 |
Plan Review Details - Permit 07090034
Plan Review Stops For Permit 07090034 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
10 |
Status |
P |
Date |
2009-02-27 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2009-02-27 |
Time |
13:11 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2009-02-24 |
Time |
07:00 |
Sent To |
PC |
|
Notes |
2009-02-24 07:59:22 | 2/27/09 TWO SHEETS SUBMITTED. S-1 AMD S-3A INDICATING | | THE LOCATION OF SLAB BEING POURED UNDER THIS PERMIT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
9 |
Status |
P |
Date |
2008-11-20 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-11-20 |
Time |
07:44 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-11-20 |
Time |
07:44 |
Sent To |
PC |
|
Notes |
2008-11-20 07:45:41 | REVIEW TRUSS DRAWINGS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
8 |
Status |
F |
Date |
2008-10-28 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-10-28 |
Time |
07:28 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-10-28 |
Time |
07:28 |
Sent To |
PC |
|
Notes |
2008-10-27 15:56:55 | BUILDING PLAN REVIEW | | PERMIT: 07090034 | | ADD: 314 10TH STREET | | CONT: KENNEDY CONTRACTORS, INC. | | TEL: (561)434-1307 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: REVISION | | ACTION: DENIED | | | | SHEETS A-01/A-02/A-03/A-04/A-05/A-08 AND SHEETS S-1 - | | S-4. | | | | 1) SHEETS A-03 AND A-04 SHOW DORMERS ON THE ELEVATIONS | | PLANS. THESE DORMERS ARE NOT SHOWN ON THE PERMITTED SET | | OF DRAWINGS. IF THE DORMERS WILL BE INSTALLED, PROVIDE | | THE STRUCTURAL FRAMING DETAILS SHOWING THE ATTACHMENT | | METHODS FOR THE DORMERS; THE PLANS ALSO SHOW EIFS | | OUTRIGGERS BUT NO INFORMATION OR DETAILS HOW THEY WILL | | BE ATTACHED TO THE STRUCTURE. THE BUILDING OFFICIAL MAY | | REQUIRE DETAILS, COMPUTATIONS, DIAGRAMS, AND OTHER DATA | | NECESSARY TO DESCRIBE THE CONSTRUCTION OR INSTALLATION | | OF SYSTEMS. 106.1.2. | | | | 2) SHEET A-05 MAKES REFERENCE TO DETAIL #3 / S-2, THE | | DETAIL ON S-2 DO NOT CORRESPOND WITH SECTION INDICATED | | ON SHEET A-05. THE NEW PLANS ALSO SHOW TWO LAYERS R-21 | | INSULATION AND 3? CONTINUOUS SCREEN VENTS ON SHEET A-05 | | #4 THEN, ON SHEET S-4 #1 THE INSULATION SHOWN IS R30 | | AND THE SCREEN VENTS ARE 7? X 25? SPACED 8? O/C. THE | | DETAILS ALSO FAIL TO SHOW THE EIFS AS INDICATED ON THE | | ELEVATION DRAWINGS. CLARIFY. | | | | NOTE: PLEASE MAKE SURE THE DETAILS AND INFORMATION | | CORRESPOND WITH THE PLANS. SHOP DRAWINGS WILL BE | | REQUIRED FOR THE NEW FLOOR SYSTEM. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2008-10-16 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-10-16 |
Time |
08:00 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-10-16 |
Time |
07:44 |
Sent To |
PC |
|
Notes |
2008-10-27 15:56:01 | | | | | | | | 2008-10-16 07:28:25 | REVISION TO ELEVATOR PIT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2008-09-26 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-09-26 |
Time |
11:17 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-09-26 |
Time |
10:59 |
Sent To |
PC |
|
Notes |
2008-09-26 11:18:50 | SOIL REPORT SUBMITTAL. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2008-08-07 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-08-07 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-08-07 |
Time |
07:52 |
Sent To |
PC |
|
Notes |
2008-08-07 08:44:08 | PLANS WERE TAKEN TO THE COUNTY FOR IMPACT FEES, THEN | | RETURNED TO OUR OFFICE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2008-07-31 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-07-31 |
Time |
07:35 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-07-30 |
Time |
07:51 |
Sent To |
|
|
Notes |
2008-07-31 07:32:52 | PROVISOR: (1)FBC 2303.4.1 THE TRUSS DRAWINGS SHALL BE | | SUBMITTED AND REVIEWED BEFORE INSTALLATION. | | (2)FBC 1802.2THE FOUNDATION | | AND SOIL INVESTIGATION REPORT SHALL BE SUBMITTED PRIOR | | TO ANY | | FOUNDATION WORK. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2008-05-14 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-05-14 |
Time |
12:01 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-05-12 |
Time |
12:54 |
Sent To |
|
|
Notes |
2008-05-14 12:01:57 | REVIEW #3 | | BUILDING PLAN REVIEW #3 | | PERMIT: 07090034 | | ADD: 314 10TH ST | | CONT: KENNEDY CONTRACTORS, INC. | | TEL: (561)434-1300 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 3RD REVIEW 5-12-08 | | ACTION: DENIED | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 1B) OK | | 1C) OK | | | | 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 1E)OK. | | 2)OK | | | | **SECOND REQUEST.** NOTED | | 3) 1802.2.1 QUESTIONABLE SOIL. WHERE THE | | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE | | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS | | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE | | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH | | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF | | SECTIONS 1802.4 THROUGH 1802.6. | | | | 4) OK | | 5) OK | | 6) OK | | 7) OK | | 8) OK | | 9) OK | | 10)OK | | 11) OK | | 12) OK | | 13). OK | | 14)OK | | 15) OK | | 16) OK | | 17)OK | | 18) OK | | 19)OK | | 20) OK | | | | **THE AMOUNT AND TYPE OF DOORS INDICATED IS INCORRECT, | | THE INSULATION ON THE PLANS DIFFERS FROM THE ENERGY | | CALCS, THE TYPE OF ROOF IS DIFFERENT: THE ENERTY CALCU | | SHOWS BUILT-UP GRAVEL THE PLANS SHOW METAL** | | 21) ENERGY CALCULATIONS, SYSTEMS SUMMARY REPORT, PLEASE | | RECHECK THE AMOUNT OF WINDOW OPENING IN EACH ZONE AND | | WALL FACE, AS WELL AS DOORS. THE NUMBER OF EXTERIOR | | DOORS WAS NOT FILLED IN! 106.1.2 ADDITIONAL INFORMATION | | REQUIRED. | | | | 22)OK | | 23) OK | | | | 24)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING | | PROVIDE 2 COPIES (3 IF THRESHOLD OR RESIDENT INSPECTOR) | | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS | | FOLLOWS: | | A) SINGLE HUNG WINDOWS | | B) FIXED/ STOREFRONT WINDOWS | | C) MULLIONS VERTICAL OK | | D) SIDE LUTES | | E) SWING GLAZED DOORS (1) (INDICATE THE DOOR TO BE | | INSTALLED) | | F) EXTERIOR HOLLOW METAL SWING DOORS (4) CHECK ENERGY | | CALCS. | | G) TRUSS ANCHORS OK | | H) ROOF ASSEMBLIES FL#704-R1 IS MISSING THE SEAM-LOC | | REPORT | | | | 25)OK | | 26) OK | | 27) REMOVED | | 28) OK | | 29)OK | | 30)OK | | 31)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE | | APPLICABLE. | | | | ** SUBMIT A WINDOW SCHEDULE SHOWING THE HEIGHT AND | | WIDTH OF EACH WINDOW** | | | | MYRON JACOBS. | | BUILDING PLAN REVIEW | | TEL: (561)805-6726 | | FAX: (561)659-8026 | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2008-03-21 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-03-21 |
Time |
11:28 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-03-19 |
Time |
13:58 |
Sent To |
PC |
|
Notes |
2008-03-21 11:28:39 | | | BUILDING PLAN REVIEW | | PERMIT: 07090034 | | ADD: 314 10TH ST | | CONT: KENNEDY CONTRACTORS, INC. | | TEL: (561)434-1300 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 2NDREVIEW | | ACTION: DENIED | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 1B) OK | | | | 1C) **NOTE**106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 | | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN | | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF | | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY | | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE | | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS | | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | DETERMINED BY THE BUILDING OFFICIAL. | | | | 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 1E) OK | | 2)OK | | | | **2ND REQUEST** | | 3) 1802.2.1 QUESTIONABLE SOIL. WHERE THE | | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE | | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS | | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE | | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH | | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF | | SECTIONS 1802.4 THROUGH 1802.6. | | | | **NOTED; HOWEVER, EACH ACCESSIBLE PARKING SPACE MUST BE | | NO LESS THAN 12 FEET WIDE 11-4.6.2 (GREY AREA)** | | 4) SP-1 PLEASE PROVIDE ADDITIONAL INFORMATION AS HOW | | THE ACCESSIBLE ROUTE FROM THE HANDICAPPED PARKING SPACE | | AT ELEVATION 13.5?TO THE FINISH FLOOR ELEVATION OF | | 14.0?. | | 11-4.3.2(3). SHEET S-1 DETAIL# 7 IS NOT CLEAR IF THERE | | IS A | | | | **NOTED, HOWEVER, THE SECOND MEANS OF EGRESS THE | | INTERIOR STAIRS ALSO REQUIRE AN AREA OF RESCUE | | ASSISTANCE. SHOW COMPLIIANCE.