Plan Review Details - Permit 07090593
Plan Review Stops For Permit 07090593
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-04-18 Cont ID  
Sent By mjacobs Date 2008-04-18 Time 08:12 Rev Time 0.00
Received By mjacobs Date 2008-04-18 Time 07:22 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-03-28 Cont ID  
Sent By mjacobs Date 2008-03-28 Time 15:58 Rev Time 0.00
Received By mjacobs Date 2008-03-28 Time 14:38 Sent To  
Notes
2008-03-28 15:58:41BUILDING PLAN REVIEW
 PERMIT: 07090593
 ADD: 701 S. ROSEMARY AVE #200
 CONT: SURFSIDE
 TEL: (561) ###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3-38-08
 REVIEW: REVISION
 ACTION: DENIED
  
 1)TO HELP SPEED UP THE PROCESS FOR ALL REVISIONS, THE
 REVISED AREA NEEDS TO BE CLOUDED WITH A REVISION NUMBER
 WHERE IT CAN BE IDENTIFY EASILY. THIS REVISION HAS MANY
 CLOUDED AREAS WITH NO NUMBERS WHICH MAKES IT DIFFICULT
 TO IDENTIFY THE REVISED AREA FROM THE PREVIOUS
 REVISION. THE DATE OF THE REVISION DRAWING SHALL
 CORRESPOND WITH THE REVISION NUMBER WHICH WILL HELP TO
 IDENTIFY THE AREA. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED. FBC 106.1.1
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status N Date 2008-03-27 Cont ID  
Sent By mjacobs Date 2008-03-27 Time 11:34 Rev Time 0.00
Received By mjacobs Date 2008-03-27 Time 11:14 Sent To PC
Notes
2008-03-27 11:30:41PROCESS PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-24 Cont ID  
Sent By mjacobs Date 2008-03-24 Time 07:54 Rev Time 0.00
Received By mjacobs Date 2008-03-24 Time 07:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-12-19 Cont ID  
Sent By mjacobs Date 2007-12-19 Time 06:21 Rev Time 0.00
Received By mjacobs Date 2007-12-19 Time 06:02 Sent To PC
Notes
2007-12-19 06:22:06PROCESS PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-15 Cont ID  
Sent By mjacobs Date 2007-12-15 Time 08:05 Rev Time 0.00
Received By mjacobs Date 2007-12-14 Time 15:46 Sent To  
Notes
2007-12-15 07:24:41PROVISOR.:
 WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, "HARD" NONABSORBENT SURFACE, TO A HEIGHT
 OF 4 FEET ABOVE THE FLOOR.FBC 1210.02. PAINT ON
 DRYWALL ISNOT A "HARD" SURFACE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-08 Cont ID  
Sent By jjohnsto Date 2007-11-08 Time 16:44 Rev Time 2.00
Received By jjohnsto Date 2007-11-08 Time 14:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-09 Cont ID  
Sent By jjohnsto Date 2007-10-09 Time 11:18 Rev Time 3.00
Received By jjohnsto Date 2007-10-09 Time 11:14 Sent To  
Notes
2007-10-09 11:18:17CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 07090593
 BUILDING PLAN EXAMINERII
 PROJECT NUSH SPA/SALON
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS
 701 S. ROSEMARY, STE 200
  DATE OCTOBER 5, 2007
  
 BUILDINGPLANREVIEW
  
 CORRECTION SUBMITTAL
 WHEN RE-SUBMITTINGCORRECTED PLANS FOR PERMITTING,
 PLEASEREMOVE AND REPLACE ANY SHEETS AS NECESSARY.
 INCLUDE A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER WITH A DESCRIPTION OF THE
 REVISION MADE. IDENTIFY THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND AND INCLUDE THE OLD
 SHEETS IN THE RE-SUBMITTAL PACKAGE FOR THE PLAN
 REVIEWER?S REFERENCE.
 THIS SHALL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
 COMMENT-FOR YOUR INFORMATION
  
 F.S.713.13NOTICE OF COMMENCEMENT
 FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION.
 IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED
 WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL
 AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT
 ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE
 FIRST INSPECTION.
 COMMENT-FOR YOUR INFORMATION
  
  
 NOTE ON COVER SHEET 1
 FBC2004 BUILDING W/ 2005 AND 6 REVISIONS
 FBC2004 ACCESSIBILITYCHAPTER 11
 FBC2004 EXISTING BUILDING
 LEVEL OF ALTERATION
 TYPE OF CONSTRUCTION
 SPRINKLED / UN-SPRINKLED
 NUMBER OF STORIES
 WIND SPEED AND EXPOSURE
 WIND IMPORTANCE FACTOR
 TYPE OF OCCUPANCY
 OCCUPANT LOAD-GROSS - NET
 COMMENTS- PLEASE ADDRESS THE FOLLOWING,FBC 2004
 ACCESSIBILITY,FBC 2004EXISTING BUILDINGS,
 NUMBER OF STORIES,
  
 FBC EXISTING 503.2 CARPETING.
 NEW CARPETING USED AS AN INTERIOR FLOOR FINISH MATERIAL
 SHALL COMPLY WITH THE RADIANT FLUX REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING .
  
