENIED
 SEE COMMENTS ON PLUMBING REVIEW STOP

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-09-29 Cont ID  
Sent By kstevens Date 2007-09-29 Time 14:16 Rev Time 0.00
Received By kstevens Date 2007-09-29 Time 14:15 Sent To  
Notes
2008-04-23 14:19:19DENIED
 SEE COMMENTS ON PLUMBING REVIEW STOP

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2008-12-10 Cont ID  
Sent By adarroug Date 2008-12-10 Time 16:30 Rev Time 0.00
Received By adarroug Date 2008-12-10 Time 16:30 Sent To P
Notes
2008-12-10 16:31:05TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2008-12-10 Cont ID  
Sent By adarroug Date 2008-12-10 Time 11:07 Rev Time 0.00
Received By adarroug Date 2008-12-10 Time 11:07 Sent To E
Notes
2008-12-10 11:08:23TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2008-11-18 Cont ID  
Sent By adarroug Date 2008-11-18 Time 13:15 Rev Time 0.00
Received By adarroug Date 2008-11-18 Time 13:15 Sent To P
Notes
2008-11-18 13:15:33TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2008-11-18 Cont ID  
Sent By adarroug Date 2008-11-18 Time 13:12 Rev Time 0.00
Received By adarroug Date 2008-11-18 Time 13:12 Sent To E
Notes
2008-11-18 13:12:49TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-11-18 Cont ID  
Sent By adarroug Date 2008-11-18 Time 11:52 Rev Time 0.00
Received By adarroug Date 2008-11-18 Time 11:52 Sent To M
Notes
2008-11-18 11:53:15TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-09-26 Cont ID  
Sent By adarroug Date 2008-09-26 Time 15:10 Rev Time 0.00
Received By adarroug Date 2008-09-26 Time 15:10 Sent To  
Notes
2008-09-26 15:11:21TO "COMM" BD#55

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-09-15 Cont ID  
Sent By adarroug Date 2008-09-15 Time 10:16 Rev Time 0.00
Received By adarroug Date 2008-09-15 Time 10:16 Sent To B
Notes
2008-09-15 10:16:20TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-09-15 Cont ID  
Sent By adarroug Date 2008-09-15 Time 10:08 Rev Time 0.00
Received By adarroug Date 2008-09-15 Time 10:08 Sent To M
Notes
2008-09-15 10:09:09TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-08-28 Cont ID  
Sent By tgordon Date 2008-08-28 Time 08:48 Rev Time 0.00
Received By tgordon Date 2008-08-28 Time 08:48 Sent To E
Notes
2008-08-28 08:49:27TO "ELECT" D.P.

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-08-28 Cont ID  
Sent By tgordon Date 2008-08-28 Time 08:46 Rev Time 0.00
Received By tgordon Date 2008-08-28 Time 08:46 Sent To E
Notes
2008-08-28 08:47:51TO "ELECT"D.P.

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-08-28 Cont ID  
Sent By tgordon Date 2008-08-28 Time 08:40 Rev Time 0.00
Received By tgordon Date 2008-08-28 Time 08:40 Sent To B
Notes
2008-08-28 08:41:30TO "BUILD" JIM W.

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-08-28 Cont ID  
Sent By tgordon Date 2008-08-28 Time 08:33 Rev Time 0.00
Received By tgordon Date 2008-08-28 Time 08:33 Sent To B
Notes
2008-08-28 08:34:17TO "BUILD" JIM W.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-08-14 Cont ID  
Sent By adarroug Date 2008-08-14 Time 16:06 Rev Time 0.00
Received By adarroug Date 2008-08-14 Time 16:06 Sent To B
Notes
2008-08-14 16:06:45TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-07-24 Cont ID  
Sent By adarroug Date 2008-07-24 Time 08:20 Rev Time 0.00
Received By adarroug Date 2008-07-24 Time 08:20 Sent To  
Notes
2008-07-24 08:27:41TO "COMM" BD#10--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-07-03 Cont ID  
Sent By shill Date 2008-07-03 Time 16:19 Rev Time 0.00
Received By shill Date 2008-07-03 Time 16:19 Sent To  
Notes
2008-07-03 16:19:54TO "COMM" BD#17--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 09:11 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 09:11 Sent To  
Notes
2008-05-16 09:12:13TO "COMM" BD#39/PLANS ON RACK--1 BOX***PRIVATE
 PROVIDER***3RD SET OF PLANS NEED TO BE STAMPED BY ALL
 TRADES.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-07 Cont ID  
Sent By adarroug Date 2008-05-07 Time 11:51 Rev Time 0.00
Received By adarroug Date 2008-05-07 Time 11:51 Sent To  
Notes
2008-05-07 11:58:47TO "COMM" BD#8**PRIVATE PROVIDER**/PLANS ON RACK--3
 ROLLS, 3 BINDERS, 1 BOX W/2 BINDERS AND 1 FOLDER

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-17 Cont ID  
Sent By adarroug Date 2008-04-17 Time 08:33 Rev Time 0.00
Received By adarroug Date 2008-04-17 Time 08:33 Sent To  
Notes
2008-04-17 08:34:29TO "COMM" BD#41/PLANS ON RACK--3 ROLLS, 2 BINDERS AND 1
 LARGE FOLDER***PRIVATE PROVIDER****

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-07 Cont ID  
Sent By adarroug Date 2008-03-07 Time 15:59 Rev Time 0.00
Received By adarroug Date 2008-03-07 Time 15:59 Sent To  
Notes
2008-03-07 16:10:17*****PRIVATE PROVIDER****
  
  
 TO "COMM" BD#12/PLANS ON RACK--2 ROLLS AND 1 BOX
2008-03-04 14:35:193/3/08 WHEN PLANS ARE RESUBMITTED, PLEASE ADD LETTER
 FROM HGA STRUCTURAL ENGINEERS TO THE RESUBMITTAL
 PACKAGE.THE LETTER (DATED 2/29/08) IS WITH AISHA.RB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-22 Cont ID  
Sent By adarroug Date 2008-01-22 Time 13:19 Rev Time 0.00
Received By adarroug Date 2008-01-22 Time 13:19 Sent To  
Notes
2008-01-22 13:24:20TO "COMM" BD#38--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-05 Cont ID  
Sent By mawillia Date 2007-10-04 Time 12:16 Rev Time 0.00
Received By lmartine Date 2007-09-24 Time 11:40 Sent To  
Notes
2007-09-24 11:41:12TO "COMM" BD#43--PRIVATE PROVIDER--

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 18:04 Rev Time 0.00
Received By rregueir Date 2008-11-22 Time 18:04 Sent To PC
Notes
2008-11-22 18:04:53REVISED M1.1

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2008-09-24 Cont ID  
Sent By rregueir Date 2008-09-24 Time 15:22 Rev Time 0.00
Received By rregueir Date 2008-09-24 Time 13:09 Sent To PC
Notes
2008-09-24 15:22:26PAGES M1.1 AND M2.1 REVISED 9/9/08

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-08-08 Cont ID  
Sent By rregueir Date 2008-08-08 Time 10:20 Rev Time 0.00
Received By rregueir Date 2008-08-08 Time 08:38 Sent To B
Notes
2008-08-08 10:20:37REVISED M1.1 DATED 7/7/08

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-05-16 Cont ID  
Sent By rregueir Date 2008-05-16 Time 14:34 Rev Time 0.00
Received By rregueir Date 2008-05-16 Time 14:33 Sent To  
Notes
2008-05-16 14:34:16ALL PROPERLY SIGNED AND DATED AFFIDAVITS FOR MECHANICAL
 PAGES HAVE BEEN PROVIDED.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-05-12 Cont ID  
Sent By rregueir Date 2008-05-12 Time 14:03 Rev Time 0.00
Received By rregueir Date 2008-05-12 Time 13:52 Sent To  
Notes
2008-05-12 14:02:47THE PRIVATE PROVIDER AFFIDAVIT FOR MECHANICAL PLANS
 DATED 2/21/08 ARE NOT ATTACHED TO PLANS. UPON SEARCHING
 OLD DOCUMENTATION WHICH WAS RETURNED WITH THIS
 SUBMITTAL, ONE ORIGINAL, CORRECTLY DATED AFFIDAVIT WAS
 FOUND. A SECOND ORIGINAL AFFIDAVIT IS NEEDED TO
 COMPLETE TWO IDENTICAL PERMIT SETS OF PLANS AND SATISFY
 THE AUDIT REQUIREMENTS OF FS 553.791. PER A PHONE
 CONVERSATION WITH CYNTHIA FUENTES OF CAPRI ENGINEERING,
 A SECOND AFFIDAVIT WILL BE MAILED TO THIS OFFICE IN
 ORDER TO FACILITATE A PASSED AUDIT. THIS AUDIT IS ON
 HOLD PENDING RECEIPT OF THE MISSING AFFIDAVIT AND WILL
 BE PLACED IN A TEMPORARY FAILED STATUS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-04-28 Cont ID  
Sent By rregueir Date 2008-04-23 Time 11:20 Rev Time 0.00
Received By rregueir Date 2008-04-23 Time 10:17 Sent To  
Notes
2008-04-23 13:57:10REVIEW #: 4TH
 ACTION: PASSED
  
 PLANS AND SUBMITTALS HAVE BEEN AUDITED FOR COMPLIANCE
 WITH FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS, FBC CH.1
 AS AMENDED BY THE CITY OF WEST PALM BEACH AND FS
 553.791.
  
