Plan Review Stops For Permit 07090593 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
8 |
Status |
P |
Date |
2008-04-18 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-04-18 |
Time |
08:12 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-04-18 |
Time |
07:22 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
F |
Date |
2008-03-28 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-03-28 |
Time |
15:58 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-03-28 |
Time |
14:38 |
Sent To |
|
|
Notes |
2008-03-28 15:58:41 | BUILDING PLAN REVIEW | | PERMIT: 07090593 | | ADD: 701 S. ROSEMARY AVE #200 | | CONT: SURFSIDE | | TEL: (561) ###-#### | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 3-38-08 | | REVIEW: REVISION | | ACTION: DENIED | | | | 1)TO HELP SPEED UP THE PROCESS FOR ALL REVISIONS, THE | | REVISED AREA NEEDS TO BE CLOUDED WITH A REVISION NUMBER | | WHERE IT CAN BE IDENTIFY EASILY. THIS REVISION HAS MANY | | CLOUDED AREAS WITH NO NUMBERS WHICH MAKES IT DIFFICULT | | TO IDENTIFY THE REVISED AREA FROM THE PREVIOUS | | REVISION. THE DATE OF THE REVISION DRAWING SHALL | | CORRESPOND WITH THE REVISION NUMBER WHICH WILL HELP TO | | IDENTIFY THE AREA. CONSTRUCTION DOCUMENTS SHALL BE OF | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | EXTENT OF THE WORK PROPOSED. FBC 106.1.1 | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | FAX (561) 805-6676 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
N |
Date |
2008-03-27 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-03-27 |
Time |
11:34 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-03-27 |
Time |
11:14 |
Sent To |
PC |
|
Notes |
2008-03-27 11:30:41 | PROCESS PLANS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2008-03-24 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-03-24 |
Time |
07:54 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-03-24 |
Time |
07:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2007-12-19 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-12-19 |
Time |
06:21 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-12-19 |
Time |
06:02 |
Sent To |
PC |
|
Notes |
2007-12-19 06:22:06 | PROCESS PLANS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-12-15 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-12-15 |
Time |
08:05 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-12-14 |
Time |
15:46 |
Sent To |
|
|
Notes |
2007-12-15 07:24:41 | PROVISOR.: | | WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL | | HAVE A SMOOTH, "HARD" NONABSORBENT SURFACE, TO A HEIGHT | | OF 4 FEET ABOVE THE FLOOR.FBC 1210.02. PAINT ON | | DRYWALL ISNOT A "HARD" SURFACE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-11-08 |
|
|
Cont ID |
|
Sent By |
jjohnsto |
Date |
2007-11-08 |
Time |
16:44 |
Rev Time |
2.00 |
Received By |
jjohnsto |
Date |
2007-11-08 |
Time |
14:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-10-09 |
|
|
Cont ID |
|
Sent By |
jjohnsto |
Date |
2007-10-09 |
Time |
11:18 |
Rev Time |
3.00 |
Received By |
jjohnsto |
Date |
2007-10-09 |
Time |
11:14 |
Sent To |
|
|
Notes |
2007-10-09 11:18:17 | CONSTRUCTION SERVICES DEPARTMENT | | 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH, | | FLORIDA33401 | | TEL:561-805-6713FAX: | | 561-805-6731 | | | | JAMES JOHNSTON, PERMIT NO 07090593 | | BUILDING PLAN EXAMINERII | | PROJECT NUSH SPA/SALON | | E-MAIL:JJOHNSTON @WPB.ORG ADDRESS | | 701 S. ROSEMARY, STE 200 | | DATE OCTOBER 5, 2007 | | | | BUILDINGPLANREVIEW | | | | CORRECTION SUBMITTAL | | WHEN RE-SUBMITTINGCORRECTED PLANS FOR PERMITTING, | | PLEASEREMOVE AND REPLACE ANY SHEETS AS NECESSARY. | | INCLUDE A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER WITH A DESCRIPTION OF THE | | REVISION MADE. IDENTIFY THE SHEET OR SPECIFICATION PAGE | | WHERE THE CHANGES CAN BE FOUND AND INCLUDE THE OLD | | SHEETS IN THE RE-SUBMITTAL PACKAGE FOR THE PLAN | | REVIEWER?S REFERENCE. | | THIS