Plan Review Details - Permit 07090635
Plan Review Stops For Permit 07090635
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-12-19 Cont ID  
Sent By btrobaug Date 2007-12-19 Time 17:16 Rev Time 0.00
Received By btrobaug Date 2007-12-19 Time 17:16 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-10 Cont ID  
Sent By btrobaug Date 2007-10-10 Time 12:39 Rev Time 0.00
Received By btrobaug Date 2007-10-10 Time 12:25 Sent To M
Notes
2007-10-10 12:38:59 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 REPEAT COMMENTS. SEE THAT THE ELECTRICAL CONTRACTOR IS
 NOTIFIED OF THESE.
  
 1} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A)
 (3).
  
 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND RECORD RETENTION PER
 106.1.3 FBC AS AMENDED.
  
 3} PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE
 EQUIPMENT TO BE INSTALLED.
  
 4} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-24 Cont ID  
Sent By btrobaug Date 2007-09-24 Time 16:10 Rev Time 0.00
Received By btrobaug Date 2007-09-24 Time 15:56 Sent To Z
Notes
2007-09-24 16:10:52 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A)
 (3).
  
 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND RECORD RETENTION PER
 106.1.3 FBC AS AMENDED.
  
 3} PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE
 EQUIPMENT TO BE INSTALLED.
  
 4} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-14 Cont ID  
Sent By adarroug Date 2007-12-14 Time 15:51 Rev Time 0.00
Received By adarroug Date 2007-12-14 Time 15:51 Sent To Z
Notes
2007-12-14 15:51:56TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-04 Cont ID  
Sent By adarroug Date 2007-10-04 Time 09:25 Rev Time 0.00
Received By adarroug Date 2007-10-04 Time 09:25 Sent To Z
Notes
2007-10-04 09:25:54TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-24 Cont ID  
Sent By btrobaug Date 2007-09-24 Time 16:13 Rev Time 0.00
Received By btrobaug Date 2007-09-24 Time 09:25 Sent To PC
Notes
2007-09-24 09:27:13TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-20 Cont ID  
Sent By tgordon Date 2007-12-20 Time 11:28 Rev Time 0.30
Received By tgordon Date 2007-12-20 Time 11:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-10-16 Cont ID  
Sent By tgordon Date 2007-10-16 Time 14:33 Rev Time 0.30
Received By tgordon Date 2007-10-16 Time 14:33 Sent To  
Notes
2007-10-16 14:34:50PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS NEED THE JOB ADDRESS ON THEM, SEE W.P.B.
 AMEND. 106.1.3.
  
 2) PLANS NEED AN EQUIPMENT SCHEDULE ON THEM (MAKE,
 MODEL NO; SEER, TOTAL & SENSIBLE BTU'S, HEATER KW,
 ETC.) SEE W.P.B. AMEND. 106.3.5.4 (10).
  
 3) PLANS NEED THE SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN, SEE W.P.B. AMEND. 106.1.3.
  
 4) PLANS NEED TO SHOW THE LOCATION OF ALL SUPPLY AND
 RETURN AIR GRILLS, AND DUCT WORK.
  
 5) SHOW HOW RETURN AIR IS GETTING BACK TO THE AIR
 HANDLER.
  
 6) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 7) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, SEE F.B.C. 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-24 Cont ID  
Sent By tgordon Date 2007-09-24 Time 10:26 Rev Time 0.30
Received By tgordon Date 2007-09-24 Time 10:25 Sent To E
Notes
2007-09-24 10:42:31PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS NEED THE JOB ADDRESS ON THEM, SEE W.P.B.
 AMEND. 106.1.3.
  
 2) PLANS NEED AN EQUIPMENT SCHEDULE ON THEM (MAKE,
 MODEL NO; SEER, TOTAL & SENSIBLE BTU'S, HEATER KW,
 ETC.) SEE W.P.B. AMEND. 106.3.5.4 (10).
  
 3) PLANS NEED THE SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN, SEE W.P.B. AMEND. 106.1.3.
  
 4) PLANS NEED TO SHOW THE LOCATION OF ALL SUPPLY AND
 RETURN AIR GRILLS, AND DUCT WORK.
  
 5) SHOW HOW RETURN AIR IS GETTING BACK TO THE AIR
 HANDLER.
  
 6) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 7) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, SEE F.B.C. 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-12-18 Cont ID  
Sent By choops Date 2007-12-18 Time 15:30 Rev Time 0.00
Received By choops Date 2007-12-18 Time 15:30 Sent To E
Notes
2007-12-18 15:31:43***APPROVED - RESUB #2***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-09 Cont ID  
Sent By choops Date 2007-10-09 Time 11:50 Rev Time 0.00
Received By choops Date 2007-10-09 Time 11:50 Sent To E
Notes
2007-10-09 11:51:12***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE LOCATION OF THE PROPOSED EQUIPMENT, WITH
 SETBACK DIMENSIONS TO THE PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-24 Cont ID  
Sent By choops Date 2007-09-24 Time 17:21 Rev Time 0.00
Received By choops Date 2007-09-24 Time 17:21 Sent To  
Notes
2007-09-24 17:22:53***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE LOCATION OF THE PROPOSED EQUIPMENT, WITH
 SETBACK DIMENSIONS TO THE PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720