Plan Review Details - Permit 07090034
Plan Review Stops For Permit 07090034
Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2009-02-27 Cont ID  
Sent By mjacobs Date 2009-02-27 Time 13:11 Rev Time 0.00
Received By mjacobs Date 2009-02-24 Time 07:00 Sent To PC
Notes
2009-02-24 07:59:222/27/09 TWO SHEETS SUBMITTED. S-1 AMD S-3A INDICATING
 THE LOCATION OF SLAB BEING POURED UNDER THIS PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-11-20 Cont ID  
Sent By mjacobs Date 2008-11-20 Time 07:44 Rev Time 0.00
Received By mjacobs Date 2008-11-20 Time 07:44 Sent To PC
Notes
2008-11-20 07:45:41REVIEW TRUSS DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-10-28 Cont ID  
Sent By mjacobs Date 2008-10-28 Time 07:28 Rev Time 0.00
Received By mjacobs Date 2008-10-28 Time 07:28 Sent To PC
Notes
2008-10-27 15:56:55BUILDING PLAN REVIEW
 PERMIT: 07090034
 ADD: 314 10TH STREET
 CONT: KENNEDY CONTRACTORS, INC.
 TEL: (561)434-1307
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION
 ACTION: DENIED
  
 SHEETS A-01/A-02/A-03/A-04/A-05/A-08 AND SHEETS S-1 -
 S-4.
  
 1) SHEETS A-03 AND A-04 SHOW DORMERS ON THE ELEVATIONS
 PLANS. THESE DORMERS ARE NOT SHOWN ON THE PERMITTED SET
 OF DRAWINGS. IF THE DORMERS WILL BE INSTALLED, PROVIDE
 THE STRUCTURAL FRAMING DETAILS SHOWING THE ATTACHMENT
 METHODS FOR THE DORMERS; THE PLANS ALSO SHOW EIFS
 OUTRIGGERS BUT NO INFORMATION OR DETAILS HOW THEY WILL
 BE ATTACHED TO THE STRUCTURE. THE BUILDING OFFICIAL MAY
 REQUIRE DETAILS, COMPUTATIONS, DIAGRAMS, AND OTHER DATA
 NECESSARY TO DESCRIBE THE CONSTRUCTION OR INSTALLATION
 OF SYSTEMS. 106.1.2.
  
 2) SHEET A-05 MAKES REFERENCE TO DETAIL #3 / S-2, THE
 DETAIL ON S-2 DO NOT CORRESPOND WITH SECTION INDICATED
 ON SHEET A-05. THE NEW PLANS ALSO SHOW TWO LAYERS R-21
 INSULATION AND 3? CONTINUOUS SCREEN VENTS ON SHEET A-05
 #4 THEN, ON SHEET S-4 #1 THE INSULATION SHOWN IS R30
 AND THE SCREEN VENTS ARE 7? X 25? SPACED 8? O/C. THE
 DETAILS ALSO FAIL TO SHOW THE EIFS AS INDICATED ON THE
 ELEVATION DRAWINGS. CLARIFY.
  
 NOTE: PLEASE MAKE SURE THE DETAILS AND INFORMATION
 CORRESPOND WITH THE PLANS. SHOP DRAWINGS WILL BE
 REQUIRED FOR THE NEW FLOOR SYSTEM.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-10-16 Cont ID  
Sent By mjacobs Date 2008-10-16 Time 08:00 Rev Time 0.00
Received By mjacobs Date 2008-10-16 Time 07:44 Sent To PC
Notes
2008-10-27 15:56:01 
  
  
  
2008-10-16 07:28:25REVISION TO ELEVATOR PIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-09-26 Cont ID  
Sent By mjacobs Date 2008-09-26 Time 11:17 Rev Time 0.00
Received By mjacobs Date 2008-09-26 Time 10:59 Sent To PC
Notes
2008-09-26 11:18:50SOIL REPORT SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-08-07 Cont ID  
Sent By mjacobs Date 2008-08-07 Time 09:51 Rev Time 0.00
Received By mjacobs Date 2008-08-07 Time 07:52 Sent To PC
Notes
2008-08-07 08:44:08PLANS WERE TAKEN TO THE COUNTY FOR IMPACT FEES, THEN
 RETURNED TO OUR OFFICE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-07-31 Cont ID  
Sent By mjacobs Date 2008-07-31 Time 07:35 Rev Time 0.00
Received By mjacobs Date 2008-07-30 Time 07:51 Sent To  
Notes
2008-07-31 07:32:52PROVISOR: (1)FBC 2303.4.1 THE TRUSS DRAWINGS SHALL BE
 SUBMITTED AND REVIEWED BEFORE INSTALLATION.
 (2)FBC 1802.2THE FOUNDATION
 AND SOIL INVESTIGATION REPORT SHALL BE SUBMITTED PRIOR
 TO ANY
 FOUNDATION WORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-05-14 Cont ID  
Sent By mjacobs Date 2008-05-14 Time 12:01 Rev Time 0.00
Received By mjacobs Date 2008-05-12 Time 12:54 Sent To  
Notes
2008-05-14 12:01:57REVIEW #3
 BUILDING PLAN REVIEW #3
 PERMIT: 07090034
 ADD: 314 10TH ST
 CONT: KENNEDY CONTRACTORS, INC.
 TEL: (561)434-1300
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW 5-12-08
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) OK
 1C) OK
  
 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E)OK.
 2)OK
  
 **SECOND REQUEST.** NOTED
 3) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6.
  
 4) OK
 5) OK
 6) OK
 7) OK
 8) OK
 9) OK
 10)OK
 11) OK
 12) OK
 13). OK
 14)OK
 15) OK
 16) OK
 17)OK
 18) OK
 19)OK
 20) OK
  
 **THE AMOUNT AND TYPE OF DOORS INDICATED IS INCORRECT,
 THE INSULATION ON THE PLANS DIFFERS FROM THE ENERGY
 CALCS, THE TYPE OF ROOF IS DIFFERENT: THE ENERTY CALCU
 SHOWS BUILT-UP GRAVEL THE PLANS SHOW METAL**
 21) ENERGY CALCULATIONS, SYSTEMS SUMMARY REPORT, PLEASE
 RECHECK THE AMOUNT OF WINDOW OPENING IN EACH ZONE AND
 WALL FACE, AS WELL AS DOORS. THE NUMBER OF EXTERIOR
 DOORS WAS NOT FILLED IN! 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 22)OK
 23) OK
  
 24)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING
 PROVIDE 2 COPIES (3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) SINGLE HUNG WINDOWS
 B) FIXED/ STOREFRONT WINDOWS
 C) MULLIONS VERTICAL OK
 D) SIDE LUTES
 E) SWING GLAZED DOORS (1) (INDICATE THE DOOR TO BE
 INSTALLED)
 F) EXTERIOR HOLLOW METAL SWING DOORS (4) CHECK ENERGY
 CALCS.
 G) TRUSS ANCHORS OK
 H) ROOF ASSEMBLIES FL#704-R1 IS MISSING THE SEAM-LOC
 REPORT
  
 25)OK
 26) OK
 27) REMOVED
 28) OK
 29)OK
 30)OK
 31)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 ** SUBMIT A WINDOW SCHEDULE SHOWING THE HEIGHT AND
 WIDTH OF EACH WINDOW**
  
 MYRON JACOBS.
 BUILDING PLAN REVIEW
 TEL: (561)805-6726
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-03-21 Cont ID  
Sent By mjacobs Date 2008-03-21 Time 11:28 Rev Time 0.00
Received By mjacobs Date 2008-03-19 Time 13:58 Sent To PC
Notes
2008-03-21 11:28:39 
 BUILDING PLAN REVIEW
 PERMIT: 07090034
 ADD: 314 10TH ST
 CONT: KENNEDY CONTRACTORS, INC.
 TEL: (561)434-1300
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) OK
  
 1C) **NOTE**106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) OK
 2)OK
  
 **2ND REQUEST**
 3) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6.
  
 **NOTED; HOWEVER, EACH ACCESSIBLE PARKING SPACE MUST BE
 NO LESS THAN 12 FEET WIDE 11-4.6.2 (GREY AREA)**
 4) SP-1 PLEASE PROVIDE ADDITIONAL INFORMATION AS HOW
 THE ACCESSIBLE ROUTE FROM THE HANDICAPPED PARKING SPACE
 AT ELEVATION 13.5?TO THE FINISH FLOOR ELEVATION OF
 14.0?.
 11-4.3.2(3). SHEET S-1 DETAIL# 7 IS NOT CLEAR IF THERE
 IS A
  
 **NOTED, HOWEVER, THE SECOND MEANS OF EGRESS THE
 INTERIOR STAIRS ALSO REQUIRE AN AREA OF RESCUE
 ASSISTANCE. SHOW COMPLIIANCE.**
 5) AREAS OF RESCUE ASSISTANCE ARE REQUIRED IN 2 STORY
 BUILDINGS NOT HAVING FIRE SPRINKLERS; PLEASE SEE
 11-4.1.3 EXCEPTION# 9.
 IN BUILDINGS OR FACILITIES, OR PORTIONS OF
 BUILDINGS OR FACILITIES, REQUIRED TO BE ACCESSIBLE,
 ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN THE
 SAME NUMBER AS REQUIRED FOR EXITS BY LOCAL
 BUILDING/LIFE SAFETY REGULATIONS. WHERE A REQUIRED EXIT
 FROM AN OCCUPIABLE LEVEL ABOVE OR BELOW A LEVEL OF
 ACCESSIBLE EXIT DISCHARGE IS NOT ACCESSIBLE, AN AREA OF
 RESCUE ASSISTANCE SHALL BE PROVIDED ON EACH SUCH LEVEL
 (IN A NUMBER EQUAL TO THAT OF INACCESSIBLE REQUIRED
 EXITS).AREAS OF RESCUE ASSISTANCE SHALL COMPLY WITH
 SECTION 11-4.3.11 . A HORIZONTAL EXIT, MEETING THE
 REQUIREMENTS OF LOCAL BUILDING/LIFE SAFETY REGULATIONS,
 SHALL SATISFY THE REQUIREMENT FOR AN AREA OF RESCUE
 ASSISTANCE.
 EXCEPTION: AREAS OF RESCUE ASSISTANCE ARE NOT REQUIRED
 IN BUILDINGS OR FACILITIES HAVING A SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM.
  
