Plan Review Details - Permit 07090327
Plan Review Stops For Permit 07090327
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-20 Cont ID  
Sent By shill Date 2008-02-20 Time 14:56 Rev Time 0.00
Received By shill Date 2008-02-20 Time 14:56 Sent To  
Notes
2008-02-20 14:57:17REVISION DATED 1/25/08

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-27 Cont ID  
Sent By shill Date 2007-11-27 Time 11:00 Rev Time 0.00
Received By shill Date 2007-11-27 Time 11:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-21 Cont ID  
Sent By shill Date 2007-09-21 Time 16:40 Rev Time 0.00
Received By shill Date 2007-09-21 Time 16:40 Sent To  
Notes
2007-09-21 16:52:02****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)FOUNDATION NOTES, NOTES FOR REINFORCED UNIT
 MASONRY, STATE THAT THIS STRUCTURE IS BASED ON RATIONAL
 ANALYSIS.PROVIDE MORE INFORMATION.
  
 2.)NOTES FOR REINFORCED UNIT MASONRY STATE THGAT THIS
 IS BASED ON FBC R4407.5.APPLICABLE CODE IS FBC, NOT
 THE RESIDENTIAL CODE.CHAPTER 44 IS HIGH VELOCITY; WE
 ARE NOT IN THE HVHZ.CODE COMPLIANCE CANNOT BE
 DETERMINED AS DESIGN CRITERIA IS NOT CLEAR.
  
 3.)ON THE SITE PLAN, SHOW DISTANCE FROM THE PROPERTY
 LINE.THE GATES CANNOT ENCROACH THE PROPERTY LINE,
 FBC3202.2.
  
 4.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2008-02-20 Cont ID  
Sent By rchokshi Date 2008-02-20 Time 11:39 Rev Time 0.00
Received By rchokshi Date 2008-02-20 Time 11:39 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2007-11-21 Cont ID  
Sent By rchokshi Date 2007-11-21 Time 13:20 Rev Time 0.00
Received By rchokshi Date 2007-11-21 Time 13:20 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By rchokshi Date 2007-09-17 Time 13:15 Rev Time 0.00
Received By rchokshi Date 2007-09-17 Time 13:09 Sent To B
Notes
2007-09-17 13:15:10**** FAILED ****
  
 1. MUST MEET MINIMUM LENGTH,WIDTH, & HEIGHT PER CITY
 STANDARDS.
 ADUMPSTER SKETCH WITH MINIMUM DIMENSION ENCLOSED
 FOR YOUR USE.
 IF YOU CAN NOT MEET MINIMUM DIMENSIONS DUMPSTER &
 ITS LOCATION,NEED A LETTER FROM SANITATION DEPT.
 2. MUST BE ACCESSIBLE TO CITY PICK UP TRUCK FOR
 LOADIN/UNLOADING DUMPSTER.
 3. PLEASE SHOWON DRAWINGTHE MINIMUM DIMENSIONS OF
 DUMPSTER AND ITS LOCATION PER CITY STANDARDS.
  
 RASIK CHOKSHI805-6723

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-06 Cont ID  
Sent By adarroug Date 2008-02-06 Time 09:29 Rev Time 0.00
Received By adarroug Date 2008-02-06 Time 09:29 Sent To Z
Notes
2008-02-06 09:29:22TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 16:53 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 16:53 Sent To Z
Notes
2007-11-15 16:53:42TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-21 Cont ID  
Sent By shill Date 2007-09-21 Time 16:52 Rev Time 0.00
Received By shill Date 2007-09-12 Time 14:20 Sent To  
Notes
2007-09-12 14:21:01TO "Z" BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2008-02-12 Cont ID  
Sent By choops Date 2008-02-12 Time 11:43 Rev Time 0.00
Received By choops Date 2008-02-12 Time 11:43 Sent To ENG
Notes
2008-02-12 11:45:05***APPROVED - REVISION - REDUCE DUMPSTER SIZE/REDUCE
 GATE SIZE.***
  
 PROVISO:REQUIRES APPROVAL FROM CITY'S DEPARTMENT OF
 PUBLIC WORKS, REGARDING ACCESSIBILITY AND SIZE OF
 ENCLOSURE.
  
  
  
 SENT TO "ENG" - RC

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-20 Cont ID  
Sent By choops Date 2007-11-20 Time 11:44 Rev Time 0.00
Received By choops Date 2007-11-20 Time 11:44 Sent To ENG
Notes
2007-11-20 11:46:50***APPROVED - RESUB #1***
  
 PROVISO:REQUIRES APPROVAL FROM CITY'S DEPARTMENT OF
 PUBLIC WORKS, REGARDING ACCESSIBILITY.
  
  
  
 SENT TO "ENG" - RC

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-14 Cont ID  
Sent By choops Date 2007-09-14 Time 13:16 Rev Time 0.00
Received By choops Date 2007-09-14 Time 13:16 Sent To ENG
Notes
2007-09-14 13:21:09***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWIN THE LOCATION OF THE ENCLOSURE WITH SETBACK
 DIMENSIONS TO THE PROPERTY LINES.
  
 2)AS THE ENCLOSURE DOES NOT MEET THE STANDARDS SET
 FORTH IN SECTION 94-444 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS...ANY VARIATIONS SHALL BE
 APPROVED BY THE CITY'S ENGINEERING AND PUBLIC WORKS
 DEPARTMENT.
  
 3)INDICATE LANDSCAPING SHOWING COMPLIANCE WITH
 SECTION 94-444.
  
 4)MAY NOT TAKE UP REQUIRED PARKING...INDICATE SUCH.
  
 5)CHAINLINK FENCE NOT ADEQUATE AS PER SECTION
 94-444
  
 6)ENCLOSURE SHALL BE CONSISTANT WITH THE
 ARCHITECTURE OF THE BUILDING...INDICATE SUCH.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720