 ENERGY CALCULATIONS AS SUBMITTED WERE NOT CONSIDERED
 FOR COMPLIANCE WITH THE MECHANICAL PROVISIONS OF FBCB
 CHAPTER 13. EXISTING BUILDINGS NOT MEETING THE
 DEFINITION OF A RENOVATION (FBCB 13-202) IN WHICH NEW
 HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING
 SYSTEMS ARE INSTALLED ARE REQUIRED TO MEET THE BASIC
 PRESCRIPTIVE MINIMUM EFFICIENCIES LISTED IN THIS CODE
 FOR THE SYSTEM(S) BEING CHANGED IN ACCORDANCE WITH FBCB
 13-400.0.C.4. THIS REQUIREMENT HAS BEEN DEMONSTRATED ON
 THE PLANS FOR MECHANICAL SYSTEMS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-03-17 Cont ID  
Sent By rregueir Date 2008-03-17 Time 10:27 Rev Time 0.00
Received By rregueir Date 2008-03-17 Time 09:57 Sent To  
Notes
2008-03-17 10:27:52REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 ALL PREVIOUS REVIEW COMMENTS HAVE BEEN ADEQUATELY
 ADDRESSED. HOWEVER, REVIEW CANNOT BE PASSED AT THIS
 TIME. THESE PLANS HAVE BEEN SUBMITTED UNDER THE PRIVATE
 PROVIDER PROVISIONS OF FS 553.791. AN AFFIDAVIT WAS
 SUBMITTED TO THIS DEPARTMENT FOR THE REVIEW OF THE
 MECHANICAL SHEETS AS REQUIRED BY 553.791(6). HOWEVER,
 THE AFFIDAVIT, WHILE NOTARIZED, WAS NOT SIGNED BY THE
 RESPONSIBLE PLAN REVIEWER AS REQUIRED BY THIS SECTION.
 IT IS NOT CLEAR WHAT WAS BEING NOTARIZED, SINCE THERE
 WAS NO SIGNATURE ON THE AFFIDAVIT.
  
 THIS SHEET IS BEING RETAINED BY THIS OFFICE FOR
 SUBMITTAL TO THE PROPER AUTHORITIES FOR INVESTIGATION
 AS A PROHIBITED ACT IN ACCORDANCE WITH FS 117.107(3): A
 NOTARY PUBLIC MAY NOT AFFIX HIS OR HER SIGNATURE TO A
 BLANK FORM OF AFFIDAVIT OR CERTIFICATE OF
 ACKNOWLEDGMENT AND DELIVER THAT FORM TO ANOTHER PERSON
 WITH THE INTENT THAT IT BE USED AS AN AFFIDAVIT OR
 ACKNOWLEDGMENT.
  
 PLEASE RESUBMIT PLANS WITH A CORRECTLY COMPLETED
 AFFIDAVIT FOR VERIFICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-02-05 Cont ID  
Sent By rregueir Date 2008-02-05 Time 17:18 Rev Time 0.00
Received By rregueir Date 2008-02-04 Time 11:28 Sent To  
Notes
2008-02-05 17:19:37REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 5: OK
  
 6. ACCESS PANELS MUST BE LARGE ENOUGH TO ALLOW SERVICE
 OR REPLACEMENT OF THE APPLIANCE WITHOUT REMOVING
 ELEMENTS OF PERMANENT CONSTRUCTION IN ACCORDANCE WITH
 FBC, M 306.1. ARE ACCESS PANELS LARGE ENOUGH TO ALLOW
 APPLIANCE TO BE REPLACED? THIS ITEM MAY BE COORDINATED
 WITH FIELD INSPECTOR.
  
 7 THROUGH 9: OK
  
 10. OK. NOTE: GREASE DUCT MANUFACTURER?S INSTALLATION
 INSTRUCTIONS ARE REQUIRED TO BE ON SITE FOR INSPECTION.
 ALSO, PROVIDE INFORMATION ON HOW THIS LISTED PRODUCT IS
 TO BE CONNECTED TO THE EXISTING GREASE DUCT IN A MANNER
 WHICH WILL MAINTAIN ITS LISTING. IS THERE A PRODUCT
 FROM THE MANUFACTURER WHICH FACILITATES THIS
 TRANSITION/CONNECTION? BASED ON A CONVERSATION WITH
 METAL-FAB, THEY MAKE SUCH A TRANSITION FOR THEIR G4
 DUCT BUT NOT FOR THE SPECIFIED G2 DUCT. A SITE-SPECIFIC
 DETAIL IN CONJUNCTION WITH AN ENGINEERING JUDGMENT FROM
 THE MANUFACTURER MAY BE ABLE TO RESOLVE THIS ISSUE.
 THIS COULD BE A PROVISO ITEM TO BE ADDRESSED PRIOR TO
 INSPECTION IF NECESSARY.
  
 11. OK. THROUGH PENETRATION FIRESTOP SYSTEM UL
 INSTALLATION DETAIL MAY BE SHOWN ON PLANS OR PROVIDED
 IN FIELD FOR INSPECTION.
  
 12. GREASE DUCT SUPPORT DETAIL #7 ON M3.1 IS NOT IN
 CONFORMANCE WITH SUPPORT DETAIL FROM MANUFACTURER?S
 INSTALLATION INSTRUCTIONS. SUPPORTS SHALL BE IN
 ACCORDANCE WITH MANUFACTURER?S INSTALLATION
 INSTRUCTIONS AND LISTING PER FBC, M 304.1. SEE
 EXCEPTION TO FBC, M 506.3.1.1.
  
 13 AND 14: OK
  
 15. PRODUCT APPROVAL WITH APPROVED INSTALLATION
 INSTRUCTIONS SHALL BE PROVIDED WITH PERMIT
 DOCUMENTATION. PRODUCT APPROVALS SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL IN ACCORDANCE
 WITH FBC 106.3.3 (LOCAL AMENDMENT).
  
 16. OK
  
 17. THIS COMMENT WAS NOT ADDRESSED. AHU #1 STILL SHOWS
 A 3 HP MOTOR WHILE THE MODEL NUMBER OF THE APPLIANCE
 INDICATES A 5 HP MOTOR. ALSO, THE MOTOR RATINGS ON AHU4
 AND AHU 5 ARE STILL IN EXCESS OF THE HP ALLOWED IN
 TABLE 13-410.1.1.1. THE MAXIMUM HP ALLOWED FOR THIS
 EQUIPMENT IS 1.2 HP PER 1000 CFM. THEREFORE THE MAXIMUM
 MOTOR NAMEPLATE RATING ALLOWED FOR THESE UNITS BASED ON
 THE CFM SHOWN ON THE EQUIPMENT SCHEDULE WOULD BE 4.62
 HP. PLEASE ADDRESS THIS COMMENT AND RESUBMIT.
  
 18. METHOD B CALCULATIONS ARE NOT AN OPTION TO
 DEMONSTRATE COMPLIANCE FOR THIS PROJECT IN ACCORDANCE
 WITH FBC 13-400.0.C.4. HOWEVER, WITH THE EXCEPTION OF
 COMMENT #17 ABOVE, THE MATERIALS AND SYSTEMS SHOWN MEET
 THE MINIMUM PRESCRIPTIVE EFFICIENCIES REQUIRED BY THIS
 SECTION. ONCE COMMENT #17 IS ADDRESSED, CODE COMPLIANCE
 WILL HAVE BEEN DEMONSTRATED ON THE PLANS. THEREFORE,
 THE METHOD B CALCULATIONS PROVIDED WILL NOT BE REVIEWED
 IN RELATION TO MECHANICAL SYSTEMS.
  
