Plan Review Details - Permit 07090466
Plan Review Stops For Permit 07090466
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-03-28 Cont ID  
Sent By lmartine Date 2008-03-28 Time 14:21 Rev Time 0.00
Received By lmartine Date 2008-03-28 Time 14:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-03-10 Cont ID  
Sent By mjacobs Date 2008-03-10 Time 15:33 Rev Time 0.00
Received By lmartine Date 2008-03-10 Time 14:20 Sent To  
Notes
2008-03-10 15:33:02 
 1041 45TH ST 2ND REV.DOC
 BUILDING PLAN REVIEW
 PERMIT: 07090466
 ADD: 1041 45TH STREET
 CONT: NEUTRON ELECTRIC
 TEL: (561)201-5005
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD 3-10-08
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS, PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT APPLICATION (FIRST TIME
 REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE
 2004 FBC BUILDING WITH THE 2007 REVISIONS.
  
 2) 3RDREQUEST, MISSING INFORMATION ON PLAN IN REGARDS
 TO WIND: 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE
 CONSTRUCTION DRAWINGS, 1)- BASIC WIND SPEED, MPH 2)-
 WIND IMPORTANCE FACTOR, & BUILDING CATEGORY3)- WIND
 EXPOSURE
  
 3) 3RDREQUEST,2004 FBC 1609.1.3 PLEASE PROVIDE
 INFORMATION ON THE ANCHORAGE THE GENERATOR TO RESIST
 THE MOMENT OF OVERTURNING, UPLIFT AND SLIDING.
 GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE SIZE
 OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE
 INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.
  
 THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. PLEASE SEE ELECTRICAL
 COMMENTS FOR ADDITIONAL INFORMATION REQUIRED FOR THE
 DESIGNER. FL.S .S 481.229 (ARCHITECT) OR FL.S.S 471.003
 (ENGINEER). THIS AREA IS IN A FLOOD ZONE AH; THEREFORE
 THE ELEVATION OF THE CONCRETE SHALL BE A MINIMUM OF
 17'6", WHICH SHALL BE STATED OF THE ENGINEERED PLANS.
 ALL DIMENSIONS FOR THE CONCRETE SLAB SHALL BE INDICATED
 ON THE DRAWINGS INCLUDING THE THICKNESS. INDICATE THE
 CLEARANCE AROUND THE GENERATOR FOR MAINTENANCE AND
 REPAIR WORK.
  
 **NOTE** IN ORDER TO PROVIDE CONFORMITY TO OUR RECORD
 RETENTION PROGRAM 'NO WHITE-OUT OR HANDWRITING IN PEN
 OR PENCIL' ON THE DRAWINGS OR REPORTS WILL BE
 ACCEPTABLE. CLEARLY STATE IF THE GENERATOR IS USED FOR
 LIFE SAFETY ISSUES.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)805-6676
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-17 Cont ID  
Sent By jwitmer Date 2007-12-17 Time 10:46 Rev Time 0.77
Received By jwitmer Date 2007-12-17 Time 10:46 Sent To  
Notes
2007-12-17 10:48:17BUILDING PLAN REVIEW
 PERMIT: 07090466
 ADD: 1041 45TH STREET
 CONT: NEUTRON ELECTRIC
 TEL: (561)201-5005
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT APPLICATION (FIRST TIME
 REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE
 2004 FBC BUILDING WITH THE2007 REVISIONS.
  
 2) 2ND REQUEST, MISSING INFORMATION ON PLAN IN REGARDS
 TO WIND: 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE
 CONSTRUCTION DRAWINGS, 1)- BASIC WIND SPEED, MPH 2)-
 WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
  
 3) 2ND REQUEST,2004 FBC 1609.1.3 PLEASE PROVIDE
 INFORMATION ON THE ANCHORAGE THE GENERATOR TO RESIST
 THE MOMENT OF OVERTURNING, UPLIFT AND SLIDING.
 GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE
 SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE
 INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.
  
 THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. PLEASE SEE ELECTRICAL
 COMMENTS FOR ADDITIONAL INFORMATION REQUIRED FOR THE
 DESIGNER. FL S S 481.229 (ARCHITECT)OR FL S S 471.003
 (ENGINEER).
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-20 Cont ID  
Sent By jwitmer Date 2007-10-20 Time 09:21 Rev Time 0.75
Received By jwitmer Date 2007-10-20 Time 09:19 Sent To  
Notes
2007-10-20 09:47:03BUILDING PLAN REVIEW
 PERMIT: 07090466
 ADD: 1041 45TH STREET
 CONT: NEUTRON ELECTRIC
 TEL: (561)201-5005
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT APPLICATION (FIRST TIME
 REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE
 2004 FBC BUILDING WITH THE2007 REVISIONS.
  
 2) MISSING INFORMATION ON PLAN IN REGARDS TO WIND: 2004
 FL. BLD CODE 1603.1.4 THE FOLLOWING INFORMATION RELATED
 TO WIND SHALL BE SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
  
 3) 2004 FBC 1609.1.3 PLEASE PROVIDE INFORMATION ON THE
 ANCHORAGE THE GENERATOR TO RESIST THE MOMENT OF
 OVERTURNING, UPLIFT AND SLIDING.
 GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE
 SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE
 INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.
  
 THE NEW SLAB AND HOLD DOWN DETAILS: 104.2.1* ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. PLEASE SEE ELECTRICAL
 COMMENTS FOR ADDITIONAL INFORMATION REQUIRED FOR THE
 DESIGNER. FL S S 481.229 (ARCHITECT)OR FL S S 471.003
 (ENGINEER).
  
  
 4) PLEASE PROVIDE A SITE PLAN INDICA PROVIDE PLANS
 ENOUGH TO VERIFY LOCATION OF GENERATOR VERSES BUILDING
 OPENINGS WINDOWS, DOORS OR SOFFIT TYPE VENTS, ETC.
  
 MECHANICAL CODE
 804.3.4 HORIZONTAL TERMINATIONS. HORIZONTAL
 TERMINATIONS SHALL COMPLY WITH THE FOLLOWING
 REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO WALKWAYS, THE
 TERMINATION OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT
 LESS THAN 7 FEET (2134 MM) ABOVE THE LEVEL OF THE
 WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM)
 ABOVE ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048
 MM).
 3.THE VENT SYSTEM SHALL TERMINATE AT LEAST 4 FEET
 (1219 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM OR
 1 FOOT
 (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR INLET
 INTO THE BUILDING.
 4.THE VENT TERMINATION POINT SHALL NOT BE LOCATED
 CLOSER THAN 3 FEET (914 MM) TO AN INTERIOR CORNER
 FORMED BY TWO
 WALLS PERPENDICULAR TO EACH OTHER.
 5.THE VENT TERMINATION SHALL NOT BE MOUNTED
 DIRECTLY ABOVE OR WITHIN 3 FEET (914 MM) HORIZONTALLY
 FROM AN OIL TANK
 VENT OR GAS METER.
 6.THE BOTTOM OF THE VENT TERMINATION SHALL BE
 LOCATED AT LEAST 12 INCHES (305 MM) ABOVE FINISHED
 GRADE.
  