  
  
  
  
 FBC BUILDING CHAPTER 11ACCESSIBILITY
  
 11-7.2 SALES AND SERVICE COUNTERS, TELLER WINDOWS,
 INFORMATION COUNTERS.
 (1)IN DEPARTMENT STORES AND MISCELLANEOUS RETAIL
 STORES WHERE COUNTERS HAVE CASH REGISTERS AND ARE
 PROVIDED FOR SALES OR DISTRIBUTION OF GOODS OR SERVICES
 TO THE PUBLIC, AT LEAST ONE OF EACH TYPE SHALL HAVE A
 PORTION OF THE COUNTER WHICH IS AT LEAST 36 INCHES (915
 MM) IN LENGTH WITH A MAXIMUM HEIGHT OF 36 INCHES (915
 MM) ABOVE THE FINISH FLOOR. IT SHALL BE ON AN
 ACCESSIBLE ROUTE COMPLYING WITH SECTION 11-4.3 . THE
 ACCESSIBLE COUNTERS MUST BE DISPERSED THROUGHOUT THE
 BUILDING OR FACILITY. IN ALTERATIONS WHERE IT IS
 TECHNICALLY INFEASIBLE TO PROVIDE AN ACCESSIBLE
 COUNTER, AN AUXILIARY COUNTER MEETING THESE
 REQUIREMENTS MAY BE PROVIDED.
 COMMENTS-SHEETA.2DETAIL RECEPTION / SALES COUNTER
 FOR ACCESSIBILITY
  
 11-4.13 DOORS.SEE TEA/MED.CONSDOOR NO 4
 COMMENTS- ALL REQUIRED DOORS SHALL HAVE AT LEAST A 29?
 CLEAR OPENING FOR ACCESSIBILITY
  
 11-4.13 DOORS.SEE LOUNGEPOCKET DOOR NO 5
 COMMENTS- ALL REQUIRED DOORS SHALL HAVE AT LEAST A 29?
 CLEAR OPENING FOR ACCESSIBILITY
 11-4.13.9 DOOR HARDWARE.
 HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERATING
 DEVICES ON ACCESSIBLE DOORS SHALL HAVE A SHAPE THAT IS
 EASY TO GRASP WITH ONE HAND AND DOES NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING, OR TWISTING OF THE WRIST TO
 OPERATE. LEVER-OPERATED MECHANISMS, PUSH-TYPE
 MECHANISMS, AND U-SHAPED HANDLES ARE ACCEPTABLE
 DESIGNS. WHEN SLIDING DOORS ARE FULLY OPEN, OPERATING
 HARDWARE SHALL BE EXPOSED AND USABLE FROM BOTH SIDES.
 HARDWARE REQUIRED FOR ACCESSIBLE DOOR PASSAGE SHALL BE
 MOUNTED NO HIGHER THAN 48 INCHES (1219 MM) ABOVE FINISH
 FLOOR.
 COMMENTS- POCKET DOOR NOT IN COMPLIANCE
  
 11-4.13 DOORS.SEE STEAM ROOMDOOR NO ?
 COMMENTS- ALL REQUIRED DOORS SHALL HAVE AT LEAST A 29?
 CLEAR OPENING FOR ACCESSIBILITY
  PLEASE IDENTIFY THIS DOOR ON THE DOOR
 SCHEDULE
  
  
 11-4.13.9 DOOR HARDWARE.
 HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERATING
 DEVICES ON ACCESSIBLE DOORS SHALL HAVE A SHAPE THAT IS
 EASY TO GRASP WITH ONE HAND AND DOES NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING, OR TWISTING OF THE WRIST TO
 OPERATE. LEVER-OPERATED MECHANISMS, PUSH-TYPE
 MECHANISMS, AND U-SHAPED HANDLES ARE ACCEPTABLE
 DESIGNS. WHEN SLIDING DOORS ARE FULLY OPEN, OPERATING
 HARDWARE SHALL BE EXPOSED AND USABLE FROM BOTH SIDES.
 HARDWARE REQUIRED FOR ACCESSIBLE DOOR PASSAGE SHALL BE
 MOUNTED NO HIGHER THAN 48 INCHES (1219 MM) ABOVE FINISH
 FLOOR.
 COMMENTS- IDENTIFY HARDWARE SCHEDULE ON ALL DOORS
2007-10-01 14:31:58TO "BOB"#15

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-08-11 Cont ID  
Sent By dpalmer Date 2008-08-11 Time 09:09 Rev Time 0.00
Received By dpalmer Date 2008-08-11 Time 09:09 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-07-18 Cont ID  
Sent By dpalmer Date 2008-07-18 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2008-07-18 Time 12:46 Sent To PC
Notes
2008-07-18 12:46:21** DENIED REVISIONS **
  
  
  
 1) NOTE: PLEASE COORDINATE ALL PLANS. PLEASE SEE THE
 REVISION #5 SHEETS SUBMITTED ON 6/30CONTAIN CHANGES
 WHICH ARE LABELED REVISION #4 YET THE REVISION #4 IS
 NOT THE SAME AS THE REVISION #4 ON SHEETS SUBMITTED
 6/23/08.
 PLEASE SEE THERE ARE NO REV #5 CLOUDS/TRIANGLES SHOWN
 ON PLANS SUBMITTED 6/30/08.
  
