Plan Review Details - Permit 07080934
Plan Review Stops For Permit 07080934
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2008-02-20 Cont ID  
Sent By mawillia Date 2008-02-20 Time 15:02 Rev Time 0.00
Received By lursu Date 2008-02-20 Time 14:46 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-12-12 Cont ID  
Sent By lursu Date 2007-12-12 Time 11:41 Rev Time 0.00
Received By lursu Date 2007-12-12 Time 11:41 Sent To  
Notes
2007-12-12 11:42:29PERMIT ASSIGNED TO THE NEW UNIT ADDRESS 115 FOR THE NEW
 RESTAURANT .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-09-26 Cont ID  
Sent By lursu Date 2007-09-26 Time 13:19 Rev Time 0.00
Received By lursu Date 2007-09-26 Time 13:19 Sent To  
Notes
2007-09-26 13:25:23PLEASE CLARIFY THE EXACT JOB LOCATION AND ALSO IF THIS
 IS A NEW UNIT .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-21 Cont ID  
Sent By jwitmer Date 2008-02-21 Time 08:32 Rev Time 0.88
Received By jwitmer Date 2008-02-21 Time 08:32 Sent To PC
Notes
2008-02-21 08:33:24REVISION# 2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-28 Cont ID  
Sent By mawillia Date 2007-12-28 Time 15:01 Rev Time 0.55
Received By mawillia Date 2007-12-28 Time 15:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-15 Cont ID  
Sent By jwitmer Date 2007-10-15 Time 07:37 Rev Time 0.77
Received By jwitmer Date 2007-10-15 Time 07:36 Sent To  
Notes
2007-10-15 08:02:07BUILDING PLAN REVIEW
 PERMIT: 07080934
 ADD: 101 N CLEMATIS ST SUITE NO. ______
 CONT: FISHERCONTRACTING
 TEL: (561)758-6545
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS.
  
 2) PLEASE CORRECT THE PERMIT APPLICATION DESCRIPTION OF
 WORK TO INCLUDE A TENANT BUILDOUT. SEE ELECTRICAL,
 MECHANICAL AND PLUMBING SHEETS INCLUDE MORE THAN JUST
 THE ADDITION OF A TENANT SEPERATION WALL.
  
 3)SHEET E0.1 TRANSFORMER MOUNTINGDETAIL, 106.1.2
 ADDITIONAL INFORMATION REQUIRED, PLEASE PROVIDE THE
 WEIGHT OF THE TRANSFORMER, TYPE OF FLOOR SLAB,
 THICKNESS OF FLOOR SLAB,
 TYPE OF HILTI HDI FASTENER TO BE USED AND SAFETY FACTOR
 THAT WAS FIGURED.
  
 4) SHEET 3.1 CODE SUMMARY 2.2CORRECT THE TYPE OF
 CONSTRUCTION TO THE 2004 FBC SEE TABLE 503.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-06 Cont ID  
Sent By dpalmer Date 2007-12-05 Time 14:37 Rev Time 0.00
Received By dpalmer Date 2007-12-05 Time 14:37 Sent To  
Notes
2008-01-02 12:04:032008-01-01
  
  
 CHANGED TO A *P* AS ADDRESS OF SUITE 115 WAS
 DETERMINED. CHANGED ON TITLE BLOCKS ON BOTH SETS.
2007-12-06 15:55:52PASSED RESULT HAS CHANGED TO A FAILED STATUS.
 ELECTRICAL PLANS ARE OK, HOWEVER ADDRESS IS AN ISSUE
 AND WILL BECOME FAILED BY THE ADDRESSING REVIEWER. ONCE
 THE CORRECT ADDRESS FOR SUITE/UNIT NUMBER HAS BEEN
 DETERMINED AND SIGNED OFF BY ADDRESSING THE SUITE/UNIT
 # MAY BE ADDED TO TITLE BLOCKS. THERE IS NO NEED TO
 REPRINT ELECTRICAL SHEETS FOR THIS.
 PLEASE KNOW THERE ARE MULTIPLE PROJECTS IN THIS SAME
 BUILDING WHICH IS APPLYING AS SUITE 100.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-23 Cont ID  
Sent By dpalmer Date 2007-09-23 Time 10:30 Rev Time 0.00
Received By dpalmer Date 2007-09-23 Time 09:48 Sent To  
Notes
2007-09-23 10:30:582007-09-23 10:30:58
  
 ** DENIED**
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THE ADDRESS FOR UNIT/SUITE SHALL BE
 STATED ON PERMIT APPLICATION AND TITLE BLOCKS FOR
 PLANS.
 A COPY OF PERMIT APPLICATION WAS ROUTED TO ADDRESSING
 REVIEWER. PLEASE BE AWARE OF ANY DESIGNATIONS WHICH MAY
 BE ASSIGNED.
  
 3) NOTE: PLEASE CLARIFY THE PANEL HL, IS THIS A *HOUSE
 PANEL*? PLEASE ALSO BE SURE TO CONTACT CITY ENGINEERING
 DEPARTMENT FOR ANY LIGHTING WHICH ACTUALLY MAY BE
 LOCATED IN THE *RIGHT OF WAY*. THIS MAY NOT BE
 PERMITTED AND ONLY LIGHTING LOCATED ON THE LEGAL
 PROPERTY MAY BE FED FROM BUILDING ELECTRICAL SERVICE.
 RIGHT OF WAY LIGHTING IS TYPICALLY FED FROM THE CITY
 POWER LOCATED IN RIGHT OF WAYS.
  
 4) NOTE: PLEASE SEE THE LIGHTING IN THE NEW *FUTURE
 RETAIL* IS BEING SHOWN ON CIRCUITS TO PANEL *HB*> THIS
 IS A 277/480V PANEL FOR TRACK LIGHTING.
 PLEASE SEE PANEL *HB* DOES NOT CONTAIN ANY LIGHTING
 CIRCUITS AND THE CIRCUITS AS REFERENCED ARE INDICATING
 OTHER CIRCUITS.
 THIS APPEARS THAT THESE SHOULD HAVE BEEN TO PANEL
 *LB*??
 PLEASE ADJUST AND COORDINATE CIRCUITS WITH PANEL
 SCHEDULE.
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SEE THE RISER INDICATES THE TRANSFORMER
 IN THE RETAIL SPACE AS *THB* ALONG WITH THE TRANSFORMER
 LEGEND HOWEVER PLEASE SEE PANEL *HB* AS THIS PANEL
 INDICATES A TRANSFORMER *T1B*.
 PLEASE CORRELATE AND ADJUST. PLEASE ALSO SEE NEXT
 COMMENT.
  
 6) NOTE: PLEASE SEE THE TRANSFORMER WHICH IS BEING
 SHOWN AS 45KVA UNIT IS BEING SHOWN WITH 110AMP OVER
 CURRENT PROTECTION IN PANEL *HB* WHICH IS NOT
 PERMITTED. PLEASE SEE 450.3 AS THE OCP IS TO BE A
 MAXIMUM OF 125%.(UNLESS MEETING EXCEPTION WHICH THIS
 TRANSFORMER DOES NOT INDICATE).
 PLEASE CORRELATE AND ADJUST.
 THIS COMMENT IS BEING *ASSUMED* AS THE TRANSFORMER AS
 LISTED ON PANEL *HB* DOES NOT HAVE THE SAME
 DESIGNATIONS AS SHOWN ON RISER AND TRANSFORMER LEGEND.
 FBC 106.1.2.
  
 7) NOTE: PLEASE CLARIFY WHERE CONTINUOUS LOADS ARE
 SHOWN.
 215.3, 230.42, 220 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 8) NOTE: PLEASE CLARIFY THE USE OF AN *E-MON* METER. IF
 THIS IS GOING TO BE A NEW RETAIL TENANT SPACE, WOULD
 NOT A METER FROM FPL BE INSTALLED?
 PLEASE KNOW THE PLANS WILL BE ROUTED TO ZONING FOR
 DIVISION OF SPACES AND TENANTS.
 PLEASE CONTACT THE FPL SERVICE REPRESENTATIVE. PLEASE
 BE SURE TO INDICATE ANY *FLOATING NEUTRAL* KITS WHICH
 ARE TO BE INSTALLED AFTER THE FIRST MEANS OF DISCONNECT
 PER 250.6, 250.24.
  
 9) NOTE: PLEASE SEE THAT LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW LIGHTING BEING ADDED TO EXISTING
 PER 13-415.2.ABC.1.2, 13-415.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-23 09:48:002007-09-23 09:48:00
  
 PLANS REMOVED FROM INCOMING WILL BE RETURNED TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICLA REVIEW
 IS COMPLETED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-02-20 Cont ID  
Sent By mawillia Date 2008-02-20 Time 12:28 Rev Time 0.00
Received By mawillia Date 2008-02-20 Time 11:18 Sent To B
Notes
2008-02-20 12:28:49*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEET 3.1 STAMPED, INITIALED, AND DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-31 Cont ID  
Sent By mawillia Date 2007-12-31 Time 10:18 Rev Time 0.00
Received By mawillia Date 2007-12-31 Time 09:42 Sent To B
Notes
2007-12-31 10:18:33*****APPROVED*****
  
  
 PLAN SHEETS 3.1 AND E2.1 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-10-22 Cont ID  
Sent By mcarsill Date 2007-10-22 Time 15:46 Rev Time 0.00
Received By mcarsill Date 2007-10-22 Time 15:38 Sent To  
Notes
2007-10-22 15:46:211. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY
 WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 3. CONSTRUCTION RELATED WORK SHALL NOT INTERERE WITH
 ANY EXITING.
  
 4. SEPERATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM REMODEL.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER SYSTEM REMODEL CAUSED BY THE INSTALLATION OF
 THE NEW DEMISING WALL.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-20 Cont ID  
Sent By adarroug Date 2008-02-20 Time 08:21 Rev Time 0.00
Received By adarroug Date 2008-02-20 Time 08:21 Sent To FIRE
Notes
2008-02-20 11:05:23TO "MAW" DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-03 Cont ID  
Sent By adarroug Date 2007-12-03 Time 14:15 Rev Time 0.00
Received By adarroug Date 2007-12-03 Time 14:15 Sent To  
Notes
2007-12-04 11:07:14TO "COMM" BD#55
2007-12-03 14:16:11WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-02 Cont ID  
Sent By kstevens Date 2007-11-02 Time 08:40 Rev Time 0.00
Received By kstevens Date 2007-09-05 Time 11:10 Sent To  
Notes
2007-09-24 08:39:08TO "COMM" BD#23
2007-09-05 11:11:01WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-22 Cont ID  
Sent By rregueir Date 2007-12-22 Time 08:34 Rev Time 0.00
Received By rregueir Date 2007-12-22 Time 08:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-10-11 Cont ID  
Sent By hmoser Date 2007-10-11 Time 17:58 Rev Time 0.00
Received By hmoser Date 2007-10-11 Time 17:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-01-03 Cont ID  
Sent By mperson Date 2008-01-03 Time 14:14 Rev Time 0.00
Received By mperson Date 2008-01-03 Time 14:14 Sent To  
Notes
2008-01-03 14:17:45NOTE: CHANGED TO *P* AS ADDRESS OF SUITE 115 WAS
 DETERMINED. CHANGED ON TITLE BLOCKS ON BOTH SETS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-17 Cont ID  
Sent By kstevens Date 2007-12-17 Time 18:22 Rev Time 0.00
Received By kstevens Date 2007-12-17 Time 18:22 Sent To  
Notes
2007-12-17 18:24:50PLUMBING PLANS OK - THE ADDRESS FOR THE RESTAURANT IS
 115 NOT 100. SEE ADDRESSING REVIEW. PLEASE CHANGE
 UNIT/SPACE/SUITE NUMBER IN THE TITLE BLOCKS THEN
 PLUMBING STATUS WILL BE CHANGED FROM FAILED TO PASSED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-02 Cont ID  
Sent By kstevens Date 2007-11-02 Time 08:17 Rev Time 0.00
Received By kstevens Date 2007-11-02 Time 08:17 Sent To  
Notes
2007-11-02 08:40:36DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 1. THE ADDRESS SHALL INCLUDE THE UNIT/SUITE NUMBER AND
 SHALL BE INDICATED ON THE APPLICATION AND THE TITLE
 BLOCK OF EACH SHEET. SECTION 106.1.1.
  
 2. SHT P3.1 INDICATES THE WATER SUPPLY TO CONNECT
 BETWEEN THE METER AND THE BACKFLOW PREVENTOR. EACH UNIT
 SHOULD BE SEPARATELY METERED AND BY METERING ALL WATER
 FOR BOTH SPACES THROUGH THE EXISTING METER THERE MAY BE
 A CONFLICT WHERE THE RESTAURANT SPACE COULD BE CHARGED
 FOR THE WATER FOR BOTH SPACES. THE MERCANTILE SPACE
 COULD THEN POSSIBLY BE CHARGED AGAIN FOR ITS WATER USE.
 THE WATER CONNECTION SHOULD MADE UPSTREAM OF THE METER
 FOR THE RESTAURANT SPACE. MUNICIPAL CODE ARTICLE III
 SECTION 90-31(E).
  
 3. A SEPARATE RPZV BACKFLOW MAY BE REQUIRED FOR THE NEW
 MERCANTILE UNIT. SECTION 608.13.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-10-02 Cont ID  
Sent By mflis Date 2007-10-02 Time 08:30 Rev Time 0.00
Received By mflis Date 2007-10-02 Time 08:30 Sent To  
Notes
2007-10-02 08:30:58ZONING REVIEW: NOT REQUIRED
  
 * INTERIOR REMODEL WORK ONLY
  
 MATT FLIS - 822-1445