 804.3.5 VERTICAL TERMINATIONS. VERTICAL TERMINATIONS
 SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS:
 1.WHERE LOCATED ADJACENT TO WALKWAYS, THE
 TERMINATION OF MECHANICAL DRAFT SYSTEMS SHALL BE NOT
 LESS THAN 7
 FEET (2134 MM) ABOVE THE LEVEL OF THE WALKWAY.
 2.VENTS SHALL TERMINATE AT LEAST 3 FEET (914 MM)
 ABOVE ANY FORCED AIR INLET LOCATED WITHIN 10 FEET (3048
 MM).
 3.WHERE THE VENT TERMINATION IS LOCATED BELOW AN
 ADJACENT ROOF STRUCTURE, THE TERMINATION POINT SHALL BE
 LOCATED AT LEAST 3 FEET (914 MM) FROM
 SUCH STRUCTURE.
 4.THE VENT SHALL TERMINATE AT LEAST 4 FEET (1219
 MM) BELOW, 4 FEET (1219 MM) HORIZONTALLY FROM, OR 1
 FOOT (305 MM) ABOVE ANY DOOR, WINDOW OR GRAVITY AIR
 INLET FOR THE BUILDING. 5.A VENT CAP SHALL BE
 INSTALLED TO PREVENT RAIN FROM ENTERING THE VENT
 SYSTEM.
 6.THE VENT TERMINATION SHALL BE LOCATED AT LEAST 3
 FEET (914 MM) HORIZONTALLY FROM ANY PORTION OF THE ROOF
 STRUCTURE.
  
 501.2 OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY
 MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS
 AT A POINT WHERE IT WILL NOT CAUSE A NUISANCE AND FROM
 WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM. AIR SHALL NOT BE EXHAUSTED INTO AN
 ATTIC OR CRAWL SPACE
  
 401.5 OPENING LOCATION.
 OUTDOOR AIR EXHAUST AND INTAKE OPENINGS SHALL BE
 LOCATED A MINIMUM OF 10 FEET (3048 MM) FROM LOT LINES
 OR BUILDINGS ON
 THE SAME LOT. WHERE OPENINGS FRONT ON A STREET OR
 PUBLIC WAY, THE DISTANCE SHALL BE MEASURED TO THE
 CENTERLINE OF THE
 STREET OR PUBLIC WAY. TING THE LOCATION OF THE
 GENERATOR IN RELATIONSHIP TO OTHER STRUCTURES, PLEASE
 NOTE IF THERE ARE STRUCTURES WITHIN 10'-0" OF THE
 GENERATOR OPENINGS SUCH AS WINDOWS AND DOORS.
 ADDITIONAL INFORMATION REQUIRED. POSSIBLE MECHANICAL
 ISSUES.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-03-28 Cont ID  
Sent By lmartine Date 2008-03-28 Time 14:22 Rev Time 0.00
Received By lmartine Date 2008-03-28 Time 14:22 Sent To  
Notes
2008-03-28 14:24:42ELEVATION CERTIFICATE PROVIDED , SITE MEETS AND EXCEEDS
 FEMA REQUIREMENTS , OK TO APPROVE PER DEWEY.LM

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-03-04 Cont ID  
Sent By dpalmer Date 2008-03-04 Time 18:37 Rev Time 0.00
Received By dpalmer Date 2008-03-04 Time 18:37 Sent To PC
Notes
2008-03-04 18:37:28 
 NO REVIEW TO BE DONE, CONTRACTOR IS BRINGING IN NEW
 PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 13:56 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 13:56 Sent To  
Notes
2007-12-03 13:57:03 
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE MOST COMMENTS FROM PREVIOUS REVIEW
 REMAIN.
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS AND
 DOCUMENTS ALL ATTACHED INTO EACH SET RESPECTIVELY.
 PLEASE SEE ALL DOCUMENTS FOR EACH TRADE ARE DIVIDED AND
 NOT IN SETS.
 FBC 106.3.1, 106.1.2
  
 2) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH
 MOST STILL REMAIN.
 NEED TO KNOW THE OCCUPANCY OF PROJECT.
 NEED PLANS SHOWING LOCATION(S) FOR ALL EQUIPMENT,
 SERVICE EQUIPMENT ETC.
 NEED TO SHOW ALL RELEVANT CODES.
 NEED TO HAVE THE DESIGNER OF RECORD.
 ETC.
  