** | | 5) AREAS OF RESCUE ASSISTANCE ARE REQUIRED IN 2 STORY | | BUILDINGS NOT HAVING FIRE SPRINKLERS; PLEASE SEE | | 11-4.1.3 EXCEPTION# 9. | | IN BUILDINGS OR FACILITIES, OR PORTIONS OF | | BUILDINGS OR FACILITIES, REQUIRED TO BE ACCESSIBLE, | | ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN THE | | SAME NUMBER AS REQUIRED FOR EXITS BY LOCAL | | BUILDING/LIFE SAFETY REGULATIONS. WHERE A REQUIRED EXIT | | FROM AN OCCUPIABLE LEVEL ABOVE OR BELOW A LEVEL OF | | ACCESSIBLE EXIT DISCHARGE IS NOT ACCESSIBLE, AN AREA OF | | RESCUE ASSISTANCE SHALL BE PROVIDED ON EACH SUCH LEVEL | | (IN A NUMBER EQUAL TO THAT OF INACCESSIBLE REQUIRED | | EXITS).AREAS OF RESCUE ASSISTANCE SHALL COMPLY WITH | | SECTION 11-4.3.11 . A HORIZONTAL EXIT, MEETING THE | | REQUIREMENTS OF LOCAL BUILDING/LIFE SAFETY REGULATIONS, | | SHALL SATISFY THE REQUIREMENT FOR AN AREA OF RESCUE | | ASSISTANCE. | | EXCEPTION: AREAS OF RESCUE ASSISTANCE ARE NOT REQUIRED | | IN BUILDINGS OR FACILITIES HAVING A SUPERVISED | | AUTOMATIC SPRINKLER SYSTEM. | | | | 6) SHEET A-01 PLANS INDICATE A SECOND FLOOR; THERE IS | | NO MENTION OF THE USE OF FIRE SPRINKLERS FOR THIS | | BUILDING. PLEASE SEE 11-4.3.11 (1-5) THESE REQUIREMENTS | | ARE TO BE MET FOR AREAS OF RESCUE ASSISTANCE; PLEASE | | PROVIDE INFORMATION FOR COMPLIANCE WITH THESE SECTIONS. | | **A SECOND MEANS OF RESCUE ASSISTANCE IS REQUIRED AT | | THE INTERIOR STAIRWAY PER 11-4.1.3 EXCEPTION# 9.** | | | | 7) OK | | | | **NOTED, HOWEVER, 11-4.3.11.3 STAIRWAY WIDTH | | EACH STAIRWAY ADJACENT TO AN AREA OF RESCUE ASSISTANCE | | SHALL HAVE A MINIMUM CLEAR WIDTH OF 48 INCHES BETWEEN | | HANDRAILS. | | | | 8) OK | | 9) OK | | 10)OK | | | | 11) SHEET A-01 THERE IS NO WALL TAGS IDENTIFYING THE | | TYPE OF WALL CONFIGURATION TO BE USED. | | 106.1.2 ADDITIONAL INFORMATION REQUIRED. ELEVATOR PUMP | | ROOM, ELEVATOR, STAIRWELL, LOBBY AND OR TENANT | | SEPARATION WALLS. **THERE ARE NOT DETAILS FOR WALLS | | TYPES 1W/ 3W / 4W/ 5W AND 6W, ALSO SOME OF THE WALLS | | ARE NOT LABELED(TAGGED)** NOTE: PER TABLE 1016.1 | | BUSINESS OCCUPANCY CORRIDORS SERVING AN OCCUPANT LOAD | | GREATER THAN 30 WILL REQUIRE A 1HR RATING. | | | | 12) SHEET A-4 STAIRWELL NUMBER 1 DOES NOT PROVIDE A CUT | | SECTION THROUGH THE CEILING PROVIDING WHAT TYPE OF | | MATERIAL AND OR RATING WILL BE APPLIED TO THE CEILING | | OF THE STAIRWELL. ADDITIONAL INFORMATION REQUIRED | | 106.1.2. **THE DETAIL UL P544 IS MISSING THE DRYWALL | | INFORMATION.** | | | | 13) OK | | | | 14)SHEET A-01 & A-03 INDICATE THE USE OF EXTERIOR | | STAIRS. PLEASE SEE 1022.6 FOR REQUIRED SEPARATION FROM | | THE INTERIOR OF THE BUILDING AS REQUIRED IN 1019.1, | | ALSO SEE ATTACHED FIGURE 1022.6(1) FROM THE 2004 FBC | | CODE COMMENTARY. **THE FLOOR PLANS SHOW THE SEPARATION | | OF THE WINDOWS FROM THE STAIRWAY; HOWEVER THE ELEVATION | | DRAWING ON SHEET A-03 SHOWS ONE OF THE WINDOWS WITH IN | | 5 FEET OF THE STAIRWAY. THE FLOOR PLANS SHOW SINGLE | | WINDOWS AND THE ELEVATION DRAWINGS SHOWS DOUBLE | | WINDOWS. ANY WINDOW WITHIN 10 FEET OF THE STAIRS SHALL | | HAVE AT LEAST A 1 HOUR FIRE RATING. CLARIFY.** | | | | 15) SHEET A-01 & A-03 STAIR # 2 DOES NOT PROVIDE THE | | RISER NOR TREAD DIMENSION, SEE 1009.3. **THERE IS NO | | SHEET S-06 IN THE PLANS AS STATED IN YOUR RESPONSE | | LETTER.** | | | | 16) STAIR# 2 DOES NOT PROVIDE INFORMATION ON THE | | HANDRAIL OR GUARDRAIL FOR THIS EXTERIOR STAIR, NOTED | | THIS IS A PRE-FAB ENGINEERED STEEL STAIR, AGAIN THERE | | IS NO INFORMATION FOR ATTACHMENT OF STAIRS TO | | STRUCTURE. ADDITIONAL INFORMATION REQUIRED. 106.1.2. | | **THERE IS NO SHEET S-06 IN THE PLANS AS STATED IN YOUR | | RESPONSE LETTER.** | | | | **SHEET A-03 SHOWS TWO ELEVATION DRAWINGS.** | | 17)SHEET A-01 ON THE 2ND FLOOR THE PLANS INDICATE THE | | USE OF A BREAK ROOM SINKS, THE PLANS DO NOT PROVIDE AN | | ELEVATION OF THIS AREA PLEASE COMPLY WITH THE | | FOLLOWING: | | SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED | | WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH | | FLOOR. | | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH | | 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH | | SINKS. | | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT | | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) | | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN | | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR | | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL | | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE | | SINK. | | | | **THERE IS NO SHEET S-06 IN THE PLANS AS STATED IN YOUR | | RESPONSE LETTER.** | | 18) PLANS DO NOT PROVIDE ANY INFORMATION ON | | PENETRATIONS OF HORIZONTAL ASSEMBLIES, | | 711.5 PENETRATIONS .PENETRATIONS THROUGH | | FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL | | COMPLY WITH SECTION 712. 712.4.1.1 | | FIRE-RESISTANCE-RATED ASSEMBLIES. | | PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN | | APPROVED FIRE-RESISTANCE-RATED ASSEMBLY. | | PLEASE PROVIDE DETAILS FOR PENETRATIONS THROUGH THE | | FLOOR/ CEILING ASSEMBLY. | | | | | | **2 REQUEST** | | 19)ENERGY CALCULATIONS SUBMITTED ARE FORM ?A? WHOLE | | BUILDING METHOD WHERE AS THE FIRST FLOOR IS ONLY | | ASSUMPTIONS AT THIS TIME, THE CORRECT FORM WOULD BE | | EITHER ?B? OR ?C?. | | 13-400.0A. NOTE NO INSULATION IS INDICATED ON THE FIRST | | FLOOR EXTERIOR WALLS, THE WHOLE BUILDING APPROACH, | | METHOD ?A? CAN NOT BE USED. | | | | | | 20) OK | | | | **2 REQUEST** | | 21) ENERGY CALCULATIONS, SYSTEMS SUMMARY REPORT, PLEASE | | RECHECK THE AMOUNT OF WINDOW OPENING IN EACH ZONE AND | | WALL FACE, AS WELL AS DOORS. THE EXTERIOR DOORS WERE | | NOT EVEN FILLED IN! 106.1.2 ADDITIONAL INFORMATION | | REQUIRED. | | | | 22)PLANS FAIL TO INDICATE COMPLIANCE WITH 1209.2 | | ATTIC ACCESS, PLEASE PROVIDE WHERE THE ATTIC ACCESS | | SHALL BE. | | | | **PROVIDE INFORMATION ON THE RIDGE VENT SYSTEM.** | | 23) SHEET A-04 DETAIL NUMBER 4 PROVIDES AN EXTERIOR | | WALL AND ROOF SECTION. THE PLANS NEED TO SHOW | | COMPLIANCE WITH : 1203.250 PERCENT OF THE REQUIRED | | VENTILATING AREA PROVIDED BY VENTILATORS LOCATED IN THE | | UPPER PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 | | FEET (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE | | BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR | | CORNICE VENTS. | | | | **SOME OF THE PRODUCT APPROVALS ARE STILL MISSING THE | | STATE COVER SHEETS. PLEASE CIRCLE OR HI-LIGHT THE | | SYSTEM OR ITEM TO BE USED FROM EACH PRODUCT.** | | 24)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING | | PROVIDE 2 COPIES (3 IF THRESHOLD OR RESIDENT INSPECTOR) | | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS | | FOLLOWS: | | A) SINGLE HUNG WINDOWS | | B) FIXED/ STOREFRONT WINDOWS | | C) MULLIONS VERTICAL | | D) SIDE LITES | | E) SWING GLAZED DOORS | | F) EXTERIOR HOLLOW METAL SWING DOORS | | G) TRUSS ANCHORS | | H) ROOF ASSEMBLIES | | | | | | **SOME OF THE PRODUCT APPROVALS ARE STILL MISSING THE | | STATE COVER SHEETS. PLEASE CIRCLE OR HI-LIGHT THE | | SYSTEM OR ITEM TO BE USED FROM EACH PRODUCT.** | | 25)PRODUCT APPROVALS SUBMITTED WITH PERMIT | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, | | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR | | SITE SPECIFIC FORM PER RULE 9B-72. | | | | 26) OK | | 27) **DORMER DELETED** | | | | **2REQUEST** | | 28) SHEET S-2 ROOF FRAMING PLAN AND NOTES INDICATE THE | | UPLIFT LOAD CALCS ARE LOCATED ON SHEET S-4, WHERE? | | ADDITIONAL INFORMATION REQUIRED 106.1.2. | | | | 29)OK | | 30)OK | | | | **2 REQUEST** | | 31)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE | | APPLICABLE. | | | | MYRON JACOBS. | | BUILDING PLAN REVIEW | | TEL: (561)805-6726 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-10-15 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-10-15 |
Time |
16:09 |
Rev Time |
3.33 |
Received By |
jwitmer |
Date |
2007-10-15 |
Time |
16:08 |
Sent To |
|
|
Notes |
2007-10-15 17:05:09 | BUILDING PLAN REVIEW | | PERMIT: 07090034 | | ADD: 314 10TH ST | | CONT: KENNEDY CONTRACTORS, INC | | TEL: (561)434-1300 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, | | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR | | REVIEW FOR PERMIT. | | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF | | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A | | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID | | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* | | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH | | ADMINISTRATIVE CODE. | | | | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 | | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN | | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF | | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY | | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE | | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS | | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | DETERMINED BY THE BUILDING OFFICIAL. | | | | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | BUILDING WITH THE2007 REVISIONS. | | | | 2)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE | | OF OCCUPANCY: | | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT | | IS DESIGNED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | PROVISIONS OF CHAPTER 3. | | C) THE TYPE OF CONSTRUCTION AS DEFINED INTABLE 503 | | & TABLE 601. | | D) THE OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | BUILDING PERMIT | | .H ) SQ. FT. FOOTPRINT | | | | 3) 1802.2.1 QUESTIONABLE SOIL. WHERE THE | | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE | | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS | | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE | | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH | | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF | | SECTIONS 1802.4 THROUGH 1802.6 . | | | | 4) SP-1 PLEASE PROVIDE ADDITIONAL INFORMATION AS HOW | | THE ACCESSIBLE ROUTE FROM THE HANDICAPPED PARKING SPACE | | AT ELEVATION 13.5?TO THE FINISH FLOOR ELEVATION OF | | 14.0?. | | 11-4.3.2(3). SHEET S-1 DETAIL# 7 IS NOT CLEAR IF THERE | | IS A | | | | 5) AREAS OF RESCUE ASSISTANCE ARE REQUIRED IN 2 STORY | | BUILDINGS NOT HAVING FIRE SPRINKLERS, PLEASE SEE | | 11-4.1.3 EXCEPTION# 9. | | IN BUILDINGS OR FACILITIES, OR PORTIONS OF | | BUILDINGS OR FACILITIES, REQUIRED TO BE ACCESSIBLE, | | ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN THE | | SAME NUMBER AS REQUIRED FOR EXITS BY LOCAL | | BUILDING/LIFE SAFETY REGULATIONS. WHERE A REQUIRED EXIT | | FROM AN OCCUPIABLE LEVEL ABOVE OR BELOW A LEVEL OF | | ACCESSIBLE EXIT DISCHARGE IS NOT ACCESSIBLE, AN AREA OF | | RESCUE ASSISTANCE SHALL BE PROVIDED ON EACH SUCH LEVEL | | (IN A NUMBER EQUAL TO THAT OF INACCESSIBLE REQUIRED | | EXITS).AREAS OF RESCUE ASSISTANCE SHALL COMPLY WITH | | SECTION 11-4.3.11 . A HORIZONTAL EXIT, MEETING THE | | REQUIREMENTS OF LOCAL BUILDING/LIFE SAFETY REGULATIONS, | | SHALL SATISFY THE REQUIREMENT FOR AN AREA OF RESCUE | | ASSISTANCE. | | EXCEPTION: AREAS OF RESCUE ASSISTANCE ARE NOT REQUIRED | | IN BUILDINGS OR FACILITIES HAVING A SUPERVISED | | AUTOMATIC SPRINKLER SYSTEM. | | | | 6) SHEET A-01 PLANS INDICATE A SECOND FLOOR, THERE IS | | NO MENTION OF THE USE OF FIRE SPRINKLERS FOR THIS | | BUILDING. PLEASE SEE 11-4.3.11 (1-5) THESE REQUIREMENTS | | ARE TO BE MET FORAREAS OF RESCUE ASSISTANCE, PLEASE | | PROVIDE INFORMATION FOR COMPLIANCE WITH THESE SECTIONS. | | | | | | 7) SHEET A-01 & A-04 INDICATE STAIRWELL# 1, THE DETAILS | | DO NOT PROVIDE INFORMATION FOR BARRIERS TO WARN | | VISUALLY IMPAIRED PERSONS SEE 11-4.4.2 & FIGURE 8-C1. | | THE EXTERIOR STAIRS WILL NEED THE SAME BARRIER FOR THE | | VISUALLY IMPAIRED. | | | | 8) SHEET A-04 STAIR# 1 SECTION OF GUARDRAIL/ HANDRAIL | | .THIS IS AN OFFICE OCCUPANCY THAT WILL NEED TO HAVE THE | | GUARDRAIL CONFORM TO SECTION 1012.3. 4? CENTERS. | | | | 9) SHEET A-04 DETAIL# 3 IS FOR A 1-HR RATED WALL, | | PLEASE PROVIDE THE UL NUMBER OR GYPSUM | | ASSOCIATION LISTING NUMBER FOR A 1 HOUR RATED ASSEMBLY. | | 707.4. | | | | 10)SHEET A-01 THE FIRST FLOOR LOBBY WILL REQUIRE A | | 1-HR RATING. THIS BUILDING DOES NOT INDICATE THE USE OF | | FIRE SPRINKLERS, PLEASE SEE TABLE 1016.1 BUSINESS | | OCCUPANCY CORRIDORS SERVING A OCCUPANT LOAD GREATER | | THAN 30 WILL REQUIRE A 1 HR RATING. | | | | 11) SHEET A-01 THERE IS NO WALL TAGS IDENTIFYING THE | | TYPE OF WALL CONFIGURATION TO BE USED. | | 106.1.2 ADDITIONAL INFORMATION REQUIRED. ELEVATOR PUMP | | ROOM, ELEVATOR, STAIRWELL, LOBBY AND OR TENANT | | SEPARATION WALLS. | | | | 12) SHEET A-4 STAIRWELL NUMBER 1 DOES NOT PROVIDE A CUT | | SECTION THROUGH THE CEILING PROVIDING WHAT TYPE OF | | MATERIAL AND OR RATING WILL BE APPLIED TO THE CEILING | | OF THE STAIRWELL. ADDITIONAL INFORMATION REQUIRED, | | 106.1.2. | | | | 13) SHEET A-01 DOOR NUMBER 6 & 7 WILL REQUIRE FIRE | | RATED DOORS, PLEASE SEE 715.3 FOR OPENING | | PROTECTIVE?S. | | | | 14)SHEET A-01 & A-03 INDICATE THE USE OF EXTERIOR | | STAIRS. PLEASE SEE 1022.6 FOR REQUIRED SEPARATION FROM | | THE INTERIOR OF THE BUILDING AS REQUIRED IN 1019.1, | | ALSO SEE ATTACHED FIGURE 1022.6(1) FROM THE 2004 FBC | | CODE COMMENTARY. | | | | 15) SHEET A-01 & A-03 STAIR # 2 DOES NOT PROVIDE THE | | RISERNOR TREAD DIMENSION, SEE 1009.3. | | | | 16) STAIR# 2 DOES NOT PROVIDE INFORMATION ON THE | | HANDRAIL OR GUARDRAIL FOR THIS EXTERIOR STAIR, NOTED | | THIS IS A PRE-FAB ENGINEERED STEEL STAIR, AGAIN THERE | | IS NO INFORMATION FOR ATTACHMENT OF STAIRS TO | | STRUCTURE. ADDITIONAL INFORMATION REQUIRED. 106.1.2. | | | | 17)SHEET A-01 ON THE 2ND FLOOR THE PLANS INDICATE THE | | USE OF A BREAK ROOM SINK, THE PLANS DO NOT PROVIDE AN | | ELEVATION OF THIS AREA PLEASE COMPLY WITH THE | | FOLLOWING: | | SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED | | WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH | | FLOOR. | | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH | | 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH | | SINKS. | | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT | | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) | | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN | | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR | | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL | | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE | | SINK. | | | | 18) PLANS DO NOT PROVIDE ANY INFORMATION ON | | PENETRATIONS OF HORIZONTAL ASSEMBLIES, | | 711.5 PENETRATIONS .PENETRATIONS THROUGH | | FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL | | COMPLY WITH SECTION 712 . 712.4.1.1 | | FIRE-RESISTANCE-RATED ASSEMBLIES. | | PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN | | APPROVED FIRE-RESISTANCE-RATED ASSEMBLY. | | PLEASE PROVIDE DETAILS FOR PENETRATIONS THROUGH THE | | FLOOR/ CEILING ASSEMBLY. | | | | | | | | 19)ENERGY CALCULATIONS SUBMITTED ARE FORM ?A? WHOLE | | BUILDING METHOD WHERE AS THE FIRST FLOOR IS ONLY | | ASSUMPTIONS AT THIS TIME, THE CORRECT FORM WOULD BE | | EITHER ?B? OR ?C?. | | 13-400.0A. NOTE NO INSULATION IS INDICATED ON THE FIRST | | FLOOR EXTERIOR WALLS, THE WHOLE BUILDING APPROACH , | | METHOD ?A? CAN NOT BE USED. | | | | 20) THE SEALED SIGNATURE ON THE ENERGY CALCULATION IS | | EITHER A STAMP OR COPY OF THE ORIGINAL SIGNATURE. | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR | | PUBLIC | | RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN | | PROFESSIONAL AFFIXED TO THE DOCUMENT. FL STATE STAT: | | 61G15-23.002 ENGINEERS | | | | 21) ENERGY CALCULATIONS, SYSTEMS SUMMARY REPORT, PLEASE | | RECHECK THE AMOUNT OF WINDOW OPENING IN EACH ZONE AND | | WALL FACE, AS WELL AS DOORS. THE EXTERIOR DOORS WERE | | NOT EVEN FILLED IN! 106.1.2 ADDITIONAL INFORMATION | | REQUIRED. | | | | 22)PLANS FAIL TO INDICATE COMPLIANCE WITH 1209.2 | | ATTIC ACCESS, PLEASE PROVIDE WHERE THE ATTIC ACCESS | | SHALL BE. | | | | 23) SHEET A-04 DETAIL NUMBER 4 PROVIDES A EXTERIOR WALL | | AND ROOF SECTION. THE PLANS NEED TO SHOW COMPLIANCE | | WITH : 1203.250 PERCENT OF THE REQUIRED VENTILATING | | AREA PROVIDED BY VENTILATORS LOCATED IN THE UPPER | | PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 FEET | | (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE | | OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE | | VENTS. | | | | 24)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) | | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS | | FOLLOWS: | | A) SINGLE HUNG WINDOWS | | B) FIXED/ STOREFRONT WINDOWS | | C) MULLIONS VERTICAL | | D) SIDE LITES | | E) SWING GLAZED DOORS | | F) EXTERIOR HOLLOW METAL SWING DOORS | | G) TRUSS ANCHORS | | H) ROOF ASSEMBLIES | | | | 25)PRODUCT APPROVALS SUBMITTED WITH PERMIT | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, | | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR | | SITE SPECIFIC FORM PER RULE 9B-72. | | 26) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | 27) SHEET S-2 ROOF FRAMING PLAN IS MISSING THE DORMER | | SECTION OF THE ROOF, PLEASE PROVIDE | | A SECTION INDICATING HOW THE FRONT, SIDE WALLS WILL TIE | | INTO THE MAIN ROOFING SYSTEM. | | 106.1.2 ADDITIONAL INFORMATION REQUIRED. | | | | 28) SHEET S-2 ROOF FRAMING PLAN AND NOTES INDICATE THE | | UPLIFT LOAD CALCS ARE LOCATED ON SHEET S-4, WHERE? | | ADDITIONAL INFORMATION REQUIRED 106.1.2. | | | | 29)SHEET S-2ND FLOOR DETAIL# 11 INDICATES A METAL | | DECK AND CONCRETE BUT NO INFORMATION AS TO THE TYPE OF | | STEEL NOR STRENGTH AND TYPE OF THE CONCRETE MIX TO BE | | USED FOR THIS SLAB. | | NOTE S-3 FLOOR DECK NOTE# 4 INDICATES A MINIMUM YIELD | | STRENGTH OF 33,000PSI? | | | | 30)NOTE PLANS DO NOT INDICATE ANY WINDOW BUCK | | ATTACHMENT TO THE STRUCTURE. | | 1714.5.4.1 ANCHORING REQUIREMENTS. | | WINDOW AND DOOR ASSEMBLIES SHALL BE ANCHORED IN | | ACCORDANCE WITH THE PUBLISHED MANUFACTURER?S | | RECOMMENDATIONS TO ACHIEVE THE DESIGN PRESSURE | | SPECIFIED. SUBSTITUTE ANCHORING SYSTEMS USED FOR | | SUBSTRATES NOT SPECIFIED BY THE FENESTRATION | | MANUFACTURER SHALL PROVIDE EQUAL OR GREATER ANCHORING | | PERFORMANCE AS DEMONSTRATED BY ACCEPTED ENGINEERING | | PRACTICE. | | | | 1714.5.4.2 MASONRY, CONCRETE OR OTHER STRUCTURAL | | SUBSTRATE. | | WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1? | | INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE | | ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR | | SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S | | PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE | | SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE | | OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS | | OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE | | INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT | | FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE | | MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE | | LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF | | SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED | | TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE | | ROUGH OPENING SUBSTRATE. | | | | 31)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE | | APPLICABLE. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2008-07-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-07-30 |