 6) SHEET A-01 PLANS INDICATE A SECOND FLOOR; THERE IS
 NO MENTION OF THE USE OF FIRE SPRINKLERS FOR THIS
 BUILDING. PLEASE SEE 11-4.3.11 (1-5) THESE REQUIREMENTS
 ARE TO BE MET FOR AREAS OF RESCUE ASSISTANCE; PLEASE
 PROVIDE INFORMATION FOR COMPLIANCE WITH THESE SECTIONS.
 **A SECOND MEANS OF RESCUE ASSISTANCE IS REQUIRED AT
 THE INTERIOR STAIRWAY PER 11-4.1.3 EXCEPTION# 9.**
  
 7) OK
  
 **NOTED, HOWEVER, 11-4.3.11.3 STAIRWAY WIDTH
 EACH STAIRWAY ADJACENT TO AN AREA OF RESCUE ASSISTANCE
 SHALL HAVE A MINIMUM CLEAR WIDTH OF 48 INCHES BETWEEN
 HANDRAILS.
  
 8) OK
 9) OK
 10)OK
  
 11) SHEET A-01 THERE IS NO WALL TAGS IDENTIFYING THE
 TYPE OF WALL CONFIGURATION TO BE USED.
 106.1.2 ADDITIONAL INFORMATION REQUIRED. ELEVATOR PUMP
 ROOM, ELEVATOR, STAIRWELL, LOBBY AND OR TENANT
 SEPARATION WALLS. **THERE ARE NOT DETAILS FOR WALLS
 TYPES 1W/ 3W / 4W/ 5W AND 6W, ALSO SOME OF THE WALLS
 ARE NOT LABELED(TAGGED)** NOTE: PER TABLE 1016.1
 BUSINESS OCCUPANCY CORRIDORS SERVING AN OCCUPANT LOAD
 GREATER THAN 30 WILL REQUIRE A 1HR RATING.
  
 12) SHEET A-4 STAIRWELL NUMBER 1 DOES NOT PROVIDE A CUT
 SECTION THROUGH THE CEILING PROVIDING WHAT TYPE OF
 MATERIAL AND OR RATING WILL BE APPLIED TO THE CEILING
 OF THE STAIRWELL. ADDITIONAL INFORMATION REQUIRED
 106.1.2. **THE DETAIL UL P544 IS MISSING THE DRYWALL
 INFORMATION.**
  
 13) OK
  
 14)SHEET A-01 & A-03 INDICATE THE USE OF EXTERIOR
 STAIRS. PLEASE SEE 1022.6 FOR REQUIRED SEPARATION FROM
 THE INTERIOR OF THE BUILDING AS REQUIRED IN 1019.1,
 ALSO SEE ATTACHED FIGURE 1022.6(1) FROM THE 2004 FBC
 CODE COMMENTARY. **THE FLOOR PLANS SHOW THE SEPARATION
 OF THE WINDOWS FROM THE STAIRWAY; HOWEVER THE ELEVATION
 DRAWING ON SHEET A-03 SHOWS ONE OF THE WINDOWS WITH IN
 5 FEET OF THE STAIRWAY. THE FLOOR PLANS SHOW SINGLE
 WINDOWS AND THE ELEVATION DRAWINGS SHOWS DOUBLE
 WINDOWS. ANY WINDOW WITHIN 10 FEET OF THE STAIRS SHALL
 HAVE AT LEAST A 1 HOUR FIRE RATING. CLARIFY.**
  
 15) SHEET A-01 & A-03 STAIR # 2 DOES NOT PROVIDE THE
 RISER NOR TREAD DIMENSION, SEE 1009.3. **THERE IS NO
 SHEET S-06 IN THE PLANS AS STATED IN YOUR RESPONSE
 LETTER.**
  
 16) STAIR# 2 DOES NOT PROVIDE INFORMATION ON THE
 HANDRAIL OR GUARDRAIL FOR THIS EXTERIOR STAIR, NOTED
 THIS IS A PRE-FAB ENGINEERED STEEL STAIR, AGAIN THERE
 IS NO INFORMATION FOR ATTACHMENT OF STAIRS TO
 STRUCTURE. ADDITIONAL INFORMATION REQUIRED. 106.1.2.
 **THERE IS NO SHEET S-06 IN THE PLANS AS STATED IN YOUR
 RESPONSE LETTER.**
  
 **SHEET A-03 SHOWS TWO ELEVATION DRAWINGS.**
 17)SHEET A-01 ON THE 2ND FLOOR THE PLANS INDICATE THE
 USE OF A BREAK ROOM SINKS, THE PLANS DO NOT PROVIDE AN
 ELEVATION OF THIS AREA PLEASE COMPLY WITH THE
 FOLLOWING:
 SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED
 WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH
 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH
 SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 **THERE IS NO SHEET S-06 IN THE PLANS AS STATED IN YOUR
 RESPONSE LETTER.**
 18) PLANS DO NOT PROVIDE ANY INFORMATION ON
 PENETRATIONS OF HORIZONTAL ASSEMBLIES,
 711.5 PENETRATIONS .PENETRATIONS THROUGH
 FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL
 COMPLY WITH SECTION 712. 712.4.1.1
 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN
 APPROVED FIRE-RESISTANCE-RATED ASSEMBLY.
 PLEASE PROVIDE DETAILS FOR PENETRATIONS THROUGH THE
 FLOOR/ CEILING ASSEMBLY.
  
  
 **2 REQUEST**
 19)ENERGY CALCULATIONS SUBMITTED ARE FORM ?A? WHOLE
 BUILDING METHOD WHERE AS THE FIRST FLOOR IS ONLY
 ASSUMPTIONS AT THIS TIME, THE CORRECT FORM WOULD BE
 EITHER ?B? OR ?C?.
 13-400.0A. NOTE NO INSULATION IS INDICATED ON THE FIRST
 FLOOR EXTERIOR WALLS, THE WHOLE BUILDING APPROACH,
 METHOD ?A? CAN NOT BE USED.
  
  
 20) OK
  
 **2 REQUEST**
 21) ENERGY CALCULATIONS, SYSTEMS SUMMARY REPORT, PLEASE
 RECHECK THE AMOUNT OF WINDOW OPENING IN EACH ZONE AND
 WALL FACE, AS WELL AS DOORS. THE EXTERIOR DOORS WERE
 NOT EVEN FILLED IN! 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 22)PLANS FAIL TO INDICATE COMPLIANCE WITH 1209.2
 ATTIC ACCESS, PLEASE PROVIDE WHERE THE ATTIC ACCESS
 SHALL BE.
  
 **PROVIDE INFORMATION ON THE RIDGE VENT SYSTEM.**
 23) SHEET A-04 DETAIL NUMBER 4 PROVIDES AN EXTERIOR
 WALL AND ROOF SECTION. THE PLANS NEED TO SHOW
 COMPLIANCE WITH : 1203.250 PERCENT OF THE REQUIRED
 VENTILATING AREA PROVIDED BY VENTILATORS LOCATED IN THE
 UPPER PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3
 FEET (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE
 BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR
 CORNICE VENTS.
  
 **SOME OF THE PRODUCT APPROVALS ARE STILL MISSING THE
 STATE COVER SHEETS. PLEASE CIRCLE OR HI-LIGHT THE
 SYSTEM OR ITEM TO BE USED FROM EACH PRODUCT.**
 24)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING
 PROVIDE 2 COPIES (3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) SINGLE HUNG WINDOWS
 B) FIXED/ STOREFRONT WINDOWS
 C) MULLIONS VERTICAL
 D) SIDE LITES
 E) SWING GLAZED DOORS
 F) EXTERIOR HOLLOW METAL SWING DOORS
 G) TRUSS ANCHORS
 H) ROOF ASSEMBLIES
  
  
 **SOME OF THE PRODUCT APPROVALS ARE STILL MISSING THE
 STATE COVER SHEETS. PLEASE CIRCLE OR HI-LIGHT THE
 SYSTEM OR ITEM TO BE USED FROM EACH PRODUCT.**
 25)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 26) OK
 27) **DORMER DELETED**
  
 **2REQUEST**
 28) SHEET S-2 ROOF FRAMING PLAN AND NOTES INDICATE THE
 UPLIFT LOAD CALCS ARE LOCATED ON SHEET S-4, WHERE?
 ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 29)OK
 30)OK
  
 **2 REQUEST**
 31)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 MYRON JACOBS.
 BUILDING PLAN REVIEW
 TEL: (561)805-6726
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-15 Cont ID  
Sent By jwitmer Date 2007-10-15 Time 16:09 Rev Time 3.33
Received By jwitmer Date 2007-10-15 Time 16:08 Sent To  
Notes
2007-10-15 17:05:09BUILDING PLAN REVIEW
 PERMIT: 07090034
 ADD: 314 10TH ST
 CONT: KENNEDY CONTRACTORS, INC
 TEL: (561)434-1300
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS.
  
 2)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED INTABLE 503
 & TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 .H ) SQ. FT. FOOTPRINT
  
 3) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 4) SP-1 PLEASE PROVIDE ADDITIONAL INFORMATION AS HOW
 THE ACCESSIBLE ROUTE FROM THE HANDICAPPED PARKING SPACE
 AT ELEVATION 13.5?TO THE FINISH FLOOR ELEVATION OF
 14.0?.
 11-4.3.2(3). SHEET S-1 DETAIL# 7 IS NOT CLEAR IF THERE
 IS A
  
 5) AREAS OF RESCUE ASSISTANCE ARE REQUIRED IN 2 STORY
 BUILDINGS NOT HAVING FIRE SPRINKLERS, PLEASE SEE
 11-4.1.3 EXCEPTION# 9.
 IN BUILDINGS OR FACILITIES, OR PORTIONS OF
 BUILDINGS OR FACILITIES, REQUIRED TO BE ACCESSIBLE,
 ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN THE
 SAME NUMBER AS REQUIRED FOR EXITS BY LOCAL
 BUILDING/LIFE SAFETY REGULATIONS. WHERE A REQUIRED EXIT
 FROM AN OCCUPIABLE LEVEL ABOVE OR BELOW A LEVEL OF
 ACCESSIBLE EXIT DISCHARGE IS NOT ACCESSIBLE, AN AREA OF
 RESCUE ASSISTANCE SHALL BE PROVIDED ON EACH SUCH LEVEL
 (IN A NUMBER EQUAL TO THAT OF INACCESSIBLE REQUIRED
 EXITS).AREAS OF RESCUE ASSISTANCE SHALL COMPLY WITH
 SECTION 11-4.3.11 . A HORIZONTAL EXIT, MEETING THE
 REQUIREMENTS OF LOCAL BUILDING/LIFE SAFETY REGULATIONS,
 SHALL SATISFY THE REQUIREMENT FOR AN AREA OF RESCUE
 ASSISTANCE.
 EXCEPTION: AREAS OF RESCUE ASSISTANCE ARE NOT REQUIRED
 IN BUILDINGS OR FACILITIES HAVING A SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM.
  