 19. OK. NOTE: THIS COMMENT NO LONGER APPLICABLE, SEE
 COMMENT #18 ABOVE.
  
 20 AND 21: OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-01 Cont ID  
Sent By rregueir Date 2007-10-01 Time 08:52 Rev Time 0.00
Received By rregueir Date 2007-09-28 Time 17:42 Sent To  
Notes
2007-09-28 18:15:07REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG A3.1: REGARDING EQUIPMENT SUPPORT DETAIL #2, IF
 ROOFING MATERIALS EXTEND UNDER EQUIPMENT, RAISED
 EQUIPMENT SUPPORTS SHALL PROVIDE MINIMUM CLEARANCE
 HEIGHT IN ACCORDANCE WITH FBC TABLE 1509.7.
  
 2. PG A3.1: WHAT IS THE HEIGHT OF EXISTING PARAPET WALL
 ADJACENT TO NEW GREASE EXHAUST FAN? THE MINIMUM
 HORIZONTAL DISTANCE BETWEEN VERTICAL DISCHARGE FANS AND
 PARAPET-TYPE BUILDING STRUCTURES SHALL BE AT LEAST 10
 FEET UNLESS SUCH STRUCTURES ARE LOWER THAN THE TOP OF
 THE FAN DISCHARGE OPENING. IF THE FAN DISCHARGE OPENING
 IS HIGHER THAN SUCH STRUCTURE THE MINIMUM DISTANCE
 SHALL BE TWO FEET. PLEASE PROVIDE AN ELEVATION VIEW
 SHOWING THE HEIGHT OF THE FAN OUTLET AND PARAPET WALL
 AS WELL AS THE DISTANCE BETWEEN THEM TO DEMONSTRATE
 COMPLIANCE WITH FBC,M 506.5.5.
  
 3. PG A3.1: KEY NOTE #7, ANY EXISTING STANDS MAY BE
 USED AS-IS PROVIDED THE NEW EQUIPMENT IS ATTACHED TO
 MEET WIND LOADS IN ACCORDANCE WITH FBC,M 301.13 AND FBC
 CH.16. HOWEVER, ANY NEW EQUIPMENT INSTALLED ON NEW
 STANDS SHALL ALSO MEET THE CLEARANCE REQUIREMENTS OF
 FBC TABLE 1509.7.
  
 4. PG M1.1: MAU-1 IS SHOWN ABOVE THE WALK-IN COOLER.
 SERVICE ACCESS FOR MAU-1 WILL BE ABOVE THE COOLER. ARE
 THE COOLER CEILING PANELS STRUCTURALLY SOUND FOR THE
 PURPOSE OF BEING A WALKING SURFACE FOR SERVICE ACCESS?
 IF SO, PROVIDE DETAIL SHOWING SAME. ALSO, IF COOLER IS
 TO SERVE A SERVICE ACCESS, GUARDS ARE REQUIRED IN
 ACCORDANCE WITH FBC,M 304.10.
  
 5. PG FS-13: FREEZER/COOLER DETAIL INDICATES THIS IS
 FOR AN OUTDOOR INSTALLATION. PG M1.1 SHOWS THE
 FREEZER/COOLER INDOORS. PLEASE CLARIFY. FBC,M 304.1.
 ALSO, PG FS-13 CALLS FOR 3/4 INCH PLYWOOD IN
 FREEZER/COOLER CEILING PANELS. AS THIS BUILDING IS OF
 TYPE IB CONSTRUCTION, PLEASE SHOW COMPLIANCE WITH FBC
 603.1.
  
 6. PG M1.1: AHU-2 IS ABOVE A GYPSUM BOARD CEILING.
 ACCESS FOR SERVICE OR REPLACEMENT IS REQUIRED WITHOUR
 REMOVING ELEMENTS OF PERMANENT CONSTRUCTION IN
 ACCORDANCE WITH FBC,M 306.1. PLEASE SHOW HOW ACCESS TO
 THIS EQUIPMENT IS TO BE PROVIDED.
  
 7. PG M1.1: AHU-3, MOTORIZED OUTDOOR AIR DAMPER IS
 LOCATED ABOVE A GYPSUM BOARD CEILING. PROVIDE ACCESS IN
 ACCORDANCE WITH FBC,M 306.1 AND SPECIFICATION 15A 1-18
 ON PG M4.1.
  
 8. SHOW LOCATION OF DUCT MOUNTED SMOKE DETECTORS ON ALL
 AHU'S TO DEMONSTRATE COMPLIANCE WITH FBC,M 606.3.
 DETECTORS ARE TO MONITOR THE ENTIRE AIRFLOW AND BE
 ACCESSIBLE FOR INSPECTION AND MAINTENANCE.
  
 9. PROVIDE OUTDOOR AIR CALCULATIONS SHOWING OCCUPANCY
 CLASSIFICATION, OCCUPANT LOADS AND CFM REQUIRED BASED
 ON FBC,M TABLE 403.3. THIS SHOULD BE INCLUDED AS PART
 OF SIGNED AND SEALED PLANS. FBC 106.1.2.
  
 10. PG M1.2: NOTE #20 CALLS FOR GREASE DUCT (SHOWN ON
 M1.1) TO BE PITCHED MIN. 1/4 INCH PER FOOT. WHEN
 HORIZONTAL DUCTS EXCEED 75 FEET IN LENGTH, AS THEY DO
 IN THIS APPLICATION, THE SLOPE SHALL BE NOT BE LESS
 THAN 1 INCH PER FOOT IN ACCORDANCE WITH FBC,M 506.3.7.
 GIVEN THE DISTANCE AS SHOWN BETWEEN KEH-1 OUTLET TO THE
 RISER LOCATION (PLAN NOTE #33 ON M1.1), A RISE OF OVER
 100 INCHES WOULD BE REQUIRED TO MAINTAIN THE MINIMUM
 SLOPE. PLEASE VERIFY THAT THIS IS POSSIBLE AND ADJUST
 THE DESIGN, IF NECESSARY, TO SHOW COMPLIANCE WITH THIS
 SECTION.
  
 11. PG M1.2: CHILLED WATER PIPE PENETRATIONS OF FIRE
 RESISTANCE RATED WALL ASSEMBLY ARE REQUIRED TO BE
 PROTECTED WITH A THROUGH-PENETRATION FIRESTOP SYSTEM IN
 ACCORDANCE WITH FBC SEC.712. PROVIDE DETAIL WHICH
 CORRESPONDS WITH THE LISTED ASSEMBLY TO BE USED.
  
 12. PG M3.1: PROVIDE DETAIL SHOWING HOW GREASE DUCTS
 ARE TO BE SUPPORTED, INCLUDING ATTACHMENTS TO
 STRUCTURE, IN ACCORDANCE WITH FBC,M 506.3.3 AND FBC
 106.1.2.
  
 13. TYPE I HOODS SHALL BE SECURED IN PLACE BY
 NONCOMBUSTIBLE SUPPORTS. ALL TYPE I AND TYPE II HOOD
 SUPPORTS SHALL BE ADEQUATE FOR THE APPLIED LOAD OF THE
 HOOD, THE UNSUPPORTED DUCTWORK, THE EFFLUENT LOADING,
 AND THE POSSIBLE WEIGHT OF PERSONNEL WORKING IN OR ON
 THE HOOD. PROVIDE DETAIL FOR SUPPORTS ON TYPE I AND
 TYPE II HOODS. FBC,M 507.6
  
 14. PG M3.1: DETAIL 5 INDICATES "PREFABRICATED
 EQUIPMENT SUPPORT RAILS." ANY PRE-ENGINEERED EQUIPMENT
 STANDS ARE CONSIDERED STRUCTURAL COMPONNTS UNDER FAC
 RULE 9B-72 AND AS SUCH ARE SUBJECT TO THE FLORIDA
 PRODUCT APPROVAL SYSTEM. PROVIDE PRODUCT APPROVAL FOR
 THE SPECIFIC STAND(S) TO BE USED IN ALL NEW
 APPLICATIONS, INCLUDING THOSE MENTIONED IN COMMENT #3.
 FOR MORE INFORMATION ON THE FLORIDA PRODUCT APPROVAL
 SYSTEM PLEASE VISIT: WWW.FLORIDABUILDING.ORG
  
 15. PG. M3.1: WALL LOUVERS ARE CLASSIFIED AS PANEL
 WALLS UNDER FAC RULE 9B-72 AND AS SUCH ARE SUBJECT TO
 THE FLORIDA PRODUCT APPROVAL SYSTEM. PROVIDE PRODUCT
 APPROVAL FOR THE SPECIFIC LOUVER(S) TO BE USED IN ALL
 NEW APPLICATIONS. FOR MORE INFORMATION ON THE FLORIDA
 PRODUCT APPROVAL SYSTEM PLEASE VISIT:
 WWW.FLORIDABUILDING.ORG
  
 16. PG M3.1: DETAIL 5, CONNECTIONS TO SIDE-INLET
 UTILITY FANS SHALL BE FLANGED, GASKETED AND BOLTED TO
 THE INLET. PLEASE SHOW HOW DUCT IS TO BE CONNECTED TO
 EXHAUST FAN. FBC,M 506.3.2.2
  
 17. PG M2.1: AHU-4 AND AHU-5, THE HP RATING ON THESE
 FAN MOTORS EXCEEDS THE MAXIMUM ALLOWABLE MOTOR POWER IN
 ACCORDANCE WITH FBC TABLE 13-410.1.1.1. ALSO, AHU-1
 SHOWS A 3 HP MOTOR, BUT THE MODEL NUMBER SHOWN ON
 SCHEDULE INDICATES THIS SIZE UNIT WOULD HAVE A 5 HP
 MOTOR. PLEASE VERIFY MODEL NUMBERS AND SHOW ALL THREE
 UNITS TO BE IN COMPLIANCE WITH THIS SECTION.
  
