Plan Review Details - Permit 07090147
Plan Review Stops For Permit 07090147
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-29 Cont ID  
Sent By mjacobs Date 2007-10-29 Time 08:08 Rev Time 0.00
Received By mjacobs Date 2007-10-29 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-29 Cont ID  
Sent By mjacobs Date 2007-10-29 Time 06:38 Rev Time 0.00
Received By mjacobs Date 2007-10-27 Time 14:31 Sent To  
Notes
2007-10-29 06:38:19 
 BUILDING PLAN REVIEW
 PERMIT: 07090147
 ADD: 1801 S. FLAGLER DR. #603
 CONT: HAROLD M. GORDON & SONS, INC.
 TEL: (561)832- 3211
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND 10/27/07
 ACTION: DENIED
  
 1) -- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)NOTE: THE DRAWINGS SUBMITTED FOR THIS PROJECT DO
 NOT CORRESPOND WITH EACH OTHER. THERE ARE DIFFERENT
 INFORMATION AND A DIFFERENT FLOOR LAYOUT ON EACH
 DRAWING. TWO IDENTICAL SETS OF DRAWINGS SHALL BE
 SUBMITTED CONTAINING THE SAME INFORMATION AND FLOOR
 LAYOUT.
  
 3)OK
  
 4)OK
  
 **NOTE**
 THE UNIT NUMBER ON THE APPLICATION IS #603 AND THE
 DRAWINGS SUBMITTED INDICATES UNIT #817. CLARIFY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-19 Cont ID  
Sent By mjacobs Date 2007-09-19 Time 15:27 Rev Time 0.00
Received By mjacobs Date 2007-09-19 Time 13:36 Sent To  
Notes
2007-09-19 15:27:19BUILDING PLAN REVIEW
 PERMIT: 07090147
 ADD: 1801 S. FLAGLER DR. #603
 CONT: HAROLD M. GORDON & SONS, INC.
 TEL: (561)832- 3211
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) -- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)NOTE: THE DRAWINGS SUBMITTED FOR THIS PROJECT DO
 NOT CORRESPOND WITH EACH OTHER. THERE ARE DIFFERENT
 INFORMATION AND A DIFFERENT FLOOR LAYOUT ON EACH
 DRAWING. TWO IDENTICAL SETS OF DRAWINGS SHALL BE
 SUBMITTED CONTAINING THE SAME INFORMATION AND FLOOR
 LAYOUT.
  
 3)ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 106.1.2* THE
 DRAWINGS SUBMITTED SHALL BE HAVE THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DRAWINGS.
 IF AN ENGINEER OR ARCHITECT IS RESPONSIBLE, HE/SHE
 SHALL AFFIX THEIR SEAL TO SAID DRAWINGS, AND MEET THE
 REQUIREMENTS OF FS 481 AND 471.
  
 4)FBC 106.3.3*.THE PRODUCT APPROVALS SHALL BE
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. HI-LIGHT
 OR CIRCLE WHICH TYPE OF DOOR WILL BE INSTALLED FROM
 FL#8111.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2007-10-25 Cont ID  
Sent By dpalmer Date 2007-10-25 Time 08:54 Rev Time 0.00
Received By dpalmer Date 2007-10-25 Time 08:54 Sent To  
Notes
2007-10-25 08:55:28PLANS NOW SHOW ONLY WORK FOR OTHER THAN ELECTRICAL.
 NO ELECTRICAL PERMIT APPLIED FOR AND NO ELECTRICAL IN
 SCOPE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-13 Cont ID  
Sent By dpalmer Date 2007-09-13 Time 07:45 Rev Time 0.00
Received By dpalmer Date 2007-09-13 Time 07:33 Sent To  
Notes
2007-09-13 07:45:32 
 ** DENIED **
  
 1) NOTE: PLEASE BE SURE TO STATE THE RELEVANT CODES ON
 PLANS
 2004 FBC W/2006 REVISIONS.
 2002 NFPA-72
 2005 NFPA-70
  
 2) NOTE: PLEASE SEE FBC RESIDENTIAL CODE R313 AS ANY
 NEW WORK IN UNIT IS REQUIRED TO HAVE THE SMOKE ALARMS
 BROUGHT UP TO CODE MEETING NFPA-72 11.5.1.1.1. IF THESE
 CURRENTLY ARE MEETING THE LATEST EDITION OF NFPA-72
 PLEASE INDICATE THESE ON PLANS.
  
