Plan Review Details - Permit 07080644
Plan Review Stops For Permit 07080644
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-27 Cont ID  
Sent By shill Date 2007-08-27 Time 17:11 Rev Time 0.00
Received By shill Date 2007-08-27 Time 17:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-22 Cont ID  
Sent By shill Date 2007-08-22 Time 08:50 Rev Time 0.00
Received By shill Date 2007-08-22 Time 08:50 Sent To  
Notes
2007-08-22 08:54:49****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)THE LETTER FOR ENHANCED FASTENING STATES THAT YOU
 ARE USING A SYSTEM 9"OC LAPS, 12" OC FIELD.THE
 ASSEMBLY HIGHLIGHTED RQUIRES 9" SPACING IN THE FIELD
 ROWS.PLEASE REVISE EITHER THE LETTER OR SELECT THE
 APPROPRIATE ASSEMBLY.
  
  