Plan Review Details - Permit 07090562
Plan Review Stops For Permit 07090562
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-26 Cont ID  
Sent By mjacobs Date 2007-10-26 Time 18:46 Rev Time 0.00
Received By mjacobs Date 2007-10-26 Time 17:42 Sent To P
Notes
2007-10-26 18:46:38 
 PROVISOR: PROVIDE A UL DESIGN NUMBER WITH INFORMATION
 FOR THE FIRE PARTITION WALL AND ANY PENETRATION IN THE
 WALLS TO THE INSPECTOR UPON THE FIRST INSPECTION. WALL
 SEPARATING INDIVIDUAL UNITS SHALL HAVE A
 FIRE-RESISTANCE RATING AT LEAST 1 HOUR. FBC708.3

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-18 Cont ID  
Sent By mjacobs Date 2007-10-18 Time 08:52 Rev Time 0.00
Received By mjacobs Date 2007-10-18 Time 06:54 Sent To PC
Notes
2007-10-18 08:52:46BUILDING PLAN REVIEW
 PERMIT:07090562
 ADD: 2600 N. FLAGLER DR. #710
 CONT: K.L. BREEN BLDRS INC.
 TEL: (561) 856-0232
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006/2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
 10/18/07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 **NOTED, HOWEVER, THE ALTERATION LEVEL STATED IS
 INCORRECT**
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST TO
 INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISHES AND DESIGN FEES. OUR VALUATION
 REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES. ** NOTED HOWEVER, THE COST OF THE
 PROJECT SHALL BE A FAIR MARKET VALUE. **
  
 4)ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE
 DESIGNED TO THE 2004 FLORIDA BUILDING CODE. **THIS
 INFORMATION SHALL BE INDICATED ON THE DRAWINGS. **
  
 5)WPB AMENDMENTS 106.1.3 CONSTRUCTION DOCUMENTS SHALL
 BE DIMENSIONED AND DRAWN TO MINIMUM 1/8 INCH SCALE. THE
 DRAWINGS SUBMITTED DOES NOT SHOW CLEARLY THE PROPOSED
 WORK INDICATED ON THE APPLICATION. SUBMIT AN EXISTING
 FLOOR PLAN AND A PROPOSED FLOOR PLAN SHOWING ALL
 CHANGES TO PROVIDE CONFORMITY TO RECORD RETENTION
 PROGRAM. SUBMIT DRAFTSMAN QUALITY DRAWINGS WITH A WALL
 LEGEND OF EACH TYPE OF WALL TO BE CONSTRUCTED OR DEMO.
 **NO ADDRESSED**
 **NEW**
 A)WPB AMENDMENTS 106.1.3 BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER. THE PLANS SHALL BE OF DRAFTSMAN QUALITY,
 INDICATING CLEARLY THE AREA OF WORK. HAND-WRITING OR
 WHITE-OUT IS NOT ACCEPTABLE ON THE DRAWINGS. THE
 DESIGNER OF RECORD SHALL DATE, PRINT, AND SIGN THEIR
 NAME ON ALL SHEETS.
  
 B)FBC 106.1.1 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-06 Cont ID  
Sent By mjacobs Date 2007-10-06 Time 10:14 Rev Time 0.00
Received By mjacobs Date 2007-10-05 Time 17:51 Sent To  
Notes
2007-10-05 18:56:49 
  
  
  
 BUILDING PLAN REVIEW
 PERMIT:07090562
 ADD: 2600 N. FLAGLER DR. #710
 CONT: K.L. BREEN BLDRS INC.
 TEL: (561) 856-0232
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006/2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED 10/5/07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST TO
 INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISHES AND DESIGN FEES. OUR VALUATION
 REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES.
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 . -------------------------------------
 ) NUMBER OF BEDROOMS
 ) NUMBER OF ROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
  
 5)WPB AMENDMENTS 106.1.3 CONSTRUCTION DOCUMENTS SHALL
 BE DIMENSIONED AND DRAWN TO MINIMUM 1/8 INCH SCALE. THE
 DRAWINGS SUBMITTED DOES NOT SHOW CLEARLY THE PROPOSED
 WORK INDICATED ON THE APPLICATION. SUBMIT AN EXISTING
 FLOOR PLAN AND A PROPOSED FLOOR PLAN SHOWING ALL
 CHANGES TO PROVIDE CONFORMITY TO RECORD RETENTION
 PROGRAM. SUBMIT DRAFTSMAN QUALITY DRAWINGS WITH A WALL
 LEGEND OF EACH TYPE OF WALL TO BE CONSTRUCTED OR DEMO.
  