 6) SHEET A-01 PLANS INDICATE A SECOND FLOOR, THERE IS
 NO MENTION OF THE USE OF FIRE SPRINKLERS FOR THIS
 BUILDING. PLEASE SEE 11-4.3.11 (1-5) THESE REQUIREMENTS
 ARE TO BE MET FORAREAS OF RESCUE ASSISTANCE, PLEASE
 PROVIDE INFORMATION FOR COMPLIANCE WITH THESE SECTIONS.
  
  
 7) SHEET A-01 & A-04 INDICATE STAIRWELL# 1, THE DETAILS
 DO NOT PROVIDE INFORMATION FOR BARRIERS TO WARN
 VISUALLY IMPAIRED PERSONS SEE 11-4.4.2 & FIGURE 8-C1.
 THE EXTERIOR STAIRS WILL NEED THE SAME BARRIER FOR THE
 VISUALLY IMPAIRED.
  
 8) SHEET A-04 STAIR# 1 SECTION OF GUARDRAIL/ HANDRAIL
 .THIS IS AN OFFICE OCCUPANCY THAT WILL NEED TO HAVE THE
 GUARDRAIL CONFORM TO SECTION 1012.3. 4? CENTERS.
  
 9) SHEET A-04 DETAIL# 3 IS FOR A 1-HR RATED WALL,
 PLEASE PROVIDE THE UL NUMBER OR GYPSUM
 ASSOCIATION LISTING NUMBER FOR A 1 HOUR RATED ASSEMBLY.
 707.4.
  
 10)SHEET A-01 THE FIRST FLOOR LOBBY WILL REQUIRE A
 1-HR RATING. THIS BUILDING DOES NOT INDICATE THE USE OF
 FIRE SPRINKLERS, PLEASE SEE TABLE 1016.1 BUSINESS
 OCCUPANCY CORRIDORS SERVING A OCCUPANT LOAD GREATER
 THAN 30 WILL REQUIRE A 1 HR RATING.
  
 11) SHEET A-01 THERE IS NO WALL TAGS IDENTIFYING THE
 TYPE OF WALL CONFIGURATION TO BE USED.
 106.1.2 ADDITIONAL INFORMATION REQUIRED. ELEVATOR PUMP
 ROOM, ELEVATOR, STAIRWELL, LOBBY AND OR TENANT
 SEPARATION WALLS.
  
 12) SHEET A-4 STAIRWELL NUMBER 1 DOES NOT PROVIDE A CUT
 SECTION THROUGH THE CEILING PROVIDING WHAT TYPE OF
 MATERIAL AND OR RATING WILL BE APPLIED TO THE CEILING
 OF THE STAIRWELL. ADDITIONAL INFORMATION REQUIRED,
 106.1.2.
  
 13) SHEET A-01 DOOR NUMBER 6 & 7 WILL REQUIRE FIRE
 RATED DOORS, PLEASE SEE 715.3 FOR OPENING
 PROTECTIVE?S.
  
 14)SHEET A-01 & A-03 INDICATE THE USE OF EXTERIOR
 STAIRS. PLEASE SEE 1022.6 FOR REQUIRED SEPARATION FROM
 THE INTERIOR OF THE BUILDING AS REQUIRED IN 1019.1,
 ALSO SEE ATTACHED FIGURE 1022.6(1) FROM THE 2004 FBC
 CODE COMMENTARY.
  
 15) SHEET A-01 & A-03 STAIR # 2 DOES NOT PROVIDE THE
 RISERNOR TREAD DIMENSION, SEE 1009.3.
  
 16) STAIR# 2 DOES NOT PROVIDE INFORMATION ON THE
 HANDRAIL OR GUARDRAIL FOR THIS EXTERIOR STAIR, NOTED
 THIS IS A PRE-FAB ENGINEERED STEEL STAIR, AGAIN THERE
 IS NO INFORMATION FOR ATTACHMENT OF STAIRS TO
 STRUCTURE. ADDITIONAL INFORMATION REQUIRED. 106.1.2.
  
 17)SHEET A-01 ON THE 2ND FLOOR THE PLANS INDICATE THE
 USE OF A BREAK ROOM SINK, THE PLANS DO NOT PROVIDE AN
 ELEVATION OF THIS AREA PLEASE COMPLY WITH THE
 FOLLOWING:
 SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED
 WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH
 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH
 SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 18) PLANS DO NOT PROVIDE ANY INFORMATION ON
 PENETRATIONS OF HORIZONTAL ASSEMBLIES,
 711.5 PENETRATIONS .PENETRATIONS THROUGH
 FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL
 COMPLY WITH SECTION 712 . 712.4.1.1
 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN
 APPROVED FIRE-RESISTANCE-RATED ASSEMBLY.
 PLEASE PROVIDE DETAILS FOR PENETRATIONS THROUGH THE
 FLOOR/ CEILING ASSEMBLY.
  
  
  
 19)ENERGY CALCULATIONS SUBMITTED ARE FORM ?A? WHOLE
 BUILDING METHOD WHERE AS THE FIRST FLOOR IS ONLY
 ASSUMPTIONS AT THIS TIME, THE CORRECT FORM WOULD BE
 EITHER ?B? OR ?C?.
 13-400.0A. NOTE NO INSULATION IS INDICATED ON THE FIRST
 FLOOR EXTERIOR WALLS, THE WHOLE BUILDING APPROACH ,
 METHOD ?A? CAN NOT BE USED.
  
 20) THE SEALED SIGNATURE ON THE ENERGY CALCULATION IS
 EITHER A STAMP OR COPY OF THE ORIGINAL SIGNATURE.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT. FL STATE STAT:
 61G15-23.002 ENGINEERS
  
 21) ENERGY CALCULATIONS, SYSTEMS SUMMARY REPORT, PLEASE
 RECHECK THE AMOUNT OF WINDOW OPENING IN EACH ZONE AND
 WALL FACE, AS WELL AS DOORS. THE EXTERIOR DOORS WERE
 NOT EVEN FILLED IN! 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 22)PLANS FAIL TO INDICATE COMPLIANCE WITH 1209.2
 ATTIC ACCESS, PLEASE PROVIDE WHERE THE ATTIC ACCESS
 SHALL BE.
  
 23) SHEET A-04 DETAIL NUMBER 4 PROVIDES A EXTERIOR WALL
 AND ROOF SECTION. THE PLANS NEED TO SHOW COMPLIANCE
 WITH : 1203.250 PERCENT OF THE REQUIRED VENTILATING
 AREA PROVIDED BY VENTILATORS LOCATED IN THE UPPER
 PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 FEET
 (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE
 OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE
 VENTS.
  
 24)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) SINGLE HUNG WINDOWS
 B) FIXED/ STOREFRONT WINDOWS
 C) MULLIONS VERTICAL
 D) SIDE LITES
 E) SWING GLAZED DOORS
 F) EXTERIOR HOLLOW METAL SWING DOORS
 G) TRUSS ANCHORS
 H) ROOF ASSEMBLIES
  
 25)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
 26) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 27) SHEET S-2 ROOF FRAMING PLAN IS MISSING THE DORMER
 SECTION OF THE ROOF, PLEASE PROVIDE
 A SECTION INDICATING HOW THE FRONT, SIDE WALLS WILL TIE
 INTO THE MAIN ROOFING SYSTEM.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 28) SHEET S-2 ROOF FRAMING PLAN AND NOTES INDICATE THE
 UPLIFT LOAD CALCS ARE LOCATED ON SHEET S-4, WHERE?
 ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 29)SHEET S-2ND FLOOR DETAIL# 11 INDICATES A METAL
 DECK AND CONCRETE BUT NO INFORMATION AS TO THE TYPE OF
 STEEL NOR STRENGTH AND TYPE OF THE CONCRETE MIX TO BE
 USED FOR THIS SLAB.
 NOTE S-3 FLOOR DECK NOTE# 4 INDICATES A MINIMUM YIELD
 STRENGTH OF 33,000PSI?
  
 30)NOTE PLANS DO NOT INDICATE ANY WINDOW BUCK
 ATTACHMENT TO THE STRUCTURE.
 1714.5.4.1 ANCHORING REQUIREMENTS.
 WINDOW AND DOOR ASSEMBLIES SHALL BE ANCHORED IN
 ACCORDANCE WITH THE PUBLISHED MANUFACTURER?S
 RECOMMENDATIONS TO ACHIEVE THE DESIGN PRESSURE
 SPECIFIED. SUBSTITUTE ANCHORING SYSTEMS USED FOR
 SUBSTRATES NOT SPECIFIED BY THE FENESTRATION
 MANUFACTURER SHALL PROVIDE EQUAL OR GREATER ANCHORING
 PERFORMANCE AS DEMONSTRATED BY ACCEPTED ENGINEERING
 PRACTICE.
  
 1714.5.4.2 MASONRY, CONCRETE OR OTHER STRUCTURAL
 SUBSTRATE.
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1?
 INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR
 SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S
 PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE
 SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE
 OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
  
 31)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-07-30 Cont ID  
Sent By dpalmer Date 2008-07-30 Time 14:54 Rev Time 0.00
Received By dpalmer Date 2008-07-30 Time 14:54 Sent To  
Notes
2008-07-30 14:55:17*** PROVISO ***
  
 1) NOTE: PLEASE SEE EGRESS LIGHT FOR STAIR #2 UNDER
 EMERGENCY POWER IS IN QUESTION ON THE AMOUNT OF LIGHT
 FOR EGRESS PER LS 101 7.9.1.2.
  
 NEED TO REVISE PHOTO-METRICS AND AVERAGE WITH USING THE
 LEVELS ON THE INSIDE OF THE BUILDING.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-07-28 Cont ID  
Sent By dpalmer Date 2008-07-28 Time 15:12 Rev Time 0.00
Received By dpalmer Date 2008-07-28 Time 15:12 Sent To  
Notes
2008-07-28 15:12:44 
 ** FAILED REVIEW **
  
  
 1) NOTE:EGRESS LIGHTING FOR STAIR #2 DOES NOT MEET
 THE LIFE SAFETY CODE. 7.9.2.1,7.9.2.2 THE LIGHTING FOOT
 CANDLES LEVEL IS SHOWING LEVELS FROM .09, .08, .07 AND
 THEN UP TO 15.3, 14.1 ETC. THIS IS NOT POSSIBLE AS THE
 SINGLE BATTERY BACK UP FIXTURE IS AT THE TOP OF THE
 STAIRS. ALSO SHOWS TAKING ALLOWANCE AVERAGE FROM THE
 INTERIOR LIGHTING WHICH IS NOT PERMITTED.
 CALLED AND SPOKE TO ENGINEER MR. FORMICA AND HE WILL
 CALL BACK ONCE HE OBTAINS INFORMATION FROM STAFF.
 LIGHTING LEVELS ON ALL STAIRS ARE IN QUESTION. THE
 LIGHTING LUMENS UNDER CONDITIONS OF NORMAL AND
 EMERGENCY ARE TO BE VERIFIED.
  
