Plan Review Details - Permit 07090519
Plan Review Stops For Permit 07090519
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-05-17 Cont ID  
Sent By amorse Date 2008-05-17 Time 07:41 Rev Time 0.00
Received By amorse Date 2008-05-17 Time 07:41 Sent To  
Notes
2008-05-17 07:43:15 
  
 REVISION #2 WINDOW AND DOOR PRODUCT APPROVALS, (CHANGE
 OF MANUFACTURER) PASSED

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-05-17 Cont ID  
Sent By amorse Date 2008-05-17 Time 06:35 Rev Time 0.00
Received By amorse Date 2008-05-17 Time 06:35 Sent To PC
Notes
2008-05-17 06:37:55 
 REVISION #1 BEAM CHANGE AT REAR PATIO, PASSED

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-05-08 Cont ID  
Sent By amorse Date 2008-05-08 Time 16:56 Rev Time 0.00
Received By amorse Date 2008-05-08 Time 16:56 Sent To PC
Notes
2008-05-08 17:02:02 
  
 REVISION #1 DENIED
  
 1)PROVIDE ATTACHMENT DETAIL OF LVL TO TOP OF BLOCK
 COLUMNS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-03 Cont ID  
Sent By amorse Date 2008-01-03 Time 18:22 Rev Time 0.00
Received By amorse Date 2008-01-03 Time 18:22 Sent To PC
Notes
2008-01-03 18:32:01 
  
 PASSED
  
 1)PLEASE NOTE THAT NO CONNECTORS WERE STATED FOR THE
 GIRDER TRUSSES AND (2) HAVE UPLIFTS THAT EXCEED THAT OF
 THE HETAL POURED IN STRAPS ON THE DRAWINGS.
  
 2)ONLY FRENCH DOOR PRODUCT APPROVALS WERE SUBMITTED
 BUT THE ENTRY DOOR TO THE GARAGE LOOKS TO BE A METAL
 PANEL DOOR, NO SCHEDULE WAS PRESENT ON THE DRAWINGS TO
 MAKE A DETERMINATION. IF A STEEL DOOR IS USED A
 REVISION WILL BE REQUIRED FOR THAT DOOR.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-07 Cont ID  
Sent By amorse Date 2007-12-07 Time 18:40 Rev Time 0.00
Received By amorse Date 2007-12-07 Time 18:40 Sent To PC
Notes
2007-12-07 18:50:41 
  
 DENIED
  
 1)NO PRODUCT APPROVAL WAS SUBMITTED FOR THE ROOFING
 MATERIALS, PLEASE SUBMIT (2) COPIES FOR ROOF TILES
  
 2)TRUSS ENGINEERING THAT WAS SUBMITTED IS NOT
 DESIGNED TO THE LOADS REQUIRED BY THE DESIGNER OF
 RECORD IN THE CONTRACT DOCUMENTS ON SHEET S.1 PLEASE
 CLARIFY
  
 3)PLEASE KNOW THAT PER 713.13(2) F.S. IF THE
 IMPROVEMENT DESCRIBED IN THE NOC HAS NOT COMMENCED
 WITHIN 90 DAYS OF RECORDING, THE NOTICE IS VOID AND IS
 REQUIRED TO BE RE-RECORDED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-09 Cont ID  
Sent By amorse Date 2007-10-09 Time 15:47 Rev Time 0.00
Received By amorse Date 2007-10-09 Time 15:47 Sent To PC
Notes
2007-10-09 16:35:59 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 4)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $ FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 6)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 7)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 8)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 9)NO PRODUCT APPROVALS WERE SUBMITTED FOR EXTERIOR
 DOORS, WINDOWS, GARAGE DOORS, LINTELS, MULLIONS FOR
 JOINED WINDOWS, ROOFING,CONNECTORS AND STRAPS (OR ADD
 FLORIDA PRODUCT APPROVAL NUMBERS TO THE CONNECTOR
 SCHEDULE), ETC.
  
