Plan Review Details - Permit 07090553
Plan Review Stops For Permit 07090553
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-06-13 Cont ID  
Sent By lursu Date 2008-06-13 Time 11:24 Rev Time 0.00
Received By lursu Date 2007-10-23 Time 08:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-07-20 Cont ID  
Sent By jwitmer Date 2009-07-20 Time 12:10 Rev Time 0.45
Received By jwitmer Date 2009-07-20 Time 11:45 Sent To PC
Notes
2009-07-20 11:51:4407090553
 REVISIONS:
 S-4 REV# 2
 S-6 REV# 1
 S-7 REV # 3

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-07-15 Cont ID  
Sent By jwitmer Date 2009-07-15 Time 16:13 Rev Time 0.55
Received By jwitmer Date 2009-07-15 Time 15:45 Sent To  
Notes
2009-07-15 16:16:55REVISION; PRODUCT APPROVALS;
 FL 3341
 LOUVER: NOA 08-1003.07

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-12-05 Cont ID  
Sent By mjacobs Date 2008-12-05 Time 15:52 Rev Time 0.00
Received By mjacobs Date 2008-12-05 Time 15:51 Sent To PC
Notes
2008-12-05 15:52:01PROCESS PLANS AND PRINT PERMIT .

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-11-21 Cont ID  
Sent By mjacobs Date 2008-11-21 Time 10:01 Rev Time 0.00
Received By mjacobs Date 2008-11-17 Time 15:44 Sent To  
Notes
2008-11-17 15:45:39I AM WAITING FOR A FEW PRODUCT APPROVALS FROM THE
 CONTRACTOR.
  
 BUILDING PLAN REVIEW
 PERMIT: 07090553
 ADD: 6255 N. JOG ROAD
 CONT: WEST CONSTRUCTION INC.
 TEL: (561)588-2027
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 9-5-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1) OK
 2) OK
 3) OK
 4) OK
 5) OK
 6) OK
 7) OK
 8) OK
 9) OK
 10) OK
  
 PROVISOR: PRIOR TO INSTALLATION.
 11) PROVIDE THE SHOP DRAWINGS WHICH SHALL INCLUDE ALL
 ROOFING/ JOIST / ALUMINUM LADDER WITH PLATFORM AND
 STRUCTURAL DETAILS ETC. FOR THE BUILDING AS STATED ON
 SHEET S-1, S-2 AND S-5. THE DRAWINGS SHALL BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD. SHEET S-7 MAKES
 REFERENCE TO SEE NOTE #6 WHICH IN NOT ON THE SHEET.
 DETAIL #9 ON SHEET S-7 REQUIRES THE ENGINEERED DESIGN
 FOR THE OVERHANG.
  
 12) OK
 NEW: (A) OK
 (B) OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-09-05 Cont ID  
Sent By mjacobs Date 2008-09-05 Time 16:58 Rev Time 0.00
Received By mjacobs Date 2008-09-05 Time 06:57 Sent To  
Notes
2008-09-05 16:53:09BUILDING PLAN REVIEW
 PERMIT: 07090553
 ADD: 6255 N. JOG ROAD
 CONT: WEST CONSTRUCTION INC.
 TEL: (561)588-2027
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 9-5-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1) OK
 2) OK
  
 RESPONSE NOTED: HOWEVER; THIS INFORMATION IS STILL
 REQUIRED.
 3) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PLEASE
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS: (A) ROLL-UP DOORS (B) SHUTTERS
 (C) WINDOWS (D) INSULATED METAL ROOF PANELS (E) METAL
 WALL PANELS (F ) HOLLOW METAL DOORS (G) IMPACT GLASS
 DOOR (H) ALUMINUM LOUVERS 106.3.3* PRODUCT PPROVALS-
 2004 THOSE PRODUCTS THAT ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 RESPONSE NOTED: HOWEVER; THIS INFORMATION IS STILL
 REQUIRED.
 4) SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
 1. COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG.
 3. ON THE PRODUCT APPROVAL, MARK WHICH DETAILS APPLY TO
 THIS JOB. PLEASE USE INK RATHER THAN A HIGHLIGHTER. SEE
 ADDITIONAL INFORMATION IN PACKAGE.
  
 RESPONSE NOTED: HOWEVER; THIS INFORMATION IS STILL
 REQUIRED.
 5) ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
 ____ 1) CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION, SEE ATTACHED POLICY: MEAN ROOF HEIGHT/
 ROOF PITCH / ROOF DECK TYPE / AREA OF EACH ROOF TYPE
 ____2) FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE EVALUATION REPORT SUBMITTED,
 FAC9B72. WWW.FLORIDABUILDING.ORG
 ____3) FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY
 YOU ARE USING. ALSO INDICATE WHICH FASTENER IF THE
 OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
 ____5) FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
 ___ 6) SEE PRODUCT LIMITATION #7. CALCULATIONS PREPARED
 BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  
  
 6) OK
 7) OK
 8) OK
 9) OK
 10) OK
  
 PROVISOR: PRIOR TO INSTALLATION.
 11) PROVIDE THE SHOP DRAWINGS WHICH SHALL INCLUDE ALL
 ROOFING/ JOIST / ALUMINUM LADDER WITH PLATFORM AND
 STRUCTURAL DETAILS ETC. FOR THE BUILDING AS STATED ON
 SHEET S-1, S-2 AND S-5. THE DRAWINGS SHALL BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD. SHEET S-7 MAKES
 REFERENCE TO SEE NOTE #6 WHICH IN NOT ON THE SHEET.
 DETAIL #9 ON SHEET S-7 REQUIRES THE ENGINEERED DESIGN
 FOR THE OVERHANG.
  
 12) OK
  
 NEW: (A) INDICATE THE R-VALUE FOR THE FOAM INSULATION
 IN THE CMU EXTERIOR WALLS.
  
 (B) THE DRAWINGS FROM NUCOR BUILDING SYSTEMS SHALL
 CONTAIN THE ORIGINAL SIGNATURE OF THE PROFESSIONAL
 ENGINEER. THE SIGNATURE ON THE SHEETS IS A PHOTO-COPY
 SIGNATURE. ALL DOCUMENTS BEING FILED FOR PUBLIC RECORD
 SHALL CONTAIN THE ORIGINAL SIGNATURE OF THE PERSON WHO
 RESPONSIBLE FOR THE DOCUMENT. A PROFESSIONAL ENGINEER
 SHALL SIGN HIS NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS, FINAL BID DOCUMENTS AND OTHER
 DOCUMENTS PREPARED OR ISSUED BY SAID REGISTRANT AND
 BEING FILED FOR PUBLIC RECORD. FAC 61G15-23.002 AND
 FLORIDA STATUTES 471 ALSO SEE FBC 106.1. NOTE: A COVER
 OR INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE
 USED AND THAT SHEET MUST BE SIGNED, SEALED AND DATED BY
 THOSE PROFESSIONAL ENGINEERS IN RESPONSIBLE CHARGE OF
 THE PRODUCTION AND PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION, AND IF PRACTICING TROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS, THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS SHALL BE INDICATED ON THE SHEET
 WITH SUFFICIENT INFORMATION ON THE COVER SHEET OR INDEX
 SO THAT THE USER WILL BE AWARE OF EACH PORTION OF THE
 DOCUMENT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-05 Cont ID  
Sent By mjacobs Date 2008-06-05 Time 15:42 Rev Time 0.00
Received By mjacobs Date 2008-06-02 Time 14:53 Sent To  
Notes
2008-06-05 15:42:07BUILDING PLAN REVIEW
 PERMIT: 07090553
 ADD: 6255 N. JOG ROAD
 CONT: WEST CONSTRUCTION INC.
 TEL: (561)588-2027
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 6-3-08
 REVIEW: 2ST
 ACTION: DENIED
  
 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) SHEET LS-1 INDICATES THE OCCUPANCY AS A MIXED
 OCCUPANCY WITH A S-1 MEDIUM HAZARD SECTION. THERE IS NO
 MEDIUM HAZARD MENTION IN THE CODE, SO PLEASE CHANGE THE
 INFORMATION ON THE PLANS TO REFLECT THE CORRECT TYPE OF
 OCCUPANCY; SEE FBC 311 FOR ADDITIONAL INFORMATION.
 PROVIDE THE MSDS INFORMATION ON ALL TYPES AND QUANTITY
 OF MATERIALS WHICH WILL BE STORED OR PLACE IN THIS
 AREA. THE GROSS BUILDING AREA HAS THE NUMBER 17,500 X
 3, WHICH TABLE DID THIS NUMBER CAME FROM FOR THE TYPE
 VB BUILDING? CLARIFY. PLEASE INDICATE THE FLOOD ZONE
 INFORMATION ON THE PLANS.
  
 3) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PLEASE
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS: (A) ROLL-UP DOORS (B) SHUTTERS
 (C) WINDOWS (D) INSULATED METAL ROOF PANELS (E) METAL
 WALL PANELS (F ) HOLLOW METAL DOORS (G) IMPACT GLASS
 DOOR 106.3.3* PRODUCT PPROVALS- 2004 THOSE PRODUCTS
 THAT ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
 1. COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG.
 3. ON THE PRODUCT APPROVAL, MARK WHICH DETAILS APPLY TO
 THIS JOB. PLEASE USE INK RATHER THAN A HIGHLIGHTER. SEE
 ADDITIONAL INFORMATION IN PACKAGE.
  
 5) ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
 ____ 1) CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION, SEE ATTACHED POLICY: MEAN ROOF HEIGHT/
 ROOF PITCH / ROOF DECK TYPE / AREA OF EACH ROOF TYPE
 ____2) FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE EVALUATION REPORT SUBMITTED,
 FAC9B72. WWW.FLORIDABUILDING.ORG ____3)
 FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY YOU ARE
 USING. ALSO INDICATE WHICH FASTENER IF THE OPTIONS HAVE
 DIFFERENT PRESSURE LIMITATIONS. ____5) FOR THE FLAT
 DECK, SPECIFY THE ENHANCED FASTENING FOR CORNER AND
 PERIMETER ZONES.
 ___ 6) SEE PRODUCT LIMITATION #7. CALCULATIONS PREPARED
 BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  
 6) FBC 1802. THE SOIL REPORT SUBMITTED BY TIERRA
 ENGINEERING NEEDS THE ORIGINAL SEAL, CERTIFICATE OF
 AUTHORIZATION NUMBER AND SIGNATURE OF THE PERSON TAKING
 RESPONSIBLE FOR THE REPORT.
 AN ENGINEER PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND
 LICENCE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION # ON EACH SHEET PER 61G15-23.002 (2)
 FAC
  
 7) FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED. SHEET A-1 FLOOR PLAN IS MISSING THE
 DIMENSIONS FOR ALL THE ROOMS.
  
 8) SHEET S-3 DETAIL #2; ON THIS SHEET SHOWS THE
 MEZZANINE PRE-STRESSED PRE-CAST CONCRETE @ 5? O.C AND
 THE MEZZANINE PLAN SHOWS THEM AT 4? O.C. CLARIFY.
  
 9) 1009.11.5 HANDRAILS SHALL RETURN TO A WALL, GUARD OR
 THE WALKING SURFACE OR SHALL BE CONTINUOUS TO THE
 HANDRAIL OF AN ADJACENT STAIR FLIGHT. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY AT LEAST 12 INCHES BEYOND THE TOP
 RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD
 BEYOND THE BOTTOM RISER. 11-4.9(2) AT THE BOTTOM, THE
 HANDRAIL SHALL CONTINUE TO SLOPE FOR A DISTANCE OF THE
 WIDTH OF ONE TREAD FROM THE BOTTOM RISER; THE REMAINDER
 OF THE EXTENSION SHALL BE HORIZONTAL SEE FIGURE 19C AND
 19D. SEE SHEETS S-3 / A-6.
  
