Plan Review Details - Permit 07080606
Plan Review Stops For Permit 07080606
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2009-08-07 Cont ID  
Sent By jnguyen Date 2009-08-07 Time 11:29 Rev Time 0.00
Received By jnguyen Date 2009-08-06 Time 16:00 Sent To  
Notes
2009-08-07 11:07:51I CHECKED OUT THE SITE ON MY WAY TO WORK THIS MORNING.
 I CONFIRMED THAT THIS PERMIT WAS INDEED REFERENCING
 BUILDING U ON PCN# 74434316240000210 AT 2055 SPRUCE AVE
 (NOT BUILDING T ON PCN# 74434316240000200 AT 2037
 SPRUCE AVE). AFTER JAMES & I ANALYZED THE SITE PLANS, I
 CALLED THE ARCHITECT, RAFAEL RODRIGUEZ OF RAR
 ARCHITECT, INC. FOR FURTHER CLARIFICATION. HE INFORMED
 ME THAT THERE WAS NO ACCESS FROM WITHIN THE PROPOSED
 RESTAURANT DOWNSTAIRS TO THE RESIDENTIAL RENTAL UNIT
 UPSTAIRS (IT HAD A SEPARATE ENTRANCE DOOR OUTSIDE ON
 THE REAR PART OF BUILDING U.). HE ALSO ACKNOWLEDGED TO
 ME THAT THE RESTAURANT HAD ANOTHER DOOR IN THE REAR
 TOO, BUT ITS FRONT MAIN ENTRANCE DOOR FACED SPRUCE AVE.
 DESPITE THE FACTS THAT ACCESS TO PARKING OCCURED OFF
 20TH ST & THE RENTAL UNIT'S ENTRANCE WAS IN THE REAR, I
 ISSUED THE SECONDARY ADDRESS OF 2057 SPRUCE AVE FOR THE
 UPSTAIRS RENTAL UNIT BECAUSE THE FRONTAGES OF BOTH THE
 RESTAURANT & RESIDENCE FACED SPRUCE AVE. ALSO, I WANTED
 TO AVOID ANY POTENTIAL CONFUSION FOR THIS PARTICULAR
 BUILDING HAVING MULTIPLE NUMERICAL ADDRESSES OFF OF TWO
 DIFFERENT STREETS (SPRUCE AVE & 20TH ST). I CREATED THE
 GIS SPATIAL POINT FOR 2057 SPRUCE AVE & EXPORTED IT AS
 A SHAPEFILE IN MY E-MAIL NOTIFICATION TO ALL OF THE
 RELEVANT PARTIES (INCLUDING PAPA). IN COMMUNITYPLUS
 UNDER PCN# 74434316240000210, I FORMULATED SEQUENTIAL
 UNIT RECORD 0001 - 2057 SPRUCE AVE. I ALSO CORRECTED
 THE PCN# ON THE ORIGINAL PERMIT APPLICATION FROM
 74434316240000200 TO 74434316240000210, AND ADDED THE
 SECONDARY ADDRESS OF 2057 SPRUCE AVE (RENTAL UNIT) TO
 THE PRIMARY ONE OF 2055 SPRUCE AVE (RESTAURANT).
  
 JOHN NGUYEN
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE: (561) 822-1239
 FAX: (561) 822-1249
 [email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2008-08-05 Cont ID  
Sent By lursu Date 2008-08-05 Time 08:10 Rev Time 0.00
Received By lursu Date 2008-08-05 Time 08:10 Sent To  
Notes
2008-08-05 08:22:51THE ENTIRE BUILDING T WAS ASSIGNED WITH A UNIQUE
 ADDRESS AS 2037 SPRUCE AVE , HOWEVER EACH UNIT INSIDE
 THE STRUCTURE MUST HAVE A UNIQUE ADDRESS NUMBER ,AS
 EXPLAINED BELOW:
  