SHALL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | COMMENT-FOR YOUR INFORMATION | | | | F.S.713.13NOTICE OF COMMENCEMENT | | FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION. | | IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED | | WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL | | AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT | | ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE | | FIRST INSPECTION. | | COMMENT-FOR YOUR INFORMATION | | | | | | NOTE ON COVER SHEET 1 | | FBC2004 BUILDING W/ 2005 AND 6 REVISIONS | | FBC2004 ACCESSIBILITYCHAPTER 11 | | FBC2004 EXISTING BUILDING | | LEVEL OF ALTERATION | | TYPE OF CONSTRUCTION | | SPRINKLED / UN-SPRINKLED | | NUMBER OF STORIES | | WIND SPEED AND EXPOSURE | | WIND IMPORTANCE FACTOR | | TYPE OF OCCUPANCY | | OCCUPANT LOAD-GROSS - NET | | COMMENTS- PLEASE ADDRESS THE FOLLOWING,FBC 2004 | | ACCESSIBILITY,FBC 2004EXISTING BUILDINGS, | | NUMBER OF STORIES, | | | | FBC EXISTING 503.2 CARPETING. | | NEW CARPETING USED AS AN INTERIOR FLOOR FINISH MATERIAL | | SHALL COMPLY WITH THE RADIANT FLUX REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING . | | | | | | | | | | | | FBC BUILDING CHAPTER 11ACCESSIBILITY | | | | 11-7.2 SALES AND SERVICE COUNTERS, TELLER WINDOWS, | | INFORMATION COUNTERS. | | (1)IN DEPARTMENT STORES AND MISCELLANEOUS RETAIL | | STORES WHERE COUNTERS HAVE CASH REGISTERS AND ARE | | PROVIDED FOR SALES OR DISTRIBUTION OF GOODS OR SERVICES | | TO THE PUBLIC, AT LEAST ONE OF EACH TYPE SHALL HAVE A | | PORTION OF THE COUNTER WHICH IS AT LEAST 36 INCHES (915 | | MM) IN LENGTH WITH A MAXIMUM HEIGHT OF 36 INCHES (915 | | MM) ABOVE THE FINISH FLOOR. IT SHALL BE ON AN | | ACCESSIBLE ROUTE COMPLYING WITH SECTION 11-4.3 . THE | | ACCESSIBLE COUNTERS MUST BE DISPERSED THROUGHOUT THE | | BUILDING OR FACILITY. IN ALTERATIONS WHERE IT IS | | TECHNICALLY INFEASIBLE TO PROVIDE AN ACCESSIBLE | | COUNTER, AN AUXILIARY COUNTER MEETING THESE | | REQUIREMENTS MAY BE PROVIDED. | | COMMENTS-SHEETA.2DETAIL RECEPTION / SALES COUNTER | | FOR ACCESSIBILITY | | | | 11-4.13 DOORS.SEE TEA/MED.CONSDOOR NO 4 | | COMMENTS- ALL REQUIRED DOORS SHALL HAVE AT LEAST A 29? | | CLEAR OPENING FOR ACCESSIBILITY | | | | 11-4.13 DOORS.SEE LOUNGEPOCKET DOOR NO 5 | | COMMENTS- ALL REQUIRED DOORS SHALL HAVE AT LEAST A 29? | | CLEAR OPENING FOR ACCESSIBILITY | | 11-4.13.9 DOOR HARDWARE. | | HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERATING | | DEVICES ON ACCESSIBLE DOORS SHALL HAVE A SHAPE THAT IS | | EASY TO GRASP WITH ONE HAND AND DOES NOT REQUIRE TIGHT | | GRASPING, TIGHT PINCHING, OR TWISTING OF THE WRIST TO | | OPERATE. LEVER-OPERATED MECHANISMS, PUSH-TYPE | | MECHANISMS, AND U-SHAPED HANDLES ARE ACCEPTABLE | | DESIGNS. WHEN SLIDING DOORS ARE FULLY OPEN, OPERATING | | HARDWARE SHALL BE EXPOSED AND USABLE FROM BOTH SIDES. | | HARDWARE REQUIRED FOR ACCESSIBLE DOOR PASSAGE SHALL BE | | MOUNTED NO HIGHER THAN 48 INCHES (1219 MM) ABOVE FINISH | | FLOOR. | | COMMENTS- POCKET DOOR NOT IN COMPLIANCE | | | | 11-4.13 DOORS.SEE STEAM ROOMDOOR NO ? | | COMMENTS- ALL REQUIRED DOORS SHALL HAVE AT LEAST A 29? | | CLEAR OPENING FOR ACCESSIBILITY | | PLEASE IDENTIFY THIS DOOR ON THE DOOR | | SCHEDULE | | | | | | 11-4.13.9 DOOR HARDWARE. | | HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERATING | | DEVICES ON ACCESSIBLE DOORS SHALL HAVE A SHAPE THAT IS | | EASY TO GRASP WITH ONE HAND AND DOES NOT REQUIRE TIGHT | | GRASPING, TIGHT PINCHING, OR TWISTING OF THE WRIST TO | | OPERATE. LEVER-OPERATED MECHANISMS, PUSH-TYPE | | MECHANISMS, AND U-SHAPED HANDLES ARE ACCEPTABLE | | DESIGNS. WHEN SLIDING DOORS ARE FULLY OPEN, OPERATING | | HARDWARE SHALL BE EXPOSED AND USABLE FROM BOTH SIDES. | | HARDWARE REQUIRED FOR ACCESSIBLE DOOR PASSAGE SHALL BE | | MOUNTED NO HIGHER THAN 48 INCHES (1219 MM) ABOVE FINISH | | FLOOR. | | COMMENTS- IDENTIFY HARDWARE SCHEDULE ON ALL DOORS | 2007-10-01 14:31:58 | TO "BOB"#15 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2008-08-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-08-11 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-08-11 |