 ** PLEASE SEE THE NOTES BELOW ARE COPIED FROM PREVIOUS
 REVIEW.
  
 ** DENIED**
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-110 ( FBC CHAPTER 27 REFERENCED.
  
 2) NOTE: PLEASE SUBMIT LOADS ON THIS EXISTING/NEW
 GENERATOR TO BE INSTALLED.
 PLEASE PROVIDE INFORMATION IF THIS UNIT FEEDS ANY
 EMERGENCY LIFE SAFETY SYSTEMS OR LEGALLY REQUIRED
 SYSTEMS.700, 701,
 PLEASE SEE 700.12B3, 701.11B3 AS ANY LIFE SAFETY, OR
 LEGALLY REQUIRED SYSTEMS FED BY THIS UNIT WILL REQUIRE
 *ON-SITE* FUEL MEETING THE MINIMUM LOADS FOR THE
 MINIMUM SPECIFIED TIMES DEPENDING ON INSTALLATION. WHAT
 ARE THE INTENDED LOADS? 701.5, 700.5, 702.5
  
 3) NOTE: PLEASE SEE AS OCCUPATION FOR THE DESIGNATED
 GENERATOR IS NOT KNOWN, PLEASE BE AWARE OF HOUSE BILL
 7121 FOR STAND-BY SYSTEMS AND REQUIRED ON-SITE FUEL.
  
 4) NOTE: OK
  
 5) NOTE: PLEASE SEE FS 481.229 AND 471.003, EVEN WHEN
 THE SCOPE OF WORK IS NOT REQUIRED TO BE DONE BY AN
 ARCHITECT OR ENGINEER, THE SCOPE OF WORK STILL REQUIRES
 THE DESIGN TO CONTAIN THE PRINTED NAME AND SIGNATURE OF
 THE PERSON TAKING RESPONSIBILITY OF SAID PLANS.
 106.3.5, 106.1.2
  
 6) NOTE: PLEASE SEE POSSIBLE BUILDING COMMENTS WITH
 RESPECT TO ANY FLOOD ZONE WHICH WOULD REQUIRE THE
 GENERATOR TO BE MOUNTED 6INCHES ABOVE BFE> (IF IN FLOOD
 ZONE).
  
 7) NOTE: PLEASE SUBMIT TWO COPIES OF ALL DOCUMENTS
 SPECS/CUT SHEETS.
 FBC 106.1
  
 8) NOTE: PLEASE PROVIDE SITE/OVERVIEW OF THE LOCATION
 OF THIS UNIT AND ALL RELEVANT EQUIPMENT.
 PLEASE SEE 225.31-225.39 FOR REQUIRED DISCONNECTING
 MEANS FOR FEEDERS FROM THE GENERATOR.
 AS NO SITE PLANS AND OTHER NEEDED INFORMATION WAS
 SUBMITTED NO REVIEW OF THIS FOR CODE COMPLIANCE CAN BE
 DONE.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR
 REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL
 BE NEW COMMENTS ON THE FOLLOWING REVIEW.
 NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS
 SUBMITTED.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-14 Cont ID  
Sent By dpalmer Date 2007-10-14 Time 14:43 Rev Time 0.00
Received By dpalmer Date 2007-10-14 Time 14:28 Sent To  
Notes
2007-10-14 14:43:40 
  
 ** DENIED**
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-110 ( FBC CHAPTER 27 REFERENCED.
  
 2) NOTE: PLEASE SUBMIT LOADS ON THIS EXISTING/NEW
 GENERATOR TO BE INSTALLED.
 PLEASE PROVIDE INFORMATION IF THIS UNIT FEEDS ANY
 EMERGENCY LIFE SAFETY SYSTEMS OR LEGALLY REQUIRED
 SYSTEMS.700, 701,
 PLEASE SEE 700.12B3, 701.11B3 AS ANY LIFE SAFETY, OR
 LEGALLY REQUIRED SYSTEMS FED BY THIS UNIT WILL REQUIRE
 *ON-SITE* FUEL MEETING THE MINIMUM LOADS FOR THE
 MINIMUM SPECIFIED TIMES DEPENDING ON INSTALLATION. WHAT
 ARE THE INTENDED LOADS? 701.5, 700.5, 702.5
  
 3) NOTE: PLEASE SEE AS OCCUPATION FOR THE DESIGNATED
 GENERATOR IS NOT KNOWN, PLEASE BE AWARE OF HOUSE BILL
 7121 FOR STAND-BY SYSTEMS AND REQUIRED ON-SITE FUEL.
  