 IF EACH UNIT HAS A SEPARATE STREET ENTRANCE THAN A
 UNIQUE ADDRESS NUMBER (SEE SECTION 1, PARAGRAPH 1.2 -
 ADDRESSING GUIDE POLICY ) IS REQUIRED .
 IF THE UNIT HAS A COMMON ENTRANCE AS THE REST OF THE
 UNITS THAN EACH UNIT SHOULD BE ASSIGNED WITH A UNIT
 DESIGNATOR; EXAMPLES OF ASSIGNING UNITS ARE:
 - FIRST FLOOR - UNITS FROM 101 TO 199 ; 2037 SPRUCE AVE
 # 101 - INDICATES THE FIRST UNIT ON THE FIRST FLOOR
 - SECOND FLOOR - UNIT FROM 201 TO 299 ; 2037 SPRUCE AVE
 # 201 - INDICATES THE FIRST UNIT ON THE SECOND FLOOR
  
 QUESTIONS/COMMENTS:
  
 LACRAMIOARA URSU, MA ,GISP
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-07-20 Cont ID  
Sent By jwitmer Date 2009-07-20 Time 15:54 Rev Time 0.99
Received By jwitmer Date 2009-07-20 Time 15:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-07-20 Cont ID  
Sent By jwitmer Date 2009-07-20 Time 16:22 Rev Time 0.55
Received By jwitmer Date 2009-07-20 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2009-03-04 Cont ID  
Sent By mjacobs Date 2009-02-04 Time 08:47 Rev Time 0.00
Received By mjacobs Date 2009-02-04 Time 08:47 Sent To  
Notes
2009-03-04 08:47:30PER ROBERT BROWN: THIS PERMIT CAN REMAIN OPEN DUE TO
 THE FACT THAT PERMIT #06011130 WHICH IS THE SHELL
 BUILDING PERMIT HAD CONTINUOUS ACTIVITY WITHIN THE PAST
 SIX MONTHS; IN FACT THE CERTIFICATE OF OCCUPANCY WAS
 ISSUED ON 2/18/09 BY CHUCK JORDAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-08-21 Cont ID  
Sent By mjacobs Date 2008-08-21 Time 15:16 Rev Time 0.00
Received By mjacobs Date 2008-08-21 Time 12:11 Sent To PC
Notes
2008-08-21 15:11:10 
  
 3RD RREVIEW
 BUILDING PLAN REVIEW
 PERMIT: 07080606
 ADD: 2037 SPRUCE AVE
 CONT: JHAMTEC CONSTRUCTION
 TEL: (561)602-0009
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD AUGUST 21, 2008
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) OK
  
 DUE TO THE FACT THAT PERMIT #06011130 IS AN EXPIRED
 PERMIT AND THE BUILDING DOES NOT HAVE A CERTIFICATE OF
 OCCUPANCY OR FINAL INSPECTION THE SHALL MEET THE
 REQUIREMENTS OF THE SECTION BELOW.
 NOTE: THE REVISION #1 TO THE DOOR ON SHEET A-1 DOES NOT
 COMPLY WITH FIGURE 24. A 2'-8" X 6'- 8" DOOR WILL NOT
 MEET THE 32" MINIMUM REQUIREMENT. THE DISTANCE SHALL BE
 MEASURED FROM THE INSIDE FACE OF THE DOOR TO THE FACE
 OF THE DOOR STOP. PLEASE TAKE A LOOK AT THE DRAWING
 SUBMITTED ON SHEET A-1. SEE CODE SECTION MENTION BELOW.
 ACCESSIBLE PARKING SPACES SERVING BUILDINGS SHALL BE
 LOCATED ON THE SHORTEST ROUTE.
 4) 11-4.1.6(2) DUTY TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 % OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA.
 (A)(I) OK
 (II) AN ACCESSIBLE ROUTE
 (III) OK
 (IIII) OK
  
 FRONT ENTRY DOOR, A PAIR OF 5'-0" DOORS, SEE11-4.13.5
 CLEAR WIDTH. DOORWAYS SHALL HAVE A MINIMUM CLEAR
 OPENING OF 32 INCHES WITH THE DOOR OPEN 90 DEGREES,
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE
 STOP [SEE FIGURE 24 (A), FIGURE 24 (B), FIGURE 24 (C),
 AND FIGURE 24 (D)]. OPENINGS MORE THAN 24 INCHES (610
 MM) IN DEPTH SHALL COMPLY WITH SECTIONS 11-4.2.1 AND
 11-4.3.3 [SEE FIGURE 24 (E)].
  
