Plan Review Details - Permit 07090538
Plan Review Stops For Permit 07090538
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-01-10 Cont ID  
Sent By shill Date 2008-01-10 Time 18:39 Rev Time 0.00
Received By shill Date 2008-01-10 Time 18:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-12-13 Cont ID  
Sent By shill Date 2007-12-13 Time 17:52 Rev Time 0.00
Received By shill Date 2007-12-13 Time 17:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-12-05 Cont ID  
Sent By shill Date 2007-12-05 Time 15:47 Rev Time 0.00
Received By shill Date 2007-12-05 Time 15:47 Sent To  
Notes
2007-12-05 15:56:26****CORRECTIONS****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.SEE 11-4.9.4, HANDRAILS FOR STAIRS, AND REVISE
 PLANS.
  
 4TH REVIEW, NOT ADDRESSED.EXTENSIONS AT TOP AND
 BOTTOM NOT PROPERLY SHOWN.PLEASE SEE THE CODE
 REFERENCE AND SHOW ALL HANDRAIL EXTENSION DIMENSIONS.
 ALSO SEE FBC 11 FIGURES 18 AND 19.
  
 2.SEE 11-4.8.5, HANDRAILS FOR RAMPS, AND REVISE
 PLANS.
  
 SEE ITEM 1.PLEASE SHOW EXTENSIONS INCLUDING ALL
 DIMENSIONS TO SHOW CODE COMPLIANCE.
  
 3.ADDRESSED.
  
 4.NO PICKET SPACING OR ANY OTHER DIMENSIONS SHOWN FOR
 THE STAIRS.PLEASE SEE FBC1009 AND SHOW COMPLIANCE.
  
 5.ENGINEER'S DESIGN IS FOR A POOL RAILING.SEE
 FBC1009, FBC1607.STATE DESIGN CRITERIA FOR HANDRAILS.
 IT IS NOT CLEAR IF GUARDRAIL STRENGTH IS REQUIRED AS
 RISE WAS NOT SHOWN AS REQUESTED.
  
 6.SHOW RISE FOR RAMP.SEE FBC1012.1.
  
 7.RAILING HEIGHT ON SHEET 1 (38") CONFLICTS WITH
 SHEET 2 (42").
  
 8.THIS IS NOT CONSIDERED A RAMP IF THE SLOPE IS LESS
 THAN 1:20, FBC11-3.IF IT IS NOT A RAMP, THE HANDRAIL
 EXTENSIONS ARE NOT REQUIRED TO COMPLY WITH FBC11-4.8.
 HAVE THE ENGINEER REVISE THE PLAN TO SHOW THE SLOPE.
  
 9.HANDRAILS ARE REQUIRED AT BOTH SIDES OF STAIRS AND
 RAMPS, FBC11-4.8.5(1), 11-4.9.4.THE EXCEPTION NOTED
 BY CONTRACTOR IN AN EMAIL IS FOR GUARDRAILS. A
 GUARDRAIL IS NOT REQUIRED, BUT HANDRAILS ARE REQUIRED.
  
  
 10.A 4X PLAN REVIEW FEE HAS BEEN CHARGED,
 FS553.80(2)(B), AS REQUIRED BY FLORIDA STATUTE, SEE
 ATTACHED.THIS FEE WILL BE CHARGED EVERY TIME THE
 COMMENTS ARE NOT ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-11-08 Cont ID  
Sent By shill Date 2007-11-08 Time 10:26 Rev Time 0.00
Received By shill Date 2007-11-08 Time 10:26 Sent To  
Notes
2007-11-08 10:38:09****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.SEE 11-4.9.4, HANDRAILS FOR STAIRS, AND REVISE
 PLANS.
  
 3RD REVIEW, NOT ADDRESSED.EXTENSIONS AT TOP AND
 BOTTOM NOT PROPERLY SHOWN.PLEASE SEE THE CODE
 REFERENCE AND SHOW ALL HANDRAIL EXTENSION DIMENSIONS.
 ALSO SEE FBC 11 FIGURES 18 AND 19.
  
 2.SEE 11-4.8.5, HANDRAILS FOR RAMPS, AND REVISE
 PLANS.
  
 SEE ITEM 1.PLEASE SHOW EXTENSIONS INCLUDING ALL
 DIMENSIONS TO SHOW CODE COMPLIANCE.
  
 NEW COMMENTS:
  
 3.SHOW HEIGHT OF STAIR RAILING AS WELL AS RISE; SEE
 FBC11-4.8.
  
 4.NO PICKET SPACING OR ANY OTHER DIMENSIONS SHOWN FOR
 THE STAIRS.PLEASE SEE FBC1009 AND SHOW COMPLIANCE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-30 Cont ID  
Sent By shill Date 2007-10-30 Time 17:27 Rev Time 0.00
Received By shill Date 2007-10-30 Time 17:27 Sent To  
Notes
2007-10-30 17:31:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.SEE 11-4.9.4, HANDRAILS FOR STAIRS, AND REVISE
 PLANS.
  
 2.SEE 11-4.8.5, HANDRAILS FOR RAMPS, AND REVISE
 PLANS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-21 Cont ID  
Sent By shill Date 2007-09-21 Time 16:19 Rev Time 0.00
Received By shill Date 2007-09-21 Time 16:19 Sent To  
Notes
2007-09-21 16:21:41****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE A DETAIL FOR THE RAMP AND RAILING.SEE
 FBC11-4.8.5.THE DETAIL PROVIDED WAS FOR A POOL
 BARRIER, NOT A HANDRAIL.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-03 Cont ID  
Sent By adarroug Date 2008-01-03 Time 14:59 Rev Time 0.00
Received By adarroug Date 2008-01-03 Time 14:59 Sent To B
Notes
2008-01-03 14:59:38TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-29 Cont ID  
Sent By adarroug Date 2007-11-29 Time 08:45 Rev Time 0.00
Received By adarroug Date 2007-11-29 Time 08:45 Sent To B
Notes
2007-11-29 08:46:06TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-05 Cont ID  
Sent By adarroug Date 2007-11-05 Time 16:52 Rev Time 0.00
Received By adarroug Date 2007-11-05 Time 16:52 Sent To B
Notes
2007-11-05 16:53:14TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 09:28 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 09:28 Sent To B
Notes
2007-10-11 09:29:08TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-21 Cont ID  
Sent By shill Date 2007-09-21 Time 16:21 Rev Time 0.00
Received By shill Date 2007-09-19 Time 09:20 Sent To  
Notes
2007-09-19 09:21:33TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2007-09-21 Cont ID  
Sent By choops Date 2007-09-21 Time 12:15 Rev Time 0.00
Received By choops Date 2007-09-21 Time 12:15 Sent To B
Notes
***NONE***