 10) FBC 505.1 THE CLEAR HEIGHT ABOVE AND BELOW THE
 MEZZANINE FLOOR CONSTRUCTION SHALL NOT BE LESS THAN 7
 FEET. CLEARLY INDICATE THE HEIGHT BETWEEN THE MEZZANINE
 FLOOR AND THE CEILING ABOVE. 110.4.2 STORAGE & FACTORY-
 INDUSTRIAL OCCUPANCIES. THE CALCULATIONS FOR THE
 MEZZANINE FLOOR LOAD SHALL BE SUBMITTED AND ACCOMPANIED
 BY AN AFFIDAVIT FROM THE ARCHITECT OR ENGINEER STATING
 THE SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS
 PER SQ FT. THE COMPUTATIONS & AFFIDAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
  
 11) PROVIDE THE SHOP DRAWINGS WHICH SHALL INCLUDE ALL
 ROOFING/ JOIST / ALUMINUM LADDER WITH PLATFORM AND
 STRUCTURAL DETAILS ETC. FOR THE BUILDING AS STATED ON
 SHEET S-1, S-2 AND S-5. THE DRAWINGS SHALL BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD. SHEET S-7 MAKES
 REFERENCE TO SEE NOTE #6 WHICH IN NOT ON THE SHEET.
 DETAIL #9 ON SHEET S-7 REQUIRES THE ENGINEERED DESIGN
 FOR THE OVERHANG.
  
 12) 11-4.4.2 HEAD ROOM. WALKS, HALLS, CORRIDORS,
 PASSAGEWAYS, AISLES OR OTHER CIRCULATION SPACES SHALL
 HAVE 80 INCHES MINIMUM CLEAR HEAD ROOM (SEE FIGURE
 8(A). IF VERTICAL CLEARANCE OF AN AREA ADJOINING AN
 ACCESSIBLE ROUTE IS REDUCED TO LESS THAN 80 IN.
 (NOMINAL DIMENSION), A BARRIER TO WARN BLIND OR
 VISUALLY-IMPAIRED PERSONS SHALL BE PROVIDED. (SEE
 FIGURE 8(C-1).
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
2008-06-04 17:58:16 

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2007-10-29 Time   Rev Time 12.00
Received By jjohnsto Date 2007-10-26 Time 09:55 Sent To  
Notes
2007-10-29 11:40:30CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR,
 WEST PALM BEACH, FLORIDA33401
 TEL:561-805-6713FAX:561-805-6731
  
 JAMES JOHNSTON,
 BUILDING PLAN EXAMINER II
 E-MAIL:JJOHNSTON @WPB.ORG
  
  
  
  
 BASIC WIND SPEED ? MPH140
  
 PERMIT NO 07090553
 PROJECTMAINTENANCE FACILITY SOLID WASTE ADDRESS
 6255 N JOG ROAD
  
 DATE10/26/07
  
  
 BUILDINGPLANREVIEW
  
 FLORIDA BUILDING CODES 2004
  
 1
 PROJECT INFORMATION SHEETLS-1
 FBCBUILDING503
 TYPE OF CONSTRUCTION V - B
 THEB OCCUPANCY IS RATED V-B
 S-1 OCCUPANCY IS RATEDV-B
 COMMENT-PLEASE NOTE ON SHEETLS-1
  
  
 1-A
 WPB AMENDMENTS TO FBC 2004 EDITION
 BASIC WIND SPEED
 117.1 BASIC WIND SPEED. THE CITY OF WEST PALM BEACH
 FALLS ENTIRELY IN THE 140 MPH REGION COMMENT-THE
 BASIC WIND SPEED IS 140 MPH
 PLEASE NOTE ON SHEETLS-1
  
  
 1-B
 FBCBUILDING1604.5
 WIND IMPORTANCE FACTORII
 COMMENT-
 PLEASE NOTE ON SHEETLS-1
  
 1-C
 FBCBUILDING 1604.5
 WIND EXPOSURE
 COMMENT-
 PLEASE NOTE ON SHEETLS-1
  
  
 2
 FBCBUILDING1802.6SOIL TEST REPORT
 THE SOIL CLASSIFICATION AND DESIGN LOAD-BEARING
 CAPACITY
 SHALL BE SHOWN ON THE CONSTRUCTION DOCUMENT.
 WHERE REQUIRED BY THE BUILDING OFFICIAL, A WRITTEN
 REPORT
 OF THE INVESTIGATION SHALL BE SUBMITTED THAT INCLUDES,
 BUT NEED NOT BE LIMITED TO, THE FOLLOWING INFORMATION:
 COMMENT-PLEASE SUBMIT THE SOIL TEST REPORT FOR THIS
 PROJECT
  
  
 3
 WPB ADMENDMENT109.3.4 TERMITES. BUILDING COMPONENTS
 AND BUILDING SURROUNDINGS REQUIRED TO BE PROTECTED FROM
 TERMITE DAMAGE IN ACCORDANCE WITH SECTION 1503.6,
 SECTION 2304.13 OR SECTION 2304.11.6, SPECIFICALLY
 REQUIRED TO BE INSPECTED FOR TERMITES IN ACCORDANCE
 WITH SECTION 2114, OR REQUIRED TO HAVE CHEMICAL SOIL
 TREATMENT IN ACCORDANCE WITH SECTION 1816 SHALL NOT BE
 COVERED OR CONCEALED UNTIL THE RELEASE
 FROM THE BUILDING OFFICIAL HAS BEEN RECEIVED COMMENT
 PLEASE PROVIDE THIS INFORMATION ON DRAWINGS
  
  
 4
 FLORIDA STATUE713.13NOTICE OF COMMENCEMENT FILE
 NOTICE WITH THE CLERK OF COURT RECORDING DIVISION. IF
 THE
 WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED WITHIN
 90
 DAYS OF FILING THE NOTICE WILL BECOME NULL AND VOID.
 SUBMIT THE NOTICE AT THE TIME OF PERMIT ISSUANCE AND
 POST A COPY AT THE JOB SITE BEFORE THE FIRST
 INSPECTION.
 COMMENT-FOR YOUR INFORMATION
  
  
 5
 FBC BUILDING504.2 AUTOMATIC SPRINKLER SYSTEM
 INCREASE.
 THIS CHAPTER OF THE CODE ALLOWS THE BUILDING HEIGHT TO
 BE INCREASED BY 20? AND THE MAXIMUM NO. OF STORIES
 INCREASE BY ONE STORY
 COMMENT-FOR YOUR INFORMATION TYPE OF
  
  
 5-A
 FBC BUILDING506.3 AUTOMATIC SPRINKLER SYSTEM
 INCREASE
  
 COMMENT-
 AREA INCREASE WITH AUTOMATIC SPRINKLER SYSTEM IS 300
 PERCENT FOR SINGLE STORY BUILDING
 COMMENT-FOR YOUR INFORMATION
  
 6
 PRODUCT APPROVALS REQUIRED
 FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3
 REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS
 SUBMIT TWO COPIES OF EACH APPROVAL
 ( 3 COPIES IF A THRESHOLD BUILDING ) WITH FLORIDA
 PRODUCT
 APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S
 SIGNATURE AS APPLICABLE, STATING ?TO THE BEST OF THEIR
 KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH
 THE PLANS AND SPECIFICATIONS.
 SEE:WEB SITEWWW.FLORIDABUILDING.COM
  
 ALUMINUM WINDOWS
 FIXED GLASS
 MULLION TUBES
 ALUMINUM OUT -SWING DOORS
 HOLLOW METAL DOORS
 EXTERIOR GLAZED DOORS
 HURRICANE SHUTTERS
 LOUVERS,NO REPORT SUBMITTED
 ROLL UP DOOR
 COMMENT-PLEASE PROVIDE THE FOLLOWING FLORIDA PRODUCT
 APPROVALS
  
  
 7
 FBC BUILDING1609.6 SIMPLIFIED WIND LOAD METHOD.
 1609.1 APPLICATIONS.
 BUILDINGS, STRUCTURES AND PARTS THEREOF SHALL BE
 DESIGNED
 TO WITHSTAND THE MINIMUM WIND LOADS PRESCRIBED HEREIN.
  
 COMMENT-PLEASEPROVIDE THE DESIGN PRESSURE FOR THE
 WINDOWS AND DOORS, GARAGE DOORS, LOUVERS, MULLIONS
  
  
 8
 WPB AMENDMENTS TO FBC 2004 EDITION
 110.4.2 STORAGE AND FACTORY-INDUSTRIAL OCCUPANCIES. IT
 SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT,
 PROPRIETOR OR OCCUPANT OF GROUP S WHERE EXCESSIVE FLOOR
 LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT
 ARCHITECT OR ENGINEER IN COMPUTING THE SAFE LOAD
 CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY
 AN AFFIDAVIT FROM THE ARCHITECT OR ENGINEER STATING THE
 SAFE ALLOWABLE FLOOR LOAD ON EACH FLOOR IN POUNDS PER
 SQUARE FOOT UNIFORMLY DISTRIBUTED
 110.4.3 SIGNS REQUIRED.
 COMMENTIN EVERY BUILDING OR PART OF A BUILDING A SAFE
 FLOOR LOAD SHALL BE POSTED IN A CONSPICUOUS LOCATION.
 THIS SECTION REFERS TO THE MEZZANINE. PLEASE
 FURNISH THE SAFE LOAD CAPACITY AND NOT ON PLAN THE
 REQUIRED INFORMATION TO BE POSTED AT THE MEZZANINE.
  
  
 9
 FBC BUILDING 2200
 THE FOLLOWING INFORMATION IS PROVIDED FOR
 REVIEW BY THE DESIGNER OF RECORD, THE
 SPECIALITY ENGINEER, AND THE PROJECT
 ENGINEER
  
  
 10
 FBC BUILDING2223.5.3
 COMMENT THE MANUFACTURER SHALL DESIGN THE METAL SYSTEM
 BUILDING AND/OR COMPONENT SYSTEM IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 16
 METAL BUILDING STRUCTURAL DESIGN, PANEL WALLS INSULATED
 PANEL CEILING, PRE-ENGINEERED METAL CANOPY
 COMMENT-PLEASE PROVIDE THE SPECIAL ENGINEERING?S
 DESIGN AND SPECIFICATIONS FOR THE METAL BUILDING
 COMPONENTS
  
  
 10-A
 FBC BUILDING2223.4.1
 COMMENT -THE STRUCTURAL ENGINEER OF RECORD AND/OR THE
 ARCHITECTOF RECORD SHALL REQUIRE STRUCTURAL
 SUBMITTALS FOR REVIEW
 AS AN INDICATION THAT HIS OR HER INTENT HAS BEEN
 UNDERSTOOD
 AND THAT THE SPECIFIED CRITERIA HAVE BEEN USED. THE
 STRUCTURAL SUBMITTALS SHALL BEAR THE IMPRESSED SEAL,
 SIGNATURE AND DATE OF THE SPECIALTY ENGINEER WHO
 PREPARED THEM.
  
 10-B
 FBC BUILDING2222.4.8
 METAL SIDING AND ROOF PANELS SHALL BE DESIGNED, WHERE
 POSSIBLE, TO BE CONTINUOUS OVER TWO OR MORE SPANS.
 COMMENT PLEASESUBMIT THE METAL BUILDING SPECIALTY
 ENGINEERING DESIGN FOR PLAN REVIEW COMPLIANCE NOTING
 THE INFORMATION PROVIDEDHEREIN
  
  
 10-C
 FBC BUILDING2223.5.1
 COMMENT CALCULATIONS FOR DRIFT AND DEFLECTION OF THE
 METAL
 SYSTEM BUILDING SHALL BE BY THE SPECIALTY ENGINEER.
  