 4) NOTE: PLEASE SEE RISER IS MISSING *EQUIPMENT
 GROUNDING CONDUCTOR* FROM GENERATOR TO ATS.
 PLEASE SEE 250.110, 250.122
  
 5) NOTE: PLEASE SEE FS 481.229 AND 471.003, EVEN WHEN
 THE SCOPE OF WORK IS NOT REQUIRED TO BE DONE BY AN
 ARCHITECT OR ENGINEER, THE SCOPE OF WORK STILL REQUIRES
 THE DESIGN TO CONTAIN THE PRINTED NAME AND SIGNATURE OF
 THE PERSON TAKING RESPONSIBILITY OF SAID PLANS.
 106.3.5, 106.1.2
  
 6) NOTE: PLEASE SEE POSSIBLE BUILDING COMMENTS WITH
 RESPECT TO ANY FLOOD ZONE WHICH WOULD REQUIRE THE
 GENERATOR TO BE MOUNTED 6? ABOVE BFE> (IF IN FLOOD
 ZONE).
  
 7) NOTE: PLEASE SUBMIT TWO COPIES OF ALL DOCUMENTS
 SPECS/CUT SHEETS.
 FBC 106.1
  
 8) NOTE: PLEASE PROVIDE SITE/OVERVIEW OF THE LOCATION
 OF THIS UNIT AND ALL RELEVANT EQUIPMENT.
 PLEASE SEE 225.31-225.39 FOR REQUIRED DISCONNECTING
 MEANS FOR FEEDERS FROM THE GENERATOR.
 AS NO SITE PLANS AND OTHER NEEDED INFORMATION WAS
 SUBMITTED NO REVIEW OF THIS FOR CODE COMPLIANCE CAN BE
 DONE.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR
 REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL
 BE NEW COMMENTS ON THE FOLLOWING REVIEW.
 NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS
 SUBMITTED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-03-11 Cont ID  
Sent By mawillia Date 2008-03-11 Time 10:36 Rev Time 0.00
Received By mawillia Date 2008-03-11 Time 10:20 Sent To B
Notes
2008-03-11 10:34:48*****PROVISO*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS APPEAR
 TO HAVE BEEN ADDRESSED, HOWEVER THE APPROPIATE PLAN
 SHEET(S) TO BE FIRE-STAMPED WHEN THE OTHER REVIEWERS
 HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-12-19 Cont ID  
Sent By mwennerg Date 2007-12-19 Time 14:15 Rev Time 0.00
Received By mwennerg Date 2007-12-19 Time 14:15 Sent To  
Notes
2007-12-19 14:18:35***DENIED***
 PLEASE NOTE THAT MOST COMMENTS HAVE NOT BEEN
 ADDRESSED.
  
 1) MINIMUM OF TWO (2) SETS OF MANUFACTURER
 SPECIFICATION SHEETS ARE REQUIRED. PLEASE INCLUDE ALL
 DOCUMENTS TO MAKE COMPLETE SUBMITTALS.
  
 2) OK
  
 3) WORK TO COMPLY WITH NFPA 110, STANDARD FOR EMERGENCY
 AND STANDBY POWER SYSTEMS. PLEASE ADD NOTE TO
 DRAWINGS.
  
 4) ALTHOUGH ORIGINAL GENERATOR WAS EXISTING, PROTECTION
 AROUND THE GENERATOR MAY BE REQUIRED IF THE POSSIBILITY
 OF EXPOSURE TO MECHANICAL DAMAGE EXISTS.
  