 10)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC
 2004. THE EXEMPTION FROM LICENSURE UNDER 481.229 FS
 DOES NOT EXEMPT THE DESIGNER RESPONSIBLE FOR THE
 DRAWINGS FROM SIGNING AND DATING SAID DRAWINGS.
  
 11)PROVIDE STRUCTURAL DETAIL FOR THE FRONT PORCH AREA
 THAT SHOWS POST TO BEAM CONNECTION AND BEAM TO WALL AT
 MAIN HOUSE, ETC.
  
 12)REAR COLUMNS DO NOT SHOW BEAM ABOVE OR IT'S
 DIMENSIONS FOR SUPPORT OF ROOF
  
 13)PROVIDE DETAIL OF GARAGE DOOR BUCK IF NOT STATED
 IN THE PRODUCT APPROVAL
  
 14)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 15)PROVIDE MIN. R-VALUE OF WALL AND CEILING
 INSULATION, BE SURE TO MATCH THE VALUES IN THE ENERGY
 CALC'S
  
 16)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 17)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS
 REQUIRED PER R807.1 FBC RES.
  
 18)PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER
 R322.1.1 FBC
  
 19)THE SOIL REPORT PERFORMED BY THE GEOTECHNICAL
 ENGINEER STATES A BEARING CAPACITY OF 2000 PSF AND THE
 BUILDING HAS BEEN DESIGNED ON AN ASSUMED BEARING OF
 3000 PSF
  
 20)PROVIDE DETAIL OF SEPARATION BETWEEN GARAGE AND
 RESIDENCE FOR WALLS AND DOOR PER R309.1 AND R309.2 FBC
 RES.
  
 21)PROVIDE SIZE OF ATTIC VENTILATION THAT MEETS THE
 REQUIREMENTS OF R806.2 FBC RES.
  
 22)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-12-30 Cont ID  
Sent By lwagner Date 2009-01-13 Time 10:10 Rev Time 0.00
Received By btrobaug Date 2008-12-30 Time 08:28 Sent To PC
Notes
2008-12-30 08:57:47 
  
 REVISION FOR SERVICE ONLY./WRT.
2008-12-29 08:54:42SENT TO BT.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-07-24 Cont ID  
Sent By btrobaug Date 2008-07-24 Time 11:02 Rev Time 0.00
Received By btrobaug Date 2008-07-24 Time 10:50 Sent To PC
Notes
2008-07-24 11:02:27 
  
  
  
 NONCOMPLIANT/REVISION DENIED
  
  
 1} THE ARCHITECTURAL FIRM WHO IS THE DESIGNER OF
 RECORD, MUST SIGN, SEAL AND DATE THE PLAN PER
 481.221(1)(B)FS.HE MUST APPROVE ALL CHANGES TO HIS
 DESIGN.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66, INDICATE SAME ON THE PLAN
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-12-28 Cont ID  
Sent By dpalmer Date 2007-12-28 Time 10:23 Rev Time 0.00
Received By dpalmer Date 2007-12-28 Time 09:12 Sent To P
Notes
2007-12-28 10:23:24 
 *** REDLINED PLANS***
  
 1) THE CONDUIT AND CONDUCTORS FROM METER TO MAIN
 BREAKER PANEL SHALL BE INSTALLED UNDERGROUND/IN SLAB.
 230.70, 230.71.
 IF THIS IS NOT DONE, A MAIN WITH OVER CURRENT
 PROTECTION WILL BE REQUIRED OUTSIDE ALONG WITH AN
 EQUIPMENT GROUNDING CONDUCTOR AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 2)KITCHEN WALL AS NOTED ON PREVIOUS REVIEW MUST MEET
 210.52 FOR RECEPTACLE SPACING. RECEPTACLE SHOWN IS NOT
 WITHIN 6FT OF DOOR WAY.
  
 3) PLANS SHOW TWO GARAGE DOOR OPENERS HOWEVER PANEL
 SCHEDULE ONLY SHOWS ONE CIRCUIT.
 PLEASE SEE 430.248 AS THE HP RATING OF EACH MOTOR MAY
 REQUIRE TWO SEPARATE CIRCUITS BEING DEDICATED.
  