  
 10-D
 FBC BUILDING2223.8.4
 STRUCTURAL STANDING-SEAM ROOF SHEETS SHALL BE A
 MINIMUM
 OF 24 GAUGE [0.0239 INCH (.6 MM) NOMINAL] IN THICKNESS
 COMMENT FOR YOUR INFORMATION
  
 10-E
 FBC BUILDING2223.8.5
 DIRECT SCREW ATTACHED ROOF AND WALL SHEETS MAY BE USED
 AS
 DIAPHRAGMS PROVIDED THE SHEETS ARE A MINIMUM OF 24
 GAUGE
 COMMENTFOR YOUR INFORMATION
  
 10-F
 2222.4.3
 FBC BUILDINGMETAL SIDING AND ROOF PANELS SHALL BE
 NOT
  
 LESS THAN 24 GAUGE.
 COMMENTFOR YOUR INFORMATION
  
  
 10-G
 2222.4.5
 FBC BUILDINGTHE BENDING STRESS OF METAL SIDING AND
 ROOF
 PANELS SHALL BE DESIGNED USING A SAFETY FACTOR OF NOT
 LESS
 THAN 2.5.
 COMMENT FOR YOUR INFORMATION
  
 11
 FBC BUILDING 1600 LOADS
 COMMENT PLEASE VERIFY THE SUSPENDED GYPSUM CEILING
 SUPPORTED BY THE METAL ROOF STRUCTURE SYSTEM
 COMPONENTS
 WILL CARRY THE LOAD IMPOSED BY THIS CEILING SYSTEM.
 THIS WILL BE REFLECTED IN THE STRUCTURAL DESIGN BY THE
 METAL
 BUILDING MANUFACTURER?SSPECIALTY ENGINEER
  
  
 12
 FBC BUILDING CHAPTER 11 ACCESSIBILITY
 11-4.1.2 ACCESSIBLE SITE AND EXTERIOR FACILITIES: NEW
 CONSTRUCTION
 SHEETC-1COMMENT PLEASE PROVIDE A DETAIL FOR THE
 5?
  
 WIDE HANDICAP ACCESSIBLE ISLE FROM THE PARKING LOT TO
 THE
 SIDEWALK WITH A LEVEL CONNECTION
  
  
 13
 FLORIDA BUILDING CODE BUILDING 1210.2 WALLS. COMMENT
 PLEASE NOTE ON PLAN.. WALLS WITHIN 2 FEET OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE
 FLOOR
  
  
 14
 FLORIDA BUILDING CODE BUILDING 713.1 GENERAL - FIRE
 RESISTANT JOINT SYSTEM
 COMMENTOCCUPANCY SEPARATION WALL. JOINTS
 INSTALLED
  
 IN OR BETWEEN FIRE-RESISTANCE-RATED, WALLS,FLOOR OR
 FLOOR/CEILING
 ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL
 BE
 PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
  
 15
 FBC BUILDING1207.2AIR-BORNE SOUND.
 COMMENTWALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC
 OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
  
 (STC) OF NOT LESS THAN 50

Review Stop E ELECTRICAL
Rev No 8 Status N Date 2009-10-06 Cont ID  
Sent By dpalmer Date 2009-10-06 Time 10:51 Rev Time 0.00
Received By dpalmer Date 2009-10-06 Time 10:51 Sent To PC
Notes
2009-10-06 10:53:28ELECTRICAL SITE SURVEY NOT REVIEWED AS RECORD
 ELECTRICAL PLANS.
 ALSO NOT REVIEWED AT THE REQUEST OF KURT FROM WEST
 CONSTRUCTION.
 PLANS WOULD HAVE HAD COMMENTS AS THEY WERE SEALED BY
 LAND SURVEYOR FOR RECORD ELECTRICAL PLANS.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2009-08-07 Cont ID  
Sent By dpalmer Date 2009-08-07 Time 10:37 Rev Time 0.00
Received By dpalmer Date 2009-08-07 Time 10:37 Sent To PC
Notes
2009-08-07 10:37:31E5,6 AND 7

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2009-02-10 Cont ID  
Sent By dpalmer Date 2009-02-10 Time 08:55 Rev Time 0.00
Received By dpalmer Date 2009-02-10 Time 08:52 Sent To PC
Notes
2009-02-10 08:55:48REVISED E-4

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-11-25 Cont ID  
Sent By dpalmer Date 2008-11-25 Time 09:14 Rev Time 0.00
Received By dpalmer Date 2008-11-25 Time 09:14 Sent To  
Notes
2008-11-25 09:15:46SHEET 4 TO BE REVISED BEFORE INSPECTION TO COORDINATE
 WITH SHEET E-6.
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-11-24 Cont ID  
Sent By dpalmer Date 2008-11-24 Time 11:26 Rev Time 0.00
Received By dpalmer Date 2008-11-24 Time 10:51 Sent To  
Notes
2008-11-24 11:26:37** TEMPORARY FAILED STATUS.
  
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED SHEETS E-4 AND E-6
 NEED COORDINATION. PLEASE SEE THE EXTERIOR FIXTURES
 SUBMITTED AND SHOWN ON THE PHOTO-METRICS ACTUALLY DO
 NOT INCLUDE MANY FIXTURES WHICH DO CONTRIBUTE TO THE
 LIGHTING LEVELS.
 PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS DO NOT
 INCLUDE ALL EXTERIOR FIXTURES. A CALLED WAS PLACED TO
 THE ELECTRICAL ENGINEER AND LEAD DESIGNER ON PROJECT.
 SHEETS E-4 AND E-6 WILL BE REVISED AT A LATER DATE
 HOWEVER THE ENERGY CALCULATIONS WILL NEED TO BE REVISED
 AT THIS TIME BEFORE PERMIT ISSUANCE.
 13-415.2.ABC.1.3.
  
 2) NOTE: PLEASE SEE THE 2ND SET AS THE PLANS ARE NOT
 COMPLETE. SHEETS FA1 AND FA2 ARE MISSING FROM ONE SETS.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-09-04 Cont ID  
Sent By dpalmer Date 2008-09-04 Time 13:06 Rev Time 0.00
Received By dpalmer Date 2008-09-04 Time 13:05 Sent To  
Notes
2008-09-04 13:06:12 
  
  
  
  
 ** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
  
  
 1) NOTE: PLEASE BE SURE TO SUBMIT TWO COPIES OF ALL
 DOCUMENTS. ONLY ONE SPECIFICATION BOOK WITH
 CALCULATIONS AND MANUFACTURES SPECS WAS LOCATED. IF
 THIS HAD BEEN THE ONLY COMMENT THE SECOND SET COULD
 HAVE BEEN BROUGHT IN.
 FBC 106.1
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH
 RESPECT TO THE ENERGY CALCULATIONS. THE VERSION 3.0 AS
 SUBMITTED IS NOT ADOPTED BY THE FLORIDA BUILDING CODE.
 PLEASE GO TO THE FLORIDA SOLAR ENERGY/ENERGY GAUGE
 WEBSITE AS THERE IS A PATCH/UPDATE TO CORRECT ANY
 PROGRAMS SOLD WHICH SHOW THE 3.0. THIS SHOULD BE
 *VERSION 2.5*. THE STATE AS WELL AS FLORIDA
 SOLAR/ENERGY GAUGE IS AWARE OF THIS ISSUE.
 FBC 13-400.3.A
  
 3) NOTE: PLEASE MAKE SURE ALL LIGHTING AS SHOWN ON
 PLANS AS WELL AS OTHER BUILDING COMPONENTS ARE PLACED
 IN THE INPUT DATA REPORT. THIS INFORMATION FOR ALL
 SYSTEMS AND COMPONENTS IS REQUIRED TO COORDINATE.
 PLEASE SEE THE PREVIOUS REVIEW AS SOME EXAMPLES WERE
 GIVEN YET SOME OF THESE ARE STILL THE SAME. THE
 EXAMPLES ONCE AGAIN IS THE EXTERIOR LIGHTING ON THE IDR
 WHICH IS *BLANK*. THIS IS NOT POSSIBLE WHEN THE PLANS
 CLEARLY SHOW EXTERIOR LIGHTING.
 PLEASE SEE ANOTHER EXAMPLE IS INTERIOR LIGHTING. THERE
 ARE ONLY TWO TYPES OF LIGHTING FIXTURES ON THE IDR YET
 BASED ON THE PLANS SUBMITTED THERE IS A FAR GREATER
 NUMBER OF FIXTURE TYPES.
 ** THESE ARE ONLY TWO EXAMPLES: THERE ARE OTHER ITEMS.
 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3
  
 4) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO A
 REQUIRED GROUNDING ELECTRODE RISER TO BE SHOWN FOR THE
 ATTACHMENT OF ALL TRANSFORMERS.
 THE RESPONSE MENTIONS TO SEE RISER AND NEW NOTES
 HOWEVER THIS ONLY ADDRESSES THE ONE TRANSFORMER ON THE
 LINE SIDE OF SERVICE. THE PREVIOUS COMMENT REFERENCE
 CODES FOR OTHER TRANSFORMER SUCH AS SHOWN ON RISER.
 250.20,250.30,250.58 AND 250.66
 ** PLEASE CALL TO GO OVER IF THERE ARE ANY QUESTIONS.
  
 5) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. AS THIS IS ONLY
 THE SECOND REVIEW UNDER PERMIT APPLICATION THIS IS ONLY
 A NOTICE GIVEN AT THIS TIME.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-06-13 Cont ID  
Sent By dpalmer Date 2008-06-13 Time 12:48 Rev Time 0.00
Received By dpalmer Date 2008-06-13 Time 12:48 Sent To  
Notes
2008-06-13 12:48:49** DENIED **
  
 THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION,
 SECOND REVIEW TOTAL. PLANS WERE ONLY SUBMITTED FOR
 *PLAN REVIEW* FIRST TIME.
  
 ** PLEASE SEE SOME ITEMS ARE STILL IN NEED OF
 ADDRESSING FROM PREVIOUS REVIEW. THERE ARE ALSO SOME
 NEW COMMENTS FOR CHANGES MADE TO PLANS.
  
 1) NOTE: PLEASE BE SURE THE ADDRESS OF THE PROJECT IS
 CORRECTED ON PLANS. THE APPLIED ADDRESS LOCATION AS
 GIVEN ON PREVIOUS REVIEW IS 6255 N JOG RD. HOWEVER THE
 PLANS AND CALCULATIONS NOW HAVE 6527 N JOG RD. IT IS
 UNCLEAR WHERE THIS NEW NUMERICAL DESIGNATION IS COMING
 FROM. THE PERMIT APPLICATION SUBMITTED CONTAINS 6255.
 PLEASE BE SURE TO CORRECT ALL TITLE BLOCKS ON PLANS FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 REVIEWER(S).
 ** PLEASE KNOW THAT ANY SHEETS WHICH DO NOT NEED TO BE
 REPRINTED FOR CORRECTIONS MAY HAVE THE ADDRESS
 CORRECTED BY HAND IN A NEAT FASHION. IF THERE ARE ANY
 QUESTIONS ON THIS PLEASE CALL.
 FAC61G15-23.002, 61G1-16.004, FBC ADMIN SECTIONS
 106.3.5.1.2, 106.5
  
 2) NOTE: PLEASE SEE THE PERMIT APPLICATION SHOWS IN
 DESCRIPTION THE APPLIED SQ FT AS 11,900 SQ FT AND ALSO
 AS 11,900,000 SQ FT. THIS SEEMS TO BE DONE IN ERROR.
 PLEASE KNOW HOWEVER THE ENERGY CALCULATIONS SHOW A SQ
 FT FOR CONDITIONED AND UN-CONDITIONED SPACE AS ONLY
 6120 SQ FT. THE ARCHITECTURAL SHEETS SHOW AS HIGHER SQ
 FOOTAGE THAN THE CALCULATIONS.
 FBC 106.1.2 FOR COORDINATION.
  
 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE NOW
 JUST BEING SUBMITTED FOR THE FIRST REVIEW. THE ENERGY
 CALCULATIONS SUBMITTED ARE NOT CODE COMPLIANT IN
 SEVERAL LOCATIONS. COMPONENTS OF THE BUILDING AND
 MECHANICAL SYSTEM ARE NOT COMMENTED ON BY THIS REVIEWER
 ALTHOUGH ALL SYSTEMS ON PLANS ARE REQUIRED TO
 COORDINATE WITH THE SUBMITTED CALCULATIONS AND INPUT
 DATA REPORT. IN THE REMAINDER OF THIS COMMENT THE INPUT
 DATA REPORT WILL BE NOTED AS IDR.
 PLEASE BE SURE ALL LIGHTING ON PLANS IS ACTUALLY PLACED
 INTO THE IDR. THERE ARE SEVERAL ITEMS WHICH ARE NOT
 SHOWN. THE FOLLOWING ARE SOME EXAMPLES GIVEN AS A
 BENEFIT ONLY AND ARE IN NO WAY ALL POSSIBLE ITEMS WHICH
 DO NOT COMPLY. THIS IS NOT AN EXHAUSTED LIST.
  