 2) NOTE: TYPE SA FIXTURES INDICATE 210WATTS ON SITE
 PLANS. THE IDR OF THE ENERGY CALCULATIONS STATE 175W.
 THE FIXTURE WATTAGE NOT BULB IS REQUIRED TO BE USED PER
 13-415.2.ABC.1.3.
 THIS WILL ALSO BE GONE OVER.
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-05-23 Cont ID  
Sent By dpalmer Date 2008-05-23 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2008-05-23 Time 13:02 Sent To  
Notes
2008-06-26 15:55:35MEETING HELD 6/26/08
 IT BECAME APPARENT OF THE TWO ROLLS OF REVISED NEW SETS
 OF PLANS SUBMITTEDONLY ONE ROLL CONTAINED NEW REVISED
 SHEETS. THE OTHER ROLL WAS NOT REVIEWED FOR CODE
 COMPLIANCE.
 THIS WAS AN ADMINISTRATIVE ERROR BY THE CONTRACTORS
 OFFICE.
 IN ATTENDANCE WAS MR. MICHAEL CARP, MR. KENNEDY AND MR.
 ROBERT FORMICA (ELECTRICAL ENGINEER OF RECORD).
2008-05-23 13:02:28** DENIED3RD REVIEW**
  
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE NOT THE CORRECT VERSION PER FBC 13-400.3.B. THE
 RESPONSE MENTIONS THE WORDING ON THE STATE WEBSITE
 HOWEVER PLEASE READ WHAT IT SAYS. IT STATES THE *ENERGY
 GAUGE SUMMIT VERSIONS 3.0-3.14 WHICH IS IN *VERSION
 2.5* IS ACCEPTABLE. THIS DOES NOT STATE A VERSION 3.0.
 IT IS STILL VERSION 2.5 WHICH INCORPORATES THE OTHER
 PROGRAMS. PLEASE READ THE STATEMENT AS IT CLEARLY
 STATES *IN VERSION 2.5*. THIS WAS EVEN ATTACHED TO
 ENERGY CALCULATIONS SUBMITTED. I HAVE REDLINED AND
 CIRCLED THE LINE IN WHICH THE STATE HAS PARENTHESIS
 AROUND THE WORDING: * GENERATED BY FLA/COM 2004
 COMPUTER PROGRAM, VERSION 2.5*.
 THIS REVIEWER HAS CALLED TWICE TO THE ENGINEER?S FIRM
 TO GO OVER THIS REQUIREMENT ON THIS AND OTHER PROJECTS.
 NO RETURN CALL HAS BEEN RECEIVED.
 PLEASE KNOW THIS WAS AND HAS BEEN CONFIRMED WITH THE
 FLORIDA BUILDING COMMISSION/DEPARTMENT OF COMMUNITY
 AFFAIRS ON SEVERAL OCCASIONS.
 PLEASE BE SURE OWNER AGENT IS FILLED OUT ON
 CERTIFICATION SHEET.
  
 *** PLEASE SEE SHEET E2.01 WHICH INDICATES INTERIOR
 LIGHTING POWER ALLOWANCE WHICH INDICATES *BUILDING
 METHOD A*. THIS IS NOT POSSIBLE FOR A SHELL BUILDING.
 PLEASE SEE13-101.1.6.
  
 2) NOTE: PLEASE SEE THE SUBMITTED METHOD *B* DOES NOT
 COMPLY WITH THE MINIMUM REQUIRED BY CODE.
 PLEASE SEE SOME OF THE FOLLOWING ARE GIVEN AS
 EXAMPLES.
 FOR EXAMPLE:
 PLEASE BE SURE TO INCLUDE ANY *ASSUMPTIONS* FOR FUTURE
 SHELL SPACE AT A MINIMUM. ONLY SHOWS 4 LIGHT FIXTURES
 AT 64WATTS.
 FOR EXAMPLE:
 PLEASE SEE SOME FIXTURES SHOWN WITH A *0* VALUE. HOW IS
 THIS POSSIBLE?
 FOR EXAMPLE:
 PLEASE SEE EXTERIOR LIGHTING ON THE INPUT DATA REPORT
 AS THESE STILL DO NOT MATCH/CORRELATE WITH THE PLANS.
 THE IDR SHOWS 2-50W FIXTURES AND 1-32 WATT FIXTURE. HOW
 IS THIS POSSIBLE WHEN THE PLANS CLEARLY SHOW SEVERAL
 OTHER FIXTURES WHICH HAVE NOT BEEN FIGURED OR PLACED
 INTO THE IDR. WHERE ARE THE *J* FIXTURES, THE *C*
 FIXTURES, THE *SA* FIXTURES?????
 FOR EXAMPLE:
 IN SPACE ON FIRST FLOOR WHICH IS SHOWN IN ZONE OTHER
 THAN SHELL ONLY FOUR (4) FIXTURES TOTAL ARE BEING SHOWN
 HOWEVER BASED ON THE FIRST FLOOR LIGHTING ELECTRICAL
 PLANS THERE ARE CLEARLY MORE FIXTURES.
 FOR EXAMPLE:
 PLEASE COORDINATE ALL FIXTURES AND DESIGNATIONS. ONE OF
 THESE WOULD BE *C* FIXTURE WHICH CLEARLY INDICATES THIS
 FIXTURE AS A *RESTROOM FIXTURE* ON THE FIXTURE LEGEND.
  
 **THESE ARE NOT THE ONLY LIGHTS ON PLANS WHICH STILL DO
 NOT COORDINATE WITH THE INPUT DATA REPORT AND ENERGY
 CALCULATIONS.
 THESE ARE ONLY A FEW EXAMPLES OF NON-COMPLIANCE.THIS
 IS NOT AN EXHAUSTED LIST.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 3) NOTE: PLEASE SUBMIT *MINIMUM* LIFE SAFETY
 PHOTO-METRICS SHOWING AT LEAST THE MINIMUM COMPLIANCE
 WITH THE LIFE SAFETY CODE NFPA-101 7.8.1.3, 7.9.2.2
 PLEASE SEE THE LIGHTING LEVELS SUBMITTED FOR SOME AREAS
 ARE NOT CODE COMPLIANT AND PLEASE SEE SOME AREAS LIKE
 EXTERIOR REQUIRED EGRESS STAIRS STILL DO NOT SHOW ANY
 LEVELS AT ALL.
 PLEASE SEE PLANS AND COORDINATE.
  
 4) NOTE: PLEASE SEE OTHER SHEETS IN SETS INCLUDING SITE
 LIGHTING ELECTRICAL NOW SHOW THE 2ND FLOOR EXTERIOR
 STAIRS OUT AND AWAY FROM THE BUILDING. THIS WILL AFFECT
 NOT ONLY THE REQUIRED PHOTO-METRICS HOWEVER ALSO THE
 LIGHTING ON ENERGY CALCULATIONS.
 PLEASE BE SURE TO COORDINATE ALL OF THESE SHEETS FOR
 LIFE SAFETY ETC. THIS IS A MINIMUM CODE.
 LS 101 7.8, 7.9, FBC CHAPTER 10,
 FBC ADMIN SECTIONS 106.1.2, FOR COORDINATION.
 FAC 61G15-33.004
  
 5) NOTE: PLEASE SEE COMPLIANCE FOR LIGHTING CONTROLS
 HAS NOT BEEN MET. PLEASE SEE 13-415.1.ABC.1.4 ALONE FOR
 EXTERIOR LIGHTING. NOTE #1 ON SHEET E2.01 FOR EXAMPLE
 WHICH STILL SHOWS EXTERIOR LIGHTING TO BE THROUGH
 LIGHTING CONTROL PANEL BUT NO DETAIL FOR ASTRONOMICAL
 TIME CLOCK OR PHOTO-SENSOR CONTROLS.
 RESPONSE MENTIONS THIS WAS REVISED HOWEVER BASED ON THE
 PLANS SUBMITTED THIS WAS NOT THE CASE.
 PLEASE BE SURE TO SEE THE OTHER LIGHTING AS NOTED ON
 PREVIOUS REVIEW FOR INTERIOR LIGHTING ALSO. PLEASE SEE
 SEVERAL AREAS AS NOTED ON PREVIOUS REVIEW IN WHICH
 STANDARD SWITCHES ARE BEING SHOWN. 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 FRAMING MEMBERS AND BONDING AS REQUIRED PER FBC 2704
 RESPONSE MENTIONS THIS WAS ADDED TO E3.01 HOWEVER THIS
 IS NOT THE CASE.
  
 7) NOTE: PLEASE SEE RISER STILL ONLY SHOWS 3-MAINS WHEN
 IN FACT THERE ARE 4 MAINS. PLEASE LABEL ACCORDINGLY.
 PLEASE LABEL: 1OF4, 2OF 4 ETC
 230.2E.
  
 8) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENT FOR CODE
 COMPLIANCE. THIS FEE AS REQUIRED BY STATUTORY
 REQUIREMENT HAS NOW BEEN ASSESSED. IT IS REQUIRED UNDER
 STATE STATUTE AND IS REQUIRED TO BE PAID BEFORE PLANS
 MAY BE RESUBMITTED FOR THE NEXT REVIEW. IT IS IMPORTANT
 TO KNOW ONE SET OF PLANS ARE RETAINED BY THIS OFFICE AT
 THIS TIME. IT IS ALSO IMPORTANT TO KNOW THAT IF THERE
 ARE ANY QUESTIONS, OR ANY PART OF THE REVIEW COMMENTS
 ARE NOT UNDERSTOOD IN ANY WAY, PLEASE CALL OR CONTACT
 THIS OFFICE.
 THIS REVIEW CALLED AND LEFT TWO MESSAGES IN RECENT
 WEEKS FOR RETURN CALLS TO BE MADE HOWEVER THIS TO DATE
 NO CALLS HAVE BEEN RECEIVED.
 THIS FEE UNDER STATUE IS DUE BEFORE RESUB. $9,000.00
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-02-10 Cont ID  
Sent By dpalmer Date 2008-02-10 Time 09:10 Rev Time 0.00
Received By dpalmer Date 2008-02-10 Time 09:10 Sent To  
Notes
2008-02-11 09:10:59*** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 MAY NOT USE METHOD *A*. THIS BUILDING CONTAINS A SHELL
 AND ASSUMPTIONS ARE TO BE MADE. PLEASE SEE 13-400.3.B,
 WHICH IS FOR VERSION 2.5 AS 3.0 IS NOT YET ADOPTED.
 PLEASE SEE THIS SAME SECTION AS NOTED FOR SHELL AS WELL
 AS 13-400.2.A.2. WHICH STATES AS LONG AS ALL DESIGN
 PARAMETERS ARE KNOWN THEN METHOD *A* CAN BE USED.
 HOWEVER AT THIS TIME THIS IS NOT POSSIBLE WHEN THE
 FIRST FLOOR IS STILL SHELL SPACE.
 THIS WAS MENTIONED TO SEE MECHANICAL COMMENTS ALSO.
  
