Plan Review Stops For Permit 07090070 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2008-03-06 |
|
|
Cont ID |
|
Sent By |
kconrad |
Date |
2008-03-06 |
Time |
17:55 |
Rev Time |
0.00 |
Received By |
kconrad |
Date |
2008-03-06 |
Time |
17:17 |
Sent To |
|
|
Notes |
2008-03-06 18:01:20 | REVISED PROPOSED WINDOW INSTALLATION: WAS YALE OGRON | | SERIES 500 SINGLE HUNG WNDOW AND IS NOW YALE OGRON | | SERIES 1400 ALUMINUM CASEMENT WINDOW. CONTACTED EOR | | JOHN HOLT FOR APPROVAL: REVISION ACCEPTED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-12-04 |
|
|
Cont ID |
|
Sent By |
kconrad |
Date |
2007-12-04 |
Time |
18:15 |
Rev Time |
0.00 |
Received By |
kconrad |
Date |
2007-12-04 |
Time |
16:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-10-02 |
|
|
Cont ID |
|
Sent By |
kconrad |
Date |
2007-10-02 |
Time |
18:11 |
Rev Time |
0.00 |
Received By |
kconrad |
Date |
2007-09-27 |
Time |
16:22 |
Sent To |
I |
|
Notes |
2007-09-27 16:36:34 | | | | | PROJECT:614 32 STREET/#07090070 | | | | PROJECT DETAIL: FAMILY ROOM ADDITION | | | | REVIEW: 2004 FLORIDA RESIDENTIAL CODE W/2006 REVISIONS | | | | 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS | | CITY OF WEST PALM BEACH ADMINISTRATIVE CODE/2004 | | | | STATUS: FAILED | | | | COMMENTS: | | | | 1.)301.5 . A DESIGN PROFESSIONAL OR AN | | OWNER MUST ELECT ONE OR A COMBINATION OF | | LEVELS OF ALTERATION PURSUANT TO SECTION | | 303,304 & 305 OF THIS CODE. | | | | 2) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE | | FOLLOWING: | | | | FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 3) PROVIDE LEGIBLE SURVEYS: INDICATE LOCATIONS OF | | EXISTING AND PROPOSED CONCRETE SLAB CONSTRUCTION. | | | | 4) PROVIDE PRODUCT APPROVALS FOR ALL ANCHORS/SIMPSON | | STRAPS. | | | | 5) PLEASE SUBMIT THE INDICATED EPOXY SPECIFICATIONS. | | | | 6) PLEASE SUBMIT SOIL BEARING REPORTS. | | | | 7) PROVIDE ROOF FLASHING DETAILS FOR THE SLOPED /FLAT | | ROOF TRANSITION. | | | | 8) PLEASE SELECT THE ROOF DECK TYPE AND PRODUCTS TO BE | | USED ON THE ROOFING PRODUCT APPROVAL. ADDITIONAL | | CALCULATIONS MAY BE REQUESTED AS PER LIMITATION #7/RAS | | 117 OF THE APPLICABLE NOA. | | | | 9) THE EAST AND WEST ELEVATIONS DO NOT REFLECT DETAIL | | A/A-1, SHEET A-2 WHICH SHOWS EXISTING OVERHANG OVER | | FLAT ROOF. | | | | 10) INDICATE LUMBER DIMENSION OF THE WINDOW/DOOR | | HEADERS. | | | | 11) SMOKE ALARMS SHALL BE PROVIDED AS PER THE FEBC, | | SECTION 904: | | | | 904.1SMOKE ALARMS IN AN ADDITION. | | WHENEVER AN ADDITION IS MADE TO A BUILDING OR STRUCTURE | | OF A GROUP R-3 OR R-4 OCCUPANCY, HARDWIRED, | | INTERCONNECTED SMOKE ALARMS MEETING THE REQUIREMENTS OF | | THE FLORIDA BUILDING CODE, BUILDING OR THE FLORIDA | | BUILDING CODE, RESIDENTIAL SHALL BE INSTALLED AND | | MAINTAINED IN THE ADDITION. | | | | 904.2SMOKE ALARMS IN EXISTING PORTIONS OF A | | BUILDING. | | WHENEVER AN ADDITION IS MADE TO A BUILDING OR STRUCTURE | | OF A GROUP R-3 OR R-4 OCCUPANCY, THE EXISTING BUILDING | | SHALL BE PROVIDED WITH SMOKE ALARMS AS REQUIRED BY THE | | FLORIDA BUILDING CODE, BUILDING OR THE FLORIDA BUILDING | | CODE, RESIDENTIAL AS APPLICABLE. THE SMOKE ALARMS IN | | THE EXISTING BUILDING ARE NOT REQUIRED TO BE | | INTERCONNECTED WITH SMOKE ALARMS IN OTHER PORTIONS OF | | THE BASE BUILDING. | | | | 12) REQUIRE ENERGY CALCULATIONS AS PERTHE FEBC, | | SECTION 906: | | | | SECTION 906 | | ENERGY CONSERVATION | | 906.1MINIMUM REQUIREMENTS. | | ADDITIONS