 5) OK
  
 6) OK
 7) OK
  
 **NOTE: ACCESSIBLE PARKING SHALL BE LOCATED ON THE
 SHORTEST ROUTE TO THE ENTRANCE OF THE BUILDING. THE
 PARKING LOT DOES NOT HAVE A FINAL INSPECTION THEREFORE,
 THE ISSUE OF THE ACCESSIBLE PARKING HAS TO BE
 ADDRESSED**
 8) THE SITE PLAN DOES NOT INDICATE ANY ACCESSIBLE
 PARKING PLEASE INDICATE THE HANDICAPPED PARKING AND
 ACCESS ISLE. 11-4.6.2 LOCATION. ACCESSIBLE PARKING
 SPACES SERVING A PARTICULAR BUILDING SHALL BE LOCATED
 ON THE SHORTEST SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM
 ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE. IN PARKING
 FACILITIES THAT DO NOT SERVE A PARTICULAR BUILDING,
 ACCESSIBLE PARKING SHALL BE LOCATED ON THE SHORTEST
 ACCESSIBLE ROUTE OF TRAVEL TO AN ACCESSIBLE PEDESTRIAN
 ENTRANCE OF THE PARKING FACILITY.
  
 **3RD REQUEST**
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-04 Cont ID  
Sent By mjacobs Date 2008-04-04 Time 14:51 Rev Time 0.00
Received By mjacobs Date 2008-04-02 Time 14:50 Sent To  
Notes
2008-04-04 14:50:592ND RREVIEW
 BUILDING PLAN REVIEW
 PERMIT: 07080606
 ADD: 2037 SPRUCE AVE
 CONT: JHAMTEC CONSTRUCTION
 TEL: (561)602-0009
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND APRIL 2, 2008
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLYOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) OK
  
 NOTE: THE REVISION #1 TO THE DOOR ON SHEET A-1 DOES NOT
 COMPLY WITH FIGURE 24. A 2'-8" X 6'- 8"DOOR WILL NOT
 MEET THE 32" MINIMUM REQUIREMENT. THE DISTANCE SHALL BE
 MEASURED FROM THE INSIDE FACE OF THE DOOR TO THE FACE
 OF THE DOOR STOP. PLEASE TAKE A LOOK AT THE DRAWING
 SUBMITTED ON SHEET A-1. SEE CODE SECTION MENTION BELOW.
 ACCESSIBLE PARKING SPACES SERVING BUILDINGS SHALL BE
 LOCATED ON THE SHORTEST ROUTE.
 4) 11-4.1.6(2) DUTY TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 % OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA.
 (A)(I) OK
 (II) AN ACCESSIBLE ROUTE
 (III) OK
 (IIII) OK
  
 FRONT ENTRY DOOR, A PAIR OF 5'-0" DOORS, SEE11-4.13.5
 CLEAR WIDTH. DOORWAYS SHALL HAVE A MINIMUM CLEAR
 OPENING OF 32 INCHES WITH THE DOOR OPEN 90 DEGREES,
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE
 STOP [SEE FIGURE 24 (A), FIGURE 24 (B), FIGURE 24 (C),
 AND FIGURE 24 (D)]. OPENINGS MORE THAN 24 INCHES (610
 MM) IN DEPTH SHALL COMPLY WITH SECTIONS 11-4.2.1 AND
 11-4.3.3 [SEE FIGURE 24 (E)].
  
 5) OK
  
 **NOTE: THE UL NUMBER FOR THE FLOOR CEILING ASSEMBLY
 FOR THE BASE BUILDING IS L557, SO PLEASE INDICATE THIS
 NUMBER ON THE DRAWINGS.
 6) PLEASE PROVIDE A DETAIL INDICATING THE FIRE RATING
 AT CEILING BETWEEN THIS MERCANTILE TENANT AND THE R-3
 RESIDENCE LOCATED ON THE SECOND FLOOR? ALSO PROVIDE
 WHAT TYPE OF FIRE STOPPING MATERIALS WILL BE USED
 AROUND ANY PIPES THAT PENETRATE THE CEILING FLOOR
 ASSEMBLY SYSTEM? 106.1.2*
  