 6)PER FLORIDA STATUTES 481.229 EXEMPTION FROM
 ARCHITECTURAL LICENSURE ONLY APPLIES TO 1FAMILY AND 2
 FAMILY RESIDENCES (R3) NOT MULTI FAMILY (R2) OR
 BUILDINGS OVER $25,000, THEREFORE, DRAWINGS ARE
 REQUIRED TO BE DRAWN BY A LICENSED DESIGN
 PROFESSIONAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2007-10-25 Cont ID  
Sent By dpalmer Date 2007-10-25 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2007-10-25 Time 16:08 Sent To  
Notes
2007-10-25 16:09:43REVIEW UNDER ELECTRICAL PERMIT.
 MAY NOT HAVE SWITCHED RECEPTACLE IN CLOSET TO FEED ROPE
 LIGHTING AS SHOWNS. THE MINIMUM CLEARANCES ARE NOT MET
 PER 410.8 OF THE NATIONAL ELECTRICAL CODE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-15 Cont ID  
Sent By dpalmer Date 2007-10-15 Time 11:54 Rev Time 0.00
Received By dpalmer Date 2007-10-15 Time 11:54 Sent To B
Notes
2007-10-15 11:54:41**** DENIED 2ND REVIEW****
  
  
 1) NOTE: PLEASE SEE THE PLANS SUBMITTED DO NOT CONTAIN
 ANY ELECTRICAL AND THE ELECTRICAL PERMIT APPLICATION
 AND PLANS SUBMITTED SEPARATELY DO NOT CORRELATE FOR THE
 FLOOR LAYOUT AND SCOPE OF WORK. THERE ARE COMPLETELY
 DIFFERENT WALLS, CLOSETS AND LAYOUTS
 THE ELECTRICAL PLANS ONCE REVIEWED WILL HAVE NOTES
 ATTACHED.
 PLEASE SEE THE PLANS WERE ALSO SUBMITTED IN RED PEN,
 BLACK PEN, WHITE OUT ETC.
 PLEASE SEE THAT PLANS MUST MEET A MINIMUM STANDARD FOR
 CONSTRUCTION DOCUMENTS AND MAY NOT BE DONE AS SHOWN.
 PLEASE SEE THIS WAS NOTED ON PREVIOUS REVIEW BY THE
 BUILDING REVIEWER ALSO AND PLANS WERE STILL SUBMITTED
 IN THIS FASHION.
 FBC 106.1, 106.1.2, 106.3.5.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW, IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-26 Cont ID  
Sent By dpalmer Date 2007-09-26 Time 09:41 Rev Time 0.00
Received By dpalmer Date 2007-09-26 Time 09:41 Sent To  
Notes
2007-09-26 09:41:13** DENIED **
  
 1) NOTE: PLEASE SUBMIT ELECTRICLA PLANS/DRAWINGS
 SHOWING AND INDICATING THE NEW AND EXISITNG ELECTRICAL
 WORK BEING INSTALLED OR RELOCATED.
 PLEASE KNOW ANY NEW CIRCUITING WILL NEEED TO BE SHOWN
 AND INDICATED TO THE PANEL SCHEDULE FOR MINMIMUM
 DEDICATED CIRCUITS. (SEE 210.52D, 210.11C3 FOR
 DEDICATED BATHROOMS)
 PLEASE INDICATE NEW OR EXISTING SMOKE ALARMSINSIDE
 AND OUTSIDE SLEEPING ROOMS.
 ** 210.52D, 210.11C3, 408.4, 310.16, 240.4, FBC
 106.3.5.4
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-25 Cont ID  
Sent By adarroug Date 2007-10-25 Time 15:54 Rev Time 0.00
Received By adarroug Date 2007-10-25 Time 15:54 Sent To B
Notes
2007-10-25 15:54:18TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-23 Cont ID  
Sent By adarroug Date 2007-10-23 Time 10:20 Rev Time 0.00
Received By adarroug Date 2007-10-23 Time 10:20 Sent To  
Notes
2007-10-23 10:21:43WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 10:34 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 10:34 Sent To E
Notes
2007-10-15 10:34:51TO "DPALMER" DESK/ PER "RBROWN"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-09 Cont ID  
Sent By jleech Date 2007-10-09 Time 08:47 Rev Time 0.00
Received By jleech Date 2007-09-19 Time 16:46 Sent To  
Notes
2007-09-25 15:59:50TO "BOB"#4
2007-09-19 16:48:19WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-10-09 Cont ID  
Sent By jleech Date 2007-10-09 Time 08:42 Rev Time  
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-10-27 Cont ID  
Sent By jleech Date 2007-10-27 Time 06:16 Rev Time 0.00
Received By jleech Date 2007-10-27 Time 06:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-09 Cont ID  
Sent By jleech Date 2007-10-09 Time 08:42 Rev Time 0.00
Received By jleech Date 2007-10-09 Time 08:42 Sent To  
Notes
2007-10-09 08:46:54DENIED;
 COMPLY WITH BUILDING PLAN REVIEW COMMENTS 2 THRU 6.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-10-03 Cont ID  
Sent By choops Date 2007-10-03 Time 10:02 Rev Time 0.00
Received By choops Date 2007-10-03 Time 10:02 Sent To  
Notes
2007-10-03 10:02:40*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.