Plan Review Details - Permit 07090221
Plan Review Stops For Permit 07090221
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-22 Cont ID  
Sent By shill Date 2007-10-22 Time 18:30 Rev Time 0.00
Received By shill Date 2007-10-22 Time 18:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-19 Cont ID  
Sent By shill Date 2007-10-19 Time 16:00 Rev Time 0.00
Received By shill Date 2007-10-19 Time 16:00 Sent To  
Notes
2007-10-19 16:01:52****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST, NOT ADDRESSED:
  
 1.)POOL SAFETY NOTES DO NOT COMPLY WITH FBC4101.17.
 IT STATES TO USE ONE OR A COMBINATION.IF OPTION 3 OR
 4 ARE CHOSEN, WHAT ARE THEY USED IN COMBINATION WITH?
 SAFETY (DESIGN INTENT) REQUIRED BY FLORIDA STATUTE
 SHOULD BE CLEAR ON THE PLAN. THE GENERAL NOTE IS NOT
 CODE COMPLIANT.
  
 I ATTEMPTED TO CALL THE CONTRACTOR TO DISCUSS; THE
 NUMBER ON THE APPLICATION IS A FAX.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-27 Cont ID  
Sent By shill Date 2007-09-27 Time 07:39 Rev Time 0.00
Received By shill Date 2007-09-27 Time 07:39 Sent To  
Notes
2007-09-27 07:41:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)POOL SAFETY NOTES DO NOT COMPLY WITH FBC4101.17.
 IT STATES TO USE ONE OR A COMBINATION.IF OPTION 3 OR
 4 ARE CHOSEN, WHAT ARE THEY USED IN COMBINATION WITH?
 SAFETY (DESIGN INTENT) REQUIRED BY FLORIDA STATUTE
 SHOULD BE CLEAR ON THE PLAN. THE GENERAL NOTE IS NOT
 CODE COMPLIANT.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-10 Cont ID  
Sent By btrobaug Date 2007-10-10 Time 07:29 Rev Time 0.00
Received By btrobaug Date 2007-10-10 Time 06:54 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-09-14 Cont ID  
Sent By btrobaug Date 2007-09-14 Time 13:27 Rev Time 0.00
Received By btrobaug Date 2007-09-14 Time 13:22 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-10-16 Cont ID  
Sent By mperson Date 2007-10-16 Time 16:39 Rev Time 0.00
Received By mperson Date 2007-10-16 Time 16:39 Sent To B
Notes
2007-10-16 16:40:22NOTE: THIS IS A REMODEL OF AN EXISTING POOL AND THE
 POOL HEATER IS EXISTING.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-09-26 Cont ID  
Sent By mperson Date 2007-09-26 Time 11:18 Rev Time 0.00
Received By mperson Date 2007-09-26 Time 11:18 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-05 Cont ID  
Sent By adarroug Date 2007-10-05 Time 10:34 Rev Time 0.00
Received By adarroug Date 2007-10-05 Time 10:34 Sent To E
Notes
2007-10-05 10:34:23TO "BTROBAUG" DESK/RESUB--NEW SHEETS FOR "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-27 Cont ID  
Sent By shill Date 2007-09-27 Time 07:41 Rev Time 0.00
Received By shill Date 2007-09-10 Time 16:14 Sent To  
Notes
2007-09-10 16:14:35TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-10-16 Cont ID  
Sent By mperson Date 2007-10-16 Time 16:37 Rev Time 0.00
Received By mperson Date 2007-10-16 Time 16:37 Sent To G
Notes
2007-10-16 16:38:54NOTE: THIS IS A REMODEL OF AN EXISTING POOL.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-26 Cont ID  
Sent By mperson Date 2007-09-26 Time 10:50 Rev Time 0.00
Received By mperson Date 2007-09-26 Time 10:50 Sent To G
Notes
2007-09-26 11:17:35DENIED
 REFERENCE:
 ** FBC-2004 WITH 2006 REVISIONS, SECTIONS 424.2 OR
 R4101 SWIMMING POOLS.
 ** FBC-2004 WITH 2006 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE PERMIT APPLICATION INDICATES A PLUMBING PERMIT
 BUT THE PLANS ARE INDICATING "ALL EXISTING PLUMBING TO
 REMAIN UNCHANGED & FUNCTIONAL. NO ADDITIONAL PLUMBING
 MODIFICATIONS WILL BE PERFORMED. ALL POOL/SPA
 CIRCULATION EQUIPMENT TO REMAIN UNCHANGED &
 FUNCTIONAL." THIS IS CONFUSING. THEN IN THE SUBMITTAL
 PACKAGE THERE IS A SIGNED, PROPOSAL/WORK ORDER
 INDICATING A NEW PUMP AND FILTER $850.00, REPLUMB EQ.
 $500.00 AND SALT SYSTEM AND AUTOMATION (4200 OPTION).
 PLEASE CORRELATE THE PLANS WITH THE SIGNED
 PROPOSAL/WORK ORDER ON THE RESUBMITTAL PER 106.1.1
 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-10-10 Cont ID  
Sent By choops Date 2007-10-10 Time 08:16 Rev Time 0.00
Received By choops Date 2007-10-10 Time 08:16 Sent To P
Notes
2007-10-10 08:24:37***APPROVED - RESUB #1***
  
 SENT TO "P" - MP

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-13 Cont ID  
Sent By choops Date 2007-09-13 Time 10:19 Rev Time 0.00
Received By choops Date 2007-09-13 Time 10:18 Sent To E
Notes
2007-09-13 10:22:37***FAILED***
  
  
 1)PROVIDE APPROVAL FROM BEAR ISLAND ACC
 (ARCHITECTURAL CONTROL COMMITTEE).
  
 2)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
  
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 NOTE:NO NEW POOL EQUIPMENT PERMITTED UNDER THE SCOPE
 OF THIS APPLICATION - EXISTING TO REMAIN UNCHANGED AS
 STATED BY APPLICANT.
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720