2007-09-11 11:22:20 | DENIED |
| REFERENCE: |
| ** FBC-2004 FUEL GAS WITH 2006 REVISIONS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| 1. THE GAS PERMIT CAN NOT BE ISSUED DUE TO THE FACT |
| THAT THE GENERATOR PERMIT NUMBER 06081399 HAS EXPIRED. |
| THERE HAVE BEEN NO INSPECTIONS FOR THIS GENERATOR. THE |
| CONTRACTOR FOR THIS EXPIRED PERMIT IS HARDWIRE ELECTRIC |
| INC. PHONE NUMBER (772) 460-9455. PLEASE REFERENCE THE |
| ATTACHED PERMIT INFORMATION INDICATING THIS EXPIRED |
| PERMIT STATIS. PLEASE KNOW THAT THE FOLLOWING WILL BE |
| REQUIRED FOR THE GAS AND GENERATOR RESUBMITTAL. IT IS |
| IMPORTANT THAT THEY ARE RESUBMITTED TOGETHER. |
| |
| ******IMPORTANT INFORMATION****** |
| AS OF 8/25/06 GENERATOR (GEN/RES AND |
| GEN/COM) PERMIT APPLICATIONS SHALL NOT |
| BE ACCEPTED UNLESS THE ELECTRICAL INFOR- |
| MATION AND GAS (OR DIESEL) INFORMATION |
| IS ALL SUBMITTED AT THE SAME TIME. THE |
| GENERATOR, ELECTRICAL AND GAS/DIESEL IN- |
| FORMATION WILL BE ROUTED TOGETHER. THIS |
| WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY |
| THE MANUFACTURER'S SPECI- |
| FICATIONS AND INSTALLATION INSTRUCTIONS) |
| ARE AVAILABLE TO ALL PLAN REVIEWERS. |
| |
| 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| NOTE: NEED MANUFACTURER SPECIFICATION SHEETS OF THE |
| GENERATOR AND THE MP REGULATORS (2 PSI TO 0.5 PSI |
| REGULATORS) INDICATING THE MAKE, MODEL NUMBER, LOAD |
| CAPCITY AND A LISTING FROM A NATIONALLY RECOGNIZED |
| TESTING LABORATORY (NRTL). |
| |
| 3. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR |
| VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| IMMEDIATELY AHEAD OF EACH MP REGULATOR. |
| NOTE: PLEASE CLEARLY INDICATE THE MP REGULATOR AND SHUT |
| OFF VALVE ON THE RESUBMITTED GAS RISER DIAGRAM. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |