Plan Review Details - Permit 07090511
Plan Review Stops For Permit 07090511
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-10-09 Cont ID  
Sent By shill Date 2007-10-09 Time 17:57 Rev Time 0.00
Received By shill Date 2007-10-09 Time 17:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-28 Cont ID  
Sent By shill Date 2007-09-28 Time 16:35 Rev Time 0.00
Received By shill Date 2007-09-28 Time 16:35 Sent To  
Notes
2007-09-28 16:39:37****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 ____1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13.
  
 ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY;
 MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF
 EACH ROOF TYPE
  
 _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG.THE TILE
 AND POLYFOAM NOAS ARE NO LONGER IN THE PACKAGE.THE
 FLORIDA STATE PRODUCT APPROVAL REQUIREMENT INCLUDES THE
 FLORIDA STATE PRODUCT APPROVAL COVER SHEET,
 INSTALLATION INSTRUCTIONS AND EVALUATION REPORT.
  
 _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS. THE ASSEMBLY SELECTED REFERS TO GENERAL
 LIMITATION #9, WHICH DOES NOT ALLOW ENHANCED FASTENING.
 THIS SYSTEM HAS A PRESSURE LIMITATION OF -45PSF; -89
 MINIMUM REQUIRED FOR CORNER ZONES.
  
 _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO
 BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED
 ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB
 SHEET). THIS WAS PREVIOUSLY REQUESTED BUT WAS NOT
 ADDRESSED. THE PRODUCT YOU SELECTED REQUIRES FOR THIS
 TO BE DONE BY AN ENGINEER, ARCHITECT, OR REGISTERED
 ROOF CONSULTANT.
  
 ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM
 ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72.
  
 _XX_ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-20 Cont ID  
Sent By shill Date 2007-09-20 Time 15:07 Rev Time 0.00
Received By shill Date 2007-09-20 Time 15:07 Sent To  
Notes
2007-09-20 15:07:38****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)FROM PREVIOUS LIST:
  
 YOU MAY REMOVE THE REFERENCE TO RAS150 AND SELECT AN
 APPROVED ASSEMBLY FROM THE PRODUCT APPROVAL.ALSO
 PLEASE SUBMIT AN ENHANCED FASTENING
 LETTER/SPECIFICATION.
  
 RAS 150 REFERENCE WAS REMOVED.YOU MUST SELECT AN
 APPROVED ASSEMLY FROM THE PRODUCT APPROVAL (AND IT MUST
 REFER TO GENERAL LIMITATION #7, NOT GENERAL LIMITATION
 #9).SEE LIMITATION #7 ON PAGE 30 OF THE PRODUCT
 APPROVAL.THE NOA REQUIRES THAT THE ENHANCED FASTENING
 CALCULATIONS BE SUBMITTED BY AN ARCHITECT, ENGINEER, OR
 REGISTERED ROOF CONSULTANT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-19 Cont ID  
Sent By shill Date 2007-09-19 Time 11:36 Rev Time  
Received By shill Date 2007-09-18 Time 15:23 Sent To  
Notes
2007-09-19 11:40:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1.)PRESCRIPTIVE BUR ROOF, RAS150, IS REFERENCED IN
 HIGH VELOCITY SECTION OF THE CODE ONLY; FBC1519.1.
 PLEASE ADVISE IF YOU CAN LOCATE THIS IN THE NON-HVHZ
 SECTION OF THE FBC.YOU MAY REMOVE THE REFERENCE TO
 RAS150 AND SELECT AN APPROVED ASSEMBLY FROM THE PRODUCT
 APPROVAL.ALSO PLEASE SUBMIT AN ENHANCED FASTENING
 LETTER/SPECIFICATION.
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-09-18 Cont ID  
Sent By ssherman Date 2007-09-18 Time 11:24 Rev Time  
Received By ssherman Date   Time   Sent To  
Notes
2007-09-18 11:19:31GAS STOP ENTERED IN ERROR

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-09-18 Cont ID  
Sent By ssherman Date 2007-09-18 Time 11:25 Rev Time 0.00
Received By ssherman Date 2007-09-18 Time 11:25 Sent To  
Notes
2007-09-18 11:25:42HISTORICAL APPROVAL PER FRIEDERIKE MITTNER