 ** TO DATE OF THIS REVIEW NO PERMIT HAS BEEN APPLIED
 FOR THE INSTALLATION OF THE LOW VOLTAGE SOUND SYSTEM
 WHICH IS NOW SHOWN AS REV #4.
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-12-13 Cont ID  
Sent By dpalmer Date 2007-12-13 Time 13:05 Rev Time 0.00
Received By dpalmer Date 2007-12-13 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-06 Cont ID  
Sent By dpalmer Date 2007-11-06 Time 12:11 Rev Time 0.00
Received By dpalmer Date 2007-11-06 Time 10:47 Sent To  
Notes
2007-11-06 12:11:31** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ALONG
 WITH SOME NEW COMMENTS ARE IN NEED OF BEING ADDRESSED.
  
 1) NOTE: PLEASE SEE THE CODES AND NOTES ON PLANS STILL
 NEED TO BE CORRECTED. PLEASE SEE FOR EXAMPLE: THERE ARE
 STILL CODE NOTES ON PLANS TO THE SOUTH FLORIDA BUILDING
 CODE WHICH HAS NOT BEEN IN EFFECT SINCE MARCH 02.
 PLEASE SEE THE ELECTRICAL LOADCALCULATIONS ETC.
 SHEET E.3
 FBC 106.1.2
  
  
 2) NOTE: PLEASE SEE SMOKE DETECTOR NOTES ON PLANS STILL
 CALL FOR RESIDENTIAL INSTALLATIONS.
 ** PLEASE CLARIFY ELECTRICAL NOTES, AND SMOKE DETECTORS
 NOTES AS THESE ARE REFERENCING DWELLING UNIT
 REQUIREMENTS AND NOT THAT OF A COMMERCIAL LOCATION.
 CALLS FOR ARC FAULT PROTECTION ETC.
 PLEASE ADJUST NOTES.
 FBC 106.1.2, 110.1.2 ETC ADMIN COORDINATION AND
 RELEVANT CODES WHICH MAY NOT BE FROM OTHER CODES.
  
 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES. PLEASE CORRELATE
 CIRCUITING PLANS ALSO. PLEASE SEE ROOMS WHERE
 CIRCUITING TO SPECIALTY LIGHTING AND CIRCUIT NUMBER AND
 PANEL IS BEING REFLECTED HOWEVER THESE DO NOT CORRELATE
 WITH THE SAME ROOMS.
 PLEASE SEE FOR EXAMPLE, SWITCH SHOWS A GCA -26, YET THE
 SAME ROOM SHOWS GCB 28. THIS IS THE SAME FOR SPA ROOM
 #1, #2, ETC.
 PLEASE SEE CIRCUITS WHICH REFERENCE TO A GCH PANEL YET
 NO GCH PANEL SCHEDULE WAS SUBMITTED.
 PLEASE SEE THERE ARE SEVERAL OTHER ELECTRICAL OUTLETS
 ON PLANS WHICH CONTAIN NO CIRCUITING.
 PLEASE SEE THAT THE PANEL SCHEDULES HAVE ALSO NOT BEEN
 REVISED. THE CIRCUITS ARE NOT SHOWN SPECIFIC TO ROOMS
 AND AREAS IN WHICH THEY FEED. PLEASE SEE 408.4,240.4,
 310.16.
 FBC106.1.2, 106.3.5.1.2, 106.5 ETC.
  
  
 4) NOTE: LIGHTING CONTROL DEVICES ARE NOT SHOWN FOR ALL
 LIGHTING. EXAMPLE : ALTERNATE SPA ROOM.
 PLEASE INDICATE LIGHTING CONTROLS PER FBC CHAPTER 13
 FOR NEW LIGHTING CONTROL DEVICES BEING INSTALLED.
 PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND .1.3.
 PLEASE SEE 13-101
 PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS AS
 SUBMITTED ACTUALLY CALL FOR *VA REQUIRED* ON THE
 TABLE.
  