 18. ENERGY CALCULATIONS: A METHOD A COMPLIANCE FORM HAS
 BEEN SUBMITTED FOR THIS PROJECT. HOWEVER, AS THIS IS
 NOT A WHOLE NEW BUILDING, COMPLIANCE WITH FBC CHAPTER
 13 SHALL BE DEMONSTRATED IN ACCORDANCE WITH FBC
 13-400.0.C.4. EXISTING BUILDINGS NOT MEETING THE
 DEFINITION OF A RENOVATION (SEE DEFINITION IN SEC.202)
 IN WHICH NEW HEATING, COOLING, WATER HEATING,
 ELECTRICAL OR LIGHTING SYSTEMS ARE INSTALLED SHALL MEET
 THE BASIC PRESCRIPTIVE MINIMUM EFFICIENCIES LISTED IN
 THIS CODE FOR THE SYSTEM(S) BEING CHANGED.
  
 19. IF A CODE COMPLIANCE FORM IS TO BE SUBMITTED FOR
 THIS PROJECT, THE PERSON PREPARING THE COMPLIANCE
 CALCULATION SHALL CERTIFY THAT THE CALCULATION, OR
 AMENDMENTS THERETO, IS TRUE AND ACCURATE AND
 DEMONSTRATES THAT THE BUILDING IS IN COMPLIANCE WITH
 THE REQUIREMENTS OF CHAPTER 13 OF THIS CODE. ORIGINAL
 SIGNATURE AND SEAL IS REQUIRED ON THE CERTIFICATIONS
 PAGE OF EACH SET OF CALCULATIONS. FBC 13-400.3.ABC.2.
 ONE SET OF CALCULATIONS WHICH WERE SUBMITTED CONTAINS
 NO SEAL AND PHOTOCOPIED SIGNATURES. ALSO, THE PARTY
 RESPONSIBLE UNDER SUBSECTIONS 471.003 AND 481.228 AND
 CHAPTER 489, FLORIDA STATUTES, FOR THE DESIGN AND
 SPECIFICATION OF EACH BUILDING SYSTEM SHALL CERTIFY
 THAT THE PLANS AND SPECIFICATIONS FOR THAT SYSTEM
 COMPLY WITH THE REQUIREMENTS OF CHAPTER 13 OF THIS CODE
 (SEE ALSO SECTION 13-103.2). THIS INFORMATION SHALL
 ALSO BE INCLUDED ON THE CERTIFICATIONS PAGE IN
 ACCORDANCE WITH THIS SECTION.
  
 20. M1.1: ROOM 126 (MECHANICAL ROOM) HAS TWO 196,000
 BTU/H GAS WATER HEATERS. DETAIL 9 ON PG P5.1 INDICATES
 EXHAUST AND INTAKE FOR WATER HEATERS ARE TO BE
 INSTALLED BY MECHANICAL. NO INFORMATION COULD BE FOUND
 IN MECHANICAL OR PLUMBING PLANS SHOWING ANY PROVISIONS
 FOR VENTING COMBUSTION OR DILLUTION AIR FOR THESE GAS
 APPLIANCES. SHOW MEANS OF VENTING AND COMBUSTION AIR IN
 ACCORDANCE WITH FBC,FG SEC. 304, PROVIDE CALCULATIONS
 IF COMBUSTION AIR IS REQUIRED UNDER THIS SECTION. IF A
 LISTED APPLIANCE IS BEING USED WITH INTEGRAL OR DIRECT
 VENTS, PROVIDE SUBMITTAL WITH INSTALLATION
 INSTRUCTIONS.
  
 21. EACH SHEET OF PLANS AND PRINTS WHICH MUST BE SEALED
 UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL BE
 SEALED, SIGNED AND DATED BY THE PROFESSIONAL ENGINEER
 IN RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET.
 IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) PLEASE CORRECT EACH SHEET SIGNED/SEALED
 BY AN ENGINEER WHICH IS MISSING THIS INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 8 Status   Date   Cont ID  
Sent By kstevens Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 7 Status F Date 2008-12-19 Cont ID  
Sent By kstevens Date 2008-12-19 Time 10:18 Rev Time 0.00
Received By kstevens Date 2008-12-18 Time 16:53 Sent To  
Notes
2008-12-19 10:19:16DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. SHT P2.1 THE REVISIONS ON FILE FOR PUBLIC RECORD
 SHOW REVISIONS 07/25/07, 1, 3, 11/12/07, 4, 5, 6,
 REVISION 7 (DATED 4/7/08), 4/29/08, 5/22/08 & 9 DATED
 5/30/08 BUT THE SHEET SUBMITTED FOR REVISION HAS
 DELETED THE REVISION NUMBERS 7 & 9 FROM THE REVISION
 INDEX AND ADDED 2 REVISION DATED 6/19/08 & 10/20/08
 (INDICATED AS #SK-P1 BUT NOT FOUND). IN ORDER TO REVIEW
 THE REVISIONS, EACH REVISION AFTER REVISION 7 SHALL BE
 INDICATED WITH A REVISION NUMBER AND EACH REVISION
 SHALL BE CLOUDED ON THE FLOOR PLAN AND A REVISION
 NUMBER INDICATED ON EACH CLOUDED REVISION. REVISION 7
 NUMBER SHALL BE INDICATED ON THE REVISION INDEX FOR
 DATE 4/7/08. SECTION 106.1.3.
 FBC-2004 106.1.3 QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 2. SHT P2.1 THE GAS PIPING IS INCORRECT FOR THE 3/4"
 PIPE WITH 68 CFH. PER TABLE 402.4(1) 1" PIPE IS
 REQUIRED. -- THE GAS PIPING IS INCORRECT FOR THE 1 PIPE
 WITH 106 CFH. PER TABLE 402.4(1) 1-1/4" IS REQUIRED.
 THIS IS FOR THE GAS PIPING CHANGED AT THE PATIO
 HEATERS.
  
 3. SHT P3.1 THE REVISIONS ON FILE FOR PUBLIC RECORD
 SHOW REVISIONS 07/25/07, 1, 3, 11/12/07, 4, 5, 6 &
 REVISION 7 (DATED 4/7/08, BUT THE SHEET SUBMITTED FOR
 REVISION HAS DELETED THE REVISION NUMBER 7 FROM THE
 REVISION INDEX AND ADDED 5 REVISIONS DATED 4/29/08,
 5/22/08, 5/30/08, 6/19/08 & 10/20/08 (INDICATED AS
 #SK-P1 BUT NOT FOUND). IN ORDER TO REVIEW THE
 REVISIONS, EACH REVISION AFTER REVISION 7 SHALL BE
 INDICATED WITH A REVISION NUMBER AND EACH REVISION
 SHALL BE CLOUDED ON THE FLOOR PLAN AND A REVISION
 NUMBER INDICATED ON EACH CLOUDED REVISION. REVISION 7
 NUMBER SHALL BE INDICATED ON THE REVISION INDEX FOR
 DATE 4/7/08. SECTION 106.1.3.
 FBC-2004 106.1.3 QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 4. SHT P3.1 SHT P2.1 THE GAS PIPING IS INCORRECT FOR
 THE 3/4" PIPE WITH 68 CFH. PER TABLE 402.4(1) 1" PIPE
 IS REQUIRED. -- THE GAS PIPING IS INCORRECT FOR THE 1
 PIPE WITH 106 CFH. PER TABLE 402.4(1) 1-1/4" IS
 REQUIRED. THIS IS FOR THE GAS PIPING CHANGED AT THE
 PATIO HEATERS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2008-07-08 Cont ID  
Sent By mperson Date 2008-07-08 Time 11:38 Rev Time 0.00
Received By mperson Date 2008-07-08 Time 11:38 Sent To  
Notes
2008-07-08 11:42:39REVISION #9, SHEETS P1.1, P2.1, P3.2, AND P3.3: "OK".
  