 4) LOW VOLTAGE SHOWN ON PLAN REQUIRES A SEPARATE
 PERMIT. PLANS SHOW PHONE AND CATV ONLY.
 MAY REFERENCE THESE PLANS FOR CATV AND PHONE.
 ANY OTHER SYSTEMS INSTALLED (IE: ) SPEAKERS, WILL
 REQUIRED PLANS/LAYOUT OF LOCATIONS.
  
 IF THERE ARE ANY QUESTIONS ON THE ABOVE PLEASE DO NOT
 HESITATE IN CONTACTING THIS REVIEWER DIRECTLY.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-20 Cont ID  
Sent By dpalmer Date 2007-11-20 Time 15:48 Rev Time 0.00
Received By dpalmer Date 2007-11-20 Time 08:45 Sent To M
Notes
2007-11-20 15:49:15** DENIED 2ND REVIEW **
  
 ** PLEASE KNOW AS PLANS ARE ONLY NOW BEING COMPLETED
 AND SUBMITTED FOR ELECTRICAL REVIEW THERE ARE SEVERAL
 NEW COMMENTS. THESE COMMENTS COULD NOT HAVE BEEN MADE
 ON PREVIOUS PLANS SUBMITTED..
  
 1) NOTE:PLEASE COMPLETE TITLE BLOCKS WITH LICENSE
 INFORMATION AND ADDRESS INFORMATION WHICH COORDINATES
 WITH THE STATE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION.
 PLEASE SEE IT SEEMS THE LAST NUMBER OF THE LICENSE
 NUMBER IS NOT BEING PRINTED ON SHEETS. THIS COULD HAVE
 BEEN REDLINED, HOWEVER PLANS WERE COMING BACK FOR OTHER
 COMMENTS.
 PLEASE SEE THE ADDRESS ON THE STATE SITE DOES NOT
 CORRELATE. (743 BISCAYNE ?)
  
 2) NOTE: PLEASE SEE PLANS NOW INDICATE AND NEW SERVICE
 HOWEVER PLEASE SHOW THE LOCATION OF THE SERVICE
 EQUIPMENT ON PLANS.
 WE ARE UNABLE TO DETERMINE CODE COMPLIANCE WITH MANY
 ITEMS WITHOUT THESE SHOWN ON PLANS.
 110.26, 240.24, 230.70, 230.71 ETC
  
 3) NOTE: PLEASE SEE THE SCALE ON ELECTRICAL PLANS IS
 BEING SHOWN AS QUARTER INCH PER FOOT; HOWEVER THIS DOES
 NOT CORRELATE WITH THE REST OF THE PLANS/SHEETS. PLEASE
 SEE MECHANICAL PLANS FOR EXAMPLE AS THE SAME SCALE IS
 SHOWN YET THE LAYOUT IS SUBSTANTIALLY DIFFERENT.
 PLEASE KNOW THAT REVIEW FOR SOME ITEMS SUCH AS
 RECEPTACLE SPACING CAN NOT BE DONE AT THIS TIME.
 FBC 106.3.5.4, 106.3.1, 106.1
  
 4) NOTE: PLEASE SEE 210.52 AS SOME RECEPTACLES ARE
 MISSING FOR RULING.
 PLEASE SEE KITCHEN WALL FOR EXAMPLE WHERE NO
 RECEPTACLES ARE BEING SHOWN. (ONE LOCATION NOTED
 ONLY).
  
 5) NOTE: PLEASE SEE RISER SHOWS AN EQUIPMENT GROUNDING
 CONDUCTOR FROM THE NEW METER TO THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED.
 PLEASE SEE 240.24, 250.6.
  
 6)NOTE: PLEASE SEE MISSING LOAD FOR DINING AS
 REQUIRED PER 210.52B1, 220.53.
 PLEASE SEE THAT ONE OR *MORE* OF THE REQUIRED CIRCUITS
 EACH REQUIRE 1500VA.
  