 PLEASE KNOW THE LIGHTING LEVELS AS STATED IN 13-415.2
 ON EITHER TABLE AND THE ENERGY CODE IS ACTUALLY FOR
 *MAXIMUM* LIGHTING LEVELS. THESE TABLES IN THE FBC ARE
 NOT LIGHTING REQUIRED.
 PLEASE EXPLAIN WHERE SOME OF THE LIGHTING ALLOWANCE
 FIGURES ARE DERIVED. FOR EXAMPLE OFFICE LEVELS NOTED AT
 1.5, WHEN THE CODE STATES MAXIMUM AT 1.1.
 PLEASE PLACE A TOTAL ON THE MAXIMUM ALLOWED COMPARED TO
 THE MAXIMUM DESIGN.
 PLEASE SEE THAT THE TRADE OFFS OF TOTAL SPACE IS
 PERMITTED HOWEVER THESE FIGURES NEED TO BE CORRECTED
 AND KNOW.
 PLEASE SEE 13-415.2
  
 5) NOTE:THIS IS THE SAME NOTE AS PREVIOUS.
 PLEASE SEE THE PLANS CALL FOR A STEAM ROOM DISCONNECT
 NEXT TO STEAM ROOM HOWEVER THIS DOES NOT SHOW
 CIRCUITING OR LOADS OR LISTED IN ANY PANEL? PLEASE
 COMPLETE PLANS WITH ALL CIRCUITING AND CORRELATE WITH
 PANELS.
 PLEASE SEE THE NEW LIGHTING LOADS WHICH ARE SHOWN
 CIRCUITED AND ON PANELS GCA AND GCB ARE ADDED TO THESE
 PANELS, HOWEVER AS THESE PANELS ARE FED FROM THE
 EXISTING PANEL *GC1* THE LOAD CALCULATIONS HAVE NOT
 BEEN ADJUSTED AND COMPLETED.
 PLEASE SEE ABOVE AS STEAM UNIT ETC IS ALSO NOT
 INCLUDED?
 PLEASE SEE THE CODE SECTIONS REFLECTED ON THE PANEL
 SCHEDULES FOR LOAD CALCULATIONS ARE NOT FROM THE
 CURRENT CODES.
 PLEASE SUBMIT COMPLETED PLANS FOR ALL ELECTRICAL AND
 COMPLETED UPDATED LOAD CALCULATIONS FOR ALL
 ELECTRICAL.
 PLEASE SEE NFPA-70 2005, 220, 215.5, 310.16, 240.4
 ETC.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE:THIS IS THE SAME AS PREVIOUS REVIEW. THE
 CANDELA LEVELS WERE ADDED HOWEVER NOT HORN LEVELS WHERE
 STATED FOR ADA.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE
 THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA
 REQUIRED AREAS.NO DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE KNOW AS THIS BUILDING DOES CONTAIN
 A FIRE ALARM SYSTEM, EITHER THESE DEVICES EXIST OR NEW
 LOCATIONS WILL BE REQUIRED TO MEET THE MINIMUM PER FBC
 ADA.
 .
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN.
 FBC 106.3.5.1.2, 106.1.2 ETC
 ** THIS IS BEING NOTED AS NOTES FROM FIRE MARSHAL
 AND/OR BUILDING REVIEWER MAY FOLLOW.
  
 7) NOTE: PLEASE PROVIDE NOTES ON PLANS PER
 13-413.1.ABC.1.2 AND .2.2
 PLEASE SEE THE FBC FOR ACTUAL WORDING REQUIRED ON
 CONSTRUCTION DOCUMENTS.
  
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-01 Cont ID  
Sent By dpalmer Date 2007-10-01 Time 19:21 Rev Time 0.00
Received By dpalmer Date 2007-10-01 Time 18:41 Sent To  
Notes
2007-10-01 19:21:142007-10-01 19:21:14
  
 ** DENIED ***
  
 1) NOTE: PLEASE CORRELATE WHERE WORK IS BEING PERFORMED
 AS SHEET A-2 INDICATES *ANUSKA* YET TITLE BLOCKS
 INDICATE *NUSH SPA*?
 PLEASE ADJUST AND COORDINATE.
 FBC 106.1.2, 110.1.2
 FAC 61G1-16.004
  
 2) NOTE: PLEASE SEE THE COVER SHEET DOES REFLECT THE
 RELEVANT CODES WHICH ARE TO BE PART OF PROJECT AND
 DESIGNS HOWEVER THERE ARE SEVERAL COMMENTS AND NOTES ON
 PLANS WHICH REFERENCE CODES WHICH ARE NO LONGER IN
 EFFECT. PLEASE SEE SOME OF THESE IN FACT GO BACK TO
 SOME 1996 CODES.
 PLEASE SEE EXAMPLES ON ELECTRICAL NOTES:
 #3 WHICH STATES THE SFBC, SOUTH FLORIDA BUILDING CODE.
 # 10 AND #15 WHICH REFLECTS CODE FROM THE 1996 NEC.
  
 SMOKE DETECTOR NOTES #4 WHICH GIVES CODE SECTIONS FROM
 THE 1996 NFPA-72.
  
 ** PLEASE CLARIFY ELECTRICAL NOTES, AND SMOKE DETECTORS
 NOTES AS THESE ARE REFERENCING DWELLING UNIT
 REQUIREMENTS AND NOT THAT OF A COMMERCIAL LOCATION.
 CALLS FOR ARC FAULT PROTECTION ETC.
 PLEASE ADJUST NOTES.
 FBC 106.1.2, 110.1.2 ETC ADMIN COORDINATION AND
 RELEVANT CODES WHICH MAY NOT BE FROM OTHER CODES.
  
