Plan Review Details - Permit 07090639
Plan Review Stops For Permit 07090639
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-22 Cont ID  
Sent By amorse Date 2008-03-22 Time 12:26 Rev Time 0.00
Received By amorse Date 2008-03-22 Time 12:26 Sent To PC
Notes
2008-03-22 12:27:52 
  
 PASSED BLDG REVISION FOR CANGE OF PRODUCT APPROVAL FOR
 WINDOWS AND DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-02-05 Cont ID  
Sent By amorse Date 2008-02-05 Time 18:13 Rev Time 0.00
Received By amorse Date 2008-02-05 Time 18:13 Sent To PC
Notes
2008-02-05 18:14:35 
  
 REVISION/SUBMITTAL OF TRUSS DRAWINGS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-22 Cont ID  
Sent By amorse Date 2007-12-22 Time 12:39 Rev Time 0.00
Received By amorse Date 2007-12-22 Time 12:39 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-13 Cont ID  
Sent By amorse Date 2007-12-13 Time 16:47 Rev Time 0.00
Received By amorse Date 2007-12-13 Time 16:47 Sent To PC
Notes
2007-12-13 16:56:59 
  
  
 DENIED
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE
 FIRST REVIEW:
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 *********NOTE: FEES ARE DUE IN THE AMOUNT OF $165.85
 FOR INCREASED VALUE THIS AMOUNT IS REQUIRED TO BE PAID
 PRIOR TO FURTHER PLAN REVIEW*******
  
 6)PROVIDE SCHEDULE ON DRAWINGS FOR DOOR AND WINDOW
 SIZES/DIMENSIONS, TYPES AND DESIGN PRESSURES
  
 ********NO WINDOW SIZE WAS GIVEN TO THE FIXED WINDOW
 (MARK "A") AND NO PRODUCT APPROVALS WERE SUBMITTED FOR
 FIXED WINDOW UNIT(S)********
  
 10)PROVIDE 2 COPIES OF A COMPLETED SHUTTER
 INSTALLATION SCHEDULE WITH MOUNTING TYPE FOR THE TOP
 AND BOTTOM, PANEL ORIENTATION (HORZ ORVERT), FASTENER
 TYPE ETC. FILLED OUT SEE ATTACHED SCHEDULE EXAMPLE
  
 *******NOTE, THE INFORMATION FOR THE SHUTTER SCHEDULE
 IS FOUND IN THE PRODUCT APPROVAL*******
  
 14)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-20 Cont ID  
Sent By amorse Date 2007-10-20 Time 16:47 Rev Time 0.00
Received By amorse Date 2007-10-20 Time 16:47 Sent To PC
Notes
2007-10-20 17:07:19 
  
 DENIED
  
 1)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $165.85 FOR
 INCREASED VALUE THIS AMOUNT IS REQUIRED TO BE PAID
 PRIOR TO FURTHER PLAN REVIEW
  
 4)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR
 TO SUBMITTAL. CALC'S ARE NOT SIGNED BY OWNER/AGENT AND
 ADDITIONS OR REMODELS REQUIRE A MIN R5 INSULATION AT
 EXTERIOR BLOCK WALLS AND MIN R30 IN CEILINGS WITH ATTIC
 SPACE PER 13-602.1.C.1.2 & 13-602.1.C.2 FBC FOR WALLS
 AND 13-604.1.C.1 & 13-604.1.C.2 FBC FOR CEILINGS
  
 5)PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER
 R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90 DEGREES
  
 6)PROVIDE SCHEDULE ON DRAWINGS FOR DOOR AND WINDOW
 SIZES/DIMENSIONS, TYPES AND DESIGN PRESSURES
  
 7)PROVIDE THE FOLLOWING CORRECTIONS TO SHEET A/1
 CORRECT DIMENSIONS FOR EAST ELEVATION AS THEY ADD UP TO
 26'-1", WINDOW AND DOOR DESIGN PRESSURES,CORRECT
 R-VALUES AND 3 BEDROOM WINDOWS SHOW MULLIONS IF SO
 PRODUCT APPROVALS WILL BE REQUIRED. PLEASE BE SURE THAT
 THEY WILL MEET EMERGENCY EGRESS IF MULLIONS ARE USED.
  
 8)PROVIDE PRODUCT APPROVALS FOR SIMPSON
 STRAPS/CONNECTORS OR INCLUDE THE CORRECT FLORIDA
 PRODUCT APPROVAL #'S ON THE SIMPSON SCHEDULE ON S/1 OR
 PROVIDE SIMPSON'S FLORIDA APPROVED INDEX (ON SIMPSON
 TIE WEB SITE) AND MARK/HIGHLIGHT THE CONNECTORS THAT
 WILL BE USED
  
 9)GAF GRAND TIMBERLINE SHINGLES ARE NOT LISTED UNDER
 THE FLORIDA APPROVAL #183, REMOVE THE STATE COVER AND
 APPROVE THE MIAMI-DADE REPORT THAT HAS BEEN ACCEPTED
 FOR LOCAL PRODUCT APPROVAL
  