 FOR EXAMPLE:
 PLEASE SEE THE IDR FOR EXTERIOR LIGHTING. THIS IS BLANK
 WITH NO LIGHTING AT ALL SHOWN. HOW IS THIS POSSIBLE
 WHEN THE PLANS CLEARLY SHOW SEVERAL EXTERIOR FIXTURES?
  
 FOR EXAMPLE:
 PLEASE SEE THE IDR FOR INTERIOR LIGHTING. HOW IS IT
 POSSIBLE THIS SHOWS ONLY THREE TYPES OF FIXTURES WHEN
 THE PLANS CLEARLY SHOW SEVERAL OTHER TYPES AND
 WATTAGES?
 PLEASE SEE THAT ALL LIGHTING ON PLANS AND LIGHTING
 FIXTURE LEGEND COORDINATE WITH THE IDR.
  
 FOR EXAMPLE:
 PLEASE SEE THE SQUARE FOOTAGE AS NOTED ABOVE IN NOTE #2
 DOES NOT COORDINATE WITH PLANS PR PERMIT APPLICATION.
  
 FOR EXAMPLE:
 PLEASE SEE THE METHOD OF CONTROL CAN NOT BE *MANUAL
 ON/OFF? WHEN THERE IS CLEARLY AUTOMATED CONTROLS FOR
 LOCATIONS IN AND OUTSIDE THE BUILDING.
  
 ** AS NOTED ABOVE THIS IS A BRIEF LIST FOR BENEFIT ONLY
 AND IS NOT A LIST OF ALL ITEMS WHICH DO NOT CORRELATE.
 THERE ARE OTHER ITEMS.
 PLEASE SEE 13-415.2.ABC.1.1, .1.2, .1.3, 13-415.2 ETC
  
 4) NOTE: PLEASE SEE THE VERSION OF CALCULATIONS
 SUBMITTED IS REQUIRED TO BE FLA/COM 2.5. PLEASE SEE
 13-400.3.A AS THE VERSION SUBMITTED IS NOT YET ADOPTED
 BY THE FLORIDA BUILDING CODE. THIS HAS BEEN CONFIRMED
 DIRECTLY WITH THE FLORIDA BUILDING COMMISSION.
  
 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE FOLLOWING ITEMS AS REQUESTED ON PREVIOUS
 REVIEW. THE RESPONSE LETTER MENTIONS THESE WERE
 VERIFIED FOR LISTING AND SUBMITTED HOWEVER THEY COULD
 NOT BE LOCATED IN ANY DOCUMENTS SUBMITTED. THE RESPONSE
 MENTIONS THE CONTRACTOR MAY CHANGE DURING THE
 CONSTRUCTION PROCESS. THIS IS NOT A PROBLEM, THIS
 OFFICE WOULD REQUEST ANY REVISIONS TO
 SPECS/MANUFACTURES CUT SHEET ON FILE BE SUBMITTED FOR
 REVIEW AND STAMPING. ONE COPY OF REVISED SPECS WOULD
 STAY ON FILE AND THE OTHER(S) WOULD GO BACK TO JOBSITE.
  
 PLEASE BE SURE TO SUBMIT THE SPECS/CUT SHEETS AT THIS
 TIME FOR REVIEW.
 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 6) NOTE: THE PREVIOUS REVIEW GAVE NOTICE TO REQUIRED
 LIGHTING CONTROLS. THE RESPONSE MENTIONS THIS FACILITY
 IS A 24HR OCCUPIED LOCATION AND DEVICES WILL BE
 INSTALLED IN SOME ROOMS ONLY WHICH ARE NOT 24HR USE.
 PLEASE SHOW ON THE LIGHTING PLANS WHICH ROOMS AND AREAS
 ARE GOING TO CONTAIN THE AUTOMATED CONTROLS. AT THIS
 TIME THE PLANS ONLY SHOW STANDARD SWITCHING DEVICES IN
 ALL LOCATIONS. THE DETAIL FOR OCCUPANCY SENSORS PLACED
 ON SHEET E-17 DOES NOT SHOW LOCATIONS ON PLANS.
 PLEASE REVISE LIGHTING PLANS.
 13-415.1.ABC.1.1, .1.2, .1.3.
 ** EXTERIOR LIGHTING IS SHOWN THROUGH * CONTACTOR* WITH
 PHOTO-SENSOR CONTROL. THIS WILL BE CONFIRMED TO COMPLY
 WITH FBC 13-415.1.ABC.1.4
  
 7) NOTE: PLEASE SHOW THE LOCATION AND GROUNDING
 ELECTRODE ATTACHMENT AND CONDUCTORS FOR THE
 TRANSFORMERS. THE RESPONSE MENTIONS THE RISER AND E-3
 WAS REVISED HOWEVER THIS INFORMATION COULD NOT BE
 LOCATED??
 PLEASE SEE 250.20, 250.30, 250.50, 250.58 AND 250.66
  
 8) NOTE: PLEASE VERIFY THE STORAGE AREA UPSTAIRS WILL
 NOT CONTAIN ANY LIGHTING AND WILL ONLY USE THE LIGHTING
 WHICH IS FROM OPEN AREA AS PLANS DO NOT SHOW ANY LIGHTS
 AT THIS TIME.
 FBC 106.1.2
  
 9) NOTE: PLEASE SHOW THE REQUIRED LEVELS FOR
 PHOTO-METRICS ON PLANS PER PREVIOUS REVIEW COMMENTS.
 THESE WERE SUBMITTED IN RESPONSE BOOK. HOWEVER THESE
 ARE REQUIRED TO BE SHOWN ON PLANS. THE LIGHTING FIXTURE
 USED FOR EMERGENCY USE ON PLANS ARE NOT THE SAME AS THE
 FIXTURES SHOWN THE SEPARATE PHOTO-METRICS SHEETS.
 PLEASE COORDINATE.
 FAC 61G15-33.004, NFPA-101 7.8.1.3, 7.9.2.2
  
 ** AS STATED ON PREVIOUS AS NOT ALL ITEMS ARE SHOWN AS
 OF YET THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-15 Cont ID  
Sent By dpalmer Date 2007-10-15 Time 16:11 Rev Time 0.00
Received By dpalmer Date 2007-10-15 Time 13:07 Sent To  
Notes
2007-10-15 16:11:29**** DENIED ****
  
  
 ** PLAN REVIEW
 MAINTENANCE BUILDING
 SOLID WASTE AUTHORITY
  
 1) NOTE: PLEASE KNOW THE PROJECT HAS ONLY BEEN
 SUBMITTED FOR *PLAN REVIEW* ONLY AND HAS NOT BEEN
 SUBMITTED FOR PERMIT APPLICATION.
 PLEASE KNOW ONCE ALL CODE COMMENTS ARE ADDRESSED, PLANS
 WILL STILL BE IN A FAILED STATUS UNTIL PERMIT
 APPLICATION IS MADE.
 ALL VERIFICATION OF LICENSE INFORMATION WILL BE DONE AT
 THAT TIME.
  
 2) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT
 CODES ARE STATED ON PLANS.
 PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER
 DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A
 MINIMUM.
 PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE
 REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE
 FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS
 FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE SOME CODES ON SOME SHEETS ARE NO LONGER
 IN EFFECT. FOR EXAMPLE, PLEASE SEE FA-1 WHICH
 REFERENCES THE 2000 LS CODE, 2002 NEC IN NOTES 10 AND
 12.
 PLEASE ALSO SEE NOTES MENTIONS *PALM BEACH COUNTY*, THE
 ACTUAL LOCATION IS IN THE CITY OF WEST PALM BEACH
 JURISDICTION.
  
 FBC 106.1.2, 110.1.2 ETC.
  
 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS TO COMPLY
 WITH THE CURRENT FBC AS NOTED ABOVE.
 PLEASE BE SURE ALL EXTERIOR AND INTERIOR LIGHTING ON
 PLANS COORDINATE WITH THE INPUT DATA REPORTS.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415,
 13-415.2.ABC.1.1, .1.2 AND .1.3.
 AS NO ENERGY CALCULATIONS WERE SUBMITTED NO REVIEW CAN
 BE DONE AT THIS TIME. THERE MAY BE NEW COMMENTS ON THE
 NEXT REVIEW.
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND
 .1.4 FOR MISSING LIGHTING CONTROLS REQUIRED.
 PLEASE INDICATE TIME SCHEDULING IF TIMER CONTROLLED.
 PLEASE INDICATE OVER RIDE DEVICES.
 PLEASE INDICATE OVER RIDE MAXIMUM TIMES.
 **(PLEASE SEE THE MAXIMUM TIMES FOR OCCUPANCY TYPE
 DEVICES ARE 30MINS AND MAXIMUM FOR TIMER OVER RIDE IS
 4HRS) NOTED FOR INFORMATION)
  
 5) NOTE: PLEASE CORRELATE ALL LIGHTING CONTROL DEVICES
 WITH THE SYMBOL LEGEND. FOR EXAMPLE: PLEASE SEE S WITH
 THE LETTER DESIGNATIONS IS NOT ALL ON LEGEND. SEE SX IN
 WOMEN'S TOILET, SEE SU IN JAN'S CLOSET. THESE ARE A FEW
 AS NOTED. THE COMMENT #4 WILL REQUIRE ADJUSTMENTS
 ALSO.
  
 6) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR
 MINIMUM ADA LEVELS FOR ALL HORN AND STROBE DEVICES.
 PLEASE SEE THE PLANS INDICATE ON LEGEND A *XX* FOR
 CANDELA LEVELS. PLEASE KNOW THAT ALL LEVELS ARE
 REQUIRED. PLEASE SEE THERE ARE SEVERAL LOCATIONS ON
 PLANS IN WHICH LESS THAN 75 CD IS BEING SHOWN.
 (EXAMPLE: 15, 30) PLEASE SEE .3(4) OF SECTION GIVEN AS
 THE MINIMUM LEVEL IS 75 CD.
 PLEASE ADJUST.
  