 3) NOTE: PLEASE SEE THE PLANS SPECIFICALLY INDICATE A
 NEW ELECTRICAL PANEL HOWEVER NO ELECTRICAL RISER WAS
 SUBMITTED SHOWING THIS NEW PANEL.?? PLEASE ALSO SEE
 NONE OF THE EXISTING PANELS LIST ANY OVER CURRENT
 PROTECTION FOR THIS NEW PANEL WHICH IS NOTED AND SHOWN
 ON E-2 NEXT TO EXISTING PANELS.
 PLEASE COORDINATE AS E-1 DOES NOT INDICATE ANY NEW
 PANEL?
 FBC 106.1.2, 106.3.5.1.2
 NEC 215.5, 310.16, 240.4, 408.4 ETC
  
 4) NOTE: PLEASE INDICATE LIGHTING CONTROLS PER FBC
 CHAPTER 13 FOR NEW LIGHTING CONTROL DEVICES BEING
 INSTALLED. PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND
 .1.3.
 PLEASE SEE 13-101
 PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS AS
 SUBMITTED ACTUALLY CALL FOR *VA REQUIRED* ON THE
 TABLE.
  
 PLEASE KNOW THE LIGHTING LEVELS AS STATED IN 13-415.2
 ON EITHER TABLE AND THE ENERGY CODE IS ACTUALLY FOR
 *MAXIMUM* LIGHTING LEVELS. THESE TABLES IN THE FBC ARE
 NOT LIGHTING REQUIRED.
 PLEASE LABEL ALL LIGHTING FIXTURES AS SHOWN ON PLANS
 AND CORRELATE WITH A FIXTURE LEGEND TO BE
 SHOWN/SUBMITTED. THE SAME FIXTURE INFORMATION AS LISTED
 IN THE LPC TABLE CAN BE USED HOWEVER EACH WOULD CONTAIN
 A DESIGNATION. PLEASE KNOW AT THIS TIME THERE SEEMS TO
 BE SOME COORDINATION NEED FOR FIXTURE TYPES AND COUNTS
 FOR AREAS. PLEASE SEE POS AREA FOR EXAMPLE.
 PLEASE ADJUST NOTE.
 **PLEASE CALL TO GO OVER.
  
 5) NOTE: PLEASE SEE THE PLANS CALL FOR A STEAM ROOM
 DISCONNECT NEXT TO STEAM ROOM HOWEVER THIS DOES NOT
 SHOW CIRCUITING OR LOADS OR LISTED IN ANY PANEL? PLEASE
 COMPLETE PLANS WITH ALL CIRCUITING AND CORRELATE WITH
 PANELS.
 PLEASE SEE THE NEW LIGHTING LOADS WHICH ARE SHOWN
 CIRCUITED AND ON PANELS GCA AND GCB ARE ADDED TO THESE
 PANELS, HOWEVER AS THESE PANELS ARE FED FROM THE
 EXISTING PANEL *GC1* THE LOAD CALCULATIONS HAVE NOT
 BEEN ADJUSTED AND COMPLETED.
 PLEASE SEE ABOVE AS STEAM UNIT ETC IS ALSO NOT
 INCLUDED?
 PLEASE SEE THE CODE SECTIONS REFLECTED ON THE PANEL
 SCHEDULES FOR LOAD CALCULATIONS ARE NOT FROM THE
 CURRENT CODES.
 PLEASE SUBMIT COMPLETED PLANS FOR ALL ELECTRICAL AND
 COMPLETED UPDATED LOAD CALCULATIONS FOR ALL
 ELECTRICAL.
 PLEASE SEE NFPA-70 2005, 220, 215.5, 310.16, 240.4
 ETC.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE:PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS.NO DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE KNOW AS THIS BUILDING DOES CONTAIN
 A FIRE ALARM SYSTEM, EITHER THESE DEVICES EXIST OR NEW
 LOCATIONS WILL BE REQUIRED TO MEET THE MINIMUM PER FBC
 ADA.
 .
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN.
 FBC 106.3.5.1.2, 106.1.2 ETC
 ** THIS IS BEING NOTED AS NOTES FROM FIRE MARSHAL
 AND/OR BUILDING REVIEWER MAY FOLLOW.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SHOWN ON
 PLANS AT THIS TIME, THERE VERY WELL MAY BE NEW COMMENTS
 ON THE FOLLOWING REVIEW. REVIEW NOTES CAN ONLY BE GIVEN
 FOR PLANS/DOCUMENTS AS SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2008-03-31 Cont ID  
Sent By mawillia Date 2008-03-31 Time 11:12 Rev Time 0.00
Received By mawillia Date 2008-03-31 Time 11:03 Sent To  
Notes
2008-03-31 11:11:33****FIRE-STAMPING NEEDED*****
  