Time |
14:54 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-07-30 |
Time |
14:54 |
Sent To |
|
|
Notes |
2008-07-30 14:55:17 | *** PROVISO *** | | | | 1) NOTE: PLEASE SEE EGRESS LIGHT FOR STAIR #2 UNDER | | EMERGENCY POWER IS IN QUESTION ON THE AMOUNT OF LIGHT | | FOR EGRESS PER LS 101 7.9.1.2. | | | | NEED TO REVISE PHOTO-METRICS AND AVERAGE WITH USING THE | | LEVELS ON THE INSIDE OF THE BUILDING. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2008-07-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-07-28 |
Time |
15:12 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-07-28 |
Time |
15:12 |
Sent To |
|
|
Notes |
2008-07-28 15:12:44 | | | ** FAILED REVIEW ** | | | | | | 1) NOTE:EGRESS LIGHTING FOR STAIR #2 DOES NOT MEET | | THE LIFE SAFETY CODE. 7.9.2.1,7.9.2.2 THE LIGHTING FOOT | | CANDLES LEVEL IS SHOWING LEVELS FROM .09, .08, .07 AND | | THEN UP TO 15.3, 14.1 ETC. THIS IS NOT POSSIBLE AS THE | | SINGLE BATTERY BACK UP FIXTURE IS AT THE TOP OF THE | | STAIRS. ALSO SHOWS TAKING ALLOWANCE AVERAGE FROM THE | | INTERIOR LIGHTING WHICH IS NOT PERMITTED. | | CALLED AND SPOKE TO ENGINEER MR. FORMICA AND HE WILL | | CALL BACK ONCE HE OBTAINS INFORMATION FROM STAFF. | | LIGHTING LEVELS ON ALL STAIRS ARE IN QUESTION. THE | | LIGHTING LUMENS UNDER CONDITIONS OF NORMAL AND | | EMERGENCY ARE TO BE VERIFIED. | | | | 2) NOTE: TYPE SA FIXTURES INDICATE 210WATTS ON SITE | | PLANS. THE IDR OF THE ENERGY CALCULATIONS STATE 175W. | | THE FIXTURE WATTAGE NOT BULB IS REQUIRED TO BE USED PER | | 13-415.2.ABC.1.3. | | THIS WILL ALSO BE GONE OVER. | | | | IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2008-05-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-05-23 |
Time |
13:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-05-23 |
Time |
13:02 |
Sent To |
|
|
Notes |
2008-06-26 15:55:35 | MEETING HELD 6/26/08 | | IT BECAME APPARENT OF THE TWO ROLLS OF REVISED NEW SETS | | OF PLANS SUBMITTEDONLY ONE ROLL CONTAINED NEW REVISED | | SHEETS. THE OTHER ROLL WAS NOT REVIEWED FOR CODE | | COMPLIANCE. | | THIS WAS AN ADMINISTRATIVE ERROR BY THE CONTRACTORS | | OFFICE. | | IN ATTENDANCE WAS MR. MICHAEL CARP, MR. KENNEDY AND MR. | | ROBERT FORMICA (ELECTRICAL ENGINEER OF RECORD). | 2008-05-23 13:02:28 | ** DENIED3RD REVIEW** | | | | | | | | 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS | | ARE NOT THE CORRECT VERSION PER FBC 13-400.3.B. THE | | RESPONSE MENTIONS THE WORDING ON THE STATE WEBSITE | | HOWEVER PLEASE READ WHAT IT SAYS. IT STATES THE *ENERGY | | GAUGE SUMMIT VERSIONS 3.0-3.14 WHICH IS IN *VERSION | | 2.5* IS ACCEPTABLE. THIS DOES NOT STATE A VERSION 3.0. | | IT IS STILL VERSION 2.5 WHICH INCORPORATES THE OTHER | | PROGRAMS. PLEASE READ THE STATEMENT AS IT CLEARLY | | STATES *IN VERSION 2.5*. THIS WAS EVEN ATTACHED TO | | ENERGY CALCULATIONS SUBMITTED. I HAVE REDLINED AND | | CIRCLED THE LINE IN WHICH THE STATE HAS PARENTHESIS | | AROUND THE WORDING: * GENERATED BY FLA/COM 2004 | | COMPUTER PROGRAM, VERSION 2.5*. | | THIS REVIEWER HAS CALLED TWICE TO THE ENGINEER?S FIRM | | TO GO OVER THIS REQUIREMENT ON THIS AND OTHER PROJECTS. | | NO RETURN CALL HAS BEEN RECEIVED. | | PLEASE KNOW THIS WAS AND HAS BEEN CONFIRMED WITH THE | | FLORIDA BUILDING COMMISSION/DEPARTMENT OF COMMUNITY | | AFFAIRS ON SEVERAL OCCASIONS. | | PLEASE BE SURE OWNER AGENT IS FILLED OUT ON | | CERTIFICATION SHEET. | | | | *** PLEASE SEE SHEET E2.01 WHICH INDICATES INTERIOR | | LIGHTING POWER ALLOWANCE WHICH INDICATES *BUILDING | | METHOD A*. THIS IS NOT POSSIBLE FOR A SHELL BUILDING. | | PLEASE SEE13-101.1.6. | | | | 2) NOTE: PLEASE SEE THE SUBMITTED METHOD *B* DOES NOT | | COMPLY WITH THE MINIMUM REQUIRED BY CODE. | | PLEASE SEE SOME OF THE FOLLOWING ARE GIVEN AS | | EXAMPLES. | | FOR EXAMPLE: | | PLEASE BE SURE TO INCLUDE ANY *ASSUMPTIONS* FOR FUTURE | | SHELL SPACE AT A MINIMUM. ONLY SHOWS 4 LIGHT FIXTURES | | AT 64WATTS. | | FOR EXAMPLE: | | PLEASE SEE SOME FIXTURES SHOWN WITH A *0* VALUE. HOW IS | | THIS POSSIBLE? | | FOR EXAMPLE: | | PLEASE SEE EXTERIOR LIGHTING ON THE INPUT DATA REPORT | | AS THESE STILL DO NOT MATCH/CORRELATE WITH THE PLANS. | | THE IDR SHOWS 2-50W FIXTURES AND 1-32 WATT FIXTURE. HOW | | IS THIS POSSIBLE WHEN THE PLANS CLEARLY SHOW SEVERAL | | OTHER FIXTURES WHICH HAVE NOT BEEN FIGURED OR PLACED | | INTO THE IDR. WHERE ARE THE *J* FIXTURES, THE *C* | | FIXTURES, THE *SA* FIXTURES????? | | FOR EXAMPLE: | | IN SPACE ON FIRST FLOOR WHICH IS SHOWN IN ZONE OTHER | | THAN SHELL ONLY FOUR (4) FIXTURES TOTAL ARE BEING SHOWN | | HOWEVER BASED ON THE FIRST FLOOR LIGHTING ELECTRICAL | | PLANS THERE ARE CLEARLY MORE FIXTURES. | | FOR EXAMPLE: | | PLEASE COORDINATE ALL FIXTURES AND DESIGNATIONS. ONE OF | | THESE WOULD BE *C* FIXTURE WHICH CLEARLY INDICATES THIS | | FIXTURE AS A *RESTROOM FIXTURE* ON THE FIXTURE LEGEND. | | | | **THESE ARE NOT THE ONLY LIGHTS ON PLANS WHICH STILL DO | | NOT COORDINATE WITH THE INPUT DATA REPORT AND ENERGY | | CALCULATIONS. | | THESE ARE ONLY A FEW EXAMPLES OF NON-COMPLIANCE.THIS | | IS NOT AN EXHAUSTED LIST. | | PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. | | | | 3) NOTE: PLEASE SUBMIT *MINIMUM* LIFE SAFETY | | PHOTO-METRICS SHOWING AT LEAST THE MINIMUM COMPLIANCE | | WITH THE LIFE SAFETY CODE NFPA-101 7.8.1.3, 7.9.2.2 | | PLEASE SEE THE LIGHTING LEVELS SUBMITTED FOR SOME AREAS | | ARE NOT CODE COMPLIANT AND PLEASE SEE SOME AREAS LIKE | | EXTERIOR REQUIRED EGRESS STAIRS STILL DO NOT SHOW ANY | | LEVELS AT ALL. | | PLEASE SEE PLANS AND COORDINATE. | | | | 4) NOTE: PLEASE SEE OTHER SHEETS IN SETS INCLUDING SITE | | LIGHTING ELECTRICAL NOW SHOW THE 2ND FLOOR EXTERIOR | | STAIRS OUT AND AWAY FROM THE BUILDING. THIS WILL AFFECT | | NOT ONLY THE REQUIRED PHOTO-METRICS HOWEVER ALSO THE | | LIGHTING ON ENERGY CALCULATIONS. | | PLEASE BE SURE TO COORDINATE ALL OF THESE SHEETS FOR | | LIFE SAFETY ETC. THIS IS A MINIMUM CODE. | | LS 101 7.8, 7.9, FBC CHAPTER 10, | | FBC ADMIN SECTIONS 106.1.2, FOR COORDINATION. | | FAC 61G15-33.004 | | | | 5) NOTE: PLEASE SEE COMPLIANCE FOR LIGHTING CONTROLS | | HAS NOT BEEN MET. PLEASE SEE 13-415.1.ABC.1.4 ALONE FOR | | EXTERIOR LIGHTING. NOTE #1 ON SHEET E2.01 FOR EXAMPLE | | WHICH STILL SHOWS EXTERIOR LIGHTING TO BE THROUGH | | LIGHTING CONTROL PANEL BUT NO DETAIL FOR ASTRONOMICAL | | TIME CLOCK OR PHOTO-SENSOR CONTROLS. | | RESPONSE MENTIONS THIS WAS REVISED HOWEVER BASED ON THE | | PLANS SUBMITTED THIS WAS NOT THE CASE. | | PLEASE BE SURE TO SEE THE OTHER LIGHTING AS NOTED ON | | PREVIOUS REVIEW FOR INTERIOR LIGHTING ALSO. PLEASE SEE | | SEVERAL AREAS AS NOTED ON PREVIOUS REVIEW IN WHICH | | STANDARD SWITCHES ARE BEING SHOWN. 13-415.1.ABC.1.1, | | .1.2 AND .1.3. | | | | 6) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO | | FRAMING MEMBERS AND BONDING AS REQUIRED PER FBC 2704 | | RESPONSE MENTIONS THIS WAS ADDED TO E3.01 HOWEVER THIS | | IS NOT THE CASE. | | | | 7) NOTE: PLEASE SEE RISER STILL ONLY SHOWS 3-MAINS WHEN | | IN FACT THERE ARE 4 MAINS. PLEASE LABEL ACCORDINGLY. | | PLEASE LABEL: 1OF4, 2OF 4 ETC | | 230.2E. | | | | 8) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO FS | | 553.80(2)(B) WITH RESPECT TO REPEAT COMMENT FOR CODE | | COMPLIANCE. THIS FEE AS REQUIRED BY STATUTORY | | REQUIREMENT HAS NOW BEEN ASSESSED. IT IS REQUIRED UNDER | | STATE STATUTE AND IS REQUIRED TO BE PAID BEFORE PLANS | | MAY BE RESUBMITTED FOR THE NEXT REVIEW. IT IS IMPORTANT | | TO KNOW ONE SET OF PLANS ARE RETAINED BY THIS OFFICE AT | | THIS TIME. IT IS ALSO IMPORTANT TO KNOW THAT IF THERE | | ARE ANY QUESTIONS, OR ANY PART OF THE REVIEW COMMENTS | | ARE NOT UNDERSTOOD IN ANY WAY, PLEASE CALL OR CONTACT | | THIS OFFICE. | | THIS REVIEW CALLED AND LEFT TWO MESSAGES IN RECENT | | WEEKS FOR RETURN CALLS TO BE MADE HOWEVER THIS TO DATE | | NO CALLS HAVE BEEN RECEIVED. | | THIS FEE UNDER STATUE IS DUE BEFORE RESUB. $9,000.00 | | | | | | | | ** IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2008-02-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-02-10 |
Time |
09:10 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-02-10 |
Time |
09:10 |
Sent To |
|
|
Notes |