 7) NOTE: PLEASE SEE 220.54 AS THE MINIMUM VA FOR THE
 DRYER SHALL BE 5KVA.
 (PLANS SHOW 4).
  
 8) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS ON
 PLANS. SOME ITEMS CAN NOT BE REVIEWED FOR CODE
 COMPLIANCE AT THIS TIME.
  
 9) NOTE: PLEASE SEE THE PANEL SCHEDULE AND LOAD
 CALCULATIONS ARE MISSING THE REQUIRED DEDICATED
 CIRCUIT(S) FOR GDO/ GARAGE DOOR OPENERS.
 430.148, 310.16, 240.4, 220.
 FBC 106.1.2
  
 10) NOTE: PLEASE VERIFY 350MCM FOR SERVICE ENTRANCE
 CONDUCTORS. THIS IS NOT A CODE ISSUE HOWEVER IF SHOWN
 AS 350MCM ON PLANS, THIS IS WHAT WILL BE REQUIRED TO BE
 INSTALLED. THIS IS ONLY NOTED FOR INFORMATION ONLY.
  
 11) NOTE: PLEASE MAKE NOTE FOR SECTION OF FBC
 13-606.1.ABC.1.2.4 FOR TYPE OF RECESSED LIGHTING
 FIXTURES.
  
 12) NOTE: PLEASE SEE THERE ARE SOME LIGHTING FIXTURES
 ON PLANS WHICH DO NOT INDICATE ANY CONTROLS.
 PLEASE SEE FOR EXAMPLE WHAT APPEAR TO BE MASTER BEDROOM
 LIGHTS.
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE 210.8A2 FOR REQUIRED GFI
 RECEPTACLES IN GARAGE.
 MISSING GFI DESIGNATION(S).
  
 14) NOTE: PLEASE SEE 210.8A3 AS ALL RECEPTACLES OUTSIDE
 ARE ALSO REQUIRED TO BE GFI. PLEASE SEE MISSING
 DESIGNATIONS.
  
 15) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING
 RECEPTACLE(S) PER 210.52C2 AND 4.
 PLEASE SEE THIS IS FOR WHAT IS SHOWN AS A SECOND
 ISLAND.
 PLEASE CLARIFY THE RECEPTACLE AS SHOWN. THIS IS SHOWN
 IN SINK OR UNDER SINK.
 THIS LOCATION, WALL, COUNTER SPACE IS UNCLEAR AT THIS
 TIME.
  
 ** PLEASE KNOW AS SOME ITEMS WERE NOT SHOWN AT THIS
 TIME, SOME ITEMS COULD NOT BE DETEMINED.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-23 Cont ID  
Sent By dpalmer Date 2007-09-23 Time 09:40 Rev Time 0.00
Received By dpalmer Date 2007-09-23 Time 09:16 Sent To M
Notes
2007-09-23 09:40:44 
 ** DENIED**
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THAT ALL THREE SETS OF PLANS
 SUBMITTED ARE PHOTO-COPIES AND ARE NOT ORIGINAL SIGNED,
 DATED AND SEALED PLANS AS REQUIRED PER FS 481.221.
 ** PLEASE KNOW THAT FOR A SINGLE FAMILY DWELLING ONLY
 TWO SIGNED, DATED AND SEALED SETS ARE NEEDED.
 IF A THIRD SET IS DESIRED FOR STAMPING/DUPLICATE, THEN
 A THIRD SET OF SIGNED, DATED AND SEALED PLANS MAY BE
 PROVIDED FOR STAMPING.
  
 3) NOTE: PLEASE ADJUST AND COMPLETE TITLE BLOCK WITH
 ALL LICENSE INFORMATION NEEDED. PLEASE SEE TITLE BLOCKS
 STILL INDICATE MR. LITTLE. THIS REVIEWER HAS BEEN IN
 CONTACT WITH MR. ROY FOR REQUIRED
 INFORMATION/ADJUSTMENTS.
 FAC 61G1-16.004, FS 481.219.
  