Time |
09:09 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2008-07-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-07-18 |
Time |
12:46 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-07-18 |
Time |
12:46 |
Sent To |
PC |
|
Notes |
2008-07-18 12:46:21 | ** DENIED REVISIONS ** | | | | | | | | 1) NOTE: PLEASE COORDINATE ALL PLANS. PLEASE SEE THE | | REVISION #5 SHEETS SUBMITTED ON 6/30CONTAIN CHANGES | | WHICH ARE LABELED REVISION #4 YET THE REVISION #4 IS | | NOT THE SAME AS THE REVISION #4 ON SHEETS SUBMITTED | | 6/23/08. | | PLEASE SEE THERE ARE NO REV #5 CLOUDS/TRIANGLES SHOWN | | ON PLANS SUBMITTED 6/30/08. | | | | ** TO DATE OF THIS REVIEW NO PERMIT HAS BEEN APPLIED | | FOR THE INSTALLATION OF THE LOW VOLTAGE SOUND SYSTEM | | WHICH IS NOW SHOWN AS REV #4. | | | | IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-12-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-12-13 |
Time |
13:05 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-12-13 |
Time |
13:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-11-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-11-06 |
Time |
12:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-11-06 |
Time |
10:47 |
Sent To |
|
|
Notes |
2007-11-06 12:11:31 | ** DENIED 2ND REVIEW ** | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ALONG | | WITH SOME NEW COMMENTS ARE IN NEED OF BEING ADDRESSED. | | | | 1) NOTE: PLEASE SEE THE CODES AND NOTES ON PLANS STILL | | NEED TO BE CORRECTED. PLEASE SEE FOR EXAMPLE: THERE ARE | | STILL CODE NOTES ON PLANS TO THE SOUTH FLORIDA BUILDING | | CODE WHICH HAS NOT BEEN IN EFFECT SINCE MARCH 02. | | PLEASE SEE THE ELECTRICAL LOADCALCULATIONS ETC. | | SHEET E.3 | | FBC 106.1.2 | | | | | | 2) NOTE: PLEASE SEE SMOKE DETECTOR NOTES ON PLANS STILL | | CALL FOR RESIDENTIAL INSTALLATIONS. | | ** PLEASE CLARIFY ELECTRICAL NOTES, AND SMOKE DETECTORS | | NOTES AS THESE ARE REFERENCING DWELLING UNIT | | REQUIREMENTS AND NOT THAT OF A COMMERCIAL LOCATION. | | CALLS FOR ARC FAULT PROTECTION ETC. | | PLEASE ADJUST NOTES. | | FBC 106.1.2, 110.1.2 ETC ADMIN COORDINATION AND | | RELEVANT CODES WHICH MAY NOT BE FROM OTHER CODES. | | | | 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND | | CORRELATE WITH THE PANEL SCHEDULES. PLEASE CORRELATE | | CIRCUITING PLANS ALSO. PLEASE SEE ROOMS WHERE | | CIRCUITING TO SPECIALTY LIGHTING AND CIRCUIT NUMBER AND | | PANEL IS BEING REFLECTED HOWEVER THESE DO NOT CORRELATE | | WITH THE SAME ROOMS. | | PLEASE SEE FOR EXAMPLE, SWITCH SHOWS A GCA -26, YET THE | | SAME ROOM SHOWS GCB 28. THIS IS THE SAME FOR SPA ROOM | | #1, #2, ETC. | | PLEASE SEE CIRCUITS WHICH REFERENCE TO A GCH PANEL YET | | NO GCH PANEL SCHEDULE WAS SUBMITTED. | | PLEASE SEE THERE ARE SEVERAL OTHER ELECTRICAL OUTLETS | | ON PLANS WHICH CONTAIN NO CIRCUITING. | | PLEASE SEE THAT THE PANEL SCHEDULES HAVE ALSO NOT BEEN | | REVISED. THE CIRCUITS ARE NOT SHOWN SPECIFIC TO ROOMS | | AND AREAS IN WHICH THEY FEED. PLEASE SEE 408.4,240.4, | | 310.16. | | FBC106.1.2, 106.3.5.1.2, 106.5 ETC. | | | | | | 4) NOTE: LIGHTING CONTROL DEVICES ARE NOT SHOWN FOR ALL | | LIGHTING. EXAMPLE : ALTERNATE SPA ROOM. | | PLEASE INDICATE LIGHTING CONTROLS PER FBC CHAPTER 13 | | FOR NEW LIGHTING CONTROL DEVICES BEING INSTALLED. | | PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND .1.3. | | PLEASE SEE 13-101 | | PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS AS | | SUBMITTED ACTUALLY CALL FOR *VA REQUIRED* ON THE | | TABLE. | | | | PLEASE KNOW THE LIGHTING LEVELS AS STATED IN 13-415.2 | | ON EITHER TABLE AND THE ENERGY CODE IS ACTUALLY FOR | | *MAXIMUM* LIGHTING LEVELS. THESE TABLES IN THE FBC ARE | | NOT LIGHTING REQUIRED. | | PLEASE EXPLAIN WHERE SOME OF THE LIGHTING ALLOWANCE | | FIGURES ARE DERIVED. FOR EXAMPLE OFFICE LEVELS NOTED