2008-02-11 09:10:59 | *** DENIED 2ND REVIEW *** | | | | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL | | IN NEED OF ADDRESSING. | | | | 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS | | MAY NOT USE METHOD *A*. THIS BUILDING CONTAINS A SHELL | | AND ASSUMPTIONS ARE TO BE MADE. PLEASE SEE 13-400.3.B, | | WHICH IS FOR VERSION 2.5 AS 3.0 IS NOT YET ADOPTED. | | PLEASE SEE THIS SAME SECTION AS NOTED FOR SHELL AS WELL | | AS 13-400.2.A.2. WHICH STATES AS LONG AS ALL DESIGN | | PARAMETERS ARE KNOWN THEN METHOD *A* CAN BE USED. | | HOWEVER AT THIS TIME THIS IS NOT POSSIBLE WHEN THE | | FIRST FLOOR IS STILL SHELL SPACE. | | THIS WAS MENTIONED TO SEE MECHANICAL COMMENTS ALSO. | | | | 2) NOTE: PLEASE BE SURE THE INFORMATION ON THE INPUT | | DATA REPORT FOR NEW CALCULATIONS COORDINATES WITH | | PLANS. PLEASE SEE THE INPUT DATA REPORT WILL BE NOTED | | AS IDR THROUGH THE REST OF THIS COMMENT. | | A) ** PLEASE SEE THAT ALL LIGHTING FIXTURES ON PLANS | | COORDINATE WITH THE IDR FOR INTERIOR AND EXTERIOR FOR | | THE NUMBER OF FIXTURES, THE WATTAGE AND THE METHOD OF | | CONTROLS. | | PLEASE SEE FOR EXAMPLE THE METHOD OF CONTROLS FOR SOME | | ARE NOTED A *MANUAL ON/OFF* WHICH IS NOT POSSIBLE WHEN | | ALL LIGHTING IS REQUIRED TO HAVE SOME SORT OF AUTOMATED | | SHUT OFF. | | PLEASE SEE FOR EXAMPLE THE EXTERIOR LIGHTING ON THE IDR | | SHOWS A TOTAL OF 1-100W FIXTURE YET THE PLANS CONTAIN | | MORE THAN 1-100W FIXTURE. THE PLANS ALSO CONTAIN OTHER | | FIXTURES ON THE EXTERIOR OF BUILDING. PLEASE SEE H | | FIXTURES, C FIXTURE, J-FIXTURES ETC. | | PLEASE SEE THE INTERIOR LIGHTING AS NOTED ON TABLE ON | | E2.01 DOES NOT COORDINATE WITH THE IDR ON CALCULATIONS | | FOR THE COUNT OF FIXTURES. THE IDR FOR INTERIOR | | LIGHTING DOES SEEM OK. PLEASE SEE NOTES ABOVE AS METHOD | | WILL STILL CHANGE. | | | | 3) NOTE: AS NOTED ON PREVIOUS PLANS ZONING REQUIRES A | | MINIMUM LIGHTING LEVELS FOR PARKING AREAS, YET NO | | EXTERIOR SITE LIGHTING IS SHOWN ON PLANS. THIS WILL BE | | CONFIRMED WITH ZONING. IF REQUIRED PLEASE BE SURE TO | | FOLLOW CONTROLS REQUIRED IN CHAPTER 13 AS WELL AS | | INCLUDING IN IDR. | | | | 4) NOTE: PLEASE SEE SOME AREAS ARE STILL MISSING | | REQUIRED LIGHTING CONTROLS PER 13-415.1.ABC.1.1, .1.2, | | .1.3 AND .1.4. | | A) **PLEASE SEE EXTERIOR LIGHTS NOTE MENTIONS LIGHTING | | TO BE THROUGH LCP, YET NO INFORMATION IS PROVIDED ON | | TYPE OF TIME CLOCK, BATTERY BACK UP OF POWER ETC. | | PLEASE SEE CODE SECTION 13-415.1.ABC.1.4 WHICH REQUIRES | | ONE OF TWO METHODS (BOTH COULD BE DONE ALSO). | | EITHER PHOTO-SENSOR OR ASTRONOMICAL TIME CLOCK WITH | | BATTERY BACK UP OF A MINIMUM OF 10HRS. | | | | B) ** PLEASE SEE SOME AREAS WHERE STANDARD SWITCHES ARE | | STILL BEING SHOWN. (LOBBY) | | C) ** PLEASE SEE NO MAXIMUM TIMES COULD BE LOCATED ON | | PLANS FOR ANY OF THE LIGHTING CONTROL DEVICES AS WELL | | AS THE MAXIMUM TIMES FOR OVER RIDES. | | D) ** PLEASE SEE NO SCHEDULING COULD BE LOCATED ON | | PLANS. | | E) ** PLEASE BE SURE THE OWNER AGENT IS SIGNED ON | | CERTIFICATION SHEETS. 13-103.1.1.1 | | | | 5) NOTE: PLEASE SEE THE PREVIOUS NOTES WITH RESPECT TO | | EGRESS LIGHTING FOR STAIRS UNDER NORMAL AND EMERGENCY. | | THE PHOTO-METRICS SUBMITTED WERE ONLY FOR LEVELS UNDER | | EMERGENCY FOR STAIR #1. NO LEVELS UNDER EITHER NORMAL | | OR EMERGENCY WERE LOCATED FOR STAIR #2. | | PLEASE SEE 7.8.1.3 OF LS 101 WHICH REQUIRES 10FT | | CANDLES UNDER NORMAL AND 7.9.2 WHICH ALLOWS LEVELS DOWN | | TO 1FT CANDLE UNDER EMERGENCY. | | PLEASE SUBMIT. | | FAC 61G15-33.004, | | FBC 106.1.2, 106.3.5.1.2 | | | | 6) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO A | | NOTE BEING PLACED ON PLANS FOR ALL METAL FRAMING | | MEMBERS TO BE BONDED AS REQUIRED PER FBC 2704. | | | | 7) NOTE: THE RISER SHOWS 4 MAINS, ONLY THREE LABELED AS | | MAINS. EACH OF THESE IS NOT NOTED CORRECTLY. ONE SAYS | | MAIN ONE OF ONE. HOW IS THIS POSSIBLE WHEN THERE ARE | | FOUR MAINS? TWO ARE LABELED AS MAINS TWO OF THREE AND | | THREE OF THREE. THIS DOES NOT COORDINATE WITH FIRST | | MAIN. PLEASE ALSO SEE THE HOUSE MAIN OF SERVICE DOES | | INDICATE ANY INDICATION OF MAIN ETC. | | EXAMPLE: 1 OF 4, 2 OF 4, 3 OF 4 AND 4 OF 4. | | PLANS ON SHEET E1-01 ONLY SHOWS THREE MAINS. WHERE IS | | THE FOURTH MAIN? | | PLEASE LABEL MAINS. 230.2E | | PLEASE SHOW LOCATIONS FOR GROUPING ETC. 230.70, 230.72, | | 110.26 ETC | | | | 8) NOTE: PLEASE SEE NOTICE FOR FS 553.80(2)(B) IS GIVEN | | ONLY A NOTICE AT THIS TIME AS THERE WERE REPEATED | | COMMENTS FOR CODE COMPLIANCE FOR SOME OF THE SAME | | ITEMS. | | | | ** PLEASE KNOW AS SOME ITEMS ARE STILL NOT SUBMITTED OR | | SHOWN, REVIEW OF SOME ITEMS STILL CAN NOT BE DONE. | | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH | | CAN NOT BE MADE AT THIS TIME. | | | | ** PLEASE KNOW A RESPONSE LETTER IS NOT REQUIRED | | HOWEVER IS HELPFUL IN THE REVIEW PROCESS. RESPONSES | | SUBMITTED FOR SOME OF THE OTHER TRADES ONLY. | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF THERE ARE ANY | | QUESTIONS OR IF THERE ARE ANY COMMENTS ARE NOT TYPED IN | | A CLEAR FASHION PLEASE DO NOT HESITATE IN CONTACTING | | THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-10-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-10-07 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-10-07 |
Time |
13:05 |
Sent To |
|
|
Notes |
2007-10-07 14:15:30 | 2007-10-07 14:15:30 | | | | *** DENIED *** | | | | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH | | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS | | UNDER THE NEW CODES ADOPTED BY THE STATE. | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | AFFECT DESIGNS FOR ALL TRADES. | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | REVIEWER AT A MINIMUM. | | 2004 FBC W/ 2006 REVISIONS | | 2005 NFPA-70 | | 2002 NFPA-72 | | 2003 NFPA-101 | | | | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED | | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS | | NOT MADE BY OTHER TRADE(S). | | | | 2) NOTE: PLEASE SEE THE ADDRESS ON APPLICATION AND | | ADDRESS IN OUR SYSTEM AS APPLIED FOR WITH THE PCN | | PROVIDED IS FOR 314 10TH ST, HOWEVER THE PLANS/COVER | | SHEET CLEARLY INDICATES *310* 10TH ST?? | | PLEASE COORDINATE AND CORRECT. | | FBC 106.1.2, 110.1.2 | | | | 3) NOTE: PLEASE SEE THE TITLE BLOCKS ON THE LANDSCAPE | | SHEETS ARE MISSING REQUIRED INFORMATION PER FLORIDA | | ADMINISTRATIVE CODE 61G1-16.004, AND FLORIDA STATUTES | | 481.219. | | MISSING CERTIFICATE OF AUTHORIZATION NUMBER. | | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY | | OTHER TRADES** | | | | 4) NOTE: PLEASE SEE THAT COMPLIANCE WITH NFPA-101 7.8 | | AND 7.9 NEEDS TO BE MET. | | PLEASE SEE THERE ARE SEVERAL AREAS IN WHICH BATTERY | | BACK UP TYPE OF LIGHTING FIXTURES ARE MISSING. | | FOR EXAMPLE STAIRS WHICH ONLY INDICATE A *D* FIXTURE | | WHICH BY FIXTURE LEGEND DOES NOT CONTAIN ANY BATTERY | | BACK UP?? | | PLEASE KNOW THAT LIGHTING IS REQUIRED FOR ALL EGRESS | | PATHS INCLUDING THAT TO THE EXIT DISCHARGE | | AREAS/PATHS. | | | | FOR EXAMPLE: | | PLEASE SEE THE STAIR AREAS OUTSIDE WHICH ARE PART OF | | THE EXIT DISCHARGE WHICH DOES NOT CONTAIN BATTERY BACK | | UP LIGHTING. | | PLEASE SEE AREAS AS THESE ARE EXIT PATHS HOWEVER AS | | THEY ARE NOT CONSIDERED THE PUBLIC RIGHT OF WAY OR SAFE | | DISTANCE FROM THE BUILDING, EMERGENCY LIGHTING FIXTURES | | WILL BE REQUIRED. | | PLEASE SEE THE ELEVATOR EQUIPMENT ROOM WILL BE REQUIRED | | TO HAVE A BATTERY BACK UP FIXTURE OF SOME TYPE. PLEASE | | SEE THERE ARE OTHER AREAS ALSO HOWEVER NOT ALL ARE | | LISTED. | | PLEASE SUBMIT AND PROVIDE LIGHTING PHOTO-METRICS FOR | | ALL EGRESS PATHS TO THE PUBLIC RIGHT OF WAY. PLEASE SEE | | THE LEVELS UNDER NORMAL FOR STAIRS SHALL MEET THE | | MINIMUM OF 10FT CANDLES PER 7.8.1.3 AND IS PERMITTED TO | | GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. FBC | | 106.1.2, FAC 61G15-33.004 | | NFPA-101 7.8, 7.9 | | | | 5) NOTE: PLEASE SEE THERE ARE SOME LOCATIONS IN WHICH | | EXIT SIGNSAND A LIGHTING FIXTURE WITH BATTERY BACK UP | | WILL BE REQUIRED FOE LIFE SAFETY. | | PLEASE SEE THE FUTURE BUILD OUT SPACES WHICH WILL | | REQUIRE THESE. PLEASE ALSO SEE THAT LIGHTING CONTROL | | FOR OCCUPANCY SENSOR TYPE DEVICE(S) WILL BE REQUIRED. | | THIS WAS CONFIRMED WITH THE FIRE MARSHAL. | | PLEASE SEE NFPA-101 7.8, 7.9, FBC CHAPTER 10. | | | | 6) NOTE: PLEASE KNOW AS ZONING CONTAINS MINIMUM | | REQUIREMENTS FOR DOWNTOWN MASTER PLAN AREAS AND PARKING | | LOT LIGHTING, THIS WILL AFFECT COMMENTS 6 AND 7 BELOW. | | AS NO SITE LIGHTING IS YET SUBMITTED, NO REVIEW CAN BE | | DONE. | | ZONING DOES HAVE MINIMUM PHOTO-METRIC LEVELS ALSO. | | PLEASE CONTACT AMY STELLY FOR SECTION OF THE ZONING | | ORDINANCE. | | | | 7) NOTE: PLEASE SEE THAT COMPLIANCE WITH FBC CHAPTER 13 | | IS NEEDED FOR ALL LIGHTING CONTROLS IN ALL AREAS. | | | | A) PLEASE PROVIDE INFORMATION/DESIGN/TIME SCHEDULING | | ETC ON HOW LIGHTING IS BEING CONTROLLED IN COMMON | | AREAS. | | PLEASE CLARIFY HOW THE STANDARD 3-WAY SWITCHES BEING | | SHOWN ON PLANS WILL COMPLY AND WORK WITH THE SYSTEM. | | ALSO SOME S-POLE SWITCHES WITH NO AUTOMATED CONTROL | | PLEASE SEE THE OVER RIDES SHALL BE LOCATED SO THE | | OCCUPANT WHEN ENTERING A SPACE CAN NOT ONLY CONTROL THE | | LIGHTING IN AN OVER RIDE CIRCUMSTANCE BUT MUST ALSO SEE | | THE LIGHTING IN WHICH IS BEING CONTROLLED. THERE IS | | ONLY ONE EXCEPTION TO THE LIGHTING FOR REQUIRED VISUAL | | CONTACT OF LIGHTS BEING CONTROLLED. | | PLEASE SEE THE OCCUPANCY DEVICES AS SHOWN NEED TO STATE | | THE MAXIMUM TIMES. | | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | | B) PLEASE SEE EXTERIOR LIGHTING CONTROLS AS A STANDARD | | TIME CLOCK IS NOT ALL THAT IS REQUIRED. | | 13-415.1.ABC.1.4 | | | | | | 8) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 FOR | | ENERGY CALCULATIONS/LIGHTING PERFORMANCE CALCULATIONS | | NEEDS TO BE MET. | | **IMPORTANT** PLEASE BE SURE TO SEE MECHANICAL REVIEW | | COMMENTS FOR POSSIBLE METHOD BEING SUBMITTED AND USED | | FOR WHAT IS BEING SHOWN AS SHELL ON PLANS.