 7) OK
  
 **NOTE: ACCESSIBLE PARKING SHALL BE LOCATED ON THE
 SHORTEST ROUTE TO THE ENTRANCE OF THE BUILDING.**8)
 THE SITE PLAN DOES NOT INDICATE ANY ACCESSIBLE PARKING
 PLEASE INDICATE THE HANDICAPPED PARKING AND ACCESS
 ISLE. 11-4.6.2 LOCATION. ACCESSIBLE PARKING SPACES
 SERVING A PARTICULAR BUILDING SHALL BE LOCATED ON THE
 SHORTEST SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM
 ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE. IN PARKING
 FACILITIES THAT DO NOT SERVE A PARTICULAR BUILDING,
 ACCESSIBLE PARKING SHALL BE LOCATED ON THE SHORTEST
 ACCESSIBLE ROUTE OF TRAVEL TO AN ACCESSIBLE PEDESTRIAN
 ENTRANCE OF THE PARKING FACILITY.
  
 **2ND REQUEST**
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-18 Cont ID  
Sent By jwitmer Date 2007-09-18 Time 20:15 Rev Time 2.00
Received By jwitmer Date 2007-09-18 Time 20:08 Sent To  
Notes
2007-09-18 21:12:392037 SPRUCE AVE
 SEPT 18, 2007
 BUILDING PLAN REVIEW
 PERMIT: 07080606
 ADD: 2037 SPRUCE AVE
 CONT: JHAMTREE CONSTRUCTION
 TEL: (561)602-0009
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION O FTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 IS THIS A FIRST OCCUPANCY FOR THIS SPACE?
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
  
 4) 11-4.1.6(2) DUTY TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 % OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX
 OR A SINGLE UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STORAGE OR ALARMS.
  
 FRONT ENTRY DOOR, A PAIR OF 5'-0" DOORS, SEE11-4.13.5
 CLEAR WIDTH. DOORWAYS SHALL HAVE A MINIMUM CLEAR
 OPENING OF 32 INCHES (813 MM) WITH THE DOOR OPEN 90
 DEGREES, MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 OPPOSITE STOP [SEE FIGURE 24 (A), FIGURE 24 (B), FIGURE
 24 (C), AND FIGURE 24 (D)]. OPENINGS MORE THAN 24
 INCHES (610 MM) IN DEPTH SHALL COMPLY WITH SECTIONS
 11-4.2.1 AND 11-4.3.3 [SEE FIGURE 24 (E)].
  
 5) RESTROOM WALL FINISHES:1210.2 WALLS. WALLS WITHIN 2
 FEET (610 MM) OF URINALS AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF 4
 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 6) PLEASE PROVIE A DETAIL INDICATING THE FIRE RATING AT
 CEILING BETWEEN THIS MERCANTILE TENANT AND THE R-3
 RESIDENCE LOCATED ON THE SECOND FLOOR? ALSO PROVIDE
 WHAT TYPE OF FIRE STOPPING MATERIALS WILL BE USED
 AROUND ANY PIPES THAT PENETRATE THE CEILING FLOOR
 ASSEMBLY SYSTEM? 106.1.2*
  
 7) 11-5.2 COUNTERS AND BARS. WHERE FOOD OR DRINK IS
 SERVED AT COUNTERS EXCEEDING 34 INCHES (865 MM) IN
 HEIGHT FOR CONSUMPTION BY CUSTOMERS SEATED ON STOOLS OR
 STANDING AT THE COUNTER, A PORTION OF THE MAIN COUNTER
 WHICH IS 60 INCHES (1525 MM) IN LENGTH MINIMUM SHALL BE
 PROVIDED IN COMPLIANCE WITH SECTION 11-4.32 OR SERVICE
 SHALL BE AVAILABLE AT ACCESSIBLE TABLES WITHIN THE SAME
 AREA.
  
