Plan Review Details - Permit 07090363
Plan Review Stops For Permit 07090363
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-10-15 Cont ID  
Sent By shill Date 2008-10-15 Time 15:48 Rev Time 0.00
Received By shill Date 2008-10-15 Time 15:48 Sent To  
Notes
2008-10-15 15:48:16RESTAMP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-25 Cont ID  
Sent By shill Date 2008-02-25 Time 15:58 Rev Time 0.00
Received By shill Date 2008-02-25 Time 15:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-13 Cont ID  
Sent By shill Date 2007-12-13 Time 14:44 Rev Time 0.00
Received By shill Date 2007-12-13 Time 14:44 Sent To  
Notes
2007-12-13 14:53:49****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471.025 (SEAGRASS SURVEY).
  
 2.SEE ZONING COMMENTS REGARDING REQUIRED APPROVALS.
 ZONING APPROVAL REQUIRED BEFORE A BUILDING PERMIT CAN
 BE ISSUED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-24 Cont ID  
Sent By shill Date 2007-09-24 Time 18:05 Rev Time 0.00
Received By shill Date 2007-09-24 Time 18:05 Sent To  
Notes
2007-09-24 18:06:15****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE A COPY OF THE US ARMY CORP OF ENGINEERS
 PERMIT.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-02-22 Cont ID  
Sent By btrobaug Date 2008-02-22 Time 07:50 Rev Time 0.00
Received By btrobaug Date 2008-02-22 Time 07:37 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By btrobaug Date 2007-12-03 Time 15:14 Rev Time 0.00
Received By btrobaug Date 2007-12-03 Time 14:07 Sent To  
Notes
2007-12-03 15:14:45 
  
 SAME COMMENTS AS THE PREVIOUS REVIEW.
 SEE ZONING COMMENTS REGARDING REQUIREMENTS FOR ELECTRIC
 AT THE DOCK. THE NEC DOES NOT COVER RESIDENTIAL DOCKS
 AND THEREFORE A SINGLE RECEPTACLE COULD BE INSTALLED TO
 MEET THE MUNICIPAL REQUIREMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-24 Cont ID  
Sent By btrobaug Date 2007-09-24 Time 15:21 Rev Time 0.00
Received By btrobaug Date 2007-09-24 Time 13:52 Sent To B
Notes
2007-09-24 14:38:45 
  
 SEE ZONING COMMENTS REGARDING REQUIREMENTS FOR ELECTRIC
 AT THE DOCK. THE NEC DOES NOT COVER RESIDENTIAL DOCKS
 AND THEREFORE A SINGLE RECEPTACLE COULD BE INSTALLED TO
 MEET THE MUNICIPAL REQUIREMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-10-06 Cont ID  
Sent By adarroug Date 2008-10-06 Time 09:33 Rev Time 0.00
Received By adarroug Date 2008-10-06 Time 09:33 Sent To B
Notes
2008-10-06 09:34:01TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-15 Cont ID  
Sent By adarroug Date 2008-05-15 Time 09:55 Rev Time 0.00
Received By adarroug Date 2008-05-15 Time 09:55 Sent To P
Notes
2008-05-15 09:56:18TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 15:59 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 15:59 Sent To P
Notes
2008-05-02 15:59:34TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-13 Cont ID  
Sent By shill Date 2008-02-13 Time 13:34 Rev Time 0.00
Received By shill Date 2008-02-13 Time 13:34 Sent To Z
Notes
2008-02-13 13:34:44TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 15:32 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 15:32 Sent To Z
Notes
2007-11-27 15:32:54TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-24 Cont ID  
Sent By shill Date 2007-09-24 Time 18:06 Rev Time 0.00
Received By shill Date 2007-09-13 Time 10:26 Sent To  
Notes
2007-09-13 10:26:14TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-05-15 Cont ID  
Sent By mperson Date 2008-05-15 Time 14:19 Rev Time 0.00
Received By mperson Date 2008-05-15 Time 14:19 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-05-05 Cont ID  
Sent By mperson Date 2008-05-05 Time 09:52 Rev Time 0.00
Received By mperson Date 2008-05-05 Time 09:52 Sent To PC
Notes
2008-05-05 11:01:04PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING PLAN REVIEW COMMENTS FOR THE
 PURPOSE OF CONTINUITY. NEW COMMENTS WILL BE SO NOTED
 FOLLOWING THE PREVIOUS REVIEW COMMENTS.
  