(ONLY NOTED) | | PLEASE SEE THE FOLLOWING WHICH WILL HAVE REFERENCE TO | | THE INPUT DATA REPORT AS IDR. | | | | A) PLEASE CORRELATE ALL LIGHTING WHICH IS ON PLANS AND | | CONSUMES ENERGY WITH THAT OF THE IDR. | | FOR EXAMPLE: | | PLEASE SEE THE EXTERIOR LIGHTING WHICH INDICATES A | | *NONE ENTERED*. PLEASE EXPLAIN HOW THIS IS POSSIBLE | | WHEN PLANS CLEARLY SHOW EXTERIOR LIGHTING? | | | | PLEASE BE SURE THE FIXTURE LEGEND COORDINATES WITH THE | | LIGHTING IN THE IDR. | | PLEASE ALSO SEE FOR EXAMPLE THE INTERIOR LIGHTING WHICH | | NEEDS TO COORDINATE WITH PLANS. | | PLEASE SEE THE AREAS DO NOT MATCH. | | PLEASE SEE THE NUMBER OF FIXTURES ON EACH AND EACH | | AREA/ROOM DESIGNATION DOES NOT CORRELATE. | | PLEASE SEE THE IDR DOES NOT CONTAIN ALL LIGHTING AS | | SHOWN ON PLANS AND THE FIXTURE LEGEND | | PLEASE SEE THE METHOD OF CONTROLS INDICATES *MANUAL | | ON/OFF* WHICH IS ALSO NOT POSSIBLE WHEN LIGHTING | | CONTROLS ARE AUTOMATED ETC. | | | | ** PLEASE BE SURE TO COORDINATE ALL FIXTURES ON PLANS | | WITH THE IDR. | | PLEASE SEPARATE TO ROOMS AND AREAS ON THE IDR. REVIEW | | OF MANY ITEMS CAN NOT BE DONE. | | | | PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR ALLOWANCES. | | PLEASE SEE 13-415.1.A, 13-415.2 ETC. | | | | ** PLEASE SEE 2004 FBC CHAPTER 13 FOR ALL ELECTRICAL | | LIGHTING CONTROLS AND CALCULATIONS REQUIRED. | | | | 9) NOTE: PLEASE SEE ALL THREE SETS OF ENERGY | | CALCULATIONS SUBMITTED CONTAIN A RAISED SEAL OVER A | | *PHOTO-COPIED* SIGNATURE WHICH IS NOT PERMITTED PER FAC | | 61G15-23.002 AND FS 471.025. | | PLEASE KNOW THIS OFFICE HAS INFORMED THIS SAME DESIGNER | | ON PREVIOUS PROJECTS AS THIS IS NOT PERMITTED. PLEASE | | BE SURE TO ADDRESS THIS ISSUE AS THESE WILL BE LEFT | | WITH NO OTHER CHOICE BUT TO FORWARD THESE TO THE STATE | | BOARD OF ENGINEERS AND LEGAL COUNSEL. | | ** PLEASE BE SURE THE OWNER AGENT IS SIGNED PER | | 13-103.1.1.1 | | | | | | 10) NOTE: PLEASE CLARIFY THE GROUNDING AS AN *EQUIPMENT | | GROUNDING CONDUCTOR* IS BEING SHOWN ON THE LINE SIDE OF | | THE FIRST MEANS OF DISCONNECT WHICH IS NOT PERMITTED. | | PLEASE SEE 250.24BA AND 250.6 AS THIS WILL CREATE | | OBJECTIONABLE CURRENTS. | | | | 250.50 **PLEASE PLACE NOTE ON PLANS FOR FBC 2704 WHICH | | REQUIRES METAL FRAMING MEMBERS TO BE BONDED. | | | | 11) NOTE: THIS IS ONLY NOTED FOR INFORMATION ONLY: | | PLEASE KNOW IF THE BUILDING CONTAINS A FA PANEL OR IS | | REQUIRED TO HAVE ONE INSTALLED PER BUILDING OR FIRE | | MARSHAL REVIEW, PLEASE BE SURE TO SEE FBC 2004 | | 11-4.28.1, .2 AND .3(4) AND STATE THE MINIMUM HORN, | | STROBE LEVELS ON PLANS FOR ADA REQUIRED AREAS. DEVICES | | ARE BEING SHOWN ON PLANS/LEGEND. PLEASE CORRELATE WITH | | PLANS, AND FA SHEETS SUBMITTED. THIS IS NOTED FOR | | INFORMATION ONLY!! | | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A | | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS | | REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM | | SETS. | | FBC 106.3.5.1.2 | | | | 12) NOTE: PLEASE CLARIFY ALL CONTINUOUS AND LARGEST | | MOTOR LOADS AT 125%. | | PLEASE SHOW. 215.3, 230.42 (SOME ARE SHOWN) | | | | 13) NOTE: PLEASE SEE FEEDER CONDUIT/CONDUCTORS FROM | | 225AMP CIRCUIT BREAKER MAIN IS BEING SHOWN GOING | | THROUGH THE LINE GUTTER WHICH IS NOT PERMITTED. MAY NOT | | INSTALL UNPROTECTED AND PROTECTED CONDUCTORS IN THE | | SAME GUTTER AS SHOWN. | | PLEASE ADJUST RISER AND SEE 230.7 AS * OTHER CONDUCTORS | | IN RACEWAY OR CABLE | | CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE | | INSTALLED IN THE SAME SERVICE RACEWAY OR SERVICE | | CABLE. | | ALL FEEDER AND BRANCH-CIRCUIT CONDUCTORS MUST BE | | SEPARATED FROM SERVICE CONDUCTORS. SERVICE CONDUCTORS | | ARE NOT PROVIDED WITH OVER-CURRENT PROTECTION WHERE | | THEY RECEIVE THEIR SUPPLY; THEY ARE PROTECTED AGAINST | | OVERLOAD CONDITIONS AT THEIR LOAD END BY THE SERVICE | | DISCONNECT FUSES OR CIRCUIT BREAKERS. THE AMOUNT OF | | CURRENT THAT COULD BE IMPOSED ON FEEDER OR | | BRANCH-CIRCUIT CONDUCTORS, SHOULD THEY BE IN THE SAME | | RACEWAY AND A FAULT OCCUR, WOULD BE MUCH HIGHER THAN | | THE AMPACITY OF THE FEEDER OR BRANCH-CIRCUIT | | CONDUCTORS.* | | | | 14) NOTE: PLEASE SEE DISCONNECTS AS SHOWN FOR THE | | CONDENSING UNITS DO NOT MEET 110.26. | | PLEASE ADJUST. | | | | 15) NOTE: PLEASE LABEL AND IDENTIFY ALL MAINS AND | | FUTURE MAINS. | | 230.2E. | | EXAMPLE: MAIN 1OF 4, 2 OF 4 ETC | | | | 16) NOTE: PLEASE SEE THAT PANEL SCHEDULES ARE TO BE | | SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED. | | PLEASE SEE 408.4. (MAY BE NUMERICAL DESIGNATIONS) | | | | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE | | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A | | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE | | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. | | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED | | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE | | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, | | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE | | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT | | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS | | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR | | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT | | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE | | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT | | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS | | SECTION.* | | 408.4, 310.16, 240.4 ETC | | FBC 106.3.5.1.2, 106.5, 106.1.2 | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | 2007-10-07 13:05:38 | 2007-10-07 13:05:08 | | | | IN ELECTRIC FOR REVIEW |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2008-02-25 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2008-02-25 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2008-02-25 |
Time |
13:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2007-10-16 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2007-10-16 |
Time |
13:55 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2007-10-16 |
Time |
13:46 |
Sent To |
|
|
Notes |
2007-10-16 13:55:46 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | NOI. | | YOU CAN GET NOI INFO FROM | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | EFFECTIVE MAY 1, 2003 | | 2. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR | | SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP | | PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM | | 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES. | | PHONE# 494-1040 | | 3. PLEASE MAKE SURE DUMPSTER LOCATION ON DWG MUST BE | | ACCESSIBLE FOR CITY'SPICKUP TRUCK. | | 4. PLEASE SHOW ON CALCULATTION THAT YOU HAVE CONSIDERED | | FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA TO | | DETERMINE THE FIRST FLOOR ELEVATION, PARKING LOT | | ELEVATION, CROWN OF THE ROAD ELEVATION, SIDEWALK ETC. | | 5. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA, | | GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU | | ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE | | THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH | | AND USED IN STORM WATER QUALITY CALCULATIONS. | | 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE | | SO WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM ALL | | OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE | | CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING | | ELEVATION, ETC ON DRAWINGS, CALCULATION FOR | | EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET | | DETENTION AREAS IN STORM WATER CALS. | | 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | YOUR SITE FOR STORM WATER DRAIN. | | 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM | | WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE | | APPROVED FROM 100045TH STREET ENGINEERING SERVICES. | | 9. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION | | DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT | | FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE | | SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST & | | PARTICLES. | | 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED. | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | PERMITTING PROCESS | | | | RASIK CHOKSHI805-6723 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2008-07-31 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-07-31 |