  
 REVISED PLAN SHEET A-1 TO BE STAMPED, INITIALED, AND
 DATED WHEN THE BUILDING REVIEW COMMENT HAS BEEN
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-03-26 Cont ID  
Sent By mawillia Date 2008-03-26 Time 12:09 Rev Time 0.00
Received By mawillia Date 2008-03-26 Time 12:01 Sent To  
Notes
2008-03-26 12:08:23****REVISION APPROVED*****
  
  
 REVISED PLAN SHEET A-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-12-17 Cont ID  
Sent By mawillia Date 2007-12-17 Time 13:08 Rev Time 0.00
Received By mawillia Date 2007-12-17 Time 12:57 Sent To B
Notes
2007-12-17 13:08:13*****APPROVED*****
  
 PLAN SHEETS LS-1, A-1, AND E-1 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-11-06 Cont ID  
Sent By mwennerg Date 2007-11-06 Time 13:27 Rev Time 0.00
Received By mwennerg Date 2007-11-06 Time 13:27 Sent To  
Notes
2007-11-06 13:30:54***APPROVED***
  
 1) PLANS STILL INDICATE NOTE REFERENCING RESIDENTIAL
 SMOKE DETECTORS. SHEET E.3 NOTE 3.
  
 2) OK
  
 3) OK
  
 4) OK
  
 5) OK
  
 6) OK
  
 PLANS WILL BE STAMPED WHEN RETURNED FOR OTHER REVIEW
 COMMENTS PROVIDED THAT NON-APPLICABLE INFORMATION IS
 DELETED.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-04 Cont ID  
Sent By mwennerg Date 2007-10-04 Time 15:59 Rev Time 0.00
Received By mwennerg Date 2007-10-04 Time 15:59 Sent To  
Notes
2007-10-04 16:15:45***DENIED***
  
 1) PLANS INDICATE SMOKE DETECTORS AS IT APPLIES TO
 RESIDENTIAL OCCUPANCIES. PLEASE REMOVE INFORMATION THAT
 IS NOT APPLICABLE TO THIS PROJECT.
  
 2) PLANS ARE SOMEWHAT CONFUSING REGARDING EXITING.
 PLEASE PROVIDE A CLEAR ILLUSTRATION AND COMMON PATH OF
 TRAVEL OF REQUIRED MEANS OF EGRESS SHOWING WHERE
 PERSONS EXIT TO.
  
 3) INDICATE THE LOCATIONS OF REQUIRED 2A-10B,C RATED
 FIRE EXTINGUISHERS THAT SHALL BE LOCATED NOT TO EXCEED
 75' TRAVEL DISTANCE.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 6) DOES THE DOOR TO THE STAIRWELL SWING IN THE CORRECT
 DIRECTION?PLANS INDICATE AN OCCUPANT LOAD OF 100.
 EXIT DOORS TO SWING IN DIRECTION OF TRAVEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-08-05 Cont ID  
Sent By adarroug Date 2008-08-05 Time 16:14 Rev Time 0.00
Received By adarroug Date 2008-08-05 Time 16:14 Sent To  
Notes
2008-08-05 16:15:14TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-07-01 Cont ID  
Sent By adarroug Date 2008-07-01 Time 14:11 Rev Time 0.00
Received By adarroug Date 2008-07-01 Time 14:11 Sent To E
Notes
2008-07-01 14:12:18TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-06-24 Cont ID  
Sent By adarroug Date 2008-06-24 Time 15:16 Rev Time 0.00
Received By adarroug Date 2008-06-24 Time 15:16 Sent To E
Notes
2008-06-24 15:16:39TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-04-16 Cont ID  
Sent By adarroug Date 2008-04-16 Time 10:33 Rev Time 0.00
Received By adarroug Date 2008-04-16 Time 10:33 Sent To B
Notes
2008-04-16 10:35:07TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-03-27 Cont ID  
Sent By adarroug Date 2008-03-27 Time 14:43 Rev Time 0.00
Received By adarroug Date 2008-03-27 Time 14:43 Sent To P
Notes
2008-03-27 14:43:18TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-03-27 Cont ID  
Sent By adarroug Date 2008-03-27 Time 14:38 Rev Time 0.00
Received By adarroug Date 2008-03-27 Time 14:38 Sent To  
Notes
2008-03-27 14:39:58TO "BOB"#9--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-03-27 Cont ID  
Sent By adarroug Date 2008-03-27 Time 14:18 Rev Time 0.00
Received By adarroug Date 2008-03-27 Time 14:18 Sent To M
Notes
2008-03-27 14:18:43TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-03-20 Cont ID  
Sent By adarroug Date 2008-03-20 Time 14:45 Rev Time 0.00
Received By adarroug Date 2008-03-20 Time 14:45 Sent To P
Notes
2008-03-20 14:45:52TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-03-20 Cont ID  
Sent By adarroug Date 2008-03-20 Time 13:42 Rev Time 0.00
Received By adarroug Date 2008-03-20 Time 13:42 Sent To M
Notes
2008-03-20 13:42:29TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-20 Cont ID  
Sent By adarroug Date 2008-03-20 Time 13:39 Rev Time 0.00
Received By adarroug Date 2008-03-20 Time 13:39 Sent To  
Notes
2008-03-20 13:39:54TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-12 Cont ID  
Sent By adarroug Date 2007-12-12 Time 10:46 Rev Time 0.00
Received By adarroug Date 2007-12-12 Time 10:46 Sent To  
Notes
2007-12-12 11:28:44TO "BOB"#18
2007-12-12 10:47:08WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-26 Cont ID  
Sent By adarroug Date 2007-10-26 Time 16:01 Rev Time 0.00
Received By adarroug Date 2007-10-26 Time 16:01 Sent To  
Notes
2007-11-05 10:53:27TO "BOB"#7
2007-10-26 16:01:32WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-10 Cont ID  
Sent By tgordon Date 2007-10-10 Time 15:28 Rev Time 0.00
Received By tgordon Date 2007-09-20 Time 16:32 Sent To  
Notes
2007-09-20 16:34:05WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-03-28 Cont ID  
Sent By tgordon Date 2008-03-28 Time 11:18 Rev Time 0.30
Received By tgordon Date 2008-03-28 Time 11:18 Sent To  
Notes
2008-03-28 11:19:57REVISION TO MECHANICAL PLAN PAGE M-1.
  