 1. PROVIDE TWO COPIES OF A SITE PLAN WITH THE
 FOLLOWING INFORMATION.
  
 A} POINT OF CONNECTION LOCATION OF THE PROPOSED 3/4"
 WATER SERVICE TO THE PROPOSED NEW FINGER DOCK BEING
 INDICATED ON THE ELECTRICAL PLAN. PER FBC PLUMBING
 SECTION *601.1 SCOPE.
 ** NOTE: AT A MINIMUM PLANS MUST BE CORRELATED. THE
 SUBMITTED SITE PLAN BY GENERAL PLUMBING INC.DOES NOT
 REFLECT THE SIGNED AND SEALED PLAN BY THE ENGINEER.THE
 SIGNED AND SEALED PLAN BY THE ENGINEER IS INDICATING
 3/4" SCH. 40 WATER LINE TO THE DOCK, HOWEVER THE PLAN
 BY THE PLUMBING CONTR. IS INDICATING A 1" PVC WATER
 LINE TO THE DOCK. PLEASE CORRELATE THE PLANS PER
 (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B} **OK** COMMENT ADDRESSED.
  
 C} **OK** COMMENT ADDRESSED.
  
 D} CLEARLY INDICATE IF THE DOCK IS GOING TO HAVE HOSE
 CONNECTIONS (SILLCOCK, HOSE BIBB, WALL HYDRANT OR OTHER
 TYPE OF HOSE CONNECTION) AND THE LOCATION OF THE HOSE
 CONNECTION AND THAT THE HOSE CONNECTIONS WILL BE
 PROTECTED BY AN ATMOSPHERIC-TYPE VACUUM BREAKER. PER
 FBC PLUMBING SECTION *601.1 SCOPE AND SECTION
 608.15.4.2 HOSE CONNECTIONS.
 **NOTE: THE SUBMITTED PLANS BY GENERAL PLUMBING INC.
 DO NOT CLEARLY INDICATE THAT THE HOSE BIBBS ON THE DOCK
 WILL BE PROTECTED BY AN ATMOSPHERIC-TYPE VACUUM
 BREAKER. PER FBC PLUMBING SECTION 601.1 SCOPE AND
 SECTION 608.15.4.2 HOSE CONNECTIONS.
  
 THE FOLLOWING ARE NEW COMMENTS.
  
 2. THE BACKFLOW ASSEMBLY MUST BE INSTALLED ON PRIVATE
 PROPERTY AS CLOSE TO THE SOURCE OF SUPPLY AS POSSIBLE.
 THE DOCK IS NOT CONSIDERED PRIVATE PROPERTY. PER CITY
 W.P.B. BACKFLOW DEPARMENT.
  
 3. PLANS SUBMITTED BY GENERAL PLUMBING INC. ARE
 INDICATING A 3/4" BACKFLOW PREVENTER BEING SUPPLIED BY
 A 1" LINE. PER FBC PLUMBING TABLE 603.1 (D.) ALL
 BACKFLOW ASSEMBLIES SHALL BE AT LEAST THE SAME SIZE AS
 THE LINE THEY ARE INSTALLED. IF IT IS THE INTENT TO
 HAVE A 1" SUPPLY LINE TO THE BACKFLOW PREVENTER THEN
 THE BACKFLOW PREVENTER MUST BE 1", ALSO THE SIGNED AND
 SEALED PLANS FROM THE ENGINEER MUST BE CHANGED TO
 REFLECT A 1" SUPPLY FROM METER TO BACKFLOW PREVENTER.
  
 4. THE SUBMITTAL FOR THE REDUCED PRESSURE PRINCIPLE
 BACKFLOW PREVENTER DOES NOT CLEARLY INDICATE THAT IT
 COMPLIES WITH ONE OF THE FOLLOWING APPLICABLE
 STANDARDS, ASSE 1013, AWWA C511, CAN/CSA B64.4. PER FBC
 PLUMBING TABLE 608.1 APPLICATION OF BACKFLOW
 PREVENTERS.
  
 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
 NOTE: THE PLUMBING CONTRACTOR GENERAL PLUMBING INC.
 MUST SIGN THEIR DRAWINGS AND SUBMITTALS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-25 Cont ID  
Sent By mperson Date 2008-02-25 Time 14:59 Rev Time 0.00
Received By mperson Date 2008-02-25 Time 14:59 Sent To B
Notes
2008-02-25 15:27:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PROVIDE TWO COPIES OF A SITE PLAN WITH THE
 FOLLOWING INFORMATION.
  
 A} POINT OF CONNECTION LOCATION OF THE PROPOSED 3/4"
 WATER SERVICE TO THE PROPOSED NEW FINGER DOCK BEING
 INDICATED ON THE ELECTRICAL PLAN. PER FBC PLUMBING
 SECTION *601.1 SCOPE.
  
 B} LOCATION OF THE REQUIRED RPZV BACKFLOW PREVENTER
 (NOTE: THE RPZV BACKFLOW PREVENTER MUST BE INSTALLED ON
 PRIVATE PROPERTY AS CLOSE TO THE SOURCE OF SUPPLY (NEW
 FINGER DOCK) AS POSSIBLE). PER FBC PLUMBING SECTION
 *608.1 GENERAL.
  
 C} CLEARLY INDICATE THE PIPING MATERIAIL OF THE
 PROPOSED WATER SERVICE TO THE NEW FINGER DOCK AS WELL
 AS TO THE INLET AND OUTLET OF THE REQUIRED RPZV
 BACKFLOW PREVENTER. PER FBC PLUMBING SECTION *601.1
 SCOPE.
  
 D} CLEARLY INDICATE IF THE DOCK IS GOING TO HAVE HOSE
 CONNECTIONS (SILLCOCK, HOSE BIBB, WALL HYDRANT OR OTHER
 TYPE OF HOSE CONNECTION) AND THE LOCATION OF THE HOSE
 CONNECTION AND THAT THE HOSE CONNECTIONS WILL BE
 PROTECTED BY AN ATMOSPHERIC-TYPE VACUUM BREAKER. PER
 FBC PLUMBING SECTION *601.1 SCOPE AND SECTION
 608.15.4.2 HOSE CONNECTIONS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-02-15 Cont ID  
Sent By choops Date 2008-02-15 Time 11:10 Rev Time 0.00
Received By choops Date 2008-02-15 Time 11:10 Sent To E
Notes
2008-02-15 11:11:07***APPROVED - RESUB #2***
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2007-12-03 Cont ID  
Sent By choops Date 2007-12-03 Time 10:29 Rev Time 0.00
Received By choops Date 2007-12-03 Time 10:29 Sent To E
Notes
2007-12-03 10:30:22***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 1)DOCK MUST PROVIDE POTABLE WATER AND ELECTRIC
 SERVICE (MAY BE PERMITTED SEPARATELY, HOWEVER PLANS
 MUST SHOW THEY WILL BE IN EXISTENCE).PURSUANT TO
 SECTION 94-304(E)(1)(C)(5)(II).
  
 2)THE EXEMPTION THAT YOU SITE IS AN EXEMPTION FOR AN
 ENVIRONMENTAL RESOURCE PERMIT FROM DEP.THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS
 REQUIRE WRITTEN APPROVAL FROM BOTH DEP AND U.S. ARMY
 CORPS OF ENGINEERS.YOU HAVE PROVIDED WRITTEN APPROVAL
 FROM DEP, IN THE FORM OF THE SELF-CERTIFICATIONS,
 HOWEVER, I HAVE BEEN ADVISED BY DEP THIS DOCUMENT DOES
 NOT ENCOMPASS THE CORPS.THEREFORE, WRITTEN APPROVAL
 FROM THE U.S. ARMY CORPS OF ENGINEERS IS REQUIRED.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-20 Cont ID  
Sent By choops Date 2007-09-20 Time 14:51 Rev Time 0.00
Received By choops Date 2007-09-20 Time 14:51 Sent To B
Notes
2007-09-20 14:55:34***FAILED***
  
 NOTE: PROPOSED DOCK SHALL MEET ALL REQUIREMENTS FOUND
 IN SECTION 94-304(E) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS)
  
 1)MUST PROVIDE U.S. ARMY CORPS OF ENGINEERS
 APPROVAL.
  
 2)PLEASE PROVIDE A SEAGRASS STUDY SHOWING COMPLIANCE
 WITH THE AFORMENTIONED SECTION OF THE ZLDRS.
  
 3)DOCK MUST PROVIDE POTABLE WATER AND ELECTRIC
 SERVICE (MAY BE PERMITTED SEPARATELY, HOWEVER PLANS
 MUST SHOW THEY WILL BE IN EXISTANCE).PURSUANT TO
 SECTION 94-304(E)(1)(C)(5)(II).
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720