 8) THE SITE PLAN DOES NOT INDICATE ANY ACCESSIBLE
 PARKING PLEASE INDICATE THE HANDICAPPED PARKING AND
 ACCESS ISLE. 11-4.6.2 LOCATION.
 ACCESSIBLE PARKING SPACES SERVING A PARTICULAR BUILDING
 SHALL BE LOCATED ON THE SHORTEST SAFELY ACCESSIBLE
 ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE
 ENTRANCE. IN PARKING FACILITIES THAT DO NOT SERVE A
 PARTICULAR BUILDING, ACCESSIBLE PARKING SHALL BE
 LOCATED ON THE SHORTEST ACCESSIBLE ROUTE OF TRAVEL TO
 AN ACCESSIBLE PEDESTRIAN ENTRANCE OF THE PARKING
 FACILITY.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-08-13 Cont ID  
Sent By dpalmer Date 2009-07-31 Time 14:13 Rev Time 0.00
Received By dpalmer Date 2009-07-31 Time 14:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-07-31 Cont ID  
Sent By dpalmer Date 2008-07-31 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2008-07-31 Time 14:39 Sent To  
Notes
2008-07-31 14:39:27** DENIED3RD REVIEW **
  
 ** THERE ARE STILL COMMENTS FROM PREVIOUS REVIEW ALONG
 WITH SEVERAL NEW COMMENTS BASED ON NEW INFORMATION NOW
 BEING PROVIDED.
  
  
  
 1) NOTE: PLEASE KNOW THE BASE BUILDING PERMIT #06011130
 WHICH WAS PREVIOUSLY FOR THE SHELL BUILDING HAS BEEN
 EXPIRED DUE TO INACTIVITY UNDER THE FBC 105.3.2 BY
 HAROLD PISKURA
 PERMIT FOR BASE BUILDING NEEDS TO BE RE-APPLIED FOR
 FINALS.
 PLEASE ALSO KNOW AS THE BASE BUILDING DESIGN TEAM IS
 RESPONSIBLE FOR SUCH BUILDING UNTIL SUCH TIME AS
 CERTIFICATE OF COMPLETION OR CERTIFICATE OF OCCUPANCY
 IS ISSUED ALL PLANS FOR PERMITTED WORK WHILE A SHELL
 BUILDING IS UNDER CONSTRUCTION SHALL CONTAIN A *SHOP
 DRAWING* REVIEW STAMP AND SIGNATURE FROM EACH DESIGNER
 ON THEIR RESPECTIVE PAGES BEFORE PERMIT MAY BE ISSUED
 FOR TENANT BUILD OUT.
 FS 471,481. ONCE THE SHELL OBTAINS AS C OF C ETC THEN
 THE PLANS DO NOT NEED TO GO BACK TO THE BASE BUILDING
 DESIGN TEAM.
  
 2) NOTE: PLEASE KNOW AS THE BASE BUILDING/SHELL
 CONTRACTOR IS THE SAME AS APPLIED FOR THIS SCOPE OF
 WORK A LETTER OF UNDERSTANDING IS NOT REQUIRED.
  
 3) NOTE: PLEASE KNOW THIS IS THE FIRST TIME ENERGY
 CALCULATIONS ARE BEING SUBMITTED. THE PREVIOUS TWO
 REVIEWS REQUESTED LIGHTING PERFORMANCE CALCULATIONS AND
 THE SPECIFIC CODE SECTIONS GIVEN WERE
 13-415.2.ABC.1.1,.1.2 AN D.1.3. THE CODE SECTIONS FOR
 METHOD OF CALCULATIONS GIVEN WERE 13-400.3.B,
 13-400.3.C. SECTION 13-400.3.A WAS NOT GIVEN AS METHOD
 *A* MAY NOT BE USED.
 PLANS WERE SUBMITTED WITH METHOD *A*. PLEASE SEE THE
 FLORIDA BUILDING CODE 13-400.0.A, 13-101.1.1. PLEASE
 EXPLAIN HOW METHOD *A* MAY BE USED WHEN THIS TENANT
 BUILDING IS NOT A WHOLE BUILDING.
 PLEASE SEE THAT IN ANY CASE THE INFORMATION AS
 SUBMITTED AND SHOWN ON THE INPUT DATA REPORT IS NOT
 COMPLETE NOR DOES IT COORDINATE WITH PLANS IN SEVERAL
 ASPECTS. SOME EXAMPLES WILL BE NOTED BY THIS REVIEWER
 AND PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES AS
 WELL.
 PLEASE SEE 13-103.1. MEETING THE EXCEPTIONS UNDER FS
 471.003 AND THIS SECTION OF THE FBC REQUIRES LICENSED
 DESIGNER.
  