 *** PROVISO ***
 1) ALL SHOWER ROOMS AND TOILET ROOMS NEED TO COMPLY
 WITH 2004 FBC/M TABLE 403.3 REGARDING EXHAUST.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-03-20 Cont ID  
Sent By tgordon Date 2008-03-20 Time 15:30 Rev Time 0.50
Received By tgordon Date 2008-03-20 Time 15:30 Sent To  
Notes
2008-03-20 15:41:35PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** MECHANICAL REVISION **
 *** DENIED ***
 1) SEE YELLOW HIGH LIGHT ON PLAN SHOWING DUCTS (FLEX)
 THAT NEEDS TO BE SIZED, PER 2004 FBC/M 106.3.5.
  
 2) SEE YELLOW HIGH LIGHT ON PLAN SHOWING A SUPPLY AIR
 GRILL THAT NEEDS THE SIZE AND CFM'S SHOWN.
  
 3) SEE YELLOW HIGH LIGHT ON PLAN SHOWING A RETURN AIR
 GRILL THAT NEEDS THE SIZE ADDED.
  
 4) SEE YELLOW HIGH LIGHT ON PLAN SHOWING A SUPPLY AIR
 GRILL IN THE WAX ROOM AND ONE IN THE HALL LISTED AS
 RETURN GRILLS, ALSO SEE NOTE #2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-12 Cont ID  
Sent By tgordon Date 2007-12-12 Time 15:00 Rev Time 0.25
Received By tgordon Date 2007-12-12 Time 15:00 Sent To  
Notes
2007-12-12 15:01:15*** PROVISO ***
 1) ALL SHOWER ROOMS AND TOILET ROOMS NEED TO COMPLY
 WITH 2004 FBC/M TABLE 403.3 REGARDING EXHAUST.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-06 Cont ID  
Sent By tgordon Date 2007-11-06 Time 08:18 Rev Time 0.30
Received By tgordon Date 2007-11-06 Time 08:18 Sent To  
Notes
2007-11-06 08:21:50*** PROVISO ***
 1) ALL SHOWER ROOMS AND TOILET ROOMS NEED TO COMPLY
 WITH 2004 FBC/M TABLE 403.3 REGARDING EXHAUST.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-10-10 Cont ID  
Sent By tgordon Date 2007-10-10 Time 15:28 Rev Time 0.30
Received By tgordon Date 2007-10-10 Time 15:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-04-01 Cont ID  
Sent By jleech Date 2008-04-01 Time 08:29 Rev Time 0.00
Received By jleech Date 2008-04-01 Time 08:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-03-24 Cont ID  
Sent By jleech Date 2008-03-24 Time 09:31 Rev Time 0.00
Received By jleech Date 2008-03-24 Time 09:14 Sent To  
Notes
2008-03-24 09:48:35REVISION DENIED;
 1. PAGE P-1 WOMAN'S LOUNGE, ONE SHOWER SHALL MEET
 HANDICAP CODE REQUIREMENTS. SHOW GRAB BARS AND SEAT ON
 PLANS.
 2. PAGE P-2 SHOWER SIZE ANDCLEARENCES DETAIL AND SHOWER
 SEAT DESIGN DETAIL WERE DELETED ON NEW P-2. THOSE
 DETAILS ARE REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-12-15 Cont ID  
Sent By jleech Date 2007-12-15 Time 09:44 Rev Time 0.00
Received By jleech Date 2007-12-15 Time 09:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-17 Cont ID  
Sent By jleech Date 2007-11-17 Time 09:01 Rev Time 0.00
Received By jleech Date 2007-11-17 Time 08:35 Sent To  
Notes
2007-11-17 09:23:17DENIED;
 1. WOMEN'S LOUNGE HANDICAP SHOWER DOES NOT COMPLY. THE
 CLEAR FLOOR SPACE SHALL EXTEND 12" PAST THE SEAT. WALL