 7) NOTE: PLEASE ADJUST ALL CIRCUITING ON PANEL
 SCHEDULE(S) AS THE CIRCUITS ARE REQUIRED TO BE SPECIFIC
 TO ALL ROOMS AND AREAS IN WHICH THEY FEED. PLEASE KNOW
 THE GENERAL USE OF *LIGHTING* AND *RECEPTACLES* NEEDS
 TO BE SPECIFIC.
 THE ROOMS AND AREAS MAY CONTAIN A NUMERICAL DESIGNATION
 IF DESIRED.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY
 FROM THE NEC.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2, 110.1.2, 106.1.2
  
 8) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR THE FOLLOWING ITEMS.
 ATS, AND GENERATOR TAP BOX.
 ** PLEASE BE AWARE THERE ARE TAP BOXES ON THE MARKER
 WHICH THIS AHJ HAS SEEN WHICH ARE NOT LISTED FOR USE,
 AND WET/OUTDOORLOCATIONS WHEN CONNECTIONS ARE MADE.
 90.7, 110.3
 FBC 106.1.2
  
 9) NOTE: PLEASE CLARIFY GENERATOR, AS THE TRANSFER
 SWITCH BEING INSTALLED IS AN AUTOMATIC DEVICE WHICH
 LENDS TO A PERMANENTLY INSTALLED GENERATOR HOWEVER
 COULD NOT LOCATE THIS UNIT ON PLANS.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 10) NOTE: PLEASE CLARIFY THE MAIN AS SHOWN ON RISER
 AHEAD OF THE ATS. THIS DISCONNECT SEEMS TO INDICATE A
 *SHUNT TRIP* PUSH BUTTON OF SOME TYPE FROM A GLASS
 BREAK. DOES THIS MAIN STILL CONTAIN A MANUAL MEANS OF
 DISCONNECT RATED FOR THE LOAD SERVED PER 230.76 AND
 230.79?
 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 11) NOTE: PLEASE CLARIFY THE MAIN CIRCUIT BREAKER FOR
 PANEL DP. THE RISER CONTAINS A NOTE WHICH MENTIONS THIS
 IS NOT TO BE SERVICE ENTRANCE RATED?
 AS THE INSTALLATION OF THE GENERATOR IS NOT CLEAR AT
 THIS TIME, PLEASE BE SURE TO SEE 225.31-225.39 ALONG
 WITH 702.11 AS THE DISCONNECTING MEANS FOR THE FEEDERS
 COMING FROM A GENERATOR NEEDS TO MEET THE SECTIONS AS
 NOTED ABOVE.
 PLEASE ALSO CLARIFY THE NOTE ON THE PANEL DP WHICH
 MENTIONS THIS EQUIPMENT IS: * 800A, 277/480V,
 *4P*,,,,*.IT IS UNCLEAR WHAT THE 4P IS. IS THE
 NEUTRAL BEING CONTROLLED BY THIS BREAKER?
 PLEASE SUBMIT THE SPECS/CUT SHEET FOR THIS EQUIPMENT.
 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 12) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR THE STAIRS
 UNDER NORMAL AND EMERGENCY USE. PLEASE SEE NFPA-101
 7.8.1.3, AND 7.9.2.2 FOR MINIMUM LEVELS OF 10FT CANDLES
 UNDER NORMAL AND IS PERMITTED DOWN TO 1FT CANDLE UNDER
 EMERGENCY.
 FAC 61G15-33.004
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE THE FOOTING STEEL WHICH IS
 REQUIRED TO BE PART OF THE GROUNDING ELECTRODE SYSTEM
 COULD NOT BE LOCATED ON RISER/PLANS PER 250.50.
  
 14) NOTE: PLEASE INDICATE A DETAIL/SHOW LOCATION OF THE
 TRANSFORMER GROUNDING ELECTRODE SYSTEM PER 250.20,
 250.30, AND 250.50
  
 15) NOTE: PLEASE SEE THE ADDRESS IS MISSING ON
 PLANS/TITLE BLOCKS PER 61G15-23.002 AND 61G1-16.004.
 FBC 110.1.2, 106.1.2, 106.3.5
 PLEASE KNOW THE ADDRESS LOCATION AS APPLIED FOR AT THE
 PCN LOCATION PROVIDED ON PLAN REVIEW APPLICATION IS
 6255 N. JOG RD.
 THIS IS NOT YET CONFIRMED AND HAS BEEN ROUTED TO THE
 ADDRESSING REVIEWER FOR VERIFICATION FOR ACTUAL SITE
 ADDRESS CONFIRMATION.
 PLEASE DO NOT BASE ADDRESS ON TITLE BLOCKS UNTIL
 VERIFIED WITH THE ADDRESSING REVIEWER.
  
 16) NOTE: PLEASE KNOW ALL LOW VOLTAGE AS SHOWN ON PLANS
 WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS. THESE
 MAY BE USED FOR REFERENCING HOWEVER WILL BE REQUIRED TO
 PULL SEPARATE PERMITS.
 THE LV FOR CATV
 LV FOR SECURITY IS REQUIRED UNDER SEPARATE LV PERMIT
 FROM CATV, PHONE ETC.
 ** THIS IS NOTED FOR INFORMATIONAL PURPOSE ONLY AND NO
 CORRECTIONS OR ADJUSTMENTS TO PLANS ARE NEEDED.
  
 17) NOTE: PLEASE KNOW THE AIC RATINGS SHALL BE SET AND
 STATED BY THE ENGINEER OF RECORD. THE AVAILABLE FAULT
 CURRENT SHOULD BE DETERMINED AND SIZING OF EQUIPMENT IS
 REQUIRED BASED ON THE AVAILABLE FAULT CURRENT.
 NOTES ON RISER *KEYED NOTES* MENTIONS THIS IS TO BE
 DONE BY THE ELECTRICAL CONTRACTOR AND THE LEVELS ON
 PLANS ARE FOR BIDDING PURPOSES ONLY.
 PLEASE SEE 110.9 NEC.
 FBC 106.1.2, 106.3.5, ETC AS THE RECORD SETS OF PLANS
 ARE REQUIRED TOCONTAIN THE ACTUAL INSTALLED AND
 SPECIFIED.
  
 18) NOTE: PLEASE VERIFY CIRCUITING FOR SITE LIGHTING
 AS SHOWN ON E-3 WHICH IS CIRCUITED TO H1-6 AND THIS
 SAME CIRCUIT IS FOR SEVERAL WALL LIGHTING FIXTURES ON
 BUILDING ON E-6.
 PLEASE SEE PANEL SCHEDULE ON E-10 MENTIONS WALL
 LIGHTING ONLY.
  
 19) NOTE: *** IMPORTANT, AS THERE ARE SEVERAL ITEMS NOT
 YET SUBMITTED FOR REVIEW, REVIEW NOTES ABOVE CAN ONLY
 BE DONE ON DOCUMENTS AND PLANS SUBMITTED.
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW BASED
 ON NEW PLANS, CHANGES ETC WHICH CAN NOT BE MADE AT THIS
 TIME.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2007-10-15 13:07:27 
  
 IHN ELEC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2009-08-11 Cont ID  
Sent By efabian Date 2009-08-11 Time 15:32 Rev Time 0.25
Received By efabian Date 2009-08-11 Time 15:32 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2008-09-04 Cont ID  
Sent By rchokshi Date 2008-09-04 Time 11:05 Rev Time 0.00
Received By rchokshi Date 2008-09-04 Time 11:05 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2008-08-29 Cont ID  
Sent By rchokshi Date 2008-08-29 Time 14:04 Rev Time 0.00
Received By rchokshi Date 2008-08-29 Time 13:52 Sent To  
Notes
2008-08-29 14:04:01****FAILED ******
  
 1. PLEASE SHOW ON DRAWINGS THE TURBIDITY BARRIER
 DETAILS OF POLLUTION PREVENTION PER FDEP. DRAWING PLANS
 MUST SHOW TURBIDITY BARRIER AROUND THE CATCH BASINS,
 WATER FALLS, ANY LAKES ETC DURING CONSTRUCTION AND ALL
 DEMOLITION PHASE PER FDEP.
  
 PLEASE RESPOND EACH ITEM IN DETAIL AND REFERENCE
 DRAWINGS TO EXPEDITE YOUR PERMITTING PROCESS
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-05-30 Cont ID  
Sent By rchokshi Date 2008-05-30 Time 14:12 Rev Time 0.00
Received By rchokshi Date 2008-05-30 Time 13:50 Sent To  
Notes
2008-05-30 14:12:38****FAILED ******
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 OUR RESPONSE: YOUR RESPONSE PROVIDED IN APPENDIX B IS
 NOT ENOUGH. YOU NEED TO APPLY FOR NOI AT FDEP, NPDES. I
 HAVE PROVIDED WEB SIDE ABOVE FOR YOU.
  
 2. PLEASE SHOW ON STORM WATER QUALITY CALCULATION THAT
 YOU HAVE CONSIDERED FLOOD ZONE AREA, & 5,10, 25, 100
 YEAR FLOOD CRITERIA AND CROWN OF THE ROAD WHEN YOU
 DETERMINE THE FIRST FLOOR ELEVATION.
  
 3. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA YOU
 ARE DEVELOPING, GREEN AREA, LAKE AREA, PARKING AREA,
 IMPERVIOUS,PERVIOUS AREAYOU ARE DEVELOPING FOR THIS
 PROJECT .
  
 4. A COPY OF SFWMD PERMIT,,GEO-TECH REPORT &STORM
 WATER QUALITY CALCULATIONS MUST BE APPROVED FROM 1000
 45TH STREET ENGINEERING SERVICES BEFORE WE APPROVE.
  
 5. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC. DRAWING PLANS MUST
 SHOW SILT FENCE AROUND THE WHOLESITE & TURBIDITY
 AROUND THE CATCH BASINS DURING CONSTRUCTION AND ALL
 DEMOLITION PHASE.HEIGHT OF FENCE SHOULD BE HIGH
 ENOUGH PER FDEP TO STOP DUST PARTICLES.
  
 6. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVE.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-10-31 Cont ID  
Sent By rchokshi Date 2007-10-31 Time 10:23 Rev Time 0.00
Received By rchokshi Date 2007-10-31 Time 10:23 Sent To  
Notes
2007-10-31 10:23:19****FAILED ******
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM
 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES.
 PHONE# 494-1040
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION.
 5. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE.
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES.
 9. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS DURING
 CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES.
  
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-12-04 Cont ID  
Sent By mawillia Date 2008-12-04 Time 13:27 Rev Time 0.00
Received By mawillia Date 2008-12-04 Time 12:32 Sent To  
Notes
2008-12-04 13:26:29*****PROVISO*****
  
  
 PLAN SHEETS C-3, C-5, LS-1, A-1, A-2, A-3, E-6, FA-1
 THRU FA-4, FP-1 & FP-2 WERE STAMPED, INITIALED, AND
 DATED. PLEASE BE ADVISED THAT SHEET FP-2 IN ONE OF THE
 PLAN SETS IS MISSING AND THEREFORE NEEDS TO BE
 SUBMITTED FOR FIRE-STAMPING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-09-22 Cont ID  
Sent By mawillia Date 2008-09-22 Time 16:24 Rev Time 0.00
Received By mawillia Date 2008-09-22 Time 16:06 Sent To  
Notes
2008-09-22 16:20:29*****PROVISO*****
  
 ALL PREVIOUS PLAN REVIEW COMMENTS HAVE BEEN ADDRESSED;
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 OTHER REVIEW COMMENTS HAVE BEEN SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-06-24 Cont ID  
Sent By mawillia Date 2008-06-24 Time 14:37 Rev Time 0.00
Received By mawillia Date 2008-06-24 Time 13:09 Sent To  
Notes
2008-06-24 13:13:37*****DENIED*****
  
 ## PREVIOUS COMMENTS (WHICH STILL NEED TO BE
 ADDRESSED):
  
 04. LANDSCAPING SHALL NOT INTERFERE OR HINDER ACCESS TO
 FIRE PROTECTION EQUIPMENT AND DEVICES. COULD NOT LOCATE
 COMMENT AS INDICATED IN YOUR RESPONSE
  
 07. ON THE APPROPIATE EXTERIOR ELEVATION, POST THE
 NUMERICAL ADDRESS ON THE BUILDING. INDICATE WHICH
 EXTERIOR ELEVATION WOULD BE THE FRONT OR MAIN ENTRANCE
 TO THE BUILDING. AS PER WEST PALM BEACH CODE, ADDRESSES
 SHALL BE POSTED ON THAT PORTION OF THE STRUCTURE
 FRONTING OR FACING UPON THE STREET OR PRINCIPAL
 VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE VISIBLE
 TO APPROACHING VEHICLES.
  
 11. THE FIRE DEPARTMENT CONNECTION (FDC) SHALL BE
 EQUIPPED WITH KNOX LOCKING CAPS. FOR APPLICATIONS,
 CONTACT WEST PALM BEACH FIRE PREVENTION BUREAU AT
 561-804-4724. ADD COMMENT TO SHEET FP-1
  
 12. ELECTRONIC SWITCHES, CHAIN AND LOCK SHALL BE
 REQUIRED ON THE FIRE LINE BACKFLOW DEVICE. ADD COMMENT
 TO SHEET C-3 AND/OR SHEET FP-1.
  
 ## NEW COMMENT:
 AA. ON SHEET E-6, THERE IS AN EMERGENCY LIGHT
 ILLUSTRATED ON THE SOUTH WALL OF THE TOOL STORAGE (ROOM
 120) BUT NONE ILLUSTRATED ON SHEETS LS-1 AND A-2;
 PLEASE CORRELATE THE PLAN SHEETS TO REFLECT SAME
 LOCATION AND/OR NUMBER OF DEVICES.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-06 Cont ID  
Sent By mawillia Date 2007-11-06 Time 23:25 Rev Time 0.00
Received By mawillia Date 2007-11-01 Time 10:13 Sent To  
Notes
2007-11-01 10:57:58*****DENIED*****
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 03.THE PROPOSED FIRE HYDRANTS SHALL BE INSTALLED,
 COMPLETED, AND IN SERVICE PRIOR TO CONSTRUCTION WORK.
 ADD TO HYDRANT INFORMATION, SHEET C-5.
  
 04.LANDSCAPING SHALL NOT INTERFERE OR HINDER ACCESS
 TO FIRE PROTECTION EQUIPMENT AND DEVICES.
  
 05.ON THE LIFE SAFETY SHEET (LS-1) IN THE OCCUPANT
 LOAD REFERENCE,THE OCCUPANT LOAD OF 81 LISTED DOES
 NOT CORRELATE WITH 71 AS COMPUTED BY THIS WRITER.
  
 06.SPECIFY THE WALL AND CEILING FINISH MATERIALS FOR
 EXITS, EXIT AISLE CORRIDORS, AND OTHER SPACES IN TERMS
 OF CLASS A, CLASS B, OR CLASS C.
  
 07.ON THE APPROPIATE EXTERIOR ELEVATION, POST THE
 NUMERICAL ADDRESS ON THE BUILDING.AS PER WEST PALM
 BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6" IN
 HEIGHT AND NO LESS THAN 1" IN WIDTH.PLEASE BE ADVISED
 THAT THE INSTALLATION OF HURRICANE SHUTTERS SHALL NOT
 OBSCURE OR BLOCK VISIBILITY OF THE ADDRESS NUMBERS.
  
 08.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW THE
 LOCATION OF THE KNOX BOX.FOR APPLICATIONS, CONTACT
 WEST PALM BEACH FIRE PREVENTION BUREAU AT
 561-804-4724.
  
 09.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE STAIR
 HANDRAILS/GUARD RAILS.
  
 10.ON SHEET A-9 DOOR SCHEDULE NOTE #1 IS UNCLEAR AND
 INCORRECT.CLARIFY BY CHAPTER AND SECTION AS PER
 REFERENCING NFPA 101- 2003 EDITION.
  
 11.SHOW THE LOCATION OF THE FIRE DEPARTMENT
 CONNECTION (FDC).THE FDC SHALL BE EQUIPPED WITH KNOX
 LOCKING CAPS.FOR APPLICATIONS, CONTACT WEST PALM
 BEACH FIRE PREVENTION BUREAU AT 561-804-4724.
  
 12.ELECTRONIC SWITCHES, CHAIN AND LOCK SHALL BE
 REQUIRED ON THE FIRE LINE BACKFLOW DEVICE.
  
 13.ON SHEET E-6, THERE ARE TWO EMERGENCY LIGHTS
 ILLUSTRATED ON THE SOUTH WALL OF THE WORKSHOP BUT ONLY
 ONE ILLUSTRATED ON SHEETS LS-1 AND A-2;PLEASE
 CORRELATE THE PLAN SHEETS TO REFLECT SAME LOCATION
 AND/OR NUMBER OF DEVICES.
  
 14.ON SHEET E-6 AND LS-1 THERE IS AN EXIT LIGHT
 ILLUSTARATED IN THE OFFICE AREA HALLWAY BUT IS NOT
 SHOWN ON SHEET A-2;PLEASE CORRELATE THE PLAN SHEETS
 TO REFLECT SAME LOCATION AND/OR NUMBER OF DEVICES.
  
 15.ON SHEET FA-1, DELETE REFERENCE IN NOTE #3 TO THE
 PALM BEACH COUNTY CODE.
  
 16.ON SHEET FA-1, AMEND THE FIRE ALARM SEQUENCE OF
 OPERATIONS TO REFLECT THAT DUCT SMOKE DETECTORS
 INITIATE A GENERAL FIRE ALARM INSTEAD OF A SUPERVISORY
 ALARM.
  
 17.THE NUMBER OF DEVICES ILLUSTRATED FOR ROOM 108 ON
 SHEET FA-2 DOES NOT CORRELATE WITH THE FIRE ALARM RISER
 SHOWN ON THE FA-3 SHEET.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2009-09-30 Cont ID  
Sent By rmcdouga Date 2009-09-29 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2009-09-29 Time 15:49 Sent To  
Notes
2009-09-30 15:48:44SENT TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2009-08-06 Cont ID  
Sent By lmartine Date 2009-07-22 Time 16:03 Rev Time 0.00
Received By lmartine Date 2009-07-22 Time 16:02 Sent To  
Notes
2009-08-06 16:04:15C-37, RELOCATION OF HANDI CAP STALLS REVISION

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-07-29 Cont ID  
Sent By jgomez Date 2009-07-29 Time 08:45 Rev Time 0.00
Received By jgomez Date 2009-07-29 Time 08:45 Sent To  
Notes
2009-07-29 08:45:35SENT TO K. STEVENS' DESK.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-07-16 Cont ID  
Sent By rmcdouga Date 2009-07-16 Time 11:25 Rev Time 0.00
Received By rmcdouga Date 2009-07-15 Time 11:24 Sent To  
Notes
2009-07-16 11:25:36STRUCTURAL REVISIONS TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-07-14 Cont ID  
Sent By dpalmer Date 2009-07-14 Time 14:06 Rev Time 0.00
Received By dpalmer Date 2009-07-14 Time 14:06 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-06-22 Cont ID  
Sent By rmcdouga Date 2009-06-22 Time 09:55 Rev Time 0.00
Received By rmcdouga Date 2009-06-22 Time 09:55 Sent To  
Notes
2009-06-22 09:55:45TO C42

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-05-05 Cont ID  
Sent By dpalmer Date 2009-05-05 Time 14:07 Rev Time 0.00
Received By dpalmer Date 2009-05-05 Time 14:07 Sent To E
Notes
2009-05-05 14:08:00TO DVP

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-01-27 Cont ID  
Sent By adarroug Date 2009-01-27 Time 08:18 Rev Time 0.00
Received By adarroug Date 2009-01-27 Time 08:18 Sent To E
Notes
2009-01-27 08:18:37TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-11-07 Cont ID  
Sent By adarroug Date 2008-11-07 Time 15:05 Rev Time 0.00
Received By adarroug Date 2008-11-07 Time 15:05 Sent To  
Notes
2008-11-07 15:08:19TO "COMM" BD#23/PLANS ON RACK/1 ROLL, LARGE FOLDED
 PLANS/BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 10:51 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 10:51 Sent To  
Notes
2008-08-21 10:52:04TO "COMM" BD#45

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-13 Cont ID  
Sent By adarroug Date 2008-05-13 Time 12:31 Rev Time 0.00
Received By adarroug Date 2008-05-13 Time 12:31 Sent To  
Notes
2008-05-13 12:31:50TO "COMM" BD#26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-01 Cont ID  
Sent By kstevens Date 2007-12-01 Time 10:39 Rev Time 0.00
Received By kstevens Date 2007-09-20 Time 08:34 Sent To  
Notes
2007-10-12 16:28:10TO "COMM" BD#45
2007-09-20 08:35:06WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-07-20 Cont ID  
Sent By rregueir Date 2009-07-20 Time 16:06 Rev Time 0.00
Received By rregueir Date 2009-07-20 Time 15:46 Sent To PC
Notes
2009-07-20 16:06:27REVISED M1

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 14:28 Rev Time 0.00
Received By rregueir Date 2008-11-22 Time 14:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-09-04 Cont ID  
Sent By rregueir Date 2008-09-04 Time 09:26 Rev Time 0.00
Received By rregueir Date 2008-09-03 Time 16:25 Sent To  
Notes
2008-09-04 09:26:39TEMPORARY FAIL:
  
 MISSING ONE SET OF ENERGY CALCULATIONS AND 2 SETS OF
 COOLING LOAD CALCULATIONS. SPOKE TO KEVIN. IF MISSING
 DOCUMENTS ARE PROVIDED PRIOR TO COMPLETION OF ALL
 REVIEWS, THEY WILL BE INCORPORATED INTO THE SUBMITTAL
 AND MECHANICAL REVIEW WILL PASS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-05-28 Cont ID  
Sent By rregueir Date 2008-05-28 Time 16:25 Rev Time 0.00
Received By rregueir Date 2008-05-27 Time 16:11 Sent To  
Notes
2008-05-28 16:25:50REVIEW #: 2ND **1ST REVIEW FOR PERMIT**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK EXCEPT: PRODUCT APPROVALS SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL IN ACCORDANCE
 WITH FBCB 106.3.3.
  
 2 THROUGH 9: OK
  
 10. ENERGY CALCULATIONS: ON THE CERTIFICATIONS PAGE OF
 THE COMPLIANCE FORM, THE BUILDING SHELL AND
 ELECTRICAL/LIGHTING DESIGNERS HAVE NOT CERTIFIED
 COMPLIANCE WITH THE ENERGY CODE. DESIGN PROFESSIONALS
 RESPONSIBLE UNDER FLORIDA LAW FOR THE DESIGN OF
 LIGHTING, ELECTRICAL, MECHANICAL, AND PLUMBING SYSTEMS
 AND THE BUILDING SHELL, SHALL CERTIFY COMPLIANCE OF
 THOSE BUILDING SYSTEMS WITH THE CODE BY SIGNING AND
 PROVIDING THEIR PROFESSIONAL REGISTRATION NUMBER ON THE
 ENERGY CODE FORM PROVIDED AS PART OF THE PLANS AND
 SPECIFICATIONS TO THE BUILDING DEPARTMENT, OR:
 TYPED NAMES AND REGISTRATION NUMBERS MAY BE PROVIDED IN
 LIEU OF A SIGNATURE WHERE ALL RELEVANT INFORMATION HAS
 BEEN INCLUDED ON SIGNED AND SEALED PLANS IN ACCORDANCE
 WITH FBCB 13-103.1.1.1. SHOW COMPLIANCE BY PROVIDING
 ONE OF THE TWO REQUIREMENTS LISTED ABOVE.
  
 THE FOLLOWING ARE EXAMPLES OF AREAS IN THE INPUT DATA
 REPORT (IDR) WHICH DO NOT CORRESPOND WITH THE SYSTEMS
 AND ASSEMBLIES SHOWN ON PLANS. THIS IS NOT AN
 EXHAUSTIVE LIST. PLEASE VERIFY ALL VALUES TO ENSURE
 THEY CORRESPOND WITH PLANS AND RESUBMIT.
  
 A) A/C SYSTEM #3 AND RELATED ENVELOPE COMPONENTS ARE
 NOT INCLUDED IN THE IDR OR SYSTEM SIZING SUMMARY.
 PLEASE CORRECT AND RESUBMIT.
  
 B) EXTERIOR BLOCK WALL (P-2 PARTITION DETAIL PG A-10)
 DOES NOT CALL FOR ANY INSULATION. THE IDR IS CALLING
 FOR 1 INCH INSULATION AT THESE WALLS.
  
 C) THERE ARE NO DOORS INCLUDED IN THE IDR.
  
 11. SEE COMMENT (A) ABOVE.
  
 12 AND 13: OK
  
 NEW: THE MECHANICAL PAGES, WHILE SIGNED AND SEALED BY
 JOSE M. MARTINEZ, HAVE THE PRINTED NAME AND LICENSE
 NUMBER OF PAUL F. HILLERS DIRECTLY BELOW THE SIGNATURE
 AND SEAL OF MR. MARTINEZ. AS THE PRINTED NAME AND
 LICENSE NUMBER OF MR. MARTINEZ APPEARS IN THE TITLE
 BLOCKS ON THE SAME PAGES, MR. HILLER?S NAME CAN BE
 STRUCK FROM THE PLANS AND THE PLANS WILL BE COMPLIANT.
  