TO EXISTING BUILDINGS OR STRUCTURES SHALL | | COMPLY WITH THE REQUIREMENTS OF CHAPTER 13 OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 13) THE PRODUCT APPROVALS SUBMITTED ARE FOR DOUBLE | | DOORS; PLAN INDICATES A SINGLE 3068 DOOR. | | | | | | PLAN REVIEW: KEN CONRAD | | PHONE: 561.805.6666 | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | PLAN REVIEW: KEN CONRAD | | PHONE: 561.805.6666 | | E-MAIL: KCONRAD @WPB.ORG |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-12-11 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-12-11 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-12-11 |
Time |
16:27 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-11-16 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-11-16 |
Time |
11:55 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-11-16 |
Time |
11:34 |
Sent To |
M |
|
Notes |
2007-11-16 11:55:37 | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | THIS COMMENT FROM THE PREVIOUS REVIEW WAS NOT | | CORRECTED; | | | | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.* | | THESE NEED TO BE ON SHEET A2 WITH THE ELECTRICAL PLANS. | | ALSO THERE ARE NOW 2 PANEL "E"S IN THE DINING ROOM. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-09-14 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-09-14 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-09-14 |
Time |
15:01 |
Sent To |
M |
|
Notes |
2007-09-14 15:18:56 | | | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-03-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-04 |
Time |
11:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-04 |
Time |
11:00 |
Sent To |
B |
|
Notes |
2008-03-04 11:00:19 | TO "KCONRAD" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-01-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-01-17 |
Time |
15:56 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-01-17 |
Time |
15:56 |
Sent To |
M |
|
Notes |
2008-01-17 15:56:23 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-12-11 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-12-11 |
Time |
16:28 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-12-11 |
Time |
16:28 |
Sent To |
E |
|
Notes |
2007-12-11 16:28:31 | TO B.T./WRT. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-11-08 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-08 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-08 |
Time |
11:26 |
Sent To |
Z |
|
Notes |
2007-11-08 11:26:40 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-10-02 |
|
|
Cont ID |
|
Sent By |
kconrad |
Date |
2007-10-02 |
Time |
18:12 |
Rev Time |
0.00 |
Received By |
kconrad |
Date |
2007-09-06 |
Time |
12:43 |
Sent To |
|
|
Notes |
2007-09-06 12:43:22 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2008-01-18 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-01-18 |
Time |
10:37 |
Rev Time |
0.35 |
Received By |
tgordon |
Date |
2008-01-18 |
Time |
10:37 |
Sent To |
|
|
Notes |
2008-01-18 10:45:13 | ** REVISION TO MECHANICAL PLAN ** | | *** PROVISO *** | | 1) IF DOOR TO AHU CLOSET OPENS INTO BATHROOM MEASURES | | MUST BE TAKEN TO PREVENT RETURN AIR BEING TAKEN FROM | | BATHROOM, SEE 2004 FBC/R M1602.2 (4). | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2007-11-16 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-11-16 |
Time |
14:52 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-11-16 |
Time |