Time |
09:59 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-07-31 |
Time |
09:59 |
Sent To |
|
|
Notes |
2008-07-31 09:59:40 | SHEET A-01 STAMPED, SIGNED AND DATED |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2008-05-27 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-05-27 |
Time |
11:25 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-05-27 |
Time |
11:25 |
Sent To |
|
|
Notes |
2008-05-27 11:26:10 | IT APPEARS THAT ALL FIRE COMMENTS HAVE BEEN ADDRESSED. | | PLANS WILL BE STAMPED BY FIRE ONCE SUBMITTED WITH | | CORRECTIONS TO OTHER REVIEW COMMENTS. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2008-03-04 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-03-04 |
Time |
15:33 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-03-04 |
Time |
15:32 |
Sent To |
|
|
Notes |
2008-03-04 15:47:33 | ***DENIED*** | | | | PLEASE NOTE THAT MOST OF THE PREVIOUS COMMENTS HAVE NOT | | BEEN ADDRESSED. IT WOULD HELP EXPEDITE THIS PROCESS IF | | YOU INCLUDE A RESPONSE LETTER INDICATING HOW AND WHERE | | EACH COMMENT WAS ADDRESSED. | | | | 1) OK | | | | 2) FUTURE TENANT SEPARATIONS WILL BE REQUIRED WHEN THE | | FUTURE SPACES ARE LEASED. PLEASE ACKNOWLEDGE. | | | | 3) BUILDING ADDRESS IS REQUIRED ON ELEVATIONS THAT | | ILLUSTRATES A MINIMUM OF 6" IN HEIGHT, 1" IN WIDTH AND | | CONTRASING WITH BACKGROUND. | | | | 4) PLEASE CLARIFY EXITING PROTECTION FROM STAIR #1 AND | | EXTERIOR STAIRS REGARDING DOORS AND WINDOW EXPOSURES. | | | | 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENT FOR | | HANDRAILS AND GUARDS. INDICATE ON DETAILS. | | | | 6) WHAT SLIP RESISTANT METHODS ARE PLANNED FOR THE | | EXTERIOR FIRE STAIR? | | | | 7) ELEVATOR WARNING SIGNS REQUIRED AT ELEVATOR OPENINGS | | IN LOBBIES. | | | | 8) OK | | | | 9) TACTILE SIGNS REQUIRED AT EXIT DOORS. | | | | 10) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | WITH NFPA 241. | | | | 11) DEBRIS TO BE REMOVED FROM THE SITE DAILY. | | | | 12) OK | | | | 13) PLEASE INDICATE FIRE EXTINGUISHER LOCATIONS. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-10-22 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2007-10-22 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2007-10-22 |
Time |
14:30 |
Sent To |
|
|
Notes |
2007-10-22 14:47:42 | 1. DUCTWORK APPEARS TO PASS THROUGH STAIR # 1 ON PAGE | | M1.02. PLEASE PROVIDE DETAILS, MECHANICAL EQUIPMENT IS | | NOT ALLOWED TO PASS THROUGH A REQUIRED EXIT STAIR. | | | | 2. FUTURE TENANT SEPARATIONS WILL BE REQUIRED WHEN THE | | FUTURE SPACES ARE LEASED. | | | | 3. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A | | MINIMUM OF AT LEAST 6" HIGH NUMBERS AND AT LEAST 1" | | WIDE SHALL BE PROVIDED. NUMBERS SHOULD CONTRAST WITH | | THE BACKGROUND THEY ARE MOUNTED ON. | | | | 4. WHAT PROTECTION IS BEING AFFORDED TO EXITING FROM | | STAIR # 1 AND TO EXITING OCCURING FROM THE EXTERIOR | | STAIRS. IT APPEARS THAT DOORS IN THE LOBBY ARE NOT FIRE | | RATED AND WINDOWS APPEAR TO BE WITHIN CLOSE PROXIMITY | | TO THE EXTERIOR STAIR. THERE APPEARS TO BE NO | | PROTECTION TO PROVIDE FOR EXITING. | | | | 5. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS | | FOR ALL HANDRAILS AND GUARDRAILS. | | | | 6. WHAT SLIP RESISTANT METHODS ARE PLANNED FOR THE | | EXTERIOR FIRE STAIR. | | | | 7. ELEVATOR WARNING SIGNS REQUIRED AT ELEVATOR | | OPENINGS. | | | | 8. ELEVATOR INSTALLATION TO COMPLY WITH ANSI A17.1. | | | | 9. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | 10. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | WITH NFPA 241. | | | | 11. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | 12. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR | | WALLS AND CEILINGS. | | | | 13. PLEASE ILLUSTRATE PORTABLE FIRE EXTINGUISHER | | LOCATIONS. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | 804-4709 PHONE | | 804-4774 FAX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2009-03-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-03-27 |
Time |
09:05 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-03-27 |
Time |
09:05 |
Sent To |
Z |
|
Notes |
2009-03-27 09:05:51 | TO "Z" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2009-02-24 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2009-02-24 |
Time |
06:59 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2009-02-24 |
Time |
06:59 |
Sent To |
B |
|
Notes |
2009-02-24 07:00:25 | TO MJ DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2008-11-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-11-14 |
Time |
09:55 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-11-14 |
Time |
09:55 |
Sent To |
B |
|
Notes |
2008-11-14 09:56:06 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2008-10-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-23 |
Time |
08:56 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-23 |
Time |
08:56 |
Sent To |
B |
|
Notes |
2008-10-23 08:56:29 | TO "MJACOBS" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-09-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-09-23 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-09-23 |
Time |
10:47 |
Sent To |
B |
|
Notes |
2008-09-23 10:48:20 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-07-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-10 |
Time |
12:01 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-10 |
Time |
12:01 |
Sent To |
|
|
Notes |
2008-07-10 12:03:57 | TO "COMM" BD#43 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-05-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-05 |
Time |
15:31 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-05 |
Time |
15:31 |
Sent To |
|
|
Notes |
2008-05-05 15:34:02 | TO "COMM" BD#48 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-02-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-01 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-01 |
Time |
16:41 |
Sent To |
|
|
Notes |
2008-02-01 16:41:17 | TO "COMM" BD#63 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-11-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-11-03 |
Time |
07:05 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-06 |
Time |
12:31 |
Sent To |
|
|
Notes |
2007-10-07 13:06:21 | TO COMM BOARD #8, DVP> | 2007-09-06 12:31:33 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2008-07-11 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-07-11 |
Time |
11:09 |
Rev Time |
0.45 |
Received By |
tgordon |
Date |
2008-07-11 |
Time |
11:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2008-05-23 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-05-23 |
Time |
14:11 |
Rev Time |
0.45 |
Received By |
tgordon |
Date |
2008-05-23 |
Time |
14:11 |
Sent To |
|
|
Notes |
2008-05-23 14:23:09 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) AS NOTED IN LAST REVIEW 3-4-08 NOTE #1. THE WALL | | BETWEEN THE FIRST FLOOR MECHANICAL ROOM AND LOBBY IS | | FIRE RATED, THE 14X12 SUPPLY AIR DUCT PENETRATING THE | | WALL NEEDS A FIRE DAMPER, PER 2004 FBC/M 607.5.3 OR | | MEET THE EXCEPT. | | | | 2) AS NOTED IN LAST REVIEW 3-4-08 NOTE #2. THE 16" | | FLEXIBLE RETURN AIR DUCT MAY NOT PASS THROUGH THE FIRE | | RATED WALL, PER 2004 FBC/M 607.7, PLEASE CORRECT. | | | | 3) SEE ELECTRICAL REVIEW NOTE #1 REGARDING THE ENERGY | | CALCULATIONS, PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2008-03-04 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2008-03-04 |
Time |
17:25 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2008-03-04 |
Time |
17:25 |
Sent To |
|
|
Notes |
2008-03-04 17:43:59 | PLANS DENIED | | 1)PAGE A-01 SHOWS MECHANICAL ROOM RATED .PAGE M1.01 | | SHOWES DUCT PENETRETEING MECHANICAL ROOM WALL . PLAESE | | SEE SECTION 607.5 2004 FBC (M) WHERE REQUIRED . | | 2)FLEX AND T-FIN CAN NOT PENETRATE A RATED WALL . | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-10-29 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2007-10-29 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2007-10-29 |
Time |
10:39 |
Sent To |
|
|
Notes |
2007-10-29 11:20:00 | PLAN DENIED | | 1- PLEASE REFER TO SECTION 502.7.3.6 TERMINATION POINT | | # 2 (OUT DOOR AIR AND CONDENSORS ) PAGE M1.01. | | 2- PLEASE REFER TONFPA 101 SECTION 7.1.3.2.1.(6) | | EXHAUST FAN # 1 MUST BE 10 FT. FROM STARS. PAGE M1.01 | | 3- PLEASE REFER TO SECTION 1019.1.2 2004 FBC | | PENETRATIONS ( DUCT PENETRATING STAIR WELL ) PAGE M1.02 | | . | | 4- PLEASE REFER TO SECTION 606.2.1 SMOKE DETECTION | | SYSTEM AND SECTION 606.4.1 SUPERVISON 2004 FBC (M) PLAN | | REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2008-07-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-07-23 |
Time |
17:06 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-07-23 |
Time |
17:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2008-05-19 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-05-19 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-05-19 |
Time |
15:23 |
Sent To |
|
|
Notes |