 4) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS FOR
 REVIEW FOR CODE COMPLIANCE WITH THE PREVIOUS NOTED
 CODES ABOVE. PLEASE SEE NFPA-70 (NEC 2005) AND
 NFPA-72.
 ALL THREE SETS DO NOT CONTAIN ELECTRICAL PLANS. FBC
 106.1.2, 106.1.3, 106.3.5.4
 PLEASE PROVIDE PANEL SCHEDULE(S) WITH ALL MINIMUM
 REQUIRED CIRCUITS PER NEC. 408.4, 240.4, 310.16,
 210.52, 210.11, 220, 215.5 ETC
 PLEASE PROVIDE ALL CONDUCTOR SIZES IN PANEL(S) ALONG
 WITH CONDUCTORS SIZES.240.4, 310.16
 PLEASE PROVIDE A RISER DIAGRAM FOR NEW OR EXISTING
 PROPOSED SERVICE COMPLETE WITH ALLCONDUCTOR SIZES,
 CONDUITS, FEEDERS, GROUNDING, AIC RATINGS AND OVER
 CURRENT PROTECTION DEVICES.
 230.70, 230.71, 1100.9, 230.72, 230.76, 230.79, 310.16,
 250.50, 240.4 ETC
 PLEASE PROVIDE ALL SMOKE ALARM LOCATIONS INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS PER NFPA-72 11.5.1.1,
 11.8.3. FBC R313, FBC 905.2, ETC.
 PLEASE PROVIDE ALL RECEPTACLE LOCATIONS REQUIRED PER
 ALL OF 210.52
 PLEASE PROVIDE ALL LIGHTING AND CONTROL LOCATIONS PER
 210.70, LS 101 7.8.
 PLEASE BE SURE TO PROVIDE LISTING OF ALL ARC FAULT
 PROTECTED CIRCUITS PER 210.12.
 PLEASE PROVIDE ALL DISCONNECTING MEANS FOR EQUIPMENT AS
 REQUIRED. 440.11, 422.30, 422.31.
 PLEASE PROVIDE LOAD CALCULATIONS FOR ALL ELECTRICAL
 FROM NEW OR EXISTING SERVICE. NEC 220.**PLEASE BE SURE
 TO SEE THE NEW 2005 CODE WITH RESPECT TO WATER HEATERS
 TO BE FIGURED AT 125% PER 422.13.
 PLEASE SUBMIT ENERGY CALCULATIONS PER FBC CHAPTER 13.
 PLEASE BE SURE TO REFERENCE ANY RECESSED LIGHTING PER
 FBC 13-606.1.ABC.1.2.4 FOR *AIR MOVEMENT* ALLOWANCES
 FROM CONDITIONED SPACE.
  
 ** PLEASE SEE SOME OF THE ITEMS REFLECT ABOVE ARE IN NO
 WAY ALL ITEMS IN THE NEC WHICH WILL BE REVIEWED.
 THE ITEMS ABOVE ARE FOR ITEMS NEEDED, AS EACH DWELLING
 AND SCOPE OF WORK VARIES AND PLANS WERE NOT SUBMITTED
 FOR REVIEW IT IS NOT POSSIBLE TO GIVE CODE COMPLIANT
 REVIEW AT THIS TIME.
 PLEASE KNOW THERE MAY VERY WELL BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH COULD NOT BE MADE AT THIS TIME.
 **IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2009-01-23 Cont ID  
Sent By rregueir Date 2009-01-23 Time 15:31 Rev Time 0.00
Received By rregueir Date 2009-01-23 Time 15:30 Sent To P
Notes
2009-01-23 15:31:04ROUTED TO LWAGNER DESK