 10)PROVIDE 2 COPIES OF A COMPLETED SHUTTER
 INSTALLATION SCHEDULE WITH MOUNTING TYPE FOR THE TOP
 AND BOTTOM, PANEL ORIENTATION (HORZ ORVERT), FASTENER
 TYPE ETC. FILLED OUT SEE ATTACHED SCHEDULE EXAMPLE
  
 11)PROVIDE SYSTEM THAT WILL BE USED FOR MODIFIED
 BITUMEN ROOF FROM THE MANY LISTED IN THE PRODUCT
 APPROVAL, ALSO PROVIDE CALCULATIONS FOR THE INCREASED
 FASTENERS REQUIRED FOR THE PERIMETER AND CORNER ZONES
 PER RAS 117 (SEE LIMITATION #7 ON PAGE 32)
  
 12)SUBMIT 2 SIGNED AND SEALED ENGINEERED TRUSS
 DRAWINGS THAT COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT HAVE BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD
  
 13)NOTE THAT SCOPE OF WORK DOES NOT COVER REPLACEMENT
 OF PLUMBING PIPING AND WAS REVIEW AS ONLY FIXTURE
 REPLACEMENT IF PIPING WAS DAMAGED AND REQUIRES ANY WORK
 STATE ON THE DRAWINGS AND PROVIDE RISER DIAGRAM FOR
 COMPLETE PLUMBING REVIEW
  
 14)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-28 Cont ID  
Sent By btrobaug Date 2007-11-28 Time 16:13 Rev Time 0.00
Received By btrobaug Date 2007-11-28 Time 14:52 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-25 Cont ID  
Sent By btrobaug Date 2007-09-25 Time 08:26 Rev Time 0.00
Received By btrobaug Date 2007-09-25 Time 07:25 Sent To Z
Notes
2007-09-25 08:26:53 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET E-1, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN
 IS NEW OR EXISTING. IF NEW , PROVIDE AN AIC RATING, AND
 LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER
 ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE
 WITH ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A
 RISER DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND
 TYPE.
  
 2} NOTE #20 REQUIRES # 12 CONDUCTORS MINIMUM FOR THIS
 PROJECT. THERE ARE #14 CONDUCTORS ON THE PANEL
 SCHEDULE, CLARIFY TO AVOID CONFUSION DURING
 CONSTRUCTION. 106.1.3.
  
 3} THE NOTE IN THE PANEL SCHEDULE INDICATES THE PANEL
 IS LOCATED IN THE GARAGE, THERE IS NO GARAGE ON THE
 FLOOR PLAN. THERE IS A CARPORT SHOWN ON THE SURVEY.
 CLARIFY ALL EQUIPMENT LOCATIONS.106.1.3.
  
 4} THERE ARE TWO "BATH CIRCUITS" LISTED IN THE
 SCHEDULE, ONE, CIRCUIT# 22, IS ON A 15 AMP BREAKER.
 THAT CIRCUIT COULD NOT BE USED FOR THE REQUIRED GFCI AS
 210.11(C)(3) REQUIRES A 20 AMP CIRCUIT.PER 408.4, "THE
 IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO ALLOW
 EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS."
 CLARIFY CIRCUIT DESIGNATIONS.
  
 5} THE KITCHEN COUNTERTOP RECEPTACLE ADJACENT TO THE
 PENINSULAR MUST BE GFCI PER 210.8(A)(6), INDICATE SAME
 ON THE PLAN.
  
 6} A RECEPTACLE IS REQUIRED AT THE FRONT OF THE
 RESIDENCE PER 210.52(E).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-07-30 Cont ID  
Sent By adarroug Date 2008-07-30 Time 09:18 Rev Time 0.00
Received By adarroug Date 2008-07-30 Time 09:18 Sent To M
Notes
2008-07-30 09:18:24TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-07-17 Cont ID  
Sent By adarroug Date 2008-07-17 Time 15:59 Rev Time 0.00
Received By adarroug Date 2008-07-17 Time 15:59 Sent To M
Notes
2008-07-17 16:00:18TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-07-10 Cont ID  
Sent By adarroug Date 2008-07-10 Time 10:07 Rev Time 0.00
Received By adarroug Date 2008-07-10 Time 10:07 Sent To M
Notes
2008-07-10 10:08:03TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-03-20 Cont ID  
Sent By adarroug Date 2008-03-20 Time 14:38 Rev Time 0.00
Received By adarroug Date 2008-03-20 Time 14:38 Sent To B
Notes
2008-03-20 14:40:11TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 16:59 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 16:59 Sent To B
Notes
2008-02-01 16:59:52TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 17:18 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 17:18 Sent To Z
Notes
2007-12-19 17:18:34TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 11:47 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 11:47 Sent To Z
Notes
2007-11-19 11:47:26TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-10-20 Time   Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 11:29 Sent To  
Notes
2007-09-24 11:29:36TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-07-30 Cont ID  
Sent By tgordon Date 2008-07-30 Time 13:48 Rev Time 0.30
Received By tgordon Date 2008-07-30 Time 13:48 Sent To  
Notes
2008-07-30 13:48:48REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-07-18 Cont ID  
Sent By tgordon Date 2008-07-18 Time 09:07 Rev Time 0.40
Received By tgordon Date 2008-07-18 Time 09:07 Sent To  
Notes
2008-07-18 09:08:27REVISION TO MECH. PLAN AND COOLING LOAD CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-07-10 Cont ID  
Sent By tgordon Date 2008-07-10 Time 14:04 Rev Time 0.30
Received By tgordon Date 2008-07-10 Time 14:04 Sent To  
Notes
2008-07-10 14:14:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** REVISION TO MECHANICAL PLAN **
 *** DENIED ***
  