 2) NOTE: PLEASE BE SURE THE INFORMATION ON THE INPUT
 DATA REPORT FOR NEW CALCULATIONS COORDINATES WITH
 PLANS. PLEASE SEE THE INPUT DATA REPORT WILL BE NOTED
 AS IDR THROUGH THE REST OF THIS COMMENT.
 A) ** PLEASE SEE THAT ALL LIGHTING FIXTURES ON PLANS
 COORDINATE WITH THE IDR FOR INTERIOR AND EXTERIOR FOR
 THE NUMBER OF FIXTURES, THE WATTAGE AND THE METHOD OF
 CONTROLS.
 PLEASE SEE FOR EXAMPLE THE METHOD OF CONTROLS FOR SOME
 ARE NOTED A *MANUAL ON/OFF* WHICH IS NOT POSSIBLE WHEN
 ALL LIGHTING IS REQUIRED TO HAVE SOME SORT OF AUTOMATED
 SHUT OFF.
 PLEASE SEE FOR EXAMPLE THE EXTERIOR LIGHTING ON THE IDR
 SHOWS A TOTAL OF 1-100W FIXTURE YET THE PLANS CONTAIN
 MORE THAN 1-100W FIXTURE. THE PLANS ALSO CONTAIN OTHER
 FIXTURES ON THE EXTERIOR OF BUILDING. PLEASE SEE H
 FIXTURES, C FIXTURE, J-FIXTURES ETC.
 PLEASE SEE THE INTERIOR LIGHTING AS NOTED ON TABLE ON
 E2.01 DOES NOT COORDINATE WITH THE IDR ON CALCULATIONS
 FOR THE COUNT OF FIXTURES. THE IDR FOR INTERIOR
 LIGHTING DOES SEEM OK. PLEASE SEE NOTES ABOVE AS METHOD
 WILL STILL CHANGE.
  
 3) NOTE: AS NOTED ON PREVIOUS PLANS ZONING REQUIRES A
 MINIMUM LIGHTING LEVELS FOR PARKING AREAS, YET NO
 EXTERIOR SITE LIGHTING IS SHOWN ON PLANS. THIS WILL BE
 CONFIRMED WITH ZONING. IF REQUIRED PLEASE BE SURE TO
 FOLLOW CONTROLS REQUIRED IN CHAPTER 13 AS WELL AS
 INCLUDING IN IDR.
  
 4) NOTE: PLEASE SEE SOME AREAS ARE STILL MISSING
 REQUIRED LIGHTING CONTROLS PER 13-415.1.ABC.1.1, .1.2,
 .1.3 AND .1.4.
 A) **PLEASE SEE EXTERIOR LIGHTS NOTE MENTIONS LIGHTING
 TO BE THROUGH LCP, YET NO INFORMATION IS PROVIDED ON
 TYPE OF TIME CLOCK, BATTERY BACK UP OF POWER ETC.
 PLEASE SEE CODE SECTION 13-415.1.ABC.1.4 WHICH REQUIRES
 ONE OF TWO METHODS (BOTH COULD BE DONE ALSO).
 EITHER PHOTO-SENSOR OR ASTRONOMICAL TIME CLOCK WITH
 BATTERY BACK UP OF A MINIMUM OF 10HRS.
  
 B) ** PLEASE SEE SOME AREAS WHERE STANDARD SWITCHES ARE
 STILL BEING SHOWN. (LOBBY)
 C) ** PLEASE SEE NO MAXIMUM TIMES COULD BE LOCATED ON
 PLANS FOR ANY OF THE LIGHTING CONTROL DEVICES AS WELL
 AS THE MAXIMUM TIMES FOR OVER RIDES.
 D) ** PLEASE SEE NO SCHEDULING COULD BE LOCATED ON
 PLANS.
 E) ** PLEASE BE SURE THE OWNER AGENT IS SIGNED ON
 CERTIFICATION SHEETS. 13-103.1.1.1
  
 5) NOTE: PLEASE SEE THE PREVIOUS NOTES WITH RESPECT TO
 EGRESS LIGHTING FOR STAIRS UNDER NORMAL AND EMERGENCY.
 THE PHOTO-METRICS SUBMITTED WERE ONLY FOR LEVELS UNDER
 EMERGENCY FOR STAIR #1. NO LEVELS UNDER EITHER NORMAL
 OR EMERGENCY WERE LOCATED FOR STAIR #2.
 PLEASE SEE 7.8.1.3 OF LS 101 WHICH REQUIRES 10FT
 CANDLES UNDER NORMAL AND 7.9.2 WHICH ALLOWS LEVELS DOWN
 TO 1FT CANDLE UNDER EMERGENCY.
 PLEASE SUBMIT.
 FAC 61G15-33.004,
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO A
 NOTE BEING PLACED ON PLANS FOR ALL METAL FRAMING
 MEMBERS TO BE BONDED AS REQUIRED PER FBC 2704.
  
 7) NOTE: THE RISER SHOWS 4 MAINS, ONLY THREE LABELED AS
 MAINS. EACH OF THESE IS NOT NOTED CORRECTLY. ONE SAYS
 MAIN ONE OF ONE. HOW IS THIS POSSIBLE WHEN THERE ARE
 FOUR MAINS? TWO ARE LABELED AS MAINS TWO OF THREE AND
 THREE OF THREE. THIS DOES NOT COORDINATE WITH FIRST
 MAIN. PLEASE ALSO SEE THE HOUSE MAIN OF SERVICE DOES
 INDICATE ANY INDICATION OF MAIN ETC.
 EXAMPLE: 1 OF 4, 2 OF 4, 3 OF 4 AND 4 OF 4.
 PLANS ON SHEET E1-01 ONLY SHOWS THREE MAINS. WHERE IS
 THE FOURTH MAIN?
 PLEASE LABEL MAINS. 230.2E
 PLEASE SHOW LOCATIONS FOR GROUPING ETC. 230.70, 230.72,
 110.26 ETC
  
 8) NOTE: PLEASE SEE NOTICE FOR FS 553.80(2)(B) IS GIVEN
 ONLY A NOTICE AT THIS TIME AS THERE WERE REPEATED
 COMMENTS FOR CODE COMPLIANCE FOR SOME OF THE SAME
 ITEMS.
  
 ** PLEASE KNOW AS SOME ITEMS ARE STILL NOT SUBMITTED OR
 SHOWN, REVIEW OF SOME ITEMS STILL CAN NOT BE DONE.
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 ** PLEASE KNOW A RESPONSE LETTER IS NOT REQUIRED
 HOWEVER IS HELPFUL IN THE REVIEW PROCESS. RESPONSES
 SUBMITTED FOR SOME OF THE OTHER TRADES ONLY.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF THERE ARE ANY
 QUESTIONS OR IF THERE ARE ANY COMMENTS ARE NOT TYPED IN
 A CLEAR FASHION PLEASE DO NOT HESITATE IN CONTACTING
 THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-07 Cont ID  
Sent By dpalmer Date 2007-10-07 Time 14:15 Rev Time 0.00
Received By dpalmer Date 2007-10-07 Time 13:05 Sent To  
Notes
2007-10-07 14:15:302007-10-07 14:15:30
  
 *** DENIED ***
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THE ADDRESS ON APPLICATION AND
 ADDRESS IN OUR SYSTEM AS APPLIED FOR WITH THE PCN
 PROVIDED IS FOR 314 10TH ST, HOWEVER THE PLANS/COVER
 SHEET CLEARLY INDICATES *310* 10TH ST??
 PLEASE COORDINATE AND CORRECT.
 FBC 106.1.2, 110.1.2
  
 3) NOTE: PLEASE SEE THE TITLE BLOCKS ON THE LANDSCAPE
 SHEETS ARE MISSING REQUIRED INFORMATION PER FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004, AND FLORIDA STATUTES
 481.219.
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES**
  
 4) NOTE: PLEASE SEE THAT COMPLIANCE WITH NFPA-101 7.8
 AND 7.9 NEEDS TO BE MET.
 PLEASE SEE THERE ARE SEVERAL AREAS IN WHICH BATTERY
 BACK UP TYPE OF LIGHTING FIXTURES ARE MISSING.
 FOR EXAMPLE STAIRS WHICH ONLY INDICATE A *D* FIXTURE
 WHICH BY FIXTURE LEGEND DOES NOT CONTAIN ANY BATTERY
 BACK UP??
 PLEASE KNOW THAT LIGHTING IS REQUIRED FOR ALL EGRESS
 PATHS INCLUDING THAT TO THE EXIT DISCHARGE
 AREAS/PATHS.
  
 FOR EXAMPLE:
 PLEASE SEE THE STAIR AREAS OUTSIDE WHICH ARE PART OF
 THE EXIT DISCHARGE WHICH DOES NOT CONTAIN BATTERY BACK
 UP LIGHTING.
 PLEASE SEE AREAS AS THESE ARE EXIT PATHS HOWEVER AS
 THEY ARE NOT CONSIDERED THE PUBLIC RIGHT OF WAY OR SAFE
 DISTANCE FROM THE BUILDING, EMERGENCY LIGHTING FIXTURES
 WILL BE REQUIRED.
 PLEASE SEE THE ELEVATOR EQUIPMENT ROOM WILL BE REQUIRED
 TO HAVE A BATTERY BACK UP FIXTURE OF SOME TYPE. PLEASE
 SEE THERE ARE OTHER AREAS ALSO HOWEVER NOT ALL ARE
 LISTED.
 PLEASE SUBMIT AND PROVIDE LIGHTING PHOTO-METRICS FOR
 ALL EGRESS PATHS TO THE PUBLIC RIGHT OF WAY. PLEASE SEE
 THE LEVELS UNDER NORMAL FOR STAIRS SHALL MEET THE
 MINIMUM OF 10FT CANDLES PER 7.8.1.3 AND IS PERMITTED TO
 GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. FBC
 106.1.2, FAC 61G15-33.004
 NFPA-101 7.8, 7.9
  
 5) NOTE: PLEASE SEE THERE ARE SOME LOCATIONS IN WHICH
 EXIT SIGNSAND A LIGHTING FIXTURE WITH BATTERY BACK UP
 WILL BE REQUIRED FOE LIFE SAFETY.
 PLEASE SEE THE FUTURE BUILD OUT SPACES WHICH WILL
 REQUIRE THESE. PLEASE ALSO SEE THAT LIGHTING CONTROL
 FOR OCCUPANCY SENSOR TYPE DEVICE(S) WILL BE REQUIRED.
 THIS WAS CONFIRMED WITH THE FIRE MARSHAL.
 PLEASE SEE NFPA-101 7.8, 7.9, FBC CHAPTER 10.
  