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-12-22 Cont ID  
Sent By adarroug Date 2008-12-22 Time 16:56 Rev Time 0.00
Received By adarroug Date 2008-12-22 Time 16:56 Sent To E
Notes
2008-12-22 16:57:03TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-12-18 Cont ID  
Sent By adarroug Date 2008-12-18 Time 11:18 Rev Time 0.00
Received By adarroug Date 2008-12-18 Time 11:18 Sent To M
Notes
2008-12-18 11:18:56TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-12-18 Cont ID  
Sent By adarroug Date 2008-12-18 Time 09:50 Rev Time 0.00
Received By adarroug Date 2008-12-18 Time 09:50 Sent To M
Notes
2008-12-18 09:51:39TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-11-25 Cont ID  
Sent By adarroug Date 2008-11-25 Time 10:38 Rev Time 0.00
Received By adarroug Date 2008-11-25 Time 10:38 Sent To P
Notes
2008-11-25 10:38:47TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-09-02 Cont ID  
Sent By adarroug Date 2008-09-02 Time 16:00 Rev Time 0.00
Received By adarroug Date 2008-09-02 Time 16:00 Sent To Z
Notes
2008-09-02 16:00:41TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-07-01 Cont ID  
Sent By adarroug Date 2008-07-01 Time 11:38 Rev Time 0.00
Received By adarroug Date 2008-07-01 Time 11:38 Sent To E
Notes
2008-07-01 11:38:59TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 16:24 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 16:24 Sent To M
Notes
2008-06-17 16:24:32TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 11:18 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 11:18 Sent To B
Notes
2008-05-14 11:20:20TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 09:19 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 09:19 Sent To B
Notes
2008-05-14 09:20:03TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 11:06 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 11:06 Sent To B
Notes
2008-04-30 11:07:06TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-26 Cont ID  
Sent By spalmer Date 2007-12-26 Time 15:23 Rev Time 0.00
Received By spalmer Date 2007-12-26 Time 15:23 Sent To Z
Notes
2007-12-26 15:23:31TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-14 Cont ID  
Sent By adarroug Date 2007-11-14 Time 16:34 Rev Time 0.00
Received By adarroug Date 2007-11-14 Time 16:34 Sent To Z
Notes
2007-11-14 16:34:50TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-10-09 Time   Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 08:33 Sent To  
Notes
2007-09-20 08:33:40TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-12-18 Cont ID  
Sent By rkussner Date 2008-12-18 Time 13:12 Rev Time 0.00
Received By rkussner Date 2008-12-18 Time 13:12 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-12-18 Cont ID  
Sent By hmoser Date 2008-12-18 Time 12:58 Rev Time 0.00
Received By hmoser Date 2008-12-18 Time 12:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-06-20 Cont ID  
Sent By tgordon Date 2008-06-20 Time 08:00 Rev Time 0.45
Received By tgordon Date 2008-06-20 Time 08:00 Sent To  
Notes
2008-06-20 08:11:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN.
 *** DENIED ***
  
 1) THE MECHANICAL PLAN ON FILE IS SIGNED AND SEALED BY
 AN ARCHITECT (STEPHEN M. ROY) SO ONLY HE CAN MAKE
 REVISIONS TO THEM, PER FAC 61G1-16.003.
  
 2) THE ENERGY CALCULATIONS WILL NEED TO BE REVISED AS
 THE AIR HANDLER IS NOW INSTALLED IN THE GARAGE, PER
 2004 FBC 13-600.3.ABC.2. PLEASE SUBMIT WITH PLAN
 REVISION.
  
 3) SHOW ON THE MECHANICAL PLAN HOW RETURN AIR IS
 GETTING BACK TO THE AIR HANDLER, PER 2004 FBC/R
 M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-26 Cont ID  
Sent By tgordon Date 2007-11-26 Time 10:42 Rev Time 0.30
Received By tgordon Date 2007-11-26 Time 10:42 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-24 Cont ID  
Sent By tgordon Date 2007-09-24 Time 08:57 Rev Time 0.30
Received By tgordon Date 2007-09-24 Time 08:57 Sent To P
Notes
2007-09-24 09:12:52PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PLAN PAGE M.1 THE BUILDING AND ROOM
 LAY-OUT IS FADED AND DIFFICULT TO READ, PLEASE CORRECT.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, SEE F.B.C.
 106.1.1.
  
 2) NEED TO SHOW THE SIZE AND CFM'S FOR THE SUPPLY AIR
 GRILL IN THE FAMILY ROOM.
  