 NOTE: PER ROBERT BROWN'S INSTRUCTIONS THE PRIVATE
 PROVIDER BUILDING PLANS COMPLIANCE AFFIDAVIT FOR PLBG
 SHEETS WAS FILED WITH THE PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-05-09 Cont ID  
Sent By kstevens Date 2008-05-09 Time 09:56 Rev Time 0.00
Received By kstevens Date 2008-05-09 Time 09:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-04-23 Cont ID  
Sent By kstevens Date 2008-04-23 Time 14:09 Rev Time 0.00
Received By kstevens Date 2008-04-18 Time 14:06 Sent To  
Notes
2008-04-23 14:14:41DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODES WPB
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS AUDIT:
  
 ******FROM PREVIOUS AUDIS: (3RD AUDIT)
  
 ********FROM PREVIOUS AUDITS: (4TH AUDIT)
  
 1. OK
 2. OK
  
 3. ALL ARCHITECTURAL SHEETS ARE MISSING REQUIRED
 INFORMATION. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), SIGNED, DATED SEAL, AND THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN
 THE TITLE BLOCK. ALSO THE SEAL APPEARS TO HAVE BEEN
 SIGNED WITH INITIALS. IF THIS IS INDEED THE LEGAL
 SIGNATURE OF THE ARCHITECT OF RECORD, THEN A SIGNED,
 SEALED, NOTORIZED LETTER SHALL BE SUBMITTED SHOWING THE
 LEGAL SIGNATURE OF THE ARCHITECT FOR OUR FILES. FAC
 61G1-16.003, 61G1-16.004(2)(5)(6) & FS 481.219,
 481.2055.
 ****RESPONSE NOTED, BUT THE SIGNED, SEALED, NOTORIZED
 LETTER HAS NOT BEEN SUBMITTED AS REQUESTED.
 ********RESPONSE NOTED, BUT THE SIGNED, SEALED,
 NOTORIZED LETTER HAS NOT BEEN SUBMITTED AS REQUESTED.
  
  
  
 4. OK
 5. OK
 6. OK
  
 7. SHT FS-1 ITEM 86 WATER FILTER SYSTEM SHALL MEET THE
 REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF.
 SPECIFICATIONS SHEETS SHOWING COMPLIANCE. SECTION
 611.1.
 ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS FOR
 THE WATER FILTER HAVE NOT BEEN FOUND. ******RESPONSE
 NOTED, BUT THE MANUF. SPECIFICATIONS FOR THE WATER
 FILTER DO NOT SHOW COMPLIANCE/CERTIFICATION FOR NSF-42.
 THE REQUIREMENTS FOR NSF-42 ARE A REQUIREMENT FOR
 REDUCTION OF CHLORINE, TASTE & ODOR, CHLORAMINE, ZINC
 ETC AS WELL AS BACTERIOSTATIC EFFECTS. NSF-53 IS NOT
 SHOWN TO COMPLY WITH THE REQUIREMENTS OF NSF-42. A
 SEPARATE FILTER CAN BE ADDED TO THE SYSTEM TO COMPLY
 WITH THE REQUIREMENTS OF SECTION 611.1.
 ********RESPONSE NOTED. MANUF. SPECIFICATION SHEETS
 SUBMITTED, BUT FILTER IS NOT INDICATED ON THE PLANS.
 PLEASE SHOW THE FILTER ON FS SHEET OR PLUMBING SHEET.
  
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
  
 22. SHT P3.1 A SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G.OK
 H. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
  
 **********NEW COMMENTS**********
  
 1C. OK
 2C. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE OF THE REQUEST FOR ONE COPY OF THE
 VOIDED SHEETS TO BE SUBMITTED FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-03-08 Cont ID  
Sent By kstevens Date 2008-03-08 Time 10:16 Rev Time 0.00
Received By kstevens Date 2008-03-08 Time 10:16 Sent To  
Notes
2008-03-08 10:48:55DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODES WPB
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS: (3RD REVIEW)
  
 1. OK
 2. OK
  
 3. ALL ARCHITECTURAL SHEETS ARE MISSING REQUIRED
 INFORMATION. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), SIGNED, DATED SEAL, AND THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN
 THE TITLE BLOCK. ALSO THE SEAL APPEARS TO HAVE BEEN
 SIGNED WITH INITIALS. IF THIS IS INDEED THE LEGAL
 SIGNATURE OF THE ARCHITECT OF RECORD, THEN A SIGNED,
 SEALED, NOTORIZED LETTER SHALL BE SUBMITTED SHOWING THE
 LEGAL SIGNATURE OF THE ARCHITECT FOR OUR FILES. FAC
 61G1-16.003, 61G1-16.004(2)(5)(6) & FS 481.219,
 481.2055.
 ****RESPONSE NOTED, BUT THE SIGNED, SEALED, NOTORIZED
 LETTER HAS NOT BEEN SUBMITTED AS REQUESTED.
 ******RESPONSE NOTED, BUT THE SIGNED, SEALED, NOTORIZED
 LETTER HAS NOT BEEN SUBMITTED AS REQUESTED.
  
  
 4. OK
 5. OK
 6. OK
  
 7. SHT FS-1 ITEM 86 WATER FILTER SYSTEM SHALL MEET THE
 REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF.
 SPECIFICATIONS SHEETS SHOWING COMPLIANCE. SECTION
 611.1.
 ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS FOR
 THE WATER FILTER HAVE NOT BEEN FOUND. ******RESPONSE
 NOTED, BUT THE MANUF. SPECIFICATIONS FOR THE WATER
 FILTER DO NOT SHOW COMPLIANCE/CERTIFICATION FOR NSF-42.
 THE REQUIREMENTS FOR NSF-42 ARE A REQUIREMENT FOR
 REDUCTION OF CHLORINE, TASTE & ODOR, CHLORAMINE, ZINC
 ETC AS WELL AS BACTERIOSTATIC EFFECTS. NSF-53 IS NOT
 SHOWN TO COMPLY WITH THE REQUIREMENTS OF NSF-42. A
 SEPARATE FILTER CAN BE ADDED TO THE SYSTEM TO COMPLY
 WITH THE REQUIREMENTS OF SECTION 611.1
  
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
  
 22. SHT P3.1 A SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--NO MANUF. SHEETS
 FOR ITEM #5RICE COOKERS, THE WATER HEATERS, AND THE
 RH UNITS.
 ****RESPONSE NOTED, BUT MANUF. SHEETS ARE NOT
 SUBMITTED.
 ******RESPONSE NOTED, BUT THE RICE COOKER IS NOT LISTED
 AS BEING TESTED FOR THE GAS COMPONETS. THE ONLY LISTING
 SHOWN IS FOR NSF. PER SECTION 301.3. PLEASE SHOW
 LISTING.
  
 H. OK
 23. OK
  
 24. SHT P3.2 GREASE WASTE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. THE ISLAND VENTS SHALL CONNECT TO THE
 DRAIN AT THE LOWEST POINT, AND CLEANOUTS ARE REQUIRED
 ON BOTH VENT LINES. (SEE ATTACHED SHEET). ****RESPONSE
 NOTED, BUT THE RISER DIAGRAM STILL DOES NOT REFLECT THE
 FLOOR PLAN, NOR DOES IT MEET CODE. THERE IS A DRY
 HORIZONTAL VENT UPSTREAM OF FS3 FOR FIXTURE 63. THIS IS
 NOT SHOWN ON THE FLOOR PLAN. ALSO FS1 FOR THE
 CONDENSATE FROM THE WALK IN COOLER IS NOT SHOWN ON THE
 RISER DIAGRAM. SECTIONS 106.1.1, 905.3 & 905.4.
 ******RESPONSE NOTED, BUT THE VENT FOR THE FLOOR SINK
 INDICATED IN COMMENT ABOVE DOES NOT COMPLY WITH CODE
 SECTION 905.4. FLOOR SINK CAN BE CONNECTED ON THE RISE
 OF THE VENT TO WASH THE BASE OF THE VENT.
  