 FOR EXAMPLE:
 THE IDR SHOWS ONLY TWO (2) LIGHT FIXTURES ON THE
 INTERIOR OF THIS SPACE. HOW IS THIS POSSIBLE WHEN IN
 FACT THE PLANS SHOW MANY FIXTURES? THE FACT IS THE ONLY
 TWO FIXTURES SHOWN ARE 2 WATTS EACH. THIS IS NOT
 POSSIBLE AS THE PLANS DO NOT CORRELATE WITH ANY OF
 THIS.
  
 FORE EXAMPLE;
 ONLY ONE WALL UNDER WALLS, NO WINDOWS, NO DOORS, METAL
 BUILDING ETC. THESE WILL BE NOTED BY OTHER TRADES
 HOWEVER ARE GIVEN FOR INFORMATION AT THIS TIME.
  
 4) NOTE: PLEASE KNOW ELECTRICAL SERVICE AS SHOWN ON
 THESE PLANS DOES NOT COORDINATE WITH THE ELECTRICAL
 SERVICE ON THE BASE BUILDING. IN FACT THE ELECTRICAL
 SERVICE ON THE BASE BUILDING WHICH ALREADY HAS A FINAL
 CONTAINS MANY ITEMS WHICH ARE NOT THE SAME.
 MAINS ARE 125 AMP
 THERE IS A HOUSE PANEL NOT SHOWN.
 THE SERVICE SIZE IS NOT 400AMPS.
 THE GROUNDING ELECTRODE SYSTEM IS NOT THE SAME AND
 MEETS 250.50,250.24,250.6 ETC
 PLEASE EXPLAIN HOW THE GUTTER HAS AN EQUAL POTENTIAL IF
 THE NEUTRAL IS FLOATING TO THE FIRST MEANS OF
 DISCONNECT. BASED ON THE CODE AND THE RISER FOR BASE
 BUILDING THE SYSTEM AS SHOWN ON THIS RISER MAY NOT BE
 DONE TO MEET THE CODE.
 PLAN SHOWS THREE DISCONNECTS/MAINS
 215.5, 230.70, 230.71, 230.72, 240.4, 310.16, 250.6,
 250.24 ETC
  
 5) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR CONTROL OF
 EXTERIOR LIGHTING. PLANS MENTIONS TIME CLOCK HOWEVER
 NOT FOR ALL LIGHTS AND ALSO SHOWS STANDARD SINGLE POLE
 SWITCH. MUST MEET ONE OF THE TWO MINIMUMS IN SECTION OF
 CODE GIVEN OR BOTH.
  
 ** BASED ON COMMENTS ABOVE ONE SET OF CALCULATIONS
 ALONG WITH ONE COPY OF ELECTRICAL PLANS ARE BEING
 RETAINED BY THIS OFFICE.
  
 ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE
 NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 ***AS THERE ARE MANY ASPECTS OF THE BUILDING AND
 CALCULATIONS NOT COMPLETE AT THIS TIME THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW.
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-18 Cont ID  
Sent By dpalmer Date 2008-03-18 Time 12:01 Rev Time 0.00
Received By dpalmer Date 2008-03-18 Time 12:01 Sent To  
Notes
2008-03-18 12:01:25** DENIED 2ND REVIEW**
  
 ** PLEASE SEE SOME COMMENTS ARE THE SAME FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE
 ALSO SEE SOME NEW COMMENTS DUE TO NEW INFORMATION NOW
 ON PLANS.
  
 ** PLEASE NOTE: AS THERE IS INFORMATION STILL NOT YET
 SUBMITTED FOR REVIEW, A FULL REVIEW CAN NOT BE DONE AND
 THERE MAY VERY WELL BE NEW COMMENTS ON THE NEXT
 REVIEW.
  
 1) NOTE: PLEASE SEE NO ENERGY CALCULATIONS WERE
 SUBMITTED, NO LIGHTING PERFORMANCE CALCULATIONS ETC.
 PLEASE SEE 13-400.3.B, 13-400.3.C, 13-415.2,
 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-412 FOR WATER HEATING SYSTEMS.
 PLEASE SEE MECHANICAL REVIEW COMMENTS FOR THESE
 SECTIONS.
  