 5)WHAT BUILDING FIRE PROTECTION EQUIPMENT IS TIED TO
 AND POWERED BY THE GENERATOR DURING EMERGENCY
 OPERATIONS?
  
 NEW COMMENT:
  
 PLEASE CLEARLY ILLUSTRATE THE LOCATION OF THE GENERATOR
 AND ASSOCIATED CLEARANCES.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-26 Cont ID  
Sent By mwennerg Date 2007-10-26 Time 13:04 Rev Time 0.00
Received By mwennerg Date 2007-10-26 Time 13:04 Sent To  
Notes
2007-10-26 13:32:41***DENIED***
  
 1) MINIMUM OF TWO (2) SETS OF MANUFACTURER
 SPECIFICATION SHEETS ARE REQUIRED.
  
 2) PLEASE CLARIFY IF THE FUEL SOURCE IS PROPANE,
 NATURAL GAS OR DUEL PHASE. IS THERE AN ON SITE FUEL
 SOURCE?
  
 3) WORK TO COMPLY WITH NFPA 110, STANDARD FOR EMERGENCY
 AND STANDBY POWER SYSTEMS. PLEASE ADD NOTE TO
 DRAWINGS.
  
 4) ALTHOUGH ORIGINAL GENERATOR WAS EXISTING, PROTECTION
 AROUND THE GENERATOR MAY BE REQUIRED IF THE POSSIBILITY
 OF EXPOSURE TO MECHANICAL DAMAGE EXISTS.
  
 5)WHAT BUILDING FIRE PROTECTION EQUIPMENT IS TIED TO
 AND POWERED BY THE GENERATOR DURING EMERGENCY
 OPERATIONS?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-03-11 Cont ID  
Sent By mperson Date 2008-03-11 Time 11:14 Rev Time 0.00
Received By mperson Date 2008-03-11 Time 11:14 Sent To  
Notes
2008-03-11 11:22:04****************PROVISO****************
 THIS IS A GENERATOR CHANGE-OUT USING EXISTING PIPING,
 VALVES, REGULATORS ECT....
 NOTE: TWO COPIES OF MANUFACTURER'S SPECIFICATIONS FOR
 THE EXISTING LP/GAS 1ST AND 2ND STAGE REGULATORS WITH
 THE MAKE, MODEL NUMBER, LOAD CAPACITY, AND A LISTING
 FROM A THIRD PARTY TESTING AGENCY, REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-12-05 Cont ID  
Sent By mperson Date 2007-12-05 Time 15:17 Rev Time 0.00
Received By mperson Date 2007-12-05 Time 15:17 Sent To  
Notes
2007-12-05 16:15:04PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED 2ND TIME:
  
 **PLEASE SEE THAT MOST COMMENTS FROM THE PREVIOUS GAS
 PLAN REVIEW REMAIN.
  
 1. NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS AND
 DOCUMENTS ALL ATTACHED INTO EACH SET RESPECTIVELY.
 PLEASE SEE ALL DOCUMENTS FOR EACH TRADE ARE DIVIDED AND
 NOT IN SETS. PER *106.3.1, APPROVAL OF CONSTRUCTION
 DOCUMENTS AND *106.1.2 ADDITIONAL DATA.
  
 2. PROVIDE TWO (2) COPIES OF A SITE PLAN OR SURVEY
 THAT CLEARLY INDICATES THE PROPOSED LOCATION OF THE
 GENERATOR INDICATING ALL DIMENSIONS FROM PROPERTY LINES
 AND ADJACENT DWELLING STRUCTURES.
 **NOTE: COMMENT NOT ADDRESSED.
  
 3. OK, COMMENT ADDRESSED.
  
 4. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NOTE: COMMENT NOT ADDRESSED.
  
 5. WHAT TYPE OF GAS GAS IS BEING USED. (LP OR
 NATURAL)
 **NOTE: COMMENT IS ADDRESSED IN THE SUBMITTED
 MANUFACTURE SPECIFICATIONS BY INDICATING GENERATOR IS A
 DUEL FUEL GENERATOR. HOWEVER THERE ARE NO ISOMETRIC GAS
 RISER DIAGRAMS SUBMITTED TO INDICATE GENERATOR IS DUEL
 FUEL.
  
 6. OK, COMMENT ADDRESSED.
  
 7. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **NOTE: COMMENT NOT ADDRESSED. THERE WERE NO GAS
 ISOMETRIC RISER DIAGRAMS IN THE RESUBMITTAL.
  
 8. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 **NOTE: COMMENT NOT ADDRESSED.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 IF GAS DELIVERY PRESSURE IS GREATER THAN 2 PSI PLEASE
 SUBMIT TWO (2) COPIES OF THE MP REGULATORS BEING USED
 WITH THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 **NOTE: COMMENT NOT ADDRESSED.
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 NOTE: COMMENT NOT ADDRESSED. THE SUBMITTED
 MANUFACTURER'S SPECIFICATION SHEETS ARE INDICATING
 GENERATOR IS DUEL FUEL. PLEASE PROVIDE THE REQUESTED LP
 TANK INFORMATION AND CLEARLY INDICATE IF LP TANK IS NEW
 OR EXISTING ON THE RESUBMITTAL.
  
 11. 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 6.6.1.
 NOTE: COMMENT NOT ADDRESSED. THE SUBMITTED
 MANUFACTURER'S SPECIFICATION SHEETS ARE INDICATING
 GENERATOR IS DUEL FUEL. PLEASE PROVIDE THE REQUESTED LP
 TANK INFORMATION AND CLEARLY INDICATE IF LP TANK IS NEW
 OR EXISTING ON THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-10-26 Cont ID  
Sent By mperson Date 2007-10-26 Time 14:09 Rev Time 0.00
Received By mperson Date 2007-10-26 Time 14:09 Sent To  
Notes
2007-10-26 14:53:54DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/COM INSPECTION.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.1: SUBMITTAL
 DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
  
 2. PROVIDE TWO (2) COPIES OF A SITE PLAN OR SURVEY
 THAT CLEARLY INDICATES THE PROPOSED LOCATION OF THE
 GENERATOR INDICATING ALL DIMENSIONS FROM PROPERTY LINES
 AND ADJACENT DWELLING STRUCTURES.
  
 3. PROVIDE MANUFACTURER'S SPECFICATIONS FOR THE
 PROPOSED GENERATOR INDICATING RECOMMENDED SET BACKS
 FROM STRUCTURES.
  
 4. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE, CORRESPONDING
 LENGTHS, AND THE TYPE OF PIPE MATERIAL BEING USED ON
 THE EXISTING SYSTEM PER FBC-2004 FUEL GAS CODE.
  
 5. WHAT IS THE TYPE OF GAS BEING USED? (LP OR
 NATURAL)
  
 6. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **NOTE: WHAT IS THE BTU LOAD OF THE EXISTING
 GENERATOR?
  
 7. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **NOTE: WHAT IS THE LONGEST LENGTH OF THE EXISTING GAS
 SYSTEM?
  