 25. OK
 26. OK
 27. OK
 28. OK
  
 **********NEW COMMENTS**********
  
 1B. ALL PRIVATE PROVIDER AFFIDAVIT PROJECTS REQUIRE THE
 OWNER TO SIGN AN OWNER ACKNOWLEDGEMENT LETTER PER FS
 553.791. THIS SHALL BE SUBMITTED WITH THE PLANS AND
 APPLICATION FOR PERMIT.
 ******RESPONSE NOTED, BUT THE LETTER HAS NOT BEEN
 SUBMITTED.
  
 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
  
 **********NEW COMMENTS**********
  
 1C. THE GAS SYSTEM IS NOW INDICATED AS A 2PSI SYSTEM.
 REGULATORS ARE REQUIRED IN THE SYSTEM TO REDUCE THE
 PRESSURE FROM 2PSI TO .5 PSI PRIOR TO EACH APPLIANCE OR
 GROUP OF APPLIANCES. A SHUT OFF VALVE IS REQUIRED
 UPSTREAM OF EACH REGULATOR WITH A UNION DOWNSTREAM OF
 THE SHUT OFF VALVE. SECTION 409.4. (SHUT OFF VALVES,
 REGULATORS & UNIONS CAN NOT BE LOCATION IN THE
 CEILING).
  
 2C. SUBMIT MANUF. SPECIFICATIONS FOR THE GAS
 REGULATORS. IF THERE ARE VENT LINES ON THE REGULATORS,
 INDICATE MATERIAL FOR VENTS. (NO COMBUSTABLE MATERIALS
 FOR THE VENTS). SHOW ROUTING AND TERMINATION OF VENTS
 IF INSTALLED/REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE OF THE REQUEST FOR ONE COPY OF THE
 VOIDED SHEETS TO BE SUBMITTED FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-01-28 Cont ID  
Sent By kstevens Date 2008-01-28 Time 16:12 Rev Time 0.00
Received By kstevens Date 2008-01-25 Time 16:49 Sent To  
Notes
2008-01-28 16:53:59DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODES WPB
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. THE GREASE INTERCEPTOR SHALL BE INSPECTED AND SIZED
 BY THE UTILITY DEPT. INDUSTRIAL PRE-TREATMENT,
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO,
 (561) 822-2272, E-MAIL [email protected] OR CALVIN
 WILLIAMS (561) 822-2284, E-MAIL [email protected].
 THEIR FAX NUMBER IS (561) 822-2287. A WRITTEN
 DETERMINATION SHEET FROM ENVIRONMENTAL COMPLIANCE SHALL
 BE SUBMITTED WITH THE PLANS SHOWING APPROVAL FOR
 EXISTING AND NEW GREASE INTERCEPTORS. WPB MUNICIPAL
 CODE ARTICLE III SECTION 90-124(7).
 ****RESPONSE NOTED, BUT THE WRITTEN APPROVAL HAS NOT
 BEEN SUBMITTED.
  
 3. ALL ARCHITECTURAL SHEETS ARE MISSING REQUIRED
 INFORMATION. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), SIGNED, DATED SEAL, AND THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN
 THE TITLE BLOCK. ALSO THE SEAL APPEARS TO HAVE BEEN
 SIGNED WITH INITIALS. IF THIS IS INDEED THE LEGAL
 SIGNATURE OF THE ARCHITECT OF RECORD, THEN A SIGNED,
 SEALED, NOTORIZED LETTER SHALL BE SUBMITTED SHOWING THE
 LEGAL SIGNATURE OF THE ARCHITECT FOR OUR FILES. FAC
 61G1-16.003, 61G1-16.004(2)(5)(6) & FS 481.219,
 481.2055.
 ****RESPONSE NOTED, BUT THE SIGNED, SEALED, NOTORIZED
 LETTER HAS NOT BEEN SUBMITTED AS REQUESTED.
  
 4. OK
  
 5. SHT A8.1 DETAIL 9. SUBMIT MANUF SPECIFICATIONS FOR
 THE LAV DRAIN PAN. INDICATE REFERENCE STANDARD FOR LAV.
 SECTIONS 303, 303.1 303.2, & 303.4.
 ****RESPONSE NOTED, BUT THE LAV DRAIN PAN AND GRANITE
 LAV SHALL BE SUBMITTED AS ALTERNATIVE MATERIALS, DESIGN
 & METHODS OF CONSTRUCTION AND EQUIPMENT PER SECTION
 104.1.1 SUBMIT DETAILS AS TO THE FINISH AND POROSITY OF
 THE GRANITE AND INDICATE THE GUAGE OF THE STAINLESS
 STEEL LAV DRAIN PAN. INFORMATION SHALL BE SUBMITTED TO
 THE BUILDING OFFICIAL.
  
 6. OK
  
 7. SHT FS-1 ITEM 86 WATER FILTER SYSTEM SHALL MEET THE
 REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF.
 SPECIFICATIONS SHEETS SHOWING COMPLIANCE. SECTION
 611.1.
 ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS FOR
 THE WATER FILTER HAVE NOT BEEN FOUND.
  
 8. OK
 9. OK
  
 10. SHT FS-2 FOOD SERVICE EQUIPMENT SCHEDULE, ITEM 163
 DOES NOT INDICATE DRAINAGE, AND ITEM 173 INDICATES
 DRAINAGE FOR A STORAGE CABINET. PLEASE CLARIFY. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT THE KITCHEN SPEC BOOK HAS NOT
 BEEN FOUND.
  
 11. SHT FS-4 DETAILS INDICATED SUCH AS THE TRENCH DRAIN
 DETAIL, DRAIN SPECIFICATIONS, SECTION THRU FLOOR
 RECESS, INDIRECT WASTE & AIR GAP. WHERE THESE DESIGNED
 BY THE EQUIPMENT SUPPLIERS? PLEASE CLARIFY. SECTION
 106.1.
 ****RESPONSE NOTED, BUT THE KITCHEN CONSULTANT RESPONSE
 HAS NOT BEEN FOUND.
  
 12. ALL STRUCTURAL SHEETS. THE CERTIFICATE OF
 AUTHORIZATION NUMBER, PRINTED NAME OF THE ENGINEER, AND
 THE LICENSE NUMBER OF THE ENGINEER ARE REQUIRED ON THE
 TITLE BLOCK. ALSO THE PLANS APPEAR TO BE SIGNED WITH
 INITIALS. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ENGINEER, THEN A SIGNED, SEALED, NOTORIZED LETTER SHALL
 BE SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR
 FILES. FAC 61G15-23.002(2) & FS 471.025. ****RESPONSE
 NOTED, BUT THE SIGNED, SEALED, NOTORIZED LETTER HAS NOT
 BEEN SUBMITTED.
  
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
  
 21. SHT P2.1 PLUMBING PLAN NOTES #11 THE GAS PROVIDER
 SUPPLIES THE GAS AT EITHER 2 PSI OR 1/2 PSI, (12" TO
 14" W.C.). PLANS INDICATE 7" W.C. PLEASE CONTACT THE
 GAS PROVIDER AND INDICATE THE INLET PRESSURE PROVIDED.
 SECTION 402.
 ****RESPONSE NOTED, BUT THE INLET PRESSURE HAS BEEN
 INDICATED AS 2PSI AND .5 PSI. PLEASE CONTACT THE GAS
 PROVIDER AND INDICATE PRESSURE PROVIDED AT THE METER.
  
 22. SHT P3.1 A SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - THE LENGTHS OF PIPE ARE NOT
 INDICATED.
 ****RESPONSE NOTED, BUT THE CUT SECTIONS FROM THE METER
 TO THE FIRST RISERS ON BOTH BRANCHES HAVE NO LENGTHS
 INDICATED AS WELL AS THE LENGTH FROM THE BRANCH LINES
 TO THE PATIO HEATERS.
  
 B. OK
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED ONCE
 REQUIREMENT "A" IS ADDRESSED.
 ****RESPONSE NOTED, BUT "A" HAS NOT BEEN COMPLETLY
 ADDRESS AND THE TOTAL DISTANCE FROM THE METER TO THE
 MOST REMOTE OUTLET DOES NOT APPEAR TO BE CORRECT.
 PLEASE RECHECK THE ADDITION.
  
 D. OK
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - SEE COMMENT
 #21.
 ****RESPONSE NOTED, BUT THE DELIVERY PRESSURE CAN BE
 2PSI OR .5 PSI, BUT NOT BOTH. INDICATE THE DELIVERY
 PRESSURE.
  
 F. OK
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--NO MANUF. SHEETS
 FOR ITEM #5RICE COOKERS, THE WATER HEATERS, AND THE
 RH UNITS.
 ****RESPONSE NOTED, BUT MANUF. SHEETS ARE NOT
 SUBMITTED.
  