 1)A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 2) INFORMATION IN THE EQUIPMENT SCHEDULE IS INCORRECT
 (SEE YELLOW HIGH LIGHT ON PLAN). PLEASE CORRECT PER
 2004 FBC 106.1.1.
  
 3) PLEASE BE ADVISED THE CONDENSER UNIT MODEL NUMBER ON
 THE PLAN APPEARS TO BE DISCONTINUED BY THE ARI, IF SO
 PLEASE CORRECT PER 2004 FBC 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-29 Cont ID  
Sent By tgordon Date 2007-11-29 Time 08:30 Rev Time 0.20
Received By tgordon Date 2007-11-29 Time 08:30 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-11 Cont ID  
Sent By tgordon Date 2007-10-11 Time 09:37 Rev Time 0.40
Received By tgordon Date 2007-10-11 Time 09:37 Sent To B
Notes
2007-10-11 10:00:22PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 9A-1 SHOWS R4.2, SEE SECOND
 PAGE OF E-CAL'S TABLE 6C-1 MINIMUM FOR CONCRETE BLOCK
 IS R-5, ALSO SEE 2004 FBC 13-602.1.C.2, PLEASE
 CORRECT.
  
 2) ENERGY CALCULATIONS LINE 10A SHOWS R19, SEE SECOND
 PAGE OF E-CAL'S TABLE 6C-1 MINIMUM FOR ATTIC IS R-30,
 ALSO SEE 2004 FBC 13-604.1.C.2, PLEASE CORRECT.
  
 3) THE ENERGY CALCULATIONS NEED TO BE SIGNED BY THE
 PREPARER (NELSON MARIN) AND ALSO BY THE OWNER/AGENT,
 SEE 2004 FBC'S 13-103.1.1 AND 13-600.ABC.2.
  
 4) PLEASE CORRECT PLANS PAGE A-1 TO SHOW CORRECTED
 MINIMUM INSULATION VALUES AS STATED ABOVE.
  
 5) MECHANICAL PLAN PAGE M-1 NEEDS TO BE SEALED BY THE
 ENGINEER LUIS A. LOPEZ AS HIS INFORMATION IS IN THE
 TITLE BLOCK, SEE FAC 61G15-23.002.
  
 6) PLEASE SHOW THE LOCATION OF CONDENSER UNIT #2 ON
 MECHANICAL PLAN PAGE M-1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-10-04 Cont ID  
Sent By jleech Date 2007-10-04 Time 09:21 Rev Time 0.00
Received By jleech Date 2007-10-04 Time 09:21 Sent To M
Notes
2007-10-04 09:23:02PLUMBING FIXTURE CHANGE OUT ONLY

Review Stop Z ZONING
Rev No 3 Status P Date 2007-12-21 Cont ID  
Sent By choops Date 2007-12-21 Time 14:31 Rev Time 0.00
Received By choops Date 2007-12-21 Time 14:30 Sent To B
Notes
2007-12-21 14:31:32***APPROVED - RESUB #2***
  
  
  
  
 SENT TO "B" - AM

Review Stop Z ZONING
Rev No 2 Status F Date 2007-11-28 Cont ID  
Sent By choops Date 2007-11-28 Time 10:26 Rev Time 0.00
Received By choops Date 2007-11-28 Time 10:26 Sent To E
Notes
2007-11-28 10:26:58***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)LANDSCAPE PLANS SUBMITTED ARE INSUFFICIENT.PLANS
 SHALL SHOW EXISTING/PROPOSED.PLANS SHALL SHOW
 COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-26 Cont ID  
Sent By choops Date 2007-09-26 Time 13:12 Rev Time 0.00
Received By choops Date 2007-09-26 Time 13:12 Sent To M
Notes
2007-09-26 13:14:51***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE SCOPE OF WORK WITH SETBACK DIMENSIONS TO
 ALL PROPERTY LINES.
  
 2)AS THE PROPOSED RENOVATION EXCEEDS 50% OF THE
 IMPROVEMENT VALUE OF THE HOME, LANDSCAPING SHALL BE
 BROUGHT TO COMPLIANCE WITH SECTION 94-442 OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS(ZLDRS), PURSUANT TO
 SECTION 94-441(C) OF THE ZLDRS.PLEASE PROVIDE A
 LANDSCAPE PLAN SHOWING COMPLIANCE.
  
 3)INDICATE OVERHANG DIMENSIONS OF PROPOSED ROOF.
  
 4)PROVIDE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720