 6) NOTE: PLEASE KNOW AS ZONING CONTAINS MINIMUM
 REQUIREMENTS FOR DOWNTOWN MASTER PLAN AREAS AND PARKING
 LOT LIGHTING, THIS WILL AFFECT COMMENTS 6 AND 7 BELOW.
 AS NO SITE LIGHTING IS YET SUBMITTED, NO REVIEW CAN BE
 DONE.
 ZONING DOES HAVE MINIMUM PHOTO-METRIC LEVELS ALSO.
 PLEASE CONTACT AMY STELLY FOR SECTION OF THE ZONING
 ORDINANCE.
  
 7) NOTE: PLEASE SEE THAT COMPLIANCE WITH FBC CHAPTER 13
 IS NEEDED FOR ALL LIGHTING CONTROLS IN ALL AREAS.
  
 A) PLEASE PROVIDE INFORMATION/DESIGN/TIME SCHEDULING
 ETC ON HOW LIGHTING IS BEING CONTROLLED IN COMMON
 AREAS.
 PLEASE CLARIFY HOW THE STANDARD 3-WAY SWITCHES BEING
 SHOWN ON PLANS WILL COMPLY AND WORK WITH THE SYSTEM.
 ALSO SOME S-POLE SWITCHES WITH NO AUTOMATED CONTROL
 PLEASE SEE THE OVER RIDES SHALL BE LOCATED SO THE
 OCCUPANT WHEN ENTERING A SPACE CAN NOT ONLY CONTROL THE
 LIGHTING IN AN OVER RIDE CIRCUMSTANCE BUT MUST ALSO SEE
 THE LIGHTING IN WHICH IS BEING CONTROLLED. THERE IS
 ONLY ONE EXCEPTION TO THE LIGHTING FOR REQUIRED VISUAL
 CONTACT OF LIGHTS BEING CONTROLLED.
 PLEASE SEE THE OCCUPANCY DEVICES AS SHOWN NEED TO STATE
 THE MAXIMUM TIMES.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 B) PLEASE SEE EXTERIOR LIGHTING CONTROLS AS A STANDARD
 TIME CLOCK IS NOT ALL THAT IS REQUIRED.
 13-415.1.ABC.1.4
  
  
 8) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 FOR
 ENERGY CALCULATIONS/LIGHTING PERFORMANCE CALCULATIONS
 NEEDS TO BE MET.
 **IMPORTANT** PLEASE BE SURE TO SEE MECHANICAL REVIEW
 COMMENTS FOR POSSIBLE METHOD BEING SUBMITTED AND USED
 FOR WHAT IS BEING SHOWN AS SHELL ON PLANS.(ONLY NOTED)
 PLEASE SEE THE FOLLOWING WHICH WILL HAVE REFERENCE TO
 THE INPUT DATA REPORT AS IDR.
  
 A) PLEASE CORRELATE ALL LIGHTING WHICH IS ON PLANS AND
 CONSUMES ENERGY WITH THAT OF THE IDR.
 FOR EXAMPLE:
 PLEASE SEE THE EXTERIOR LIGHTING WHICH INDICATES A
 *NONE ENTERED*. PLEASE EXPLAIN HOW THIS IS POSSIBLE
 WHEN PLANS CLEARLY SHOW EXTERIOR LIGHTING?
  
 PLEASE BE SURE THE FIXTURE LEGEND COORDINATES WITH THE
 LIGHTING IN THE IDR.
 PLEASE ALSO SEE FOR EXAMPLE THE INTERIOR LIGHTING WHICH
 NEEDS TO COORDINATE WITH PLANS.
 PLEASE SEE THE AREAS DO NOT MATCH.
 PLEASE SEE THE NUMBER OF FIXTURES ON EACH AND EACH
 AREA/ROOM DESIGNATION DOES NOT CORRELATE.
 PLEASE SEE THE IDR DOES NOT CONTAIN ALL LIGHTING AS
 SHOWN ON PLANS AND THE FIXTURE LEGEND
 PLEASE SEE THE METHOD OF CONTROLS INDICATES *MANUAL
 ON/OFF* WHICH IS ALSO NOT POSSIBLE WHEN LIGHTING
 CONTROLS ARE AUTOMATED ETC.
  
 ** PLEASE BE SURE TO COORDINATE ALL FIXTURES ON PLANS
 WITH THE IDR.
 PLEASE SEPARATE TO ROOMS AND AREAS ON THE IDR. REVIEW
 OF MANY ITEMS CAN NOT BE DONE.
  
 PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR ALLOWANCES.
 PLEASE SEE 13-415.1.A, 13-415.2 ETC.
  
 ** PLEASE SEE 2004 FBC CHAPTER 13 FOR ALL ELECTRICAL
 LIGHTING CONTROLS AND CALCULATIONS REQUIRED.
  
 9) NOTE: PLEASE SEE ALL THREE SETS OF ENERGY
 CALCULATIONS SUBMITTED CONTAIN A RAISED SEAL OVER A
 *PHOTO-COPIED* SIGNATURE WHICH IS NOT PERMITTED PER FAC
 61G15-23.002 AND FS 471.025.
 PLEASE KNOW THIS OFFICE HAS INFORMED THIS SAME DESIGNER
 ON PREVIOUS PROJECTS AS THIS IS NOT PERMITTED. PLEASE
 BE SURE TO ADDRESS THIS ISSUE AS THESE WILL BE LEFT
 WITH NO OTHER CHOICE BUT TO FORWARD THESE TO THE STATE
 BOARD OF ENGINEERS AND LEGAL COUNSEL.
 ** PLEASE BE SURE THE OWNER AGENT IS SIGNED PER
 13-103.1.1.1
  
  
 10) NOTE: PLEASE CLARIFY THE GROUNDING AS AN *EQUIPMENT
 GROUNDING CONDUCTOR* IS BEING SHOWN ON THE LINE SIDE OF
 THE FIRST MEANS OF DISCONNECT WHICH IS NOT PERMITTED.
 PLEASE SEE 250.24BA AND 250.6 AS THIS WILL CREATE
 OBJECTIONABLE CURRENTS.
  
 250.50 **PLEASE PLACE NOTE ON PLANS FOR FBC 2704 WHICH
 REQUIRES METAL FRAMING MEMBERS TO BE BONDED.
  
 11) NOTE: THIS IS ONLY NOTED FOR INFORMATION ONLY:
 PLEASE KNOW IF THE BUILDING CONTAINS A FA PANEL OR IS
 REQUIRED TO HAVE ONE INSTALLED PER BUILDING OR FIRE
 MARSHAL REVIEW, PLEASE BE SURE TO SEE FBC 2004
 11-4.28.1, .2 AND .3(4) AND STATE THE MINIMUM HORN,
 STROBE LEVELS ON PLANS FOR ADA REQUIRED AREAS. DEVICES
 ARE BEING SHOWN ON PLANS/LEGEND. PLEASE CORRELATE WITH
 PLANS, AND FA SHEETS SUBMITTED. THIS IS NOTED FOR
 INFORMATION ONLY!!
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM
 SETS.
 FBC 106.3.5.1.2
  
 12) NOTE: PLEASE CLARIFY ALL CONTINUOUS AND LARGEST
 MOTOR LOADS AT 125%.
 PLEASE SHOW. 215.3, 230.42 (SOME ARE SHOWN)
  
 13) NOTE: PLEASE SEE FEEDER CONDUIT/CONDUCTORS FROM
 225AMP CIRCUIT BREAKER MAIN IS BEING SHOWN GOING
 THROUGH THE LINE GUTTER WHICH IS NOT PERMITTED. MAY NOT
 INSTALL UNPROTECTED AND PROTECTED CONDUCTORS IN THE
 SAME GUTTER AS SHOWN.
 PLEASE ADJUST RISER AND SEE 230.7 AS * OTHER CONDUCTORS
 IN RACEWAY OR CABLE
 CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE
 INSTALLED IN THE SAME SERVICE RACEWAY OR SERVICE
 CABLE.
 ALL FEEDER AND BRANCH-CIRCUIT CONDUCTORS MUST BE
 SEPARATED FROM SERVICE CONDUCTORS. SERVICE CONDUCTORS
 ARE NOT PROVIDED WITH OVER-CURRENT PROTECTION WHERE
 THEY RECEIVE THEIR SUPPLY; THEY ARE PROTECTED AGAINST
 OVERLOAD CONDITIONS AT THEIR LOAD END BY THE SERVICE
 DISCONNECT FUSES OR CIRCUIT BREAKERS. THE AMOUNT OF
 CURRENT THAT COULD BE IMPOSED ON FEEDER OR
 BRANCH-CIRCUIT CONDUCTORS, SHOULD THEY BE IN THE SAME
 RACEWAY AND A FAULT OCCUR, WOULD BE MUCH HIGHER THAN
 THE AMPACITY OF THE FEEDER OR BRANCH-CIRCUIT
 CONDUCTORS.*
  
 14) NOTE: PLEASE SEE DISCONNECTS AS SHOWN FOR THE
 CONDENSING UNITS DO NOT MEET 110.26.
 PLEASE ADJUST.
  
 15) NOTE: PLEASE LABEL AND IDENTIFY ALL MAINS AND
 FUTURE MAINS.
 230.2E.
 EXAMPLE: MAIN 1OF 4, 2 OF 4 ETC
  
 16) NOTE: PLEASE SEE THAT PANEL SCHEDULES ARE TO BE
 SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED.
 PLEASE SEE 408.4. (MAY BE NUMERICAL DESIGNATIONS)
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2, 106.5, 106.1.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2007-10-07 13:05:382007-10-07 13:05:08
  
 IN ELECTRIC FOR REVIEW

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2008-02-25 Cont ID  
Sent By rchokshi Date 2008-02-25 Time 13:21 Rev Time 0.00
Received By rchokshi Date 2008-02-25 Time 13:21 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By rchokshi Date 2007-10-16 Time 13:55 Rev Time 0.00
Received By rchokshi Date 2007-10-16 Time 13:46 Sent To  
Notes
2007-10-16 13:55:46***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM
 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES.
 PHONE# 494-1040
 3. PLEASE MAKE SURE DUMPSTER LOCATION ON DWG MUST BE
 ACCESSIBLE FOR CITY'SPICKUP TRUCK.
 4. PLEASE SHOW ON CALCULATTION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA TO
 DETERMINE THE FIRST FLOOR ELEVATION, PARKING LOT
 ELEVATION, CROWN OF THE ROAD ELEVATION, SIDEWALK ETC.
 5. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS.
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM ALL
 OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS.
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES.
 9. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-07-31 Cont ID  
Sent By mwennerg Date 2008-07-31 Time 09:59 Rev Time 0.00
Received By mwennerg Date 2008-07-31 Time 09:59 Sent To  
Notes
2008-07-31 09:59:40SHEET A-01 STAMPED, SIGNED AND DATED

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-05-27 Cont ID  
Sent By mwennerg Date 2008-05-27 Time 11:25 Rev Time 0.00
Received By mwennerg Date 2008-05-27 Time 11:25 Sent To  
Notes
2008-05-27 11:26:10IT APPEARS THAT ALL FIRE COMMENTS HAVE BEEN ADDRESSED.
 PLANS WILL BE STAMPED BY FIRE ONCE SUBMITTED WITH
 CORRECTIONS TO OTHER REVIEW COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-03-04 Cont ID  
Sent By mwennerg Date 2008-03-04 Time 15:33 Rev Time 0.00
Received By mwennerg Date 2008-03-04 Time 15:32 Sent To  
Notes
2008-03-04 15:47:33***DENIED***
  
 PLEASE NOTE THAT MOST OF THE PREVIOUS COMMENTS HAVE NOT
 BEEN ADDRESSED. IT WOULD HELP EXPEDITE THIS PROCESS IF
 YOU INCLUDE A RESPONSE LETTER INDICATING HOW AND WHERE
 EACH COMMENT WAS ADDRESSED.
  
