Plan Review Details - Permit 07090550
Plan Review Stops For Permit 07090550
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-21 Cont ID  
Sent By mjacobs Date 2007-12-21 Time 15:51 Rev Time 0.00
Received By mjacobs Date 2007-12-21 Time 15:44 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-05 Cont ID  
Sent By mjacobs Date 2007-10-05 Time 17:31 Rev Time 0.00
Received By mjacobs Date 2007-10-05 Time 14:53 Sent To  
Notes
2007-10-05 17:31:41 
 BUILDING PLAN REVIEW
 PERMIT: 07090550
 ADD: 2800 N FLAGLER DR. #905
 CONT: JOHN JOKI PESOLA GENERAL CONTRACTOR INC.
 TEL: (561)642-1776
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006/2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST.
 ACTION: DENIED 10/5/07
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
  
 2)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D)IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
  
 . -------------------------------------
  
 **NO RESPONSE NOT ADDRESSED**
 3)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE. **THIS APPEARS
 TO BE A LEVEL 2 ALTERATION**.
  
 4) W. PALM BEACH AMENDMENTS 106.1.3 BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER.PENCIL DRAWN PLANS ARE NOT
 ACCEPTABLE. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME, DATE
 AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE, THEN
 HE/SHE SHALL SEAL THE DRAWINGS IN ACCORDANCE WITH
 CHAPTER 481 AND 471 OF THE FLORIDA STATUTES.
  
 5)PROVIDE AN EXISTING AND PROPOSED FLOOR PLAN OF THE
 PROJECT INDICATING WHERE ALL WALLS WILL BE REMOVED AND
 IF NEW WALL WILL BE BUILT. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED, AND SHOWS IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THE
 CODE AND RELEVANT LAWS. 106.1.1.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-19 Cont ID  
Sent By dpalmer Date 2007-12-19 Time 09:29 Rev Time 0.00
Received By dpalmer Date 2007-12-19 Time 09:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-28 Cont ID  
Sent By dpalmer Date 2007-09-28 Time 18:55 Rev Time 0.00
Received By dpalmer Date 2007-09-28 Time 18:55 Sent To  
Notes
2007-09-28 18:55:582007-09-28 18:55:58
  
 ** DENIED **
  
  
 1) NOTE: PLEASE KNOW THE RELEVANT CODES ARE REQUIRED TO
 BE STATED ON PLANS/DRAWINGS
 FBC 106.1.2
  
 2) NOTE: PLEASE KNOW EVEN WHEN PLANS ARE NOT REQUIRED
 TO BE SIGNED AND SEALED BY A DESIGN PROFESSIONAL
 LICENSED UNDER FS 481 AND 471, THE LICENSE CONTRACTOR
 PERSON RESPONSIBLE FOR PLANS AND DESIGN SHALL CONTAIN
 THE PRINTED NAME AND SIGNATURE OF SAID RESPONSIBLE
 PARTY.
 FBC 106.1.2, 106.5
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-20 Cont ID  
Sent By mawillia Date 2007-12-20 Time 16:07 Rev Time 0.00
Received By mawillia Date 2007-12-20 Time 16:01 Sent To  
Notes
2007-12-20 16:07:14*****APPROVED*****
  
  
 AN APPROPIATE PLAN SHEET WAS STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-10 Cont ID  
Sent By mawillia Date 2007-10-10 Time 15:18 Rev Time 0.00
Received By mawillia Date 2007-10-10 Time 14:57 Sent To  
Notes
2007-10-10 15:18:23*****DENIED*****
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE REMOVAL OF EXISTING OR THE STOCKING OF NEW
 BUILDING MATERIALS & SUPPLIES SHALL NOT
 INTERFERE/HINDER ACCESS TO OR EGRESS FROM THE NINTH
 FLOOR OR THE BUILDING.
  
 3.WILL THE SCOPE OF WORK HAVE CAUSE FOR ANY FIRE
 SPRINKLERS AND/OR FIRE ALARM DEVICES TO BE RELOCATED?
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-14 Cont ID  
Sent By adarroug Date 2007-12-14 Time 15:23 Rev Time 0.00
Received By adarroug Date 2007-12-14 Time 15:23 Sent To  
Notes
2007-12-17 15:42:26TO "BOB"#18
2007-12-14 15:23:59WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-10 Cont ID  
Sent By mawillia Date 2007-10-10 Time 15:19 Rev Time 0.00
Received By mawillia Date 2007-09-19 Time 16:01 Sent To  
Notes
2007-09-28 10:27:56TO "BOB"#8
2007-09-19 16:02:09WAITING FOR "BOB"

Review Stop Z ZONING
Rev No 1 Status N Date 2007-10-03 Cont ID  
Sent By choops Date 2007-10-03 Time 10:01 Rev Time 0.00
Received By choops Date 2007-10-03 Time 10:01 Sent To  
Notes
2007-10-03 10:02:05*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.