 8. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 **NOTE:WHAT IS THE DELIVERY PRESSURE OF THE EXISTING
 GAS SYSTEM?
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NOTE: IF GAS DELIVERY PRESSURE IS GREATER THAN 2 PSI
 PLEASE SUBMIT TWO (2) COPIES OF THE MP REGULATORS BEING
 USED WITH THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY,
 AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 6.6.1.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-21 Cont ID  
Sent By adarroug Date 2008-02-21 Time 14:54 Rev Time 0.00
Received By adarroug Date 2008-02-21 Time 14:54 Sent To  
Notes
2008-02-21 14:57:54TO "COMM" BD#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-16 Cont ID  
Sent By adarroug Date 2007-11-16 Time 15:22 Rev Time 0.00
Received By adarroug Date 2007-11-16 Time 15:22 Sent To  
Notes
2007-11-30 13:32:21TO "COMM" BD#28
2007-11-16 15:23:19WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-26 Cont ID  
Sent By mperson Date 2007-10-26 Time 15:06 Rev Time 0.00
Received By mperson Date 2007-09-17 Time 10:47 Sent To  
Notes
2007-10-09 15:23:04TO "COMM" BD#41
2007-09-17 10:48:27WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-03 Cont ID  
Sent By tgordon Date 2007-12-03 Time 11:19 Rev Time 0.25
Received By tgordon Date 2007-12-03 Time 11:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-24 Cont ID  
Sent By tgordon Date 2007-10-24 Time 09:41 Rev Time 0.25
Received By tgordon Date 2007-10-24 Time 09:40 Sent To  
Notes
2007-10-24 09:47:00PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 2) PLEASE INDICATE IF GENERATOR IS NATURAL GAS OR
 PROPANE.
  
 3) PLEASE SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-02-29 Cont ID  
Sent By choops Date 2008-02-29 Time 15:35 Rev Time 0.00
Received By choops Date 2008-02-29 Time 15:34 Sent To  
Notes
2008-02-29 15:37:30***APPROVED - RESUB #2 - CONTR. CAME IN AND CORRECTED
 REQUESTED INFORMATION***
  
 PROVISO:GENERATOR SHALL BE SCREENED AND LANDSCAPED IN
 ACCORDANCE WITH SECTION 94-444(B) OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS: OUTDOOR STORAGE FOR
 NONRESIDENTIAL AND MULTIFAMILY USES; STORAGE AND
 DISPOSAL FACILITIES.OUTDOOR INCINERATORS, GARBAGE OR
 TRASH RECEPTACLES, FUEL OIL OR PROPANE TANKS, AND
 STORAGE RACKS SHALL NOT BE PERMITTED UNLESS APPROPRIATE
 SCREENING IS PROVIDED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL. WALLS
 SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT
 TWO-FOOT INTERVALS.

Review Stop Z ZONING
Rev No 3 Status F Date 2008-02-22 Cont ID  
Sent By choops Date 2008-02-22 Time 08:33 Rev Time 0.00
Received By choops Date 2008-02-22 Time 08:33 Sent To  
Notes
2008-02-22 08:36:29***FAILED - RESUB #2***
  
  
 REPEAT COMMENT:
  
 1)INDICATE ON SURVEYS THE PROPOSED GENERATOR SHOWING
 THE SETBACK DIMENSIONS TO ALL PROPERTY LINES.
  
 NOTE:AS THIS IS THE THIRD TIME THIS COMMENT HAS BEEN
 ISSUED, IF YOU HAVE QUESTIONS REGARDING WHAT I AM
 ASKING FOR, PLEASE DON'T HESITATE TO CALL THE NUMBER
 PROVIDED BELOW.
  
 NOTE:THE GENERATOR SHALL BE SCREENED AND LANDSCAPED
 IN ACCORDANCE WITH SECTION 94-444(B) OF THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2007-12-05 Cont ID  
Sent By choops Date 2007-12-05 Time 11:12 Rev Time 0.00
Received By choops Date 2007-12-05 Time 11:12 Sent To  
Notes
2007-12-05 11:17:33***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)INDICATE ON SURVEYS THE PROPOSED GENERATOR (WITH A
 PERMANENT UTENSIL) SHOWING THE SETBACK DIMENSIONS TO
 ALL PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-15 Cont ID  
Sent By choops Date 2007-10-15 Time 09:17 Rev Time 0.00
Received By choops Date 2007-10-15 Time 09:17 Sent To  
Notes
2007-10-15 09:19:04***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE LOCATION OF THE PROPOSED GENERATOR WITH
 SETBACK DIMENSIONS TO THE PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720