 NOTE: ASIDE FROM THE ABOVE LISTED COMMENTS, THE
 MECHANICAL PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE
 AND STAMPED. REVIEW WILL REMAIN IN FAILED STATUS
 PENDING SUCCESSFUL REVIEW OF ENERGY CALCULATIONS BY ALL
 AFFECTED TRADES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-10 Cont ID  
Sent By rregueir Date 2007-11-10 Time 11:24 Rev Time 0.00
Received By rregueir Date 2007-11-09 Time 17:46 Sent To  
Notes
2007-11-10 11:24:02REVIEW #: 1ST
 ACTION: DENIED
  
 *NOTE* THIS PLAN SUBMITTED FOR PLAN REVIEW ONLY. NO
 PERMIT APPLICATION HAS BEEN SUBMITTED AT THIS TIME.
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. WALL LOUVERS ARE LISTED AS PANEL WALLS UNDER FAC
 RULE 9B-72 AND AS SUCH A PRODUCT APPROVAL IS REQUIRED.
 PROVIDE PRODUCT APPROVALS FOR EACH TYPE OF WALL LOUVER
 TO BE USED. FOR MORE INFORMATION ON THE FLORIDA PRODUCT
 APPROVAL SYSTEM PLEASE VISIT: WWW.FLORIDABUILDING.ORG
  
 2. M-1: SUPPLY REGISTERS FOR ELECTRICAL ROOM 107 AND
 MECHANICAL ROOM 108 ARE SHOWN TO BE FED FROM THE RETURN
 DUCT FOR AHU-2. ALSO, THE RETURN GRILL FOR ELECTRICAL
 ROOM 107 IS SHOWN BEING TIED INTO THE SUPPLY BRANCH
 FROM AHU-2 WHICH FEEDS CONFERENCE ROOM 104. PLEASE
 CLARIFY HOW EACH DUCT IS SUPPOSED TO FUNCTION. FBC,M
 603.1 AND FBC 106.1.1
 NOTE: DUE TO THE ABOVE DISCREPANCIES, AIR BALANCES ON
 THESE SYSTEMS CAN NOT BE REVIEWED AT THIS TIME.
  
 3. M-1: SUPPLY AND RETURN DUCTS CROSSING CORRIDOR AT
 ROOMS 109 AND 110 ARE SHOWN WITH 3 OUT OF 4 DUCT
 PENETRATIONS OF WALLS PROTECTED WITH FIRE DAMPERS. ARE
 THESE WALLS INTENDED TO BE FIRE RESISTANCE RATED? THEY
 ARE NOT SHOWN AS SUCH BASED ON THE WALL TYPE AS SHOWN
 ON PAGES A-1 AND A-10. PLEASE COORDINATE THE LOCATIONS
 OF RATED ASSEMBLIES WITH ARCHITECTURAL DESIGNER,
 SHOWING OPENING PROTECTIVES WHERE REQUIRED IN
 ACCORDANCE WITH FBC,M 607.5.
 NOTE: IF IT IS DETERMINED THAT THESE WALLS REQUIRE A
 RATING, SHOW ALL 4 PENETRATIONS TO BE PROTECTED IN
 ACCORDANCE WITH THIS SECTION AND FBC,M 607.8.
  
 4.M-1: EF-3 ON FLOOR PLAN CALLS FOR 690 CFM. FAN
 SCHEDULE ON M-3 SHOWS EF-3 AT 640 CFM. WHICH IS
 CORRECT? VERIFY THAT FAN CAN PROVIDE THE MINIMUM
 VENTILATION AS REQUIRED BY FBC,M TABLE 403.3 FOR LOCKER
 ROOMS, TOILET ROOMS AND SHOWERS. COORDINATE FLOOR PLANS
 WITH EQUIPMENT SCHEDULES.
  
 5. M-2: WHAT IS THE MEANS AND LOCATION OF CONDENSATE
 DISPOSAL? AHU MOUNTING DETAIL SAYS TO SEE PLUMBING
 PLANS FOR CONTINUATION. NO INFORMATION REGARDING
 LOCATION OF CONDENSATE DISCHARGE COULD BE FOUND ON
 PLUMBING PLANS. SHOW CONDENSATE DISPOSAL FOR AHU?S 1,2
 AND 6 TO BE IN COMPLIANCE WITH FBC,M 307.2.1 THROUGH
 307.2.4 AND FBC 1503.6.
  
 6. M-2: FIRE DAMPER DETAIL CALLS FOR ANGLES TO BE
 FASTENED TO SLEEVE PER SMACNA RECOMMENDATIONS. FIRE
 DAMPERS ARE LISTED AND LABELED ASSEMBLIES AND AS SUCH
 SHALL BE INSTALLED PER THEIR LISTING AND MANUFACTURER?S
 INSTALLATION INSTRUCTIONS IN ACCORDANCE WITH FBC,M
 607.2. UNLESS THIS DETAIL MATCHES THE MANUFACTURER?S
 INSTRUCTIONS IT SHOULD BE REMOVED FROM PLANS AND
 REPLACED BY THE MANUFACTURER?S INSTRUCTIONS EITHER ON
 THE PLANS OR AS A SEPARATE SUBMITTAL. IT MAY BE
 REPLACED BY A GENERAL NOTE WHICH DEFERS TO
 MANUFACTURER?S INSTRUCTIONS.
  
 7. M-3: A/C UNIT SCHEDULE, CFM SHOWN ON SCHEDULE FOR
 AHUS DO NOT MATCH THOSE ON FLOOR PLAN. COORDINATE FLOOR
 PLANS AND EQUIPMENT SCHEDULE. ALSO, SEE COMMENT #2
 ABOVE.
  
 8. A/C UNIT SCHEDULE NOTE #3 INDICATES AHU-3 SHALL BE
 OF DOUBLE WALL CONSTRUCTION. NO AHU-3 IS SHOWN ON PLANS
 OR SCHEDULE. PLEASE CLARIFY. FBC 106.1.1.
  
 9. M-3 O.A. SCHEDULE SHOWS AHU-1 SYSTEM DESIGNED FOR
 460 CFM. A/C UNIT SCHEDULE INDICATES AHU-1 TO PROVIDE
 965 CFM OF O.A. WHICH IS CORRECT? PLEASE CLARIFY AND
 COORDINATE SCHEDULES.
  
 10. PROVIDE AN ENERGY CODE COMPLIANCE CERTIFICATION
 FORM (ENERGY CALCULATIONS) IN ACCORDANCE WITH FBC
 13-101.1.1 AND FBC 13-103 (ENTIRE SECTION).
  
 11. COOLING LOAD CALCULATIONS SHALL BE ATTACHED TO THE
 CODE COMPLIANCE FORM SUBMITTED TO THE BUILDING
 DEPARTMENT AT TIME OF PERMIT APPLICATION IN ACCORDANCE
 WITH FBC 13-407.1.ABC.1 AND ALL HVAC SYSTEMS AND
 EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE THAN THE
 SPACE AND SYSTEM LOADS CALCULATED IN ACCORDANCE WITH
 FBC 13-407.1.ABC.1.1.
  
 12. AHU?S 1 AND 2 SHALL BE PROVIDED WITH OFF-HOUR
 CONTROLS INCLUDING AUTOMATIC SHUTDOWN, SETBACK
 CONTROLS, OPTIMUM START CONTROLS, SHUTOFF DAMPER
 CONTROLS AND ZONE ISOLATION IN ACCORDANCE WITH FBC
 13-407.1.ABC.2.4.
  
 13. PROVIDE AN AIR BALANCE SCHEDULE SHOWING THE
 BUILDING TO BE PRESSURIZED WITH RESPECT TO THE OUTDOORS
 IN ACCORDANCE WITH FBC 13-409.1.ABC.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 9 Status N Date 2009-08-10 Cont ID  
Sent By kstevens Date 2009-08-10 Time 14:25 Rev Time 0.00
Received By kstevens Date 2009-08-10 Time 14:25 Sent To  
Notes
2009-08-10 14:26:56IRRIGATION SHEETS SUBMITTED FOR REVISION SHOW NO
 IRRIGATION CHANGES. REVISION INDEX INDICATES PARKING
 LOT STRIPING ONLY.

Review Stop P PLUMBING
Rev No 8 Status P Date 2009-07-30 Cont ID  
Sent By kstevens Date 2009-07-30 Time 16:01 Rev Time 0.00
Received By kstevens Date 2009-07-30 Time 16:01 Sent To  
Notes
2009-07-30 16:02:00REVISION OK -- SHT P-2.

Review Stop P PLUMBING
Rev No 7 Status F Date 2009-07-22 Cont ID  
Sent By kstevens Date 2009-07-22 Time 08:47 Rev Time 0.00
Received By kstevens Date 2009-07-22 Time 08:47 Sent To  
Notes
2009-07-22 08:51:12REVISION DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P-2 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THE FLOOR DRAIN SOUTH OF COL. LINE 4.5
 ALONG COL. LINE E IS NOT SHOWN ON THE RISER DIAGRAM,
 BUT IS SHOWN ON THE FLOOR PLAN ON SHEET P-1. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 301.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2009-07-22 Cont ID  
Sent By kstevens Date 2009-07-22 Time 08:47 Rev Time 0.00
Received By kstevens Date 2009-07-22 Time 08:47 Sent To  
Notes
2009-07-22 08:47:51REVISION OK -- SHT P-1.

Review Stop P PLUMBING
Rev No 5 Status F Date 2009-07-13 Cont ID  
Sent By kstevens Date 2009-07-13 Time 16:19 Rev Time 0.00
Received By kstevens Date 2009-07-13 Time 16:19 Sent To  
Notes
2009-07-13 16:56:53REVISION DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1 ADMIN
  
 1. SHT P-1 ON FILE FOR PUBLIC RECORD SHOWS A REVISION
 NUMBER 2 DATED SEPTEMBER 3, 2008 AND IS SIGNED, SEALED,
 & DATED 10-14-2008. THE REVISION SUBMITTED FOR REVIEW
 SIGNED, SEALED AND DATED 6-17-09 IS SHOWING A REVISION
 NUMBER 2 DATED JUNE 16, 2009. THE REVISION HISTORY
 SUBMITTED FOR PUBLIC RECORD SHALL BE LEFT INTACT THRU
 THE PROJECT LIFE AND NEW REVISIONS SHALL HAVE NEW
 REVISION NUMBERS. SECTION 106.1.3.
  
 2. SHT P-2 ON FILE FOR PUBLIC RECORD SHOWS A REVISION
 NUMBER 1 DATED JUNE 13, 2008 AND A REVISION NUMBER 2
 DATED SEPTEMBER 3, 2008 AND IS SIGNED, SEALED & DATED
 11-4-08. THE REVISION SUBMITTED FOR REVIEW SIGNED,
 SEALED AND DATED 6-17-09 IS SHOWING NO REVISION NUMBER
 ONE IN THE REVISION HISTORY, AND REVISION NUMBER 2
 DATED JUNE 16, 2009. THE REVISION HISTORY SUBMITTED FOR
 PUBLIC RECORD SHALL BE LEFT INTACT THRU THE PROJECT
 LIFE AND NEW REVISIONS SHALL HAVE NEW REVISION NUMBERS.
 SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-12-04 Cont ID  
Sent By kstevens Date 2008-12-03 Time 08:10 Rev Time 0.00
Received By kstevens Date 2008-12-03 Time 08:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-08-27 Cont ID  
Sent By kstevens Date 2008-08-27 Time 11:13 Rev Time 0.00
Received By kstevens Date 2008-08-21 Time 15:55 Sent To  
Notes
2008-08-27 11:25:12DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 PLAN REVIEW ONLY
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
  
 ***********NEW COMMENTS***********
  
 NEW PLUMBING SHEETS SUBMITTED
  
 1B. SHT P-2 SANITARY RISER ISOMETRIC DOES NOT REFLECT
 THE FLOOR PLAN. STACK WITH DOUBLE LAV'S P-3 SHOWS A
 TRAP TO THE STORAGE ROOM ON THE FLOOR PLAN THAT IS NOT
 ON THE RISER DIAGRAM.--THE FLOOR PLAN SHOWS A FLOOR
 DRAIN IN THE STORAGE AREA THAT CONNECTS UPSTREAM OF THE
 URINALS IN THE MEN'S ROOM 116 THAT IS NOT SHOWN ON THE
 RISER DIAGRAM. PLEASE CORRELATE. SECTIONS 106.1.1 &
 704.--FLOOR DRAIN UPSTREAM OF THE URINALS APPEARS
 TO EXCEED THE MAXIMUM DISTANCE FROM THE VENT PER TABLE
 906.1.
  