 3) SUBMIT ENERGY CALCULATIONS, SEE FBC 13.101.2.
  
 4)SUBMITCOOLING LOAD CALCULATIONS, SEE 2004 FBC
 13-607.1.ABC.1.
  
 5)SUBMIT MANUAL D CALCULATIONS FOR RESIDENTIAL DUCT
 DESIGN, SEE 2004 FBC/R M1601.1 AND FBC 13-610.1.ABC.1.
  
 6) THE ARCHITECT NEEDS TO SIGN AND SEAL THE PLANS, SEE
 F.A.C. 61G1-16.003.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-01-23 Cont ID  
Sent By lwagner Date 2009-01-23 Time 16:42 Rev Time 0.00
Received By lwagner Date 2009-01-23 Time 16:04 Sent To  
Notes
2009-01-23 16:44:03REVISION OK- SAN. ISO.

Review Stop P PLUMBING
Rev No 4 Status F Date 2009-01-13 Cont ID  
Sent By lwagner Date 2009-01-13 Time 10:16 Rev Time 0.00
Received By lwagner Date 2009-01-13 Time 09:59 Sent To  
Notes
2009-01-13 10:07:12REVISION DENIED:
 ORIGINAL ISOMETRIC DRAWING SEALED BY STEPHEN ROY .
 PLANS REQUIRED TO BE SIGNED,
 DATED AND SEALED BY THE ARCHITECT,
 PLEASE SEE FS 481.221 AND FAC 61G1-16

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-12-31 Cont ID  
Sent By jleech Date 2007-12-31 Time 10:09 Rev Time 0.00
Received By jleech Date 2007-12-31 Time 10:01 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-06 Cont ID  
Sent By jleech Date 2007-12-06 Time 14:19 Rev Time 0.00
Received By jleech Date 2007-12-06 Time 14:19 Sent To B
Notes
2007-12-06 14:31:05DENIED;
 1. THE ARCHITECTURE FURM IS REQUIRED TO SHOW CORPS.
 CERTIFICATION NUMBER IN TITLE BLOCK. FBC BUILDING
 SECTION 106.1.
 2.BATHROOM AND 1/2 BATH DOWN STREAM OF THE KITCHEN
 NOT VENTED TO CODE. SEE FBC PLUMBING SECTION 909.1. THE
 SINKS CANNOT GO THREW THE BATHROOM GROUP.
 3. THE AUTOMATIC CLOTHES WASHER IS STILL NOT VENTED.
 SHOW VENT ON SANITARY RISER DIAGRAM. ( SEE ONE P.1 PAGE
 IS MARKED IN RED)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-03 Cont ID  
Sent By jleech Date 2007-10-03 Time 08:24 Rev Time 0.00
Received By jleech Date 2007-10-03 Time 08:24 Sent To B
Notes
2007-10-03 08:31:24DENIED;
 1. SEE ELECTRICAL PLAN REVIEW'S NOTES 2 & 3.
 2. RISER DIAGRAM AND FLAT DRAWING DONOT MATCH.
 3. A 2 WAY CLEANOUT IS MISSING ON FLAT DRAWING ( MARKED
 ON PLANS IN RED) A CLEANOUT IS ALSO REQUIRED ON W/M
 VENT AT 48" AFF.
 4. VENTS MISSING FROM RISER DIAGRAM ( MARKED IN RED)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status F Date 2008-09-07 Cont ID  
Sent By mcruz Date 2008-09-07 Time 12:36 Rev Time 0.00
Received By mcruz Date 2008-09-07 Time 12:23 Sent To  
Notes
2008-09-07 12:36:18***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTYS ADDRESS AND LEGAL DESCRIPTION.
  
 3. INDICATE THE DIMENSIONS OF THE PROPOSED DRIVEWAY AND
 WALKWAY (EXISTING AND PROPOSED) LOCATED WITHIN THE
 FRONT YARD (FROM FRONT PROPERTY LINE TO THE FRONT
 BUILDING FACADE).
  