 1) OK
  
 2) FUTURE TENANT SEPARATIONS WILL BE REQUIRED WHEN THE
 FUTURE SPACES ARE LEASED. PLEASE ACKNOWLEDGE.
  
 3) BUILDING ADDRESS IS REQUIRED ON ELEVATIONS THAT
 ILLUSTRATES A MINIMUM OF 6" IN HEIGHT, 1" IN WIDTH AND
 CONTRASING WITH BACKGROUND.
  
 4) PLEASE CLARIFY EXITING PROTECTION FROM STAIR #1 AND
 EXTERIOR STAIRS REGARDING DOORS AND WINDOW EXPOSURES.
  
 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENT FOR
 HANDRAILS AND GUARDS. INDICATE ON DETAILS.
  
 6) WHAT SLIP RESISTANT METHODS ARE PLANNED FOR THE
 EXTERIOR FIRE STAIR?
  
 7) ELEVATOR WARNING SIGNS REQUIRED AT ELEVATOR OPENINGS
 IN LOBBIES.
  
 8) OK
  
 9) TACTILE SIGNS REQUIRED AT EXIT DOORS.
  
 10) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 11) DEBRIS TO BE REMOVED FROM THE SITE DAILY.
  
 12) OK
  
 13) PLEASE INDICATE FIRE EXTINGUISHER LOCATIONS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By mcarsill Date 2007-10-22 Time 14:47 Rev Time 0.00
Received By mcarsill Date 2007-10-22 Time 14:30 Sent To  
Notes
2007-10-22 14:47:421. DUCTWORK APPEARS TO PASS THROUGH STAIR # 1 ON PAGE
 M1.02. PLEASE PROVIDE DETAILS, MECHANICAL EQUIPMENT IS
 NOT ALLOWED TO PASS THROUGH A REQUIRED EXIT STAIR.
  
 2. FUTURE TENANT SEPARATIONS WILL BE REQUIRED WHEN THE
 FUTURE SPACES ARE LEASED.
  
 3. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A
 MINIMUM OF AT LEAST 6" HIGH NUMBERS AND AT LEAST 1"
 WIDE SHALL BE PROVIDED. NUMBERS SHOULD CONTRAST WITH
 THE BACKGROUND THEY ARE MOUNTED ON.
  
 4. WHAT PROTECTION IS BEING AFFORDED TO EXITING FROM
 STAIR # 1 AND TO EXITING OCCURING FROM THE EXTERIOR
 STAIRS. IT APPEARS THAT DOORS IN THE LOBBY ARE NOT FIRE
 RATED AND WINDOWS APPEAR TO BE WITHIN CLOSE PROXIMITY
 TO THE EXTERIOR STAIR. THERE APPEARS TO BE NO
 PROTECTION TO PROVIDE FOR EXITING.
  
 5. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS.
  
 6. WHAT SLIP RESISTANT METHODS ARE PLANNED FOR THE
 EXTERIOR FIRE STAIR.
  
 7. ELEVATOR WARNING SIGNS REQUIRED AT ELEVATOR
 OPENINGS.
  
 8. ELEVATOR INSTALLATION TO COMPLY WITH ANSI A17.1.
  
 9. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 10. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 11. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 12. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 13. PLEASE ILLUSTRATE PORTABLE FIRE EXTINGUISHER
 LOCATIONS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-03-27 Cont ID  
Sent By adarroug Date 2009-03-27 Time 09:05 Rev Time 0.00
Received By adarroug Date 2009-03-27 Time 09:05 Sent To Z
Notes
2009-03-27 09:05:51TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-02-24 Cont ID  
Sent By mjacobs Date 2009-02-24 Time 06:59 Rev Time 0.00
Received By mjacobs Date 2009-02-24 Time 06:59 Sent To B
Notes
2009-02-24 07:00:25TO MJ DESK.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-11-14 Cont ID  
Sent By adarroug Date 2008-11-14 Time 09:55 Rev Time 0.00
Received By adarroug Date 2008-11-14 Time 09:55 Sent To B
Notes
2008-11-14 09:56:06TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-10-23 Cont ID  
Sent By adarroug Date 2008-10-23 Time 08:56 Rev Time 0.00
Received By adarroug Date 2008-10-23 Time 08:56 Sent To B
Notes
2008-10-23 08:56:29TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-23 Cont ID  
Sent By adarroug Date 2008-09-23 Time 10:47 Rev Time 0.00
Received By adarroug Date 2008-09-23 Time 10:47 Sent To B
Notes
2008-09-23 10:48:20TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-10 Cont ID  
Sent By adarroug Date 2008-07-10 Time 12:01 Rev Time 0.00
Received By adarroug Date 2008-07-10 Time 12:01 Sent To  
Notes
2008-07-10 12:03:57TO "COMM" BD#43

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-05 Cont ID  
Sent By adarroug Date 2008-05-05 Time 15:31 Rev Time 0.00
Received By adarroug Date 2008-05-05 Time 15:31 Sent To  
Notes
2008-05-05 15:34:02TO "COMM" BD#48

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 16:41 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 16:41 Sent To  
Notes
2008-02-01 16:41:17TO "COMM" BD#63

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-03 Cont ID  
Sent By kstevens Date 2007-11-03 Time 07:05 Rev Time 0.00
Received By kstevens Date 2007-09-06 Time 12:31 Sent To  
Notes
2007-10-07 13:06:21TO COMM BOARD #8, DVP>
2007-09-06 12:31:33WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-07-11 Cont ID  
Sent By tgordon Date 2008-07-11 Time 11:09 Rev Time 0.45
Received By tgordon Date 2008-07-11 Time 11:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-05-23 Cont ID  
Sent By tgordon Date 2008-05-23 Time 14:11 Rev Time 0.45
Received By tgordon Date 2008-05-23 Time 14:11 Sent To  
Notes
2008-05-23 14:23:09PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 3-4-08 NOTE #1. THE WALL
 BETWEEN THE FIRST FLOOR MECHANICAL ROOM AND LOBBY IS
 FIRE RATED, THE 14X12 SUPPLY AIR DUCT PENETRATING THE
 WALL NEEDS A FIRE DAMPER, PER 2004 FBC/M 607.5.3 OR
 MEET THE EXCEPT.
  
 2) AS NOTED IN LAST REVIEW 3-4-08 NOTE #2. THE 16"
 FLEXIBLE RETURN AIR DUCT MAY NOT PASS THROUGH THE FIRE
 RATED WALL, PER 2004 FBC/M 607.7, PLEASE CORRECT.
  
 3) SEE ELECTRICAL REVIEW NOTE #1 REGARDING THE ENERGY
 CALCULATIONS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-03-04 Cont ID  
Sent By hmoser Date 2008-03-04 Time 17:25 Rev Time 0.00
Received By hmoser Date 2008-03-04 Time 17:25 Sent To  
Notes
2008-03-04 17:43:59PLANS DENIED
 1)PAGE A-01 SHOWS MECHANICAL ROOM RATED .PAGE M1.01
 SHOWES DUCT PENETRETEING MECHANICAL ROOM WALL . PLAESE
 SEE SECTION 607.5 2004 FBC (M) WHERE REQUIRED .
 2)FLEX AND T-FIN CAN NOT PENETRATE A RATED WALL .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By hmoser Date 2007-10-29 Time 10:39 Rev Time 0.00
Received By hmoser Date 2007-10-29 Time 10:39 Sent To  
Notes
2007-10-29 11:20:00PLAN DENIED
 1- PLEASE REFER TO SECTION 502.7.3.6 TERMINATION POINT
 # 2 (OUT DOOR AIR AND CONDENSORS ) PAGE M1.01.
 2- PLEASE REFER TONFPA 101 SECTION 7.1.3.2.1.(6)
 EXHAUST FAN # 1 MUST BE 10 FT. FROM STARS. PAGE M1.01
 3- PLEASE REFER TO SECTION 1019.1.2 2004 FBC
 PENETRATIONS ( DUCT PENETRATING STAIR WELL ) PAGE M1.02
 .
 4- PLEASE REFER TO SECTION 606.2.1 SMOKE DETECTION
 SYSTEM AND SECTION 606.4.1 SUPERVISON 2004 FBC (M) PLAN
 REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-07-23 Cont ID  
Sent By kstevens Date 2008-07-23 Time 17:06 Rev Time 0.00
Received By kstevens Date 2008-07-23 Time 17:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-05-19 Cont ID  
Sent By kstevens Date 2008-05-19 Time 15:23 Rev Time 0.00
Received By kstevens Date 2008-05-19 Time 15:23 Sent To  
Notes
2008-05-19 15:26:02DENIED 2ND TIME
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEWS;
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. **OK** COMMENT ADDRESSED.
  
 2. **OK** COMMENT ADDRESSED.
  
 3. **OK** COMMENT ADDRESSED.
  
 4. SHT A-01 THE BREAKROOM SINK SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL
 SUBSECTIONS. FORWARD APPROACH REQUIRED AND CABINET
 DOORS ARE NOT APPROVED. PLEASE PROVIDE A DETAIN WITH
 FRONTAL ELEVATION SHOWING COMPLIANCE. A TURNING AREA
 THAT COMPLIES WITH SECTION 11-4.2.3 SHALL BE PROVIDE.
 PLEASE INDICATE TURNING AREA.
 **RESPONSE NOTED, HOWEVER THE TURNING AREA THAT
 COMPLIES WITH SECTION 11-4.2.3 WAS NOT INDICATED FOR
 THE BREAKROOM.
 ****RESPONSE NOTED, BUT THE TURNING AREA AS SHOWN IS
 OUTSIDE THE BREAKROOM. THE TURNING AREA IS REQUIRED
 WITHIN THE BREAKROOM.
  
