Plan Review Details - Permit 07090304
Plan Review Stops For Permit 07090304
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-14 Cont ID  
Sent By adarroug Date 2007-09-14 Time 14:20 Rev Time 0.00
Received By adarroug Date 2007-09-14 Time 14:20 Sent To M
Notes
2007-09-14 14:20:47TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-13 Cont ID  
Sent By tgordon Date 2007-09-13 Time 13:57 Rev Time 0.00
Received By tgordon Date 2007-09-12 Time 11:06 Sent To  
Notes
2007-09-12 11:07:03TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-09-17 Cont ID  
Sent By tgordon Date 2007-09-17 Time 14:27 Rev Time 0.25
Received By tgordon Date 2007-09-17 Time 14:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-13 Cont ID  
Sent By tgordon Date 2007-09-13 Time 13:48 Rev Time 0.30
Received By tgordon Date 2007-09-13 Time 13:48 Sent To  
Notes
2007-09-13 13:57:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS SHOW 872 SQUARE FEET OF
 A/C SPACE, BUILDING PLANS ON FILE SHOW 1,197 SQUARE
 FEET OF A/C SPACE. THE TWO MUST COINCIDE, PLEASE
 RE-CALCULATE COOLING LOAD CAL'S. WITH THE CORRECT
 SQUARE FEET OF COOLING SPACE.
  
 2) AFTER RE-DOING COOLING LOAD CAL'S. CHECK THE A/C
 EQUIPMENT LISTING ON THE PLANS FOR PROPER UNIT SIZE
 (CORRECT LISTING IF NEEDED).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]