AT | | 1.5, WHEN THE CODE STATES MAXIMUM AT 1.1. | | PLEASE PLACE A TOTAL ON THE MAXIMUM ALLOWED COMPARED TO | | THE MAXIMUM DESIGN. | | PLEASE SEE THAT THE TRADE OFFS OF TOTAL SPACE IS | | PERMITTED HOWEVER THESE FIGURES NEED TO BE CORRECTED | | AND KNOW. | | PLEASE SEE 13-415.2 | | | | 5) NOTE:THIS IS THE SAME NOTE AS PREVIOUS. | | PLEASE SEE THE PLANS CALL FOR A STEAM ROOM DISCONNECT | | NEXT TO STEAM ROOM HOWEVER THIS DOES NOT SHOW | | CIRCUITING OR LOADS OR LISTED IN ANY PANEL? PLEASE | | COMPLETE PLANS WITH ALL CIRCUITING AND CORRELATE WITH | | PANELS. | | PLEASE SEE THE NEW LIGHTING LOADS WHICH ARE SHOWN | | CIRCUITED AND ON PANELS GCA AND GCB ARE ADDED TO THESE | | PANELS, HOWEVER AS THESE PANELS ARE FED FROM THE | | EXISTING PANEL *GC1* THE LOAD CALCULATIONS HAVE NOT | | BEEN ADJUSTED AND COMPLETED. | | PLEASE SEE ABOVE AS STEAM UNIT ETC IS ALSO NOT | | INCLUDED? | | PLEASE SEE THE CODE SECTIONS REFLECTED ON THE PANEL | | SCHEDULES FOR LOAD CALCULATIONS ARE NOT FROM THE | | CURRENT CODES. | | PLEASE SUBMIT COMPLETED PLANS FOR ALL ELECTRICAL AND | | COMPLETED UPDATED LOAD CALCULATIONS FOR ALL | | ELECTRICAL. | | PLEASE SEE NFPA-70 2005, 220, 215.5, 310.16, 240.4 | | ETC. | | FBC 106.3.5.1.2, 106.1.2 | | | | 6) NOTE:THIS IS THE SAME AS PREVIOUS REVIEW. THE | | CANDELA LEVELS WERE ADDED HOWEVER NOT HORN LEVELS WHERE | | STATED FOR ADA. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE | | THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA | | REQUIRED AREAS.NO DEVICES ARE BEING SHOWN ON | | PLANS/LEGEND. PLEASE KNOW AS THIS BUILDING DOES CONTAIN | | A FIRE ALARM SYSTEM, EITHER THESE DEVICES EXIST OR NEW | | LOCATIONS WILL BE REQUIRED TO MEET THE MINIMUM PER FBC | | ADA. | | . | | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A | | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS | | REQUIRED ON BASE PLANS AS SHOWN. | | FBC 106.3.5.1.2, 106.1.2 ETC | | ** THIS IS BEING NOTED AS NOTES FROM FIRE MARSHAL | | AND/OR BUILDING REVIEWER MAY FOLLOW. | | | | 7) NOTE: PLEASE PROVIDE NOTES ON PLANS PER | | 13-413.1.ABC.1.2 AND .2.2 | | PLEASE SEE THE FBC FOR ACTUAL WORDING REQUIRED ON | | CONSTRUCTION DOCUMENTS. | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-10-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-10-01 |
Time |
19:21 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-10-01 |
Time |
18:41 |
Sent To |
|
|
Notes |
2007-10-01 19:21:14 | 2007-10-01 19:21:14 | | | | ** DENIED *** | | | | 1) NOTE: PLEASE CORRELATE WHERE WORK IS BEING PERFORMED | | AS SHEET A-2 INDICATES *ANUSKA* YET TITLE BLOCKS | | INDICATE *NUSH SPA*? | | PLEASE ADJUST AND COORDINATE. | | FBC 106.1.2, 110.1.2 | | FAC 61G1-16.004 | | | | 2) NOTE: PLEASE SEE THE COVER SHEET DOES REFLECT THE | | RELEVANT CODES WHICH ARE TO BE PART OF PROJECT AND | | DESIGNS HOWEVER THERE ARE SEVERAL COMMENTS AND NOTES ON | | PLANS WHICH REFERENCE CODES WHICH ARE NO LONGER IN | | EFFECT. PLEASE SEE SOME OF THESE IN FACT GO BACK TO | | SOME 1996 CODES. | | PLEASE SEE EXAMPLES ON ELECTRICAL NOTES: | | #3 WHICH STATES THE SFBC, SOUTH FLORIDA BUILDING CODE. | | # 10 AND #15 WHICH REFLECTS CODE FROM THE 1996 NEC. | | | | SMOKE DETECTOR NOTES #4 WHICH GIVES CODE SECTIONS FROM | | THE 1996 NFPA-72. | | | | ** PLEASE CLARIFY ELECTRICAL NOTES, AND SMOKE DETECTORS | | NOTES AS THESE ARE REFERENCING DWELLING UNIT | | REQUIREMENTS AND NOT THAT OF A COMMERCIAL LOCATION. | | CALLS FOR ARC FAULT PROTECTION ETC. | | PLEASE ADJUST NOTES. | | FBC 106.1.2, 110.1.2 ETC ADMIN COORDINATION AND | | RELEVANT CODES WHICH MAY NOT BE FROM OTHER CODES. | | | | 3) NOTE: PLEASE SEE THE PLANS SPECIFICALLY INDICATE A | | NEW ELECTRICAL PANEL HOWEVER NO ELECTRICAL RISER WAS | | SUBMITTED SHOWING THIS NEW PANEL.?? PLEASE ALSO SEE | | NONE OF THE EXISTING PANELS LIST ANY OVER CURRENT | | PROTECTION FOR THIS NEW PANEL WHICH IS NOTED AND SHOWN | | ON E-2 NEXT TO EXISTING PANELS. | | PLEASE COORDINATE AS E-1 DOES NOT INDICATE