2008-05-19 15:26:02 | DENIED 2ND TIME | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | ****FROM PREVIOUS REVIEWS; | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE | | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | 1. **OK** COMMENT ADDRESSED. | | | | 2. **OK** COMMENT ADDRESSED. | | | | 3. **OK** COMMENT ADDRESSED. | | | | 4. SHT A-01 THE BREAKROOM SINK SHALL BE ACCESSIBLE. | | SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL | | SUBSECTIONS. FORWARD APPROACH REQUIRED AND CABINET | | DOORS ARE NOT APPROVED. PLEASE PROVIDE A DETAIN WITH | | FRONTAL ELEVATION SHOWING COMPLIANCE. A TURNING AREA | | THAT COMPLIES WITH SECTION 11-4.2.3 SHALL BE PROVIDE. | | PLEASE INDICATE TURNING AREA. | | **RESPONSE NOTED, HOWEVER THE TURNING AREA THAT | | COMPLIES WITH SECTION 11-4.2.3 WAS NOT INDICATED FOR | | THE BREAKROOM. | | ****RESPONSE NOTED, BUT THE TURNING AREA AS SHOWN IS | | OUTSIDE THE BREAKROOM. THE TURNING AREA IS REQUIRED | | WITHIN THE BREAKROOM. | | | | 5. OK | | 6. **OK** COMMENT ADDRESSED. | | | | 7. **OK** COMMENT ADDRESSED. | | | | 8. **OK** COMMENT ADDRESSED. | | | | 9. OK | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2008-03-14 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-03-14 |
Time |
08:03 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-03-14 |
Time |
08:03 |
Sent To |
|
|
Notes |
2008-03-14 09:22:24 | DENIED 2ND TIME | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | THE FOLLOWING COMMENTS ARE NUMBERED RO CORRESPOND WITH | | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE | | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | 1. **OK** COMMENT ADDRESSED. | | | | 2. **OK** COMMENT ADDRESSED. | | | | 3. **OK** COMMENT ADDRESSED. | | | | 4. SHT A-01 THE BREAKROOM SINK SHALL BE ACCESSIBLE. | | SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL | | SUBSECTIONS. FORWARD APPROACH REQUIRED AND CABINET | | DOORS ARE NOT APPROVED. PLEASE PROVIDE A DETAIN WITH | | FRONTAL ELEVATION SHOWING COMPLIANCE. A TURNING AREA | | THAT COMPLIES WITH SECTION 11-4.2.3 SHALL BE PROVIDE. | | PLEASE INDICATE TURNING AREA. | | **RESPONSE NOTED, HOWEVER THE TURNING AREA THAT | | COMPLIES WITH SECTION 11-4.2.3 WAS NOT INDICATED FOR | | THE BREAKROOM. | | | | 5. SHT A-02 DETAIL A. SHOW COMPLIANCE WITH 11-4.16.5 | | FLUSH CONTROLS, (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS, | | AND SHOW THE W/C TO BE 18" OFF THE WALL TO THE | | CENTERLINE OF THE FIXTURE, (FIG. 28).--HEIGHT TO | | THE TOP OF THE LAV IS NOT LEGIBLE. PLEASE CLARIFY.-- | | 29" KNEE CLEARANCE IS REQUIRED AT THE LAV PER SECTION | | 11-4.19.2. 28" IS SHOWN. | | **RESPONSE NOTED HOWEVER THERE ARE STILL ISSUES ON THE | | DETAIL WITH THE FOLLOWING: 11-4.16.5 FLUSH CONTROLS | | (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS (LEVER TYPE, PUSH | | TYPE, AND ELECTRONICALLY CONTROLED MECHANISMS ARE | | EXAMPLES OF ACCEPTABLE DESIGN). PLEASE INDICATE THESE | | REQUIRED ITEMS ON THE PLANS. | | | | 6. **OK** COMMENT ADDRESSED. | | | | 7. **OK** COMMENT ADDRESSED. | | | | 8. **OK** COMMENT ADDRESSED. | | | | 9. THE ENERGY CALCULATIONS SHALL REFLECT THE WATER | | HEATER SPECIFIED, (INSTA-HOT MODEL). THE CALCULATIONS | | INDICATE A 20 GAL WATER HEATER. THESE DO NOT CORRELATE. | | SECTION 13-103. | | **RESPONSE NOTED, HOWEVER THE WRONG FORM (400A) IS | | BEING USED. THIS IS NOT A WHOLE BUILDING WITH THE FIRST | | FLOOR BEING A SHEEL BY INDICATING FUTURE LEASABLE | | SPACE. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-11-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-11-03 |
Time |
06:08 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-11-03 |
Time |
06:08 |
Sent To |
|
|
Notes |
2007-11-03 06:53:14 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. CODE ADOPTED IS THE FBC-2004 W/2006 REVISIONS. | | PLEASE INDICATE THAT PLANS WERE DESIGNED TO THESE | | CODES. | | | | 2. THE ADDRESS ON THE COVER SHEET, SHT LA-1 & SHT SP-1 | | DOES NOT CORRELATE WITH THE ADDRESS ON THE OTHER | | SHEETS, THE APPLICATION AND THE ADDRESS ON OUR SYSTEM. | | PLEASE CORRELATE THE ADDRESS ON THESE SHEETS. SECTION | | 106.1.1. | | | | 3. SHT LA-1 THE CERTIFICATE OF AUTHROIZATION, (FIRM | | LICENSE NUMBER), IS MISSING FROM THE TITLE BLOCK FOR | | DIXIE LANDSCAPE. FAC 61G1-16.004(2) & FS 481.306. | | | | 4. SHT A-01 THE BREAKROOM SINK SHALL BE ACCESSIBLE. | | SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL | | SUBSECTIONS. FORWARD APPROACH REQUIRED AND CABINET | | DOORS ARE NOT APPROVED. PLEASE PROVIDE A DETAIN WITH | | FRONTAL ELEVATION SHOWING COMPLIANCE. A TURNING AREA | | THAT COMPLIES WITH SECTION 11-4.2.3 SHALL BE PROVIDE. | | PLEASE INDICATE TURNING AREA. | | | | 5. SHT A-02 DETAIL A. SHOW COMPLIANCE WITH 11-4.16.5 | | FLUSH CONTROLS, (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS, | | AND SHOW THE W/C TO BE 18" OFF THE WALL TO THE | | CENTERLINE OF THE FIXTURE, (FIG. 28).--HEIGHT TO | | THE TOP OF THE LAV IS NOT LEGIBLE. PLEASE CLARIFY.-- | | 29" KNEE CLEARANCE IS REQUIRED AT THE LAV PER SECTION | | 11-4.19.2. 28" IS SHOWN. | | | | 6. SHT A-02 DETAIL 1. SHOW THE W/C'S TO BE 18" OFF THE | | WALL TO THE CENTERLINE OF THE FIXTURE, (FIG 28), AND | | THE LAV SHALL BE A MINIMUM 15" OFF THE WALL TO THE | | CENTERLINE OF THE FIXTURE TO BE CENTERED ON THE 30" | | MEASUREMENT OF THE 30"X48" CLEAR FLOOR SPACE REQUIRED | | FOR THE LAV. SECTION 11-4.19.3. | | | | 7. SUBMIT A SECOND FLOOR PLUMBING PLAN SHOWING THE | | LOCATION OF ALL FIXTURES, SANITARY PIPING, VENTS, WATER | | LINES ETC. SECTION 106.3.5.1.3(1)(2)(3)(4)(5)(6)(10). | | | | 8. SUBMIT MANUFACTURE SPECIFICATION SHEETS FOR THE | | EEMAX INSTA-HOT WATER HEATER. SPECIFICATION SHEETS | | SHALL SHOW THE LISTING FOR THE WATER HEATER. | | | | 9. THE ENERGY CALCULATIONS SHALL REFLECT THE WATER | | HEATER SPECIFIED, (INSTA-HOT MODEL). THE CALCULATIONS | | INDICATE A 20 GAL WATER HEATER. THESE DO NOT CORRELATE. | | SECTION 13-103. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2009-04-01 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2009-04-01 |
Time |
09:34 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2009-04-01 |
Time |
09:34 |
Sent To |
|
|
Notes |
2009-04-01 09:34:59 | ZONING REVIEW: PASSED | | | | * SIDEWALK AND LANDSCAPE MODIFICATIONS PER ON-SITE | | CHANGES | | | | MATT FLIS - 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2008-05-19 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2008-05-19 |
Time |
09:38 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2008-05-19 |
Time |
09:38 |
Sent To |
|
|
Notes |
2008-05-19 09:38:52 | ZONING REVIEW: PASSED WITH PROVISO | | | | ** ACCORDING TO SUBMITTED SITE PLAN, DRIVEWAY ENTRANCE | | AT STREET WILL NEED TO BE RECONSTRUCTED TO MATCH NEW | | DRIVE WIDTH | | | | MATT FLIS - 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2008-02-07 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2008-02-07 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2008-02-07 |
Time |
13:59 |
Sent To |
|
|
Notes |
2008-02-07 14:00:54 | ZONING REVIEW: PASSED WITH PROVISO | | | | ** ACCORDING TO SUBMITTED SITE PLAN, DRIVEWAY ENTRANCE | | AT STREET WILL NEED TO BE RECONSTRUCTED TO MATCH NEW | | DRIVE WIDTH | | | | MATT FLIS - 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-10-23 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2007-10-23 |
Time |
13:32 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2007-10-23 |
Time |
13:32 |
Sent To |
|
|
Notes |
2007-10-23 13:40:05 | ZONING REVIEW: FAILED | | | | ** MEETING TO BE HELD WITH APPLICANT ON 10/24/07 TO | | REVIEW IN MORE DETAIL ZONING COMMENTS** | | COMMENTS BELOW ARE PRELIMINARY PRIOR TO MEETING. | | | | 1) PLEASE REVISE DRIVEWAY AND PARKING ARRANGEMENT. | | DRIVEWAY TO BE REDUCED TO 12'-0" IN WIDTH WITH PARALLEL | | PARKING SPACES A MINIMUM OF 8'-6" WIDE | | 2) ADA SPACE TO BE RELOCATED; MINIMUM WIDTH IS 8'-6" | | WITH 5'-0" ACCESS AISLE | | 3) SIDEWALK SHALL BE PROVIDED FROM SIDE ENTRY TO PUBLIC | | SIDEWALK SO THAT IT IS NOT NECESSARY TO WALK DOWN | | DRIVEWAY OR THROUGH PARKING SPACES | | 4) AT REAR, PLEASE MOVE TRASH ENCLOSURE AREA TO WESTERN | | CORNER OF SITE; STANDARD CITY DETAILS FOR ENCLOSURE | | SHOULD BE PROVIDED; ELEVATIONS SHOULD BE PROVIDED | | 5) LANDSCAPE PLAN DOES NOT MATCH ARCH SITE PLAN OR | | ELEVATIONS; DOOR IS SHOWN ON NORTH ELEVATION, BUT | | CANNOT EXIT OUT INTO LANDSCAPE AREA; PLEASE REVISE | | 6) NORTH ELEVATION SHALL BE REVISED AND TREATED AS A | | "FRONT" ELEVATION WITH APPROPRIATE DETAILS, INCLUDING | | PORCHES, RAILINGS, ETC. WHERE NECESSARY; SEE EAST | | ELEVATION FOR DETAILS TO BE USED. | | 7) "FRONT" DOOR ON NORTH ELEVATION SHOULD BE CONNECTED | | TO PUBLIC SIDEWALK, EITHER DIRECTLY, OR CONNECTING TO | | ITEM (3) ABOVE. | | 8) PLEASE REDUCE PITCH OF ROOF TO 3/12 OR 4/12 TO | | BETTER MATCH SCALE OF BUILDING. | | 9) PLEASE PROVIDE BUILDING SECTION; ARE DORMER WINDOWS | | REAL OR FAKE? IS THERE ANY INTENTION TO USE THIS THIRD | | LEVEL FOR OFFICE OR RESIDENTIAL SPACE? | | | | MATT FLIS - 822-1445 |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |