Plan Review Details - Permit 07090546
Plan Review Stops For Permit 07090546
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-10-06 Cont ID  
Sent By mjacobs Date 2007-10-06 Time 08:05 Rev Time 0.00
Received By mjacobs Date 2007-10-06 Time 07:30 Sent To  
Notes
2007-10-06 08:05:32ADDITIONAL FEES ARE DUE $422.20

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-17 Cont ID  
Sent By dpalmer Date 2007-10-17 Time 14:43 Rev Time 0.00
Received By dpalmer Date 2007-10-17 Time 13:38 Sent To PC
Notes
2007-10-17 14:43:45 
 *** PROVISO/REVISION NEEDED *****
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH STILL
 NEEDS TO BE ADDRESSED.
 THIS HAS BEEN SET UP AS A *PROVISO* WHICH WILL REQUIRE
 REVISIONS *BEFORE* ROUGH ELECTRICAL INSPECTION.
  
 1) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW, THE
 FOLLOWING CODES SHALL BE STATED ON THE ELECTRICAL PLANS
 FOR MINIMUM RELEVANT CODE DESIGN.
 FBC 2004 W/2006 REVS?
 2005 NFPA-70 (NEC).
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE TWO NEW OFFICE ROOMS BEING
 CREATED NEED TO HAVE LIGHTING CONTROLS TO MEET 13-101,
 13-415.1.ABC.1, 13-415.1.ABC.1.2.
 (TIMER TYPE DEVICES, MAXIMUM OF 4HRS, OCCUPANCY TYPE
 DEVICES 30MINS)
  
 3) NOTE: PLEASE SUBMIT A REVISED PANEL SCHEDULE AND
 LOADS FOR NEW CIRCUITS.
 220, 215.5, 408.4, 310.16, 240.4,
 FBC 106.3.5.1.2, 106.1.2
  
 ** AS STATED ON PREVIOUS REVIEW:
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-28 Cont ID  
Sent By dpalmer Date 2007-09-28 Time 19:24 Rev Time 0.00
Received By dpalmer Date 2007-09-28 Time 18:59 Sent To  
Notes
2007-09-28 19:24:552007-09-28 19:24:55
  
 ** DENIED **
  
 CORRECTIONS/ADJUSTMENTS NEEDED.
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** SOME OF THE ABOVE ARE NOTED ON PLANS.
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, 13-103 AS THE NEW
 LIGHTING CONTROL DEVICES BEING REPLACED NEED TO CONTAIN
 AUTOMATED CONTROL.(MAXIMUM OF 30MINS FOR OCCUPANCY TYPE
 DEVICES AND 4HRS FOR TIMERS).
  
 3) NOTE: PLEASE INDICATE THE CIRCUITING FOR NEW
 RECEPTACLES/LIGHTS AND TO WHICH PANEL THESE WILL BE FED
 FROM.
 PLEASE CLARIFY SIZE OF CONDUCTORS AND CIRCUIT
 AMPERAGE.
 PLEASE CLARIFY IF THIS SPACE IS ONE TENANT. THIS SEEMS
 TO BE THE CASE HOWEVER THIS IS NOT COMPLETELY CLEAR AT
 THIS TIME.
  
 ** PLEASE KNOW, IF ALL OTHER TRADES PASS THEIR REVIEW,
 A *PROVISO* MAY BE CONSIDERED FOR ISSUANCE OF PERMIT AS
 THE ABOVE ITEMS COULD BE ADJUSTED AND SUBMITTED AS A
 REVISION BEFORE ROUGH.
 THIS IS ONLY IF ALL OTHER TRADES PASS REVIEWS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-10-11 Cont ID  
Sent By mawillia Date 2007-10-11 Time 14:54 Rev Time 0.00
Received By mawillia Date 2007-10-11 Time 14:17 Sent To  
Notes
2007-10-11 14:54:36*****APPROVED*****
  
  
 PLAN SHEET A.3 STAMPED, INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 10:15 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 10:15 Sent To E
Notes
2007-10-17 10:15:49TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-11 Cont ID  
Sent By mawillia Date 2007-10-11 Time 14:17 Rev Time 0.00
Received By mawillia Date 2007-09-28 Time 10:27 Sent To  
Notes
2007-09-28 10:27:36TO "BOB"#9
2007-09-19 11:13:31WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-09-28 Cont ID  
Sent By tgordon Date 2007-09-28 Time 13:33 Rev Time 0.20
Received By tgordon Date 2007-09-28 Time 13:33 Sent To  
Notes
2007-09-28 13:33:48RE-LOCATE A/C GRILLS.

Review Stop Z ZONING
Rev No 1 Status N Date 2007-10-03 Cont ID  
Sent By choops Date 2007-10-03 Time 10:00 Rev Time 0.00
Received By choops Date 2007-10-03 Time 10:00 Sent To  
Notes
2007-10-03 10:00:21*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.