 H. OK
  
 23. SHT P3.1 GAS RISER DIAGRAM, 2-1/2" REQUIRED FOR
 1078 CFH, 1-1/4" REQUIRED TO EACH WATER HEATER, 2"
 REQUIRED FOR 374 CFH TO 1ST RH, 1" REQUIRED FOR THE
 RICE COOKERS (2) & 1-1/2" REQUIRED TO THE FRYERS. TABLE
 402.4(2) - (IF SCHEDULE 40 PIPE).
 ****RESPONSE NOTED, BUT 3/4" IS STILL SHOWN TO THE RICE
 COOKERS.
  
 24. SHT P3.2 GREASE WASTE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. THE ISLAND VENTS SHALL CONNECT TO THE
 DRAIN AT THE LOWEST POINT, AND CLEANOUTS ARE REQUIRED
 ON BOTH VENT LINES. (SEE ATTACHED SHEET). ****RESPONSE
 NOTED, BUT THE RISER DIAGRAM STILL DOES NOT REFLECT THE
 FLOOR PLAN, NOR DOES IT MEET CODE. THERE IS A DRY
 HORIZONTAL VENT UPSTREAM OF FS3 FOR FIXTURE 63. THIS IS
 NOT SHOWN ON THE FLOOR PLAN. ALSO FS1 FOR THE
 CONDENSATE FROM THE WALK IN COOLER IS NOT SHOWN ON THE
 RISER DIAGRAM. SECTIONS 106.1.1, 905.3 & 905.4.
  
 25. OK
 26. OK
 27. OK
 28. OK
  
 **********NEW COMMENTS**********
  
 1B. ALL PRIVATE PROVIDER AFFIDAVIT PROJECTS REQUIRE THE
 OWNER TO SIGN AN OWNER ACKNOWLEDGEMENT LETTER PER FS
 553.791. THIS SHALL BE SUBMITTED WITH THE PLANS AND
 APPLICATION FOR PERMIT.
  
 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE OF THE REQUEST FOR ONE COPY OF THE
 VOIDED SHEETS TO BE SUBMITTED FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-29 Cont ID  
Sent By kstevens Date 2007-09-29 Time 16:40 Rev Time 0.00
Received By kstevens Date 2007-09-27 Time 16:53 Sent To  
Notes
2007-10-01 09:52:11DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODES WPB
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ROUTE PLANS TO THE STATE OF FLORIDA, DEPT OF
 BUSINESS REGULATION, (DBPR), DIVISION OF HOTEL &
 RESTAURANT FOOD SERVICE LICENSE FOR REVIEW. REVIEWED
 SHEETS SHALL BE INSERTED INTO EACH SET OF PLANS AND THE
 TWO PAGE "SPECIFICATION WORKSHEETS" SHALL BE ATTACHED
 TO THE STAMPED PLANS REVIEWED BY DBPR. SECTION
 102.2.1.
  
 2. THE GREASE INTERCEPTOR SHALL BE INSPECTED AND SIZED
 BY THE UTILITY DEPT. INDUSTRIAL PRE-TREATMENT,
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO,
 (561) 822-2272, E-MAIL [email protected] OR CALVIN
 WILLIAMS (561) 822-2284, E-MAIL [email protected].
 THEIR FAX NUMBER IS (561) 822-2287. A WRITTEN
 DETERMINATION SHEET FROM ENVIRONMENTAL COMPLIANCE SHALL
 BE SUBMITTED WITH THE PLANS SHOWING APPROVAL FOR
 EXISTING AND NEW GREASE INTERCEPTORS. WPB MUNICIPAL
 CODE ARTICLE III SECTION 90-124(7).
  
 3. ALL ARCHITECTURAL SHEETS ARE MISSING REQUIRED
 INFORMATION. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), SIGNED, DATED SEAL, AND THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN
 THE TITLE BLOCK. ALSO THE SEAL APPEARS TO HAVE BEEN
 SIGNED WITH INITIALS. IF THIS IS INDEED THE LEGAL
 SIGNATURE OF THE ARCHITECT OF RECORD, THEN A SIGNED,
 SEALED, NOTORIZED LETTER SHALL BE SUBMITTED SHOWING THE
 LEGAL SIGNATURE OF THE ARCHITECT FOR OUR FILES. FAC
 61G1-16.003, 61G1-16.004(2)(5)(6) & FS 481.219,
 481.2055.
  
 4. SHT A1.1 KEY NOTES WERE NOT FOUND. PLEASE CORRELATE
 KEY NOTES WITH FLOOR PLAN. SECTION 106.1.1.
  
 5. SHT A8.1 DETAIL 9. SUBMIT MANUF SPECIFICATIONS FOR
 THE LAV DRAIN PAN. INDICATE REFERENCE STANDARD FOR LAV.
 SECTIONS 303, 303.1 303.2, & 303.4.
  
 6. SHT A8.1 DETAIL 10 INDICATES A STORAGE CABINET WHERE
 THE LAV DRAIN PAN SHOULD BE PLEASE CLARIFY. SECTION
 106.1.1.
  
 7. SHT FS-1 ITEM 86 WATER FILTER SYSTEM SHALL MEET THE
 REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF.
 SPECIFICATIONS SHEETS SHOWING COMPLIANCE. SECTION
 611.1.
  
 8. SHTS FI-1 THRU FS-13 ARE SEALED BY THE ARCHITECT OF
 RECORD INDICATING "REVIEWED ONLY". IF THE PLANS ARE
 SIGNED AND SEALED THEN A TITLE BLOCK, PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT, DATED SEAL ETC IS
 REQUIRED. IF REVIEWING ONLY, INDICATE WITH A SHOP
 REVIEW APPROVAL STAMP ONLY SUCH AS USED IN SUBMITTALS.
 FAC 61G1-16.004 & FS 481.2055.
  
 9. SHT FS-1 EQUIPMENT SCHEDULE ITEM #62 NOT FOUND ON
 THE FLOOR PLAN, & ITEM 147 INDICATES QTY 1 BUT 2 ARE
 SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 10. SHT FS-2 FOOD SERVICE EQUIPMENT SCHEDULE, ITEM 163
 DOES NOT INDICATE DRAINAGE, AND ITEM 173 INDICATES
 DRAINAGE FOR A STORAGE CABINET. PLEASE CLARIFY. SECTION
 106.1.1.
  
 11. SHT FS-4 DETAILS INDICATED SUCH AS THE TRENCH DRAIN
 DETAIL, DRAIN SPECIFICATIONS, SECTION THRU FLOOR
 RECESS, INDIRECT WASTE & AIR GAP. WHERE THESE DESIGNED
 BY THE EQUIPMENT SUPPLIERS? PLEASE CLARIFY. SECTION
 106.1.
  
 12. ALL STRUCTURAL SHEETS. THE CERTIFICATE OF
 AUTHORIZATION NUMBER, PRINTED NAME OF THE ENGINEER, AND
 THE LICENSE NUMBER OF THE ENGINEER ARE REQUIRED ON THE
 TITLE BLOCK. ALSO THE PLANS APPEAR TO BE SIGNED WITH
 INITIALS. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ENGINEER, THEN A SIGNED, SEALED, NOTORIZED LETTER SHALL
 BE SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR
 FILES. FAC 61G15-23.002(2) & FS 471.025.
  
 13. ALL MEP SHEETS. THE CERTIFICATE OF AUTHORIZATION
 NUMBER, PRINTED NAME OF THE ENGINEER, AND THE LICENSE
 NUMBER OF THE ENGINEER ARE REQUIRED ON THE TITLE BLOCK.
 ALSO THE PLANS APPEAR TO BE SIGNED WITH INITIALS. IF
 THIS IS INDEED THE LEGAL SIGNATURE OF THE ENGINEER,
 THEN A SIGNED, SEALED, NOTORIZED LETTER SHALL BE
 SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR FILES.
 FAC 61G15-23.002(2) & FS 471.025.
  
 14. SHT P1.1 THE CONDENSATE FROM THE AHU'S SHALL NOT
 DRAIN INTO THE SANITARY SYSTEM. THE CONDENSATE SHALL
 DRAIN SEPARATELY OUT OF THE BUILDING AND CONNECT TO
 STORM DRAINAGE, A CATCH BASIN, A DRYWELL OR INTO A
 PLANTED AREA SO AS NOT TO CREATE A HAZARD. IF THE
 CONDENSATE CONNECTS TO THE STORM LINES OUTSIDE THE
 BUILDING, THEN A RELIEF VENT, (GOOSENECK), SHALL BE
 PROVIDED AS THE CONDENSATE LINE EXITS THE BUILDING.
 MUNICIPAL CODE ARTICLE III SECTION 90-125(5).
  