 IS IN THE WAY. SEE DETAIL ON PAGE P.2. THE STALL
 ENCLOSURE WILL INTERFERE WITH THE CLEAR FLOOR SPACE.
 SECTION 11-4.21.8.
 2. SHOW LOCATION OF CONTROLS TO COMPLY WITH 11-4.21.5.
 3. TOILET ROOM (BY UTILITY ROOM) SHALL MEET HANDICAP
 REQUIREMENTS SECTION 11-4.1.2(11). IF THIS IS A PRIVATE
 BATH AT IS REQUIRED TO BE ADAPTABLE. THIS BATHROOM DOES
 NOT MEET THOSE REQUIREMENTS.
 4. SHOW DETAIL OF BREAK SINK. SHAL COMPLY WITH SECTIONS
 11-4.24.1 THRU 11-4.24.7. SINK MUST HAVE A FRONTAL
 APPROACH WITH KNEE CLEARANCE PER 11-4.24.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-04 Cont ID  
Sent By jleech Date 2007-10-04 Time 07:05 Rev Time 0.00
Received By jleech Date 2007-10-04 Time 07:05 Sent To  
Notes
2007-10-04 08:21:04DENIED;
 1. PAGE A.0 APLIICABLE CODES, PEASE ADD FLORIDA
 BUILDING CODE PLUMBING 2004/2006 SUPPLEMENTS.
 2. PAGE A.1 FLOOR PLAN DOES NOT MATCH P.1 FLOOR PLAN.
 A.1 IS MISSING 1 LAV AND URINAL.
 3. PLEASE MARK ON PLANS MENS AND WOMANS LOUNGE ON PLANS
 . ( THE FOLLOWING COMMENTS WILL ADDRESS LOUNGE "A" AS
 MENS LOUNGE AND LOUNGE "B" AS WOMANS LOUNGE.)
 4.WOMANS LOUNGE TOILETS REQUIRES A MINIMUM OF 21" FROM
 THE FRONT OF TOILET TO THE WALL. SECTION 405.3.1.
 5.A HANDICAP DRINKING FOUNTAIN IS REQUIRED TO MEET
 MINIMUM REQUIRED PLUMBING FIXTURES SEE TABLE 403.1. D/F
 SHALL COMPLY WITH FBC BUILDING CHAPTER 11
 SECTIONS11-4.1.3(10) AND 11-4.15.1 THRU 11-4.15.5.
 6. SUBMIT MANUFACTURE CUT SHEETS FOR STEAM GENERATOR,
 LOCATION, AND A DETAIL DRAWING SHOWING WATER SUPPLY AND
 LOCATION OF TEMPERATURERELIEF DISCHARGE. SEE
 SECTIONS504.6, 504.6.1, 504.7 AND 504.7.2.
 7. WOMANS LOUNGE SHOWS ONLY ONE LAVATORY PIPED TO
 SANITARY PEASE CORRECT.
 8. SHOWERS IN WOMANS LOUNGE SHOWS SHOWERS AS EXISTING
 AND ALSO THAT ONE TOILET WAS MOVED PLEASE EXPLAIN AND
 SHOW ON SANITARY RISER DIAGRAM.
 9. THE FOLLOWING PLUMBING FIXTURES ARE REQUIRED TO MEET
 CHAPTER 11 OF THE BUILDING CODE;
 ( A) MENS LOUNGE, A LAVATORY IS REQUIRED IN THE
 TOILET STALL 11-4.17.3 EXCEPTION.
 (B) URINAL TO COMPLY WITH SECTIONS 11-4.18.1 THRU
 11-4.18.4.
 (C) MEN AND WOMAN LOUNGE THE SHOWERS ARE REQUIRED
 TO MEET SECTIONS11-4.21.1 THRU 11-4.21.8. ( ONLY ONE
 SHOWER IN WOMANS LOUNGE MUST COMPLY).
 (D) ALL TOILET ROOMS SHALL COMPLY WITH SECTION
 11-4.1.2(6).
 (E) BREAK SINK SHALL COMPLY WITH SECTIONS
 11-4.24.1 THRU 11-4.24.7.
 (F) ONE OF THE TOILETS IN WOMANS LOUNGE SHALL
 MEET THE HANDICAP REQUIREMENTS SEE SECTIONS 11-4.16.1
 THRU 11-4.16.6.
 10. SHOW DETAILS ON PLANS OF ALL HANDICAP FIXTURES
 SHOWING ALL REQUIRED MEASUREMENTS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop Z ZONING
Rev No 1 Status N Date 2007-10-03 Cont ID  
Sent By choops Date 2007-10-03 Time 09:58 Rev Time 0.00
Received By choops Date 2007-10-03 Time 09:58 Sent To  
Notes
2007-10-03 09:58:44*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved