Plan Review Details - Permit 07080943
Plan Review Stops For Permit 07080943
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2007-10-30 Time   Rev Time 0.00
Received By kconrad Date 2007-10-29 Time 18:40 Sent To I
Notes
2007-10-29 19:02:10PROJECT : 1400CENTREPARK BLVD./SUITE #300/#07080943
  
 PROJECT DETAIL: INTERIOR ALTERATION/LEVEL 2
  
 REVIEW: APPROVED
  
 2004 FLORIDA BUILDING CODE W/2006 REVISIONS
 2004 FLORIDA EXISTING BUILDING CODE/2006 REVS
 CITY OF WEST PALM BEACH ADMINISTRATIVE CODE/2004
  
 COMMENTS:(X) - INDICATES COMPLIANCE.
  
 1)REQUIRE A NOTICE OF COMMENCEMENT AS PER THE
 FOLLOWING:
  
 FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2) PLEASE CONTACT MR. ALEX ORTEGA WITH THE PALM BEACH
 COUNTY HEALTH DEPARTMENT AT 561.355.3023, EXT. 148 FOR
 PROPER NOTIFICATION. AN ASBESTOS SURVEY MAY BE
 REQUIRED:
  
 105.9 ASBESTOS.
 THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT
 FOR THE DEMOLITION OR RENOVATION OF AN EXISTING
 STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT
 WHICH INDICATES THE OWNER?S OR OPERATOR?S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO
 REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH
 STATE AND FEDERAL LAW.
  
 3) TACTILE SIGNAGE SHALL BE PROVIDED AT ALL EXIT STAIR
 DOORS:
  
 1006.3.4 EXIT STAIR DOOR OR TACTILE SIGNAGE.
 TACTILE SIGNAGE STATING ?EXIT? AND COMPLYING WITH
 ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR
 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL
 BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60
 INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER
 LINE OF THE SIGN.
  
 (X) 4) PLEASE SHOW FLOOR PLAN DIMENSIONS AS PER THE
 FOLLOWING:
  
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5).
  
 (X) 5) PLEASE PROVIDE A DETAIL OF THE NEW INTERIOR WALL
 PARTITION TO CEILING BRACING CONNECTION.
  
 (X) 6) PLEASE INDICATE EXISTING FIRE-RATED WALL
 PARTITIONS.
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-13 Cont ID  
Sent By kconrad Date 2007-09-13 Time 17:55 Rev Time 0.00
Received By kconrad Date 2007-09-13 Time 16:00 Sent To I
Notes
2007-09-13 16:50:56PROJECT : 1400CENTREPARK BLVD./SUITE #300/#07080943
  
 PROJECT DETAIL: INTERIOR ALTERATION/LEVEL 2
  
 REVIEW:
  
 2004 FLORIDA BUILDING CODE W/2006 REVISIONS
 2004 FLORIDA EXISTING BUILDING CODE/2006 REVS
 CITY OF WEST PALM BEACH ADMINISTRATIVE CODE/2004
  
 COMMENTS:
  
 1)REQUIRE A NOTICE OF COMMENCEMENT AS PER THE
 FOLLOWING:
  
 FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2) PLEASE CONTACT MR. ALEX ORTEGA WITH THE PALM BEACH
 COUNTY HEALTH DEPARTMENT AT 561.355.3023, EXT. 148 FOR
 PROPER NOTIFICATION. AN ASBESTOS SURVEY MAY BE
 REQUIRED:
  
 105.9 ASBESTOS.
 THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT
 FOR THE DEMOLITION OR RENOVATION OF AN EXISTING
 STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT
 WHICH INDICATES THE OWNER?S OR OPERATOR?S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO
 REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH
 STATE AND FEDERAL LAW.
  
 3) TACTILE SIGNAGE SHALL BE PROVIDED AT ALL EXIT STAIR
 DOORS:
  
 1006.3.4 EXIT STAIR DOOR OR TACTILE SIGNAGE.
 TACTILE SIGNAGE STATING ?EXIT? AND COMPLYING WITH
 ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR
 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL
 BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60
 INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER
 LINE OF THE SIGN.
  
 4) PLEASE SHOW FLOOR PLAN DIMENSIONS AS PER THE
 FOLLOWING:
  
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5).
  
 5) PLEASE PROVIDE A DETAIL OF THE NEW INTERIOR WALL
 PARTITION TO CEILING BRACING CONNECTION.
  
 6) PLEASE INDICATE EXISTING FIRE-RATED WALL
 PARTITIONS.
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-16 Cont ID  
Sent By dpalmer Date 2007-10-16 Time 11:56 Rev Time 0.00
Received By dpalmer Date 2007-10-16 Time 11:55 Sent To  
Notes
2007-10-16 11:56:10**** PROVISO/REVISION NEEDED****
  
  
 1) NOTE:PLANS MISSING LIGHTING POWER DENSITIES FOR
 NEW OFFICES PER 13-415.2
  
 2) NOTE: PLANS MISSING MAXIMUM TIMES FOR OS DEVICES PER
 13-415.1.ABC.1.1(MAX 30MINS)
  
 3) NOTE: PLANS STILL INDICATE THE TELCO ROOM AS
 EXISTING ALONG WITH AN IT PANEL IN WHICH THIS OFFICE
 HAS NO RECORD OF THIS WORK BEING PERMITTED IN OUR
 CURRENT SYSTEM GOING BACK ALMOST 10YEARS.
 THE CONTRACTOR HAS NOW VOIDED PREVIOUS APPLIED FOR
 PERMIT FOR IT ROOM EXPANSION. (# 06101010)
 THE ENGINEER OF RECORD KNOWS OF PREVIOUS WORK APPLIED
 FOR UNDER #06101010.
 THE SERVICE AND WORK SHOWN AS *EXISTING* SHALL BE
 VERIFIED IN FIELD BY INSPECTION SERVICES STAFF. ALL
 INFORMATION WAS FORWARDED TO BOTH ASSISTANT BUILDING
 OFFICIALS TO BE ADDRESSED.
  
 4) NOTE: PLEASE REVISE PLANS AS NEEDED FOR NOTES #1 AND
 2 BEFORE ROUGH ELECTRICAL INSPECTION UNDER THE
 PERMITTED SCOPE OF WORK.
 ANY CORRECTION NOTICES ISSUED IN FIELD FOR OTHER SCOPE
 OF WORK WILL BE ADDRESSED AT THAT TIME.
 ** IF PLANS COME BACK FOR CORRECTIONS FROM ANY OTHER
 TRADES, PLEASE ADDRESS AT THAT TIME, THIS WILL
 ALLEVIATE THE NEED FOR A REVISION AT A LATER DATE
 BEFORE ROUGH.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-11 Cont ID  
Sent By dpalmer Date 2007-09-11 Time 08:44 Rev Time 0.00
Received By dpalmer Date 2007-09-11 Time 08:44 Sent To  
Notes
2007-09-11 08:44:37*** DENIED ***
  
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION AND PLANS AS
 APPLIED ARE SHOWING SEVERAL ITEMS NOW AS EXISTING.
 THESE SAME ITEMS WHICH WERE APPLIED FOR UNDER PERMIT
 06101010 WERE NOT ISSUED FOR PERMIT. THERE WERE STILL
 COMMENTS FROM THE PREVIOUS REVIEWS WHICH WERE NOT
 ADDRESSED.
 A FIELD INSPECTION NOW MAY BE CONDUCTED TO VIEW WORK
 WHICH MAY OR MAY NOT HAVE BEEN COMPLETED.
 THE PREVIOUS DENIED PLANS WERE PICKED UP ON 6/19/07 AND
 ARE STILL AN ACTIVE PERMIT APPLICATION.
 RESEARCH OF PERMITTED WORK IN THIS SPACE GOING BACK 10
 YEARS ON ONE SEARCH ALONE DOES NOT INDICATED ANY OF
 THESE ITEMS AS SHOWN ON ELECTRICAL RISER BEING
 PERMITTED.
 THIS SCOPE OF WORK WILL NOT BE ISSUED.
  
 ** PLEASE KNOW PLANS AND PERMIT APPLICATION MAY BE
 RETAINED BY THIS OFFICE.
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-10-24 Cont ID  
Sent By mwennerg Date 2007-10-24 Time 14:18 Rev Time 0.00
Received By mwennerg Date 2007-10-24 Time 14:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By mawillia Date 2007-09-17 Time 21:17 Rev Time 0.00
Received By mawillia Date 2007-09-17 Time 19:01 Sent To  
Notes
2007-09-18 00:03:37*****UNSAT*****
  
 1.ON THE COVER SHEET-BULLET #5- UNDER PROJECT DATA
 REFERENCES SUITE 500 WHEREAS; ALL OTHER INDICATIONS HAS
 THIS SPACE AS SUITE 300.PLEASE EXPLAIN.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 10:10 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 10:10 Sent To  
Notes
2007-10-16 11:03:44TO "BOB"#7
2007-10-11 10:11:01WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-17 Cont ID  
Sent By mawillia Date 2007-09-17 Time 21:18 Rev Time 0.00
Received By mawillia Date 2007-09-04 Time 10:49 Sent To  
Notes
2007-09-10 13:51:56TO "BOB"#12
2007-09-04 10:49:36WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-10-19 Cont ID  
Sent By tgordon Date 2007-10-19 Time 13:57 Rev Time 0.30
Received By tgordon Date 2007-10-19 Time 13:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-12 Cont ID  
Sent By tgordon Date 2007-09-12 Time 10:50 Rev Time 0.20
Received By tgordon Date 2007-09-12 Time 10:50 Sent To P
Notes
2007-09-12 11:03:29PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) A SITE INSPECTION MAY BE REQUIRED TO VERIFY NO
 CHANGES WERE MADE WHILE APPLYING FOR PERMIT #06101010.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-09-13 Cont ID  
Sent By choops Date 2007-09-13 Time 08:21 Rev Time 0.00
Received By choops Date 2007-09-13 Time 08:21 Sent To  
Notes
2007-09-13 08:22:01*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.