 2B. SHT P-2 DOMESTIC WATER PIPING ISOMETRIC DOES NOT
 REFLECT THE FLOOR PLAN NOR DOES IT REFLECT THE PLUMBING
 FIXTURE SCHEDULE SHOWN ON SHT P-3. RISER SHOWS A
 FIXTURE P-9 DOWNSTREAM OF FIXTURE P-7 IN THE STORAGE
 (117) ROOM. THIS IS NOT SHOWN ON THE FLOOR PLAN NOR ON
 THE FIXTURE SCHEDULE. PLEASE CORRELATE. SECTIONS
 106.1.1 & 604.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE
 SET OF THEM LOOSELY ON TOP OF THE COLLATED
 PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-06-02 Cont ID  
Sent By kstevens Date 2008-06-02 Time 08:23 Rev Time 0.00
Received By kstevens Date 2008-05-30 Time 17:01 Sent To  
Notes
2008-06-02 08:33:25DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 PLAN REVIEW ONLY
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. PER SECTION 11-4.1.3(10)(B) WHERE MORE THAN ONE
 DRINKING FOUNTAIN IS PROVIDED, AT LEAST 50% SHALL BE
 ACCESSIBLE. 3 DRINKING FOUNTAINS ARE SHOWN, 2 SHALL BE
 ACCESSIBLE.
 ****RESPONSE NOTED, BUT THE TWO DRINKING FOUNTAINS IN
 THE CORRIDOR ARE HI/LOW AND AS SUCH ONLY THE LOW
 DRINKING FOUNTAIN IS ACCESSIBLE. THE HI DRINKING
 FOUNTAIN MEETS THE CODE REQUIREMENT FOR SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING. THE DRINKING FOUNTAIN
 IN THE WORKSHOP AREA SHALL BE ACCESSIBLE. THERE IS NO
 PROVISIONS IN THE CODE FOR EQUIVALENT PROVISIONS AT THE
 SINK IN THE LUNCH ROOM. PLEASE SHOW 2 OF THE 3 DRINKING
 FOUNTAINS TO BE ACCESSIBLE. (SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS).
  
 6. OK
 7. OK
 8. OK
 9. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE
 SET OF THEM LOOSELY ON TOP OF THE COLLATED
 PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-01 Cont ID  
Sent By kstevens Date 2007-12-01 Time 10:17 Rev Time 0.00
Received By kstevens Date 2007-12-01 Time 10:17 Sent To  
Notes
2007-12-01 10:38:45DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 PLAN REVIEW ONLY
  
 1. SHT A-1 ROOM FINISH SCHEDULE FOR ROOMS 113, 115 &
 116. WALLS WITHIN 2 FEET OF WATER CLOSETS & URINALS
 SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE PER
 SECTION 1210.2. EPOXY PAINT OVER GWB IS NOT CONSIDERED
 A HARD SURFACE. PLEASE SHOW COMPLIANCE.
  
 2. SHT A-1 INDICATE TYPE OF WORK WILL BE DONE IN THE
 WORKSHOP AND TYPE AND AMOUNT OF STORAGE IN THE STORAGE
 AREA. SECTION 106.1.2.
  
 3. SHT A-7 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR
 THE URINAL:
 A. 11-4.18.4 FLUSH CONTROLS (HEIGHT)
 ___FOR LAVS:
 A. 11-4.19.5 FAUCETS
 ___FOR THE SHOWERS:
 A. 11-4.21.3 SEAT HEIGHT
 B. 11-4.21.5 CONTROLS
 C. 11-4.21.7 CURBS (MAX 1/2")
  
 4. SHT A-8 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR
 SINKS:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED).
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
  
 5. PER SECTION 11-4.1.3(10)(B) WHERE MORE THAN ONE
 DRINKING FOUNTAIN IS PROVIDED, AT LEAST 50% SHALL BE
 ACCESSIBLE. 3 DRINKING FOUNTAINS ARE SHOWN, 2 SHALL BE
 ACCESSIBLE.
  
 6. SHT P-1 THERE IS A NOTE THAT STATES 3" PVC PIPE FOR
 FUTURE USE. SEE CONT. ON CIVIL DRAWINGS. THE PIPE IS
 NOT SHOWN ON THE CIVIL PLANS. PLEASE CLARIFY WHAT THE
 PIPE WILL BE DRAINING AND TO WHERE. SECTION 106.1.2
 (MORE INFORMATION REQUIRED).
  
 7. SHT P-2 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THE STACK WITH THE DRINKING FOUNTAIN AND
 SINK IN THE STORAGE/WORKSHOP AREA SHOWS 3 FIXTURES
 CONNECTING TO THE STACK ON THE FLOOR PLAN, BUT ONLY TWO
 FIXTURES, (P-9 & P-7), ON THE RISER DIAGRAM.--THE
 FLOOR DRAIN IN THE JANITOR ROOM IS NOT SHOWN ON THE
 RISER DIAGRAM BUT IS SHOWN ON THE FLOOR PLAN. PLEASE
 CLARIFY AND CORRELATE THE RISER WITH THE FLOOR PLAN.
 SECTION 106.1.1.
  
 8. SHT P-2 AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE TO THE BUILDING. INDICATE THE BACKFLOW ON THE
 WATER RISER DIAGRAM PRIOR TO ENTERING THE BUILDING.
 SECTION 608.13.2.
  
 9. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION
 607.3.2. INDICATE METHOD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE
 SET OF THEM LOOSELY ON TOP OF THE COLLATED
 PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 2009-10-05 Cont ID  
Sent By eschneid Date 2009-10-05 Time 13:20 Rev Time 0.00
Received By eschneid Date 2009-10-05 Time 13:19 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2009-07-29 Cont ID  
Sent By eschneid Date 2009-07-29 Time 15:48 Rev Time 0.66
Received By eschneid Date 2009-07-29 Time 15:48 Sent To  
Notes
2009-07-29 15:55:51FAILED HC RELOCATION REVISION
  
 1) ZONING STAFF DOES NOT FIND A PROBLEM WITH THE
 RELOCATION OF THE HC SPACES.
  
 2) ZONING STAFF HAS IDENTIFIED THE FOLLOWING ISSUES
 WITH THE SUBMITTED PLANS:
  
 A. THE PLANS SHALL MATCH THE CONDITIONS IN THE FIELD -
 EX. THERE IS A DRIVEWAY W/CURB CUT ADJACENT TO THE
 "GENERATOR ROOM" AT THE SOUTH EAST LIMITS OF WORK THAT
 IS NOT SHOWN ON THE PLANS.
  
 B. THE CONTRACTOR AND THE CITY'S LANDSCAPE PLANNER,
 ROBERT KUSSNER (561) 822-1462, DISCUSSED SOME POSSIBLE
 CHANGES TO THE PLANS DURING THE FIELD VISIT -
 SPECIFICALLY, SIDEWALK CONNECTIONS TO SOME OF THE
 LANDINGS ADJACENT TO THE EXISTING BUILDINGS. IF THE
 CONTRACTOR STILL WISHES TO INSTALL THESE CHANGES, THEY
 SHALL BE REFLECTED ON THE PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-09-02 Cont ID  
Sent By eschneid Date 2008-09-02 Time 16:23 Rev Time 0.00
Received By eschneid Date 2008-09-02 Time 16:23 Sent To  
Notes
2008-09-02 16:25:25PASS W/PROVISO
  
 D-CURBS ARE REQUIRED TO BE INSTALLED IN THE LOCATIONS
 MARKED IN RED ON SHEETS C-1, C-2 AND LA-1 (ADJACENT TO
 PARKING).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-06-13 Cont ID  
Sent By eschneid Date 2008-06-13 Time 17:19 Rev Time 0.00
Received By eschneid Date 2008-06-13 Time 13:10 Sent To  
Notes
2008-06-13 17:23:04FAILED
  
 1) NO LANDSCAPE PLAN SUBMITTED.THE LANDSCAPE PLAN
 SHALL ADHERE TO ALL THE REQUIREMENTS OF THE CITY'S
 LANDSCAPE REGULATIONS AND BE PREPARED BY A FLORIDA
 REGISTERED LANDSCAPE ARCHITECT.
  
 2) THE PARKING DETAILS DO NOT CONFORM TO THE CITY
 STANDARD - WHEEL STOP SHALL BE TWO (2) FEET FROM END OF
 PARKING SPACE.
  
 3) ALL LANDSCAPE ISLANDS (INTERIOR AND TERMINAL) SHALL
 HAVE A SHADE OR FLOWERING TREE.
  
 4) THE AMOUNT OF FOUNDATION PLANTING IS NOT INDICATED.
  
 5) NO PARKING TABLE IS PROVIDED.
  
 6) NO LOADING SPACE PROVIDED.
  
 7) ALL LANDSCAPE SHALL BE PROTECTED FROM VEHICLE
 ENCROACHMENT BY A TYPE ?D? CURB OR WHEEL STOPS.THIS
 STANDARD IS NOT MET ALONG MOST OF THE PAVEMENT EDGES.
  
 8) WHERE IS DUMPSTER LOCATED/HOW IS TRASH DISPOSED OF?
 IF A DUMPSTER IS USED IT SHALL BE SCREENED MEETING WPB
 REQUIREMENTS.
  
 9) ALL MECHANICAL EQUIPMENT, INCLUDING GENERATORS,
 SHALL BE SCREENED.
  
 10) THANK YOU FOR PROVIDING A LETTER THAT THE BUILDING
 DOES NOT NEED TO GO THROUGH THE DEP CONDITIONS OF
 CERTIFICATION PROCESS.THIS DOES REQUIRE THAT THE
 BUILDING IS REVIEWED BY THE CITY THROUGH THE FORMAL
 SITE PLAN REVIEW PROCESS.
  
 CONTACT ERIC SCHNEIDER @ (569) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By eschneid Date 2007-10-22 Time 20:19 Rev Time 0.00
Received By eschneid Date 2007-10-22 Time 20:19 Sent To  
Notes
2007-10-22 20:43:48FAILED
  
 1) THE CITY HAS NO RECORD THAT THIS PLAN WAS SUBMITTED
 FOR REVIEW BY THE PLANNING AND ZONING DEPARTMENT UNDER
 THE REQUIREMENTS OF CHAPTER 403, FLORIDA STATUTES.
 OPTIONS - A. SUBMIT THE APPROVED POWER PLANT
 CERTIFICATION, INCLUDING THE SITE PLAN SUBMITTED FOR
 WEST PALM BEACH REVIEW AND ALL COMMENTS GENERATED BY
 THE CITY DURING SAID REVIEW; OR OPTION B. SUBMIT THE
 PLAN FOR A FORMAL SITE PLAN REVIEW BY THE CITY.
  
 THE FOLLOWING IS A CURSORY REVIEW OF THE PLANS.A FULL
 REVIEW WILL OCCUR WITH THE FORMAL SUBMITTAL TO THE
 CITY.
  
 1) NO LANDSCAPE PLAN SUBMITTED.THE LANDSCAPE PLAN
 SHALL ADHERE TO ALL THE REQUIREMENTS OF THE CITY'S
 LANDSCAPE REGULATIONS AND BE PREPARED BY A FLORIDA
 REGISTERED LANDSCAPE ARCHITECT.
  
 2) THE PARKING DETAILS DO NOT CONFORM TO THE CITY
 STANDARD.
  
 3) NO MORE THAN 10 PARKING SPACES MAY BE CONSTRUCTED IN
 A ROW UNLESS INTERRUPTED BY AN INTERIOR LANDSCAPE
 ISLAND.
  
 CONTACT ERIC SCHNEIDER @ (569) 822-1435.