 5. OK
 6. **OK** COMMENT ADDRESSED.
  
 7. **OK** COMMENT ADDRESSED.
  
 8. **OK** COMMENT ADDRESSED.
  
 9. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-03-14 Cont ID  
Sent By mperson Date 2008-03-14 Time 08:03 Rev Time 0.00
Received By mperson Date 2008-03-14 Time 08:03 Sent To  
Notes
2008-03-14 09:22:24DENIED 2ND TIME
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 THE FOLLOWING COMMENTS ARE NUMBERED RO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. **OK** COMMENT ADDRESSED.
  
 2. **OK** COMMENT ADDRESSED.
  
 3. **OK** COMMENT ADDRESSED.
  
 4. SHT A-01 THE BREAKROOM SINK SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL
 SUBSECTIONS. FORWARD APPROACH REQUIRED AND CABINET
 DOORS ARE NOT APPROVED. PLEASE PROVIDE A DETAIN WITH
 FRONTAL ELEVATION SHOWING COMPLIANCE. A TURNING AREA
 THAT COMPLIES WITH SECTION 11-4.2.3 SHALL BE PROVIDE.
 PLEASE INDICATE TURNING AREA.
 **RESPONSE NOTED, HOWEVER THE TURNING AREA THAT
 COMPLIES WITH SECTION 11-4.2.3 WAS NOT INDICATED FOR
 THE BREAKROOM.
  
 5. SHT A-02 DETAIL A. SHOW COMPLIANCE WITH 11-4.16.5
 FLUSH CONTROLS, (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS,
 AND SHOW THE W/C TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE, (FIG. 28).--HEIGHT TO
 THE TOP OF THE LAV IS NOT LEGIBLE. PLEASE CLARIFY.--
 29" KNEE CLEARANCE IS REQUIRED AT THE LAV PER SECTION
 11-4.19.2. 28" IS SHOWN.
 **RESPONSE NOTED HOWEVER THERE ARE STILL ISSUES ON THE
 DETAIL WITH THE FOLLOWING: 11-4.16.5 FLUSH CONTROLS
 (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS (LEVER TYPE, PUSH
 TYPE, AND ELECTRONICALLY CONTROLED MECHANISMS ARE
 EXAMPLES OF ACCEPTABLE DESIGN). PLEASE INDICATE THESE
 REQUIRED ITEMS ON THE PLANS.
  
 6. **OK** COMMENT ADDRESSED.
  
 7. **OK** COMMENT ADDRESSED.
  
 8. **OK** COMMENT ADDRESSED.
  
 9. THE ENERGY CALCULATIONS SHALL REFLECT THE WATER
 HEATER SPECIFIED, (INSTA-HOT MODEL). THE CALCULATIONS
 INDICATE A 20 GAL WATER HEATER. THESE DO NOT CORRELATE.
 SECTION 13-103.
 **RESPONSE NOTED, HOWEVER THE WRONG FORM (400A) IS
 BEING USED. THIS IS NOT A WHOLE BUILDING WITH THE FIRST
 FLOOR BEING A SHEEL BY INDICATING FUTURE LEASABLE
 SPACE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-03 Cont ID  
Sent By kstevens Date 2007-11-03 Time 06:08 Rev Time 0.00
Received By kstevens Date 2007-11-03 Time 06:08 Sent To  
Notes
2007-11-03 06:53:14DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. CODE ADOPTED IS THE FBC-2004 W/2006 REVISIONS.
 PLEASE INDICATE THAT PLANS WERE DESIGNED TO THESE
 CODES.
  
 2. THE ADDRESS ON THE COVER SHEET, SHT LA-1 & SHT SP-1
 DOES NOT CORRELATE WITH THE ADDRESS ON THE OTHER
 SHEETS, THE APPLICATION AND THE ADDRESS ON OUR SYSTEM.
 PLEASE CORRELATE THE ADDRESS ON THESE SHEETS. SECTION
 106.1.1.
  
 3. SHT LA-1 THE CERTIFICATE OF AUTHROIZATION, (FIRM
 LICENSE NUMBER), IS MISSING FROM THE TITLE BLOCK FOR
 DIXIE LANDSCAPE. FAC 61G1-16.004(2) & FS 481.306.
  
 4. SHT A-01 THE BREAKROOM SINK SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL
 SUBSECTIONS. FORWARD APPROACH REQUIRED AND CABINET
 DOORS ARE NOT APPROVED. PLEASE PROVIDE A DETAIN WITH
 FRONTAL ELEVATION SHOWING COMPLIANCE. A TURNING AREA
 THAT COMPLIES WITH SECTION 11-4.2.3 SHALL BE PROVIDE.
 PLEASE INDICATE TURNING AREA.
  
 5. SHT A-02 DETAIL A. SHOW COMPLIANCE WITH 11-4.16.5
 FLUSH CONTROLS, (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS,
 AND SHOW THE W/C TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE, (FIG. 28).--HEIGHT TO
 THE TOP OF THE LAV IS NOT LEGIBLE. PLEASE CLARIFY.--
 29" KNEE CLEARANCE IS REQUIRED AT THE LAV PER SECTION
 11-4.19.2. 28" IS SHOWN.
  
 6. SHT A-02 DETAIL 1. SHOW THE W/C'S TO BE 18" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE, (FIG 28), AND
 THE LAV SHALL BE A MINIMUM 15" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE TO BE CENTERED ON THE 30"
 MEASUREMENT OF THE 30"X48" CLEAR FLOOR SPACE REQUIRED
 FOR THE LAV. SECTION 11-4.19.3.
  
 7. SUBMIT A SECOND FLOOR PLUMBING PLAN SHOWING THE
 LOCATION OF ALL FIXTURES, SANITARY PIPING, VENTS, WATER
 LINES ETC. SECTION 106.3.5.1.3(1)(2)(3)(4)(5)(6)(10).
  
 8. SUBMIT MANUFACTURE SPECIFICATION SHEETS FOR THE
 EEMAX INSTA-HOT WATER HEATER. SPECIFICATION SHEETS
 SHALL SHOW THE LISTING FOR THE WATER HEATER.
  
 9. THE ENERGY CALCULATIONS SHALL REFLECT THE WATER
 HEATER SPECIFIED, (INSTA-HOT MODEL). THE CALCULATIONS
 INDICATE A 20 GAL WATER HEATER. THESE DO NOT CORRELATE.
 SECTION 13-103.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2009-04-01 Cont ID  
Sent By mflis Date 2009-04-01 Time 09:34 Rev Time 0.00
Received By mflis Date 2009-04-01 Time 09:34 Sent To  
Notes
2009-04-01 09:34:59ZONING REVIEW: PASSED
  
 * SIDEWALK AND LANDSCAPE MODIFICATIONS PER ON-SITE
 CHANGES
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 3 Status P Date 2008-05-19 Cont ID  
Sent By mflis Date 2008-05-19 Time 09:38 Rev Time 0.00
Received By mflis Date 2008-05-19 Time 09:38 Sent To  
Notes
2008-05-19 09:38:52ZONING REVIEW: PASSED WITH PROVISO
  
 ** ACCORDING TO SUBMITTED SITE PLAN, DRIVEWAY ENTRANCE
 AT STREET WILL NEED TO BE RECONSTRUCTED TO MATCH NEW
 DRIVE WIDTH
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-07 Cont ID  
Sent By mflis Date 2008-02-07 Time 13:59 Rev Time 0.00
Received By mflis Date 2008-02-07 Time 13:59 Sent To  
Notes
2008-02-07 14:00:54ZONING REVIEW: PASSED WITH PROVISO
  
 ** ACCORDING TO SUBMITTED SITE PLAN, DRIVEWAY ENTRANCE
 AT STREET WILL NEED TO BE RECONSTRUCTED TO MATCH NEW
 DRIVE WIDTH
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-23 Cont ID  
Sent By mflis Date 2007-10-23 Time 13:32 Rev Time 0.00
Received By mflis Date 2007-10-23 Time 13:32 Sent To  
Notes
2007-10-23 13:40:05ZONING REVIEW: FAILED
  
 ** MEETING TO BE HELD WITH APPLICANT ON 10/24/07 TO
 REVIEW IN MORE DETAIL ZONING COMMENTS**
 COMMENTS BELOW ARE PRELIMINARY PRIOR TO MEETING.
  
 1) PLEASE REVISE DRIVEWAY AND PARKING ARRANGEMENT.
 DRIVEWAY TO BE REDUCED TO 12'-0" IN WIDTH WITH PARALLEL
 PARKING SPACES A MINIMUM OF 8'-6" WIDE
 2) ADA SPACE TO BE RELOCATED; MINIMUM WIDTH IS 8'-6"
 WITH 5'-0" ACCESS AISLE
 3) SIDEWALK SHALL BE PROVIDED FROM SIDE ENTRY TO PUBLIC
 SIDEWALK SO THAT IT IS NOT NECESSARY TO WALK DOWN
 DRIVEWAY OR THROUGH PARKING SPACES
 4) AT REAR, PLEASE MOVE TRASH ENCLOSURE AREA TO WESTERN
 CORNER OF SITE; STANDARD CITY DETAILS FOR ENCLOSURE
 SHOULD BE PROVIDED; ELEVATIONS SHOULD BE PROVIDED
 5) LANDSCAPE PLAN DOES NOT MATCH ARCH SITE PLAN OR
 ELEVATIONS; DOOR IS SHOWN ON NORTH ELEVATION, BUT
 CANNOT EXIT OUT INTO LANDSCAPE AREA; PLEASE REVISE
 6) NORTH ELEVATION SHALL BE REVISED AND TREATED AS A
 "FRONT" ELEVATION WITH APPROPRIATE DETAILS, INCLUDING
 PORCHES, RAILINGS, ETC. WHERE NECESSARY; SEE EAST
 ELEVATION FOR DETAILS TO BE USED.
 7) "FRONT" DOOR ON NORTH ELEVATION SHOULD BE CONNECTED
 TO PUBLIC SIDEWALK, EITHER DIRECTLY, OR CONNECTING TO
 ITEM (3) ABOVE.
 8) PLEASE REDUCE PITCH OF ROOF TO 3/12 OR 4/12 TO
 BETTER MATCH SCALE OF BUILDING.
 9) PLEASE PROVIDE BUILDING SECTION; ARE DORMER WINDOWS
 REAL OR FAKE? IS THERE ANY INTENTION TO USE THIS THIRD
 LEVEL FOR OFFICE OR RESIDENTIAL SPACE?
  
 MATT FLIS - 822-1445


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved