Plan Review Stops For Permit 07090635 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-12-19 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-12-19 |
Time |
17:16 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-12-19 |
Time |
17:16 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-10-10 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-10-10 |
Time |
12:39 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-10-10 |
Time |
12:25 |
Sent To |
M |
|
Notes |
2007-10-10 12:38:59 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | REPEAT COMMENTS. SEE THAT THE ELECTRICAL CONTRACTOR IS | | NOTIFIED OF THESE. | | | | 1} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A) | | (3). | | | | 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS | | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES | | FOR CLARITY IN THE FIELD AND RECORD RETENTION PER | | 106.1.3 FBC AS AMENDED. | | | | 3} PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE | | EQUIPMENT TO BE INSTALLED. | | | | 4} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR | | REVIEW PER 106.1 FBC AS AMENDED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-09-24 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-09-24 |
Time |
16:10 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-09-24 |
Time |
15:56 |
Sent To |
Z |
|
Notes |
2007-09-24 16:10:52 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A) | | (3). | | | | 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS | | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES | | FOR CLARITY IN THE FIELD AND RECORD RETENTION PER | | 106.1.3 FBC AS AMENDED. | | | | 3} PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE | | EQUIPMENT TO BE INSTALLED. | | | | 4} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR | | REVIEW PER 106.1 FBC AS AMENDED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-12-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-14 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-14 |
Time |
15:51 |
Sent To |
Z |
|
Notes |
2007-12-14 15:51:56 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-10-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-04 |
Time |
09:25 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-04 |
Time |
09:25 |
Sent To |
Z |
|
Notes |
2007-10-04 09:25:54 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-09-24 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-09-24 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-09-24 |
Time |
09:25 |
Sent To |
PC |
|
Notes |
2007-09-24 09:27:13 | TO "M" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-12-20 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-12-20 |
Time |
11:28 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-12-20 |
Time |
11:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-10-16 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-10-16 |
Time |
14:33 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-10-16 |
Time |
14:33 |
Sent To |
|
|
Notes |
2007-10-16 14:34:50 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) PLANS NEED THE JOB ADDRESS ON THEM, SEE W.P.B. | | AMEND. 106.1.3. | | | | 2) PLANS NEED AN EQUIPMENT SCHEDULE ON THEM (MAKE, | | MODEL NO; SEER, TOTAL & SENSIBLE BTU'S, HEATER KW, | | ETC.) SEE W.P.B. AMEND. 106.3.5.4 (10). | | | | 3) PLANS NEED THE SIGNATURE OF THE PERSON RESPONSIBLE | | FOR THE DESIGN, SEE W.P.B. AMEND. 106.1.3. | | | | 4) PLANS NEED TO SHOW THE LOCATION OF ALL SUPPLY AND | | RETURN AIR GRILLS, AND DUCT WORK. | | | | 5) SHOW HOW RETURN AIR IS GETTING BACK TO THE AIR | | HANDLER. | | | | 6) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | 7) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | LAWS, SEE F.B.C. 106.1.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-09-24 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-09-24 |
Time |
10:26 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-09-24 |
Time |
10:25 |
Sent To |
E |
|
Notes |
2007-09-24 10:42:31 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) PLANS NEED THE JOB ADDRESS ON THEM, SEE W.P.B. | | AMEND. 106.1.3. | | | | 2) PLANS NEED AN EQUIPMENT SCHEDULE ON THEM (MAKE, | | MODEL NO; SEER, TOTAL & SENSIBLE BTU'S, HEATER KW, | | ETC.) SEE W.P.B. AMEND. 106.3.5.4 (10). | | | | 3) PLANS NEED THE SIGNATURE OF THE PERSON RESPONSIBLE | | FOR THE DESIGN, SEE W.P.B. AMEND. 106.1.3. | | | | 4) PLANS NEED TO SHOW THE LOCATION OF ALL SUPPLY AND | | RETURN AIR GRILLS, AND DUCT WORK. | | | | 5) SHOW HOW RETURN AIR IS GETTING BACK TO THE AIR | | HANDLER. | | | | 6) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | 7) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | LAWS, SEE F.B.C. 106.1.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2007-12-18 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-12-18 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-12-18 |
Time |
15:30 |
Sent To |
E |
|
Notes |
2007-12-18 15:31:43 | ***APPROVED - RESUB #2*** |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2007-10-09 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-10-09 |
Time |
11:50 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-10-09 |
Time |
11:50 |
Sent To |
E |
|
Notes |
2007-10-09 11:51:12 | ***FAILED - RESUB #1*** | | | | | | REPEAT COMMENT: | | | | 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY | | SHOWING THE LOCATION OF THE PROPOSED EQUIPMENT, WITH | | SETBACK DIMENSIONS TO THE PROPERTY LINES. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | TECHNICIAN | | (561)805-6720 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-09-24 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-09-24 |
Time |
17:21 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-09-24 |
Time |
17:21 |
Sent To |
|
|
Notes |
2007-09-24 17:22:53 | ***FAILED*** | | | | | | 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY | | SHOWING THE LOCATION OF THE PROPOSED EQUIPMENT, WITH | | SETBACK DIMENSIONS TO THE PROPERTY LINES. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | TECHNICIAN | | (561)805-6720 |
|
|