 4. A TREE REMOVAL/RELOCATION PERMIT SHALL BE REQUIRED.
 PLEASE CONTACT ROBERT KUSSNER, LANDSCAPE PLANNER, AT
 (561) 822-1462 FOR FURTHER INFORMATION OF THE
 APPLICATION PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2007-12-28 Cont ID  
Sent By choops Date 2007-12-28 Time 08:35 Rev Time 0.00
Received By choops Date 2007-12-28 Time 08:35 Sent To E
Notes
2007-12-28 08:36:12***APPROVED - RESUB #2***
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 2 Status F Date 2007-11-16 Cont ID  
Sent By choops Date 2007-11-16 Time 10:50 Rev Time 0.00
Received By choops Date 2007-11-16 Time 10:50 Sent To E
Notes
2007-11-16 10:57:05***FAILED - RESUB #1***
  
  
 1)LANDSCAPING INSUFFICIENT.MUST MEET MINIMUM
 REQUIREMENTS SET FORTH IN SECTION 94-442 OF THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 INCLUDING, BUT NOT LIMITED TO:ALL LANDSCAPED OPEN
 SPACE SHALL BE COVERED WITH GRASS, GROUND COVER,
 SHRUBBERY, OR OTHER SUITABLE PLANT MATERIAL.FOR
 SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHADE,
 FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR EACH 1,200
 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF. FOR
 SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHRUB SHALL
 BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF.PLANT MATERIALS USED PURSUANT TO THE
 PROVISIONS OF THIS SECTION SHALL BE EQUAL TO OR BETTER
 THAN FLORIDA DEPARTMENT OF AGRICULTURE NUMBER 1 NURSERY
 GRADE STANDARD.SHADE, FLOWERING AND FRUIT TREES.
 SHADE, FLOWERING AND FRUIT TREES PLANTED PURSUANT TO
 THE PROVISIONS OF THIS SECTION SHALL BE A MINIMUM OF
 EIGHT FEET IN HEIGHT, AND POSSESS A MINIMUM OF FIVE
 FEET OF CLEAR TRUNK SPACE.SHRUBS FOR GENERAL
 LANDSCAPE PURPOSES PLANTED PURSUANT TO THE PROVISIONS
 OF THIS SECTION SHALL BE A MINIMUM PLANT CONTAINER SIZE
 OF TWO GALLONS.
  
 NOTE:PALM TREES DO NOT COUNT AS SHADE/FLOWERING
 TREES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2009-01-13 Cont ID  
Sent By choops Date 2007-09-20 Time 16:44 Rev Time 0.00
Received By choops Date 2007-09-20 Time 16:44 Sent To E
Notes
2007-09-20 16:51:05***FAILED***
  
  
 1)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS:RENOVATIONS, REPAIR,
 ALTERATION OR REDEVELOPMENT WHICH EXCEEDS 50 PERCENT OF
 THE VALUE OF THE STRUCTURE SHALL BE BROUGHT TO
 COMPLIANCE WITH REGARD TO LANDSCAPING.
 PLEASE PROVIDE A LANDSCAPE PLAN SHOWING COMPLIANCE WITH
 SECTION 94-442 OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 2)PLEASE PROVIDE ALL DRIVEWAY DIMENSIONS AND SQUARE
 FOOTAGE OF ALL IMPERMEABLE SURFACE WITHIN THE FRONT
 YARD, IF DRIVEWAY IS TO BE INCLUDED IN THE SCOPE OF
 WORK FOR THIS PERMIT.
  
 3)PROVIDE AN EASEMENT CONSENT FORM FROM THE CITY'S
 DEPARTMENT OF PUBLIC UTILITIES (1ST FLOOR, CITY HALL)
 FOR THE EAST AND WEST SITE WALLS.
  
 4)INDICATE ELEVATION DIMENSIONS FROM GRADE RATHER
 THAN FINISHED FLOOR.
  
 5)WESTERN SITE WALL SHALL BE SHOWN ON SITE PLAN
 (A.0).
  
 6)INDICATE SETBACK DIMENSIONS FROM ANY PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720