14:52 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-09-17 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-09-17 |
Time |
09:00 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-09-17 |
Time |
09:00 |
Sent To |
P |
|
Notes |
2007-09-17 09:24:21 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) PERMIT APPLICATION STATES REPAIR BACK PORCH, BUT THE | | PLANS SHOW AN ENCLOSED ADDITION (NEW FAMILY ROOM AND | | LAUNDRY ROOM) PLEASE CORRECT DESCRIPTION OF WORK ON | | PERMIT APPLICATION. | | | | 2) PLEASE SUBMIT ENERGY CALCULATIONS, SEE FBC | | 13-101.2.2. | | | | 3) SHOW ON MECHANICAL PLANS THE SIZE OF THE RETURN AIR | | TRANSFER GRILLS TO THE TWO BEDROOMS, SEE RES. M1602.4. | | | | 4) BUILDING PLANS SHOW EXISTING LIVING AREA AS 919 S/F, | | COOLING LOAD CALCULATIONS SHOW THE SQUARE FEET AS 741. | | PLEASE CORRECT COOLING LOAD CALCULATION. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2007-12-04 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-12-04 |
Time |
15:07 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-12-04 |
Time |
14:44 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-09-17 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-17 |
Time |
12:37 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-17 |
Time |
12:36 |
Sent To |
|
|
Notes |
2007-09-17 12:51:41 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. APPLICATION INDICATESREPAIR OF BACK PORCH, BUT | | PLANS INDICATE ADDITION. PLEASE CORRELATE APPLICATION, | | WHICH REQUIRES DESCRIPTION OF PROJECT IN DETAIL,AND | | PLANS. SECTION 105.1. | | | | 2. SHT A1 AREA CALCULATIONS INDICATES NEW LIVING AREA | | 251SF TO BE NEW BEDROOMS, BUT THE FLOOR PLAN SHOWS NEW | | FAMILY ROOM AND NEW LAUNDRY ROOM. PLEASE CORRELATE | | INFORMATION. SECTION 106.1.1. | | | | 3. SHT A1 SANITARY RISER DIAGRAM. SHOW ALL PIPE SIZES. | | THE MINIMUM TRAP SIZE FOR A WASH MACHINE IS 2" PER | | TABLE 709.1, BUT RISER SHOWS 1-1/2" WASTE ARM TO THE | | TRAP. MINIMUM 2" WASTE ARM TO TRAP REQUIRED.--THE | | STACK SHALL BE A MINIMUM 3" UP TO THE SANITARY TEE PER | | SECTION 406.3. PLEASE INDICATED STACK SIZE.--THE | | WASH MACHINE REQUIRES A STANDPIPE MINIMUM 18" UPSTREAM | | OF THE TRAP. PLEASE SHOW ON RISER. SECTIONS 802.4 & | | 1002.1.--A CLEANOUT IS REQUIRED ON THE STACK. THE | | CLEANOUT, IF TO THE OUTSIDE, CAN BE LOW AT THE BASE OF | | THE STACK. IF TO THE INSIDE SHALL BE SHOWN MINIMUM 4' | | ABOVE THE FLOOR FOR ACCESS. SECTIONS 708.3.4 & 708.9. | | INDICATE CLEANOUT ON RISER. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2007-11-14 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-11-14 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-11-14 |
Time |
11:04 |
Sent To |
E |
|
Notes |
2007-11-14 11:05:05 | ***APPROVED - RESUB #1*** | | | | | | SENT TO "E" - BT |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-09-10 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-09-10 |
Time |
10:18 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-09-10 |
Time |
10:18 |
Sent To |
E |
|
Notes |
2007-09-10 10:20:23 | ***FAILED*** | | | | | | 1)PROVIDE TWO (2) COPIES OF A LEGIBLE, CURRENT | | SURVEY SHOWING ALL DIMENSIONS AND SETBACK DIMENSIONS OF | | PROPOSED ADDITION TO ALL PROPERTY LINES. | | | | 2)INDICATE DIMENSIONS FROM PROPOSED ADDITION TO THE | | EXISTING GARAGE. | | | | 3)SHOW PROPOSED A/C EQUIPMENT WITH SETBACK | | DIMENSIONS TO THE PROPERTY LINES. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | TECHNICIAN | | (561)805-6720 |
|
|