 15. SHT P1.1 CONDENSATE FROM THE COOLER/FREEZER. FLOOR
 DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. A
 FLOOR SINK OR HUB DRAIN IS REQUIRED. SECTIONS 802.3 &
 802.3.2.
  
 16. SHT P1.1 THE DISWASHER SHALL DRAIN TO THE SANITARY
 SYSTEM, NOT THE GREASE SYSTEM. MUNICIPAL CODE ARTICLE
 III SECTION 90-124(7)(B). PLEASE CHANGE THE FLOOR PLAN
 AND THE SANITARY RISER DIAGRAM.
  
 17. SHT P1.1 PLUMBING WASTE & VENT PLAN NOTES #6.
 CLEANOUTS TO BE PROVIDED AT THE BASE OF THE STACK PER
 SECTION 708.3.4. PLEASE INDICATE THE CORRECT LOCATION
 FOR THE CLEANOUTS.
  
 18. SHT P1.1 VBF'S DO NOT MEET THE REQUIREMENTS OF
 SECTION 913, ISLAND VENTS. (SEE ATTACHED SHEET FOR
 REQUIRED PIPING). PLEASE CORRECT VENTING TO COMPLY WITH
 SECTION 913.
  
 19. SHT P2.1 THE 3" GAS LINE IS INDICATED AS HAVING
 1,812 CFH & 1,482 CFH ON THE SAME LINE DOWNSTREAM OF
 THE METER. PLEASE ONLY SHOW THE CORRECT LOAD ON THE GAS
 LINE. SECTION 106.1.1.
  
 20. SHT P2.1 PLUMBING PLAN NOTES #3. THE RPZV BACKFLOWS
 SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE FLOOR FOR
 CERTIFICTION AND SERVICE. PLEASE INDICATE ON PLANS.
 SECTION 106.2.1.
  
 21. SHT P2.1 PLUMBING PLAN NOTES #11 THE GAS PROVIDER
 SUPPLIES THE GAS AT EITHER 2 PSI OR 1/2 PSI, (12" TO
 14" W.C.). PLANS INDICATE 7" W.C. PLEASE CONTACT THE
 GAS PROVIDER AND INDICATE THE INLET PRESSURE PROVIDED.
 SECTION 402.
  
 22. SHT P3.1 A SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - THE LENGTHS OF PIPE ARE NOT
 INDICATED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED ONCE
 REQUIREMENT "A" IS ADDRESSED.
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - SEE COMMENT
 #21.
  
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--NO MANUF. SHEETS
 FOR ITEM #5RICE COOKERS, THE WATER HEATERS, AND THE
 RH UNITS.
  
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. - UNION NOT SHOWN.
  
 23. SHT P3.1 GAS RISER DIAGRAM, 2-1/2" REQUIRED FOR
 1078 CFH, 1-1/4" REQUIRED TO EACH WATER HEATER, 2"
 REQUIRED FOR 374 CFH TO 1ST RH, 1" REQUIRED FOR THE
 RICE COOKERS (2) & 1-1/2" REQUIRED TO THE FRYERS. TABLE
 402.4(2) - (IF SCHEDULE 40 PIPE).
  
 24. SHT P3.2 GREASE WASTE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. THE ISLAND VENTS SHALL CONNECT TO THE
 DRAIN AT THE LOWEST POINT, AND CLEANOUTS ARE REQUIRED
 ON BOTH VENT LINES. (SEE ATTACHED SHEET).
  
 25. SHT P3.2 GREASE WASTE & VENT RISER VENT DOES NOT
 MEET CODE PER SECTION 905.4. VENTS ARE TURNING
 HORIZONTALLY PRIOR TO 6" ABOVE THE FLOOD RIM LEVEL OF
 THE FLOOR SINKS. (SEE GENERAL NOTE).
  
 26. SHT P3.2 GREASE WASTE & VENT RISER DOES NOT REFLECT
 THE FLOOR PLAN. FLOOR SINK (107) IS NOT SHOWN ON THE
 FLOOR PLAN.--IDENTIFY THE FIXTURE THAT THE ICE
 MACHINE IS DRAINING INTO. AN INDIRECT WASTE RECEPTOR IS
 REQUIRED. SECTIONS 106.1.1, 802.3 & 802.3.2.
  
 27. SHT P3.2 SANITARY WASTE & VENT RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. 2 FLOOR DRAINS ARE SHOWN ON THE FLOOR
 PLAN THAT ARE NOT ON THE RISER DIAGRAM.--PIPING TO
 FIXTURE 166 DOES NOT REFLECT THE FLOOR PLAN.-- PIPING
 UPSTREAM OF FIXTURE 162 DOES NOT RELFECT THE FLOOR
 PLAN. (AS SHOWN ON THE FLOOR PLAN IT IS A DRY
 HORIZONTAL VENT WHICH IS NOT APPROVED PER SECTION 905.3
 & SECTION 905.4.--THE ISLAND VENT FOR FIXTURE 166
 DOES NOT MEET CODE REQUIREMENT. (SEE ATTACHED SHEET).
  
 28. SHT P3.3 SHOW WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9 ON THE RISER DIAGRAM. (QUICK CLOSING
 VALVES SUCH AS WASHING MACHINE, ICE MAKER ETC.). THE
 WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NO IN THE CEILING.
 PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-04-18 Cont ID  
Sent By eschneid Date 2008-04-18 Time 16:40 Rev Time 0.00
Received By eschneid Date 2008-04-18 Time 16:40 Sent To  
Notes
2008-04-18 16:41:44SIGNAGE AND AWNINGS NEED SEPARATE PERMITS.

Review Stop Z ZONING
Rev No 3 Status F Date 2008-03-12 Cont ID  
Sent By eschneid Date 2008-03-12 Time 13:31 Rev Time 0.00
Received By eschneid Date 2008-03-12 Time 13:31 Sent To  
Notes
2008-03-12 13:34:46FAILED
  
 THE PLANS THAT HAVE BEEN SUBMITTED DO NOT REFLECT THE
 REMOVAL OF THE OUTDOOR SEATING AREA ROOF AND COLUMNS ON
 THE WEST SIDE OF THE BUILDING THAT WAS APPROVED BY A
 MINOR AMENDMENT AND FORMAL SITE PLAN ON FEBRUARY 28,
 2008.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-01-24 Cont ID  
Sent By eschneid Date 2008-01-24 Time 15:26 Rev Time 0.00
Received By eschneid Date 2008-01-24 Time 15:13 Sent To  
Notes
2008-01-24 15:25:33FAILED
  
 1) REPEAT COMMENT - THE APPROVAL OF A MINOR PLANNED
 DEVELOPMENT AMENDMENT AND FORMAL SITE PLAN REVIEW ARE
 REQUIRED FOR THE FRONT DOOR CANOPY AND THE STRUCTURE TO
 COVER THE OUTDOOR SEATING AREAS.PLEASE NOTE THAT
 ADDITIONAL COMMENTS MAY BE GENERATED AS PART OF THIS
 REVIEW PROCESS THAT WILL AFFECT THE SITE LAYOUT,
 ELEVATIONS, ETC.
  
 2) REPEAT COMMENT - A SURVEY SHOWING ALL PROPOSED
 FEATURES IN RELATION TO THE PROPERTY LINE(S) AND
 EXISTING LANDSCAPE AREAS IS REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-01-24 Cont ID  
Sent By eschneid Date 2007-09-27 Time 15:44 Rev Time 0.00
Received By eschneid Date 2007-09-27 Time 15:44 Sent To  
Notes
2007-09-27 15:45:55FAILED
  
 1) THE APPROVAL OF A MINOR PLANNED DEVELOPMENT
 AMENDMENT IS REQUIRED FOR THE FRONT DOOR CANOPY AND THE
 CANOPY OVER THE OUTDOOR SEATING, INCLUDING ALL SUPPORT
 COLUMNS.
  
 2) A SURVEY SHOWING ALL PROPOSED FEATURES IN RELATION
 TO THE PROPERTY LINE(S) IS BE REQUIRED.
  
 3) IS LANDSCAPE PROPOSED FOR REMOVAL AS PART OF THIS
 PROJECT, SPECIFICALLY THE HEDGE NEAR THE ENTRANCE?ANY
 LANDSCAPE THAT IS MODIFIED WILL NEED TO BE INCLUDE WITH
 THE MINOR AMENDMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.