ANY NEW | | PANEL? | | FBC 106.1.2, 106.3.5.1.2 | | NEC 215.5, 310.16, 240.4, 408.4 ETC | | | | 4) NOTE: PLEASE INDICATE LIGHTING CONTROLS PER FBC | | CHAPTER 13 FOR NEW LIGHTING CONTROL DEVICES BEING | | INSTALLED. PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND | | .1.3. | | PLEASE SEE 13-101 | | PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS AS | | SUBMITTED ACTUALLY CALL FOR *VA REQUIRED* ON THE | | TABLE. | | | | PLEASE KNOW THE LIGHTING LEVELS AS STATED IN 13-415.2 | | ON EITHER TABLE AND THE ENERGY CODE IS ACTUALLY FOR | | *MAXIMUM* LIGHTING LEVELS. THESE TABLES IN THE FBC ARE | | NOT LIGHTING REQUIRED. | | PLEASE LABEL ALL LIGHTING FIXTURES AS SHOWN ON PLANS | | AND CORRELATE WITH A FIXTURE LEGEND TO BE | | SHOWN/SUBMITTED. THE SAME FIXTURE INFORMATION AS LISTED | | IN THE LPC TABLE CAN BE USED HOWEVER EACH WOULD CONTAIN | | A DESIGNATION. PLEASE KNOW AT THIS TIME THERE SEEMS TO | | BE SOME COORDINATION NEED FOR FIXTURE TYPES AND COUNTS | | FOR AREAS. PLEASE SEE POS AREA FOR EXAMPLE. | | PLEASE ADJUST NOTE. | | **PLEASE CALL TO GO OVER. | | | | 5) NOTE: PLEASE SEE THE PLANS CALL FOR A STEAM ROOM | | DISCONNECT NEXT TO STEAM ROOM HOWEVER THIS DOES NOT | | SHOW CIRCUITING OR LOADS OR LISTED IN ANY PANEL? PLEASE | | COMPLETE PLANS WITH ALL CIRCUITING AND CORRELATE WITH | | PANELS. | | PLEASE SEE THE NEW LIGHTING LOADS WHICH ARE SHOWN | | CIRCUITED AND ON PANELS GCA AND GCB ARE ADDED TO THESE | | PANELS, HOWEVER AS THESE PANELS ARE FED FROM THE | | EXISTING PANEL *GC1* THE LOAD CALCULATIONS HAVE NOT | | BEEN ADJUSTED AND COMPLETED. | | PLEASE SEE ABOVE AS STEAM UNIT ETC IS ALSO NOT | | INCLUDED? | | PLEASE SEE THE CODE SECTIONS REFLECTED ON THE PANEL | | SCHEDULES FOR LOAD CALCULATIONS ARE NOT FROM THE | | CURRENT CODES. | | PLEASE SUBMIT COMPLETED PLANS FOR ALL ELECTRICAL AND | | COMPLETED UPDATED LOAD CALCULATIONS FOR ALL | | ELECTRICAL. | | PLEASE SEE NFPA-70 2005, 220, 215.5, 310.16, 240.4 | | ETC. | | FBC 106.3.5.1.2, 106.1.2 | | | | 6) NOTE:PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) | | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR | | ADA REQUIRED AREAS.NO DEVICES ARE BEING SHOWN ON | | PLANS/LEGEND. PLEASE KNOW AS THIS BUILDING DOES CONTAIN | | A FIRE ALARM SYSTEM, EITHER THESE DEVICES EXIST OR NEW | | LOCATIONS WILL BE REQUIRED TO MEET THE MINIMUM PER FBC | | ADA. | | . | | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A | | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS | | REQUIRED ON BASE PLANS AS SHOWN. | | FBC 106.3.5.1.2, 106.1.2 ETC | | ** THIS IS BEING NOTED AS NOTES FROM FIRE MARSHAL | | AND/OR BUILDING REVIEWER MAY FOLLOW. | | | | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SHOWN ON | | PLANS AT THIS TIME, THERE VERY WELL MAY BE NEW COMMENTS | | ON THE FOLLOWING REVIEW. REVIEW NOTES CAN ONLY BE GIVEN | | FOR PLANS/DOCUMENTS AS SUBMITTED. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
F |
Date |
2008-03-31 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-03-31 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-03-31 |
Time |
11:03 |
Sent To |
|
|
Notes |
2008-03-31 11:11:33 | ****FIRE-STAMPING NEEDED***** | | | | | | REVISED PLAN SHEET A-1 TO BE STAMPED, INITIALED, AND | | DATED WHEN THE BUILDING REVIEW COMMENT HAS BEEN | | ADDRESSED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2008-03-26 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-03-26 |
Time |
12:09 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-03-26 |
Time |
12:01 |
Sent To |
|
|
Notes |
2008-03-26 12:08:23 | ****REVISION APPROVED***** | | | | | | REVISED PLAN SHEET A-1 STAMPED, INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-12-17 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-12-17 |
Time |
13:08 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-12-17 |
Time |
12:57 |
Sent To |
B |
|
Notes |