 2) NOTE: PLEASE KNOW ALTHOUGH NOT REQUIRED A RESPONSE
 LETTER FROM DESIGN PROFESSIONAL IS HELPFUL IN THE
 REVIEW PROCESS. THERE ARE RESPONSES FOR ALL OTHER
 TRADES BUT ELECTRICAL.
 THIS IS ONLY NOTED AS IT MAY HELP THE REVIEW OF SAID
 PLANS.
  
 3) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM IS
 BEING SHOWN CONNECTED AFTER THE FIRST MEANS OF
 DISCONNECT ON THE TENANT MAINS??
 PLEASE SEE 250.6, 250.524 AS THIS IS NOT PERMITTED.
 PLEASE SEE THE GE SYSTEM IS ALSO STILL SHOWN TO FOOTER
 STEEL, IS THIS AN EXISTING SERVICE OR NEW? IS THERE AND
 EXISTING GROUNDING ELECTRODE CONNECTED TO FOOTER?
 250.50
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE SEE 250.104 AS THE GAS PIPE SHOULD NOT
 BE PART OF THE GROUNDING ELECTRODE SYSTEM. IS THIS A
 BOND ONLY?
  
 5) NOTE: PLEASE SEE THE SHOW WINDOWS WILL REQUIRE
 RECEPTACLES ABOVE WINDOW PER 210.62
 PLEASE ADJUST LOAD CALCULATIONS PER 220.43
  
 6) NOTE: PLEASE BE SURE TO ADJUST LOAD CALCULATIONS FOR
 MIXED USE AS UPSTAIRS IS SHOWN AS APARTMENT.
 220
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-13 Cont ID  
Sent By dpalmer Date 2007-09-13 Time 07:30 Rev Time 0.00
Received By dpalmer Date 2007-09-11 Time 20:09 Sent To  
Notes
2007-09-13 07:30:29 
  
 ** DENIED **
  
 1) NOTE: PLEASE DECLARE IF THIS IS A CHANGE IN
 OCCUPANCY OR USE ON PLANS.
 DOES NOT INDICATE THE PREVIOUS USE BEING NEW RESTAURANT
 BUILD OUT AND APPEARS TO BE A NEW BUILD OUT OF
 RESTAURANT.
  
 2) NOTE: PLEASE INCLUDE THE ADDRESS ON THE MEP PLANS AS
 SHOWN ON THE ARCHITECTURAL SHEETS.
 FAC 61G15-23.002
 FBC 106.1.2, 110.1.2
  
 3) NOTE: PLEASE SEE THE ELECTRICAL PLANS ONLY INDICATE
 ONE A/C SYSTEM BEING FIGURED INTO LOAD CALCULATIONS AND
 PANEL, YET THE ARCHITECTURAL SHEET SP-1 INDICATES AN
 EXISTING A/C SYSTEM WITH A NEW ONE BEING ADDED? NEC,
 220, FBC 106.3.5.1.2
  
 4) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS AS THE
 ADDITIONAL A/C BEING ADDED TO SPACE MAY REQUIRED ENERGY
 CALCULATIONS BY METHOD AS SPECIFIED IN 13-415.1.B,
 13-415.1.C.
 PLEASE KNOW THAT LIGHTING PERFORMANCE CALCULATIONS ARE
 STILL REQUIRED PER 13-415.2. PLEASE SEE
 TABLES415.2.C.1, 415.2.B.1.
 PLEASE SUBMIT A FIXTURE LEGEND ON PLANS WITH
 INFORMATION ON FIXTURE TYPES WATTAGE ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE INDICATE THE AIC RATINGS FOR NEW MAINS
 AND SERVICE EQUIPMENT AS SHOWN ON RISER.
 110.9.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE INDICATE *FLOATING NEUTRAL* REQUIRED AT
 THE METERS.
 250.6, 250.24
  
 7) NOTE: PLEASE SEE NFPA-96 FOR SHUT DOWN OF ALL
 ELECTRICAL UNDER HOOD.
 PLEASE INDICATE THE REQUIRED SHUNT TRIP BREAKERS.
 PLEASE SEE CHAPTERS 9 AND 10. PLEASE BE SURE TO SEE ANY
 MECHANICAL REVIEW COMMENTS.
  
 8) NOTE: PLEASE PROVIDE THE MINIMUM ADA LEVELS FOR FIRE
 ALARMS DEVICES PER 11-4.28.1, .2 AND .3(4).
  
