2007-09-20 09:25:24 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| 1) ENERGY CALCULATIONS NEED TO BE DONE BY FORM 400A-04R |
| V.2.5, SEE FBC 13-400.3.A. PLEASE CORRECT. |
| |
| 2) WHEN SUBMITTING CORRECTED ENERGY CALCULATIONS SEE |
| (IMPORTANT NOTE) ON FRONT PAGE REGARDING INPUT REPORT |
| PRINT-OUT, PLEASE COMPLY. |
| |
| 3) WHEN SUBMITTING CORRECTED ENERGY CALCULATIONS THEY |
| WILL NEED TO BE SIGNED BY OWNER/AGENT ALSO, PER 2004 |
| FBC 13-400.3.ABC.2. |
| |
| 4) ENERGY CALCULATIONS PAGE 4 SHOW SYSTEM 2 AS 14 SEER, |
| MECHANICAL PLAN SHOWS IT AS A 13 SEER, THE TWO MUST |
| COINCIDE. PLEASE CORRECT. |
| |
| 5) THE N.O.A. FOR THE A/C CONDENSER STAND EXPIRED ON |
| 5/14/07. PLEASE CORRECT. |
| |
| 6) MECHANICAL PLAN EQUIPMENT SCHEDULE NEEDS TO SHOW THE |
| MANUFACTURER'S NAME. |
| |
| 7) I COULD NOT FIND THE A/C SYSTEMS ON THE ARI |
| DIRECTORY WEB-SITE, PLEASE SUBMIT ARI DIRECTORY PAGE |
| FOR A/C SYSTEMS. |
| |
| 8) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS AND SHOW |
| OUTDOOR AIR IS BEING SUPPLIED TO THE SPACE ON |
| MECHANICAL PLAN,SEE MECH. 403.3. |
| |
| MECHANICAL PLAN REVIEW BY; |