2007-12-17 13:08:13 | *****APPROVED***** | | | | PLAN SHEETS LS-1, A-1, AND E-1 WERE STAMPED, INITIALED, | | AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2007-11-06 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2007-11-06 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-11-06 |
Time |
13:27 |
Sent To |
|
|
Notes |
2007-11-06 13:30:54 | ***APPROVED*** | | | | 1) PLANS STILL INDICATE NOTE REFERENCING RESIDENTIAL | | SMOKE DETECTORS. SHEET E.3 NOTE 3. | | | | 2) OK | | | | 3) OK | | | | 4) OK | | | | 5) OK | | | | 6) OK | | | | PLANS WILL BE STAMPED WHEN RETURNED FOR OTHER REVIEW | | COMMENTS PROVIDED THAT NON-APPLICABLE INFORMATION IS | | DELETED. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-10-04 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2007-10-04 |
Time |
15:59 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-10-04 |
Time |
15:59 |
Sent To |
|
|
Notes |
2007-10-04 16:15:45 | ***DENIED*** | | | | 1) PLANS INDICATE SMOKE DETECTORS AS IT APPLIES TO | | RESIDENTIAL OCCUPANCIES. PLEASE REMOVE INFORMATION THAT | | IS NOT APPLICABLE TO THIS PROJECT. | | | | 2) PLANS ARE SOMEWHAT CONFUSING REGARDING EXITING. | | PLEASE PROVIDE A CLEAR ILLUSTRATION AND COMMON PATH OF | | TRAVEL OF REQUIRED MEANS OF EGRESS SHOWING WHERE | | PERSONS EXIT TO. | | | | 3) INDICATE THE LOCATIONS OF REQUIRED 2A-10B,C RATED | | FIRE EXTINGUISHERS THAT SHALL BE LOCATED NOT TO EXCEED | | 75' TRAVEL DISTANCE. | | | | 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | WITH NFPA 241. | | | | 5) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | SPRINKLER AND FIRE ALARM REMODEL. | | | | 6) DOES THE DOOR TO THE STAIRWELL SWING IN THE CORRECT | | DIRECTION?PLANS INDICATE AN OCCUPANT LOAD OF 100. | | EXIT DOORS TO SWING IN DIRECTION OF TRAVEL. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
13 |
Status |
N |
Date |
2008-08-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-08-05 |
Time |
16:14 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-08-05 |
Time |
16:14 |
Sent To |
|
|
Notes |
2008-08-05 16:15:14 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
12 |
Status |
N |
Date |
2008-07-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-01 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-01 |
Time |
14:11 |
Sent To |
E |
|
Notes |
2008-07-01 14:12:18 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
11 |
Status |
N |
Date |
2008-06-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-24 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-24 |
Time |
15:16 |
Sent To |
E |
|
Notes |
2008-06-24 15:16:39 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2008-04-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-16 |
Time |
10:33 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-16 |
Time |
10:33 |
Sent To |
B |
|
Notes |
2008-04-16 10:35:07 | TO "MJACOBS" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2008-03-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-27 |
Time |
14:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-27 |
Time |
14:43 |
Sent To |
P |
|
Notes |
2008-03-27 14:43:18 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2008-03-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-27 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-27 |
Time |
14:38 |
Sent To |
|
|
Notes |
2008-03-27 14:39:58 | TO "BOB"#9--EXPEDITED-- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2008-03-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-27 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-27 |
Time |
14:18 |
Sent To |
M |
|
Notes |
2008-03-27 14:18:43 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2008-03-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-20 |
Time |
14:45 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-20 |
Time |
14:45 |
Sent To |
P |
|
Notes |
2008-03-20 14:45:52 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-03-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-20 |
Time |
13:42 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-20 |