 3) NOTE: PLEASE SEE NEC 210.12 FOR NEW INSTALLED FOR
 ARC FAULT PROTECTION.
  
 4) NOTE: PLEASE SEE PLANS INDICATE NEW OVEN, COOK-TOP
 AND MICROWAVE HOWEVER NO INFORMATION ON THE ELECTRICAL
 IS SHOWN. WILL BE THIS BE NEW CIRCUITS, RECEPTACLES? IF
 SO, PLEASE SUBMIT A PANEL SCHEDULE WITH THE MINIMUM
 CONDUCTOR SIZES, OVER CURRENT PROTECTION AND EXISTING
 LOAD WITH NEW LOAD ON PANEL.
 IF THIS IS GOING TO BE FROM EXISTING CIRCUITS, PLEASE
 INDICATE.
 408.4, 310.16, 240.4,
 FBC 106.3.5.4, 106.3.5.1.2, 106.1.2
  
 5) NOTE: PLEASE KNOW EVEN WHEN SCOPE OF WORK FALLS
 UNDER THE EXCEPTIONS OF 471 AND 481 OF THE FLORIDA
 STATUTES, THE SCOPE OF WORK STILL REQUIRES THE PLANS TO
 CONTAIN A PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS.
 PLEASE SEE FS 481.229 HOWEVER AS THE SCOPE OF WORK AS
 APPLIED WILL REQUIRE AN ARCHITECT AT A MINIMUM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2007-10-31 Time   Rev Time 0.00
Received By   Date 2007-10-31 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-01 Cont ID  
Sent By mawillia Date 2007-10-01 Time 15:16 Rev Time 0.00
Received By mawillia Date 2007-10-01 Time 15:05 Sent To  
Notes
2007-10-01 15:16:18*****UNSAT*****
  
  
 1.THE NUMERICAL ADDRESS, INCLUDING THE SUITE, SHALL
 BE IN THE TITLE BLOCK OF THE SUBMITTED PLAN SHEET(S).
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE REMOVAL OF EXISTING AND/OR THE STOCKING OF NEW
 BUILDING MATERIALS & SUPPLIES SHALL IN NO WAY INTERFERE
 OR HINDER EXIT AISLE CORRIDOR ON THE SIXTH FLOOR OR THE
 BUILDING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-18 Cont ID  
Sent By adarroug Date 2007-10-18 Time 10:40 Rev Time 0.00
Received By adarroug Date 2007-10-18 Time 10:40 Sent To  
Notes
2007-10-24 16:58:43TO "BOB"#18
2007-10-18 10:40:24WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-01 Cont ID  
Sent By mawillia Date 2007-10-01 Time 15:05 Rev Time 0.00
Received By mawillia Date 2007-09-10 Time 08:37 Sent To  
Notes
2007-09-12 16:56:45TO "BOB"#18
2007-09-10 08:39:52WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-09-17 Cont ID  
Sent By tgordon Date 2007-09-17 Time 10:24 Rev Time 0.15
Received By tgordon Date 2007-09-17 Time 10:24 Sent To  
Notes
2007-09-17 10:25:04NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2007-10-31 Time   Rev Time 0.00
Received By   Date 2007-10-31 Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-18 Cont ID  
Sent By jleech Date 2007-09-18 Time 09:05 Rev Time 0.00
Received By jleech Date 2007-09-18 Time 09:04 Sent To  
Notes
2007-09-18 09:23:08DENIED;
 1. SHOW ON PLANS WHAT PLUMBING FIXTURES WILL BE CHANGED
 OUT. WHAT SIZE TUB WAS IN THE MASTER BATHROOM? IS THE
 SHOWER IN BATHROOM # 2 THE SAME SIZE? PLEASE MARK PLANS
 THE PLUMBING FIXTURES THAT WILL NOTBE CHANGED. NOT
 ENOUGH INFORMATION.
 2. SEE ELECTRICAL PLAN REVIEW NOTE # 5.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-09-13 Cont ID  
Sent By choops Date 2007-09-13 Time 08:19 Rev Time 0.00
Received By choops Date 2007-09-13 Time 08:19 Sent To  
Notes
2007-09-13 08:20:02*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.