Time |
13:42 |
Sent To |
M |
|
Notes |
2008-03-20 13:42:29 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-03-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-20 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-20 |
Time |
13:39 |
Sent To |
|
|
Notes |
2008-03-20 13:39:54 | TO "BOB"#1 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-12-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-12 |
Time |
10:46 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-12 |
Time |
10:46 |
Sent To |
|
|
Notes |
2007-12-12 11:28:44 | TO "BOB"#18 | 2007-12-12 10:47:08 | WAITING FOR "BOB" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-10-26 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-26 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-26 |
Time |
16:01 |
Sent To |
|
|
Notes |
2007-11-05 10:53:27 | TO "BOB"#7 | 2007-10-26 16:01:32 | WAITING FOR "BOB" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-10-10 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-10-10 |
Time |
15:28 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2007-09-20 |
Time |
16:32 |
Sent To |
|
|
Notes |
2007-09-20 16:34:05 | WAITING FOR "BOB" |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2008-03-28 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-03-28 |
Time |
11:18 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-03-28 |
Time |
11:18 |
Sent To |
|
|
Notes |
2008-03-28 11:19:57 | REVISION TO MECHANICAL PLAN PAGE M-1. | | | | *** PROVISO *** | | 1) ALL SHOWER ROOMS AND TOILET ROOMS NEED TO COMPLY | | WITH 2004 FBC/M TABLE 403.3 REGARDING EXHAUST. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2008-03-20 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-03-20 |
Time |
15:30 |
Rev Time |
0.50 |
Received By |
tgordon |
Date |
2008-03-20 |
Time |
15:30 |
Sent To |
|
|
Notes |
2008-03-20 15:41:35 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | ** MECHANICAL REVISION ** | | *** DENIED *** | | 1) SEE YELLOW HIGH LIGHT ON PLAN SHOWING DUCTS (FLEX) | | THAT NEEDS TO BE SIZED, PER 2004 FBC/M 106.3.5. | | | | 2) SEE YELLOW HIGH LIGHT ON PLAN SHOWING A SUPPLY AIR | | GRILL THAT NEEDS THE SIZE AND CFM'S SHOWN. | | | | 3) SEE YELLOW HIGH LIGHT ON PLAN SHOWING A RETURN AIR | | GRILL THAT NEEDS THE SIZE ADDED. | | | | 4) SEE YELLOW HIGH LIGHT ON PLAN SHOWING A SUPPLY AIR | | GRILL IN THE WAX ROOM AND ONE IN THE HALL LISTED AS | | RETURN GRILLS, ALSO SEE NOTE #2. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-12-12 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-12-12 |
Time |
15:00 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-12-12 |
Time |
15:00 |
Sent To |
|
|
Notes |
2007-12-12 15:01:15 | *** PROVISO *** | | 1) ALL SHOWER ROOMS AND TOILET ROOMS NEED TO COMPLY | | WITH 2004 FBC/M TABLE 403.3 REGARDING EXHAUST. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2007-11-06 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-11-06 |
Time |
08:18 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-11-06 |
Time |
08:18 |
Sent To |
|
|
Notes |
2007-11-06 08:21:50 | *** PROVISO *** | | 1) ALL SHOWER ROOMS AND TOILET ROOMS NEED TO COMPLY | | WITH 2004 FBC/M TABLE 403.3 REGARDING EXHAUST. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2007-10-10 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-10-10 |
Time |
15:28 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-10-10 |
Time |
15:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2008-04-01 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2008-04-01 |
Time |
08:29 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2008-04-01 |
Time |
08:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2008-03-24 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2008-03-24 |
Time |
09:31 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2008-03-24 |
Time |
09:14 |
Sent To |
|
|
Notes |
2008-03-24 09:48:35 | REVISION DENIED; | | 1. PAGE P-1 WOMAN'S LOUNGE, ONE SHOWER SHALL MEET | | HANDICAP CODE REQUIREMENTS. SHOW GRAB BARS AND SEAT ON | | PLANS. | | 2. PAGE P-2 SHOWER SIZE ANDCLEARENCES DETAIL AND SHOWER | | SEAT DESIGN DETAIL WERE DELETED ON NEW P-2. THOSE | | DETAILS ARE REQUIRED. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2007-12-15 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-12-15 |
Time |
09:44 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-12-15 |
Time |
09:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-11-17 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-11-17 |
Time |
09:01 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-11-17 |
Time |
08:35 |
Sent To |
|
|
Notes |
2007-11-17 09:23:17 | DENIED; | | 1. WOMEN'S LOUNGE HANDICAP SHOWER DOES NOT COMPLY. THE | | CLEAR FLOOR SPACE SHALL EXTEND 12" PAST THE SEAT. WALL | | IS IN THE WAY. SEE DETAIL ON PAGE P.2. THE STALL | | ENCLOSURE WILL INTERFERE WITH THE CLEAR FLOOR SPACE. | | SECTION 11-4.21.8. | | 2. SHOW LOCATION OF CONTROLS TO COMPLY WITH 11-4.21.5. | | 3. TOILET ROOM (BY UTILITY ROOM) SHALL MEET HANDICAP | | REQUIREMENTS SECTION 11-4.1.2(11). IF THIS IS A PRIVATE | | BATH AT IS REQUIRED TO BE ADAPTABLE. THIS BATHROOM DOES | | NOT MEET THOSE REQUIREMENTS. | | 4. SHOW DETAIL OF BREAK SINK. SHAL COMPLY WITH SECTIONS | | 11-4.24.1 THRU 11-4.24.7. SINK MUST HAVE A FRONTAL | | APPROACH WITH KNEE CLEARANCE PER 11-4.24.3. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-10-04 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-10-04 |
Time |
07:05 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-10-04 |
Time |
07:05 |
Sent To |
|
|
Notes |
2007-10-04 08:21:04 | DENIED; | | 1. PAGE A.0 APLIICABLE CODES, PEASE ADD FLORIDA | | BUILDING CODE PLUMBING 2004/2006 SUPPLEMENTS. | | 2. PAGE A.1 FLOOR PLAN DOES NOT MATCH P.1 FLOOR PLAN. | | A.1 IS MISSING 1 LAV AND URINAL. | | 3. PLEASE MARK ON PLANS MENS AND WOMANS LOUNGE ON PLANS | | . ( THE FOLLOWING COMMENTS WILL ADDRESS LOUNGE "A" AS | | MENS LOUNGE AND LOUNGE "B" AS WOMANS LOUNGE.) | | 4.WOMANS LOUNGE TOILETS REQUIRES A MINIMUM OF 21" FROM | | THE FRONT OF TOILET TO THE WALL. SECTION 405.3.1. | | 5.A HANDICAP DRINKING FOUNTAIN IS REQUIRED TO MEET | | MINIMUM REQUIRED PLUMBING FIXTURES SEE TABLE 403.1. D/F | | SHALL COMPLY WITH FBC BUILDING CHAPTER 11 | | SECTIONS11-4.1.3(10) AND 11-4.15.1 THRU 11-4.15.5. | | 6. SUBMIT MANUFACTURE CUT SHEETS FOR STEAM GENERATOR, | | LOCATION, AND A DETAIL DRAWING SHOWING WATER SUPPLY AND | | LOCATION OF TEMPERATURERELIEF DISCHARGE. SEE | | SECTIONS504.6, 504.6.1, 504.7 AND 504.7.2. | | 7. WOMANS LOUNGE SHOWS ONLY ONE LAVATORY PIPED TO | | SANITARY PEASE CORRECT. | | 8. SHOWERS IN WOMANS LOUNGE SHOWS SHOWERS AS EXISTING | | AND ALSO THAT ONE TOILET WAS MOVED PLEASE EXPLAIN AND | | SHOW ON SANITARY RISER DIAGRAM. | | 9. THE FOLLOWING PLUMBING FIXTURES ARE REQUIRED TO MEET | | CHAPTER 11 OF THE BUILDING CODE; | | ( A) MENS LOUNGE, A LAVATORY IS REQUIRED IN THE | | TOILET STALL 11-4.17.3 EXCEPTION. | | (B) URINAL TO COMPLY WITH SECTIONS 11-4.18.1 THRU | | 11-4.18.4. | | (C) MEN AND WOMAN LOUNGE THE SHOWERS ARE REQUIRED | | TO MEET SECTIONS11-4.21.1 THRU 11-4.21.8. ( ONLY ONE | | SHOWER IN WOMANS LOUNGE MUST COMPLY). | | (D) ALL TOILET ROOMS SHALL COMPLY WITH SECTION | | 11-4.1.2(6). | | (E) BREAK SINK SHALL COMPLY WITH SECTIONS | | 11-4.24.1 THRU 11-4.24.7. | | (F) ONE OF THE TOILETS IN WOMANS LOUNGE SHALL | | MEET THE HANDICAP REQUIREMENTS SEE SECTIONS 11-4.16.1 | | THRU 11-4.16.6. | | 10. SHOW DETAILS ON PLANS OF ALL HANDICAP FIXTURES | | SHOWING ALL REQUIRED MEASUREMENTS. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2007-10-03 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-10-03 |
Time |
09:58 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-10-03 |
Time |
09:58 |
Sent To |
|
|
Notes |
2007-10-03 09:58:44 | *ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK | | DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. |
|
|