 9) NOTE: PLEASE CORRELATE PLANS WITH RISER. PLANS ONLY
 INDICATE ONE METER AND ONE MAIN DISCONNECT.
 PLEASE INCLUDE ALL EQUIPMENT AS SHOWN ON RISER ON THE
 PLANS WITH THE LOCATIONS.
 100.26, FBC 106.1.2
  
 10) NOTE: PLEASE SEE THE RISER WHICH INDICATES BUILDING
 STEEL AS PART OF THE GROUNDING ELECTRODE SYSTEM. THIS
 IS BEING ASSUMED THIS IS ACTUALLY *FOOTER STEEL*? IN
 EITHER CASE PLEASE KNOW AS THIS IS AN EXISTING BUILDING
 THE FOOTER STEEL WOULD NOT REQUIRE AN ATTACHMENT AS
 THIS MAY CREATE AN ADVERSE AFFECT ON THE STRUCTURAL
 INTEGRITY OF THE FOUNDATION.
 (IF SHOWN ON RISER, THEN THIS WOULD BE REQUIRED AS THIS
 IS BEING SPECIFIED.)
 PLEASE SEE MISSING GAS LINE BOND AS REQUIRED. 250.50,
 250.104.
  
 11) NOTE: PLEASE SEE NEC 422.13 AS THE WATER HEATER IS
 REQUIRED TO BE FIGURED AT 125% FOR LOAD. PLEASE KNOW
 THIS WAS A CHANGE IN THE 2005 NEC.
 230.42, 215.3, 422.13 ETC
  
 12) NOTE: PLEASE CORRELATE RISER AND PANEL SCHEDULE.
 THE PANEL SCHEDULE SHOWS PANEL WITH A 150AMP MAIN
 CIRCUIT BREAKER, AND RISER SHOWS THIS WITH A 200AMP
 MAIN CIRCUIT BREAKER.
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE 210.8B2 AS ALL RECEPTACLES IN
 KITCHEN AREAS ARE REQUIRED TO BE GFI/GFI PROTECTED
 WHETHER OR NOT THESE ARE FEEDING COUNTER SPACE AREAS.
 PLEASE KNOW THIS WOULD INCLUDE REFRIGERATION EQUIPMENT
 ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2007-09-13 06:58:412007-09-13 06:58:41
  
 IN REVIEW
2007-09-12 20:31:362007-09-12 20:31:36
  
 REVIEW TO BE COMPLETED 9/13, NOTES TO FOLLOW.
2007-09-12 19:58:392007-09-12 19:58:39
  
 REVIEW COMMENCED
2007-09-11 20:09:202007-09-11 20:09:20
  
 IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-08-03 Cont ID  
Sent By mawillia Date 2009-08-03 Time 11:48 Rev Time 0.00
Received By mawillia Date 2009-08-03 Time 11:34 Sent To B
Notes
2009-08-03 11:41:34******APPROVED*****
  
 PLAN SHEETS A-1 AND E-2 WERE STAMPED, INITIALED, AND
 DATED
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-08-14 Cont ID  
Sent By mawillia Date 2008-08-14 Time 12:04 Rev Time 0.00
Received By mawillia Date 2008-08-14 Time 11:52 Sent To  
Notes
2008-08-14 12:04:12******DENIED*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER REVIEWERS AS WELL AS THE FOLLOWING COMMENT
 (FROM THE PREVIOUS FIRE PLAN REVIEW) HAVE BEEN
 ADDRESSED:
  
 2. THE DIRECTIONAL ARROW ON SHEET P-1, M-1, AND E-2 DO
 NOT CORRELATE TO WHAT IS CORRECTLY SHOWN ON SHEET A-1.
 AMEND DIRECTIONAL LEGEND
  
 BE ADVISED THAT THE ABOVE COMMENT IS THE SAME AS TAKEN
 FROM THE PREVIOUS FIRE PLAN REVIEW. PLEASE ADDRESS
 ACCORDINGLY!!!!!!!
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-04-10 Cont ID  
Sent By mawillia Date 2008-04-10 Time 15:58 Rev Time 0.00
Received By mawillia Date 2008-04-10 Time 15:09 Sent To  
Notes
2008-04-10 15:26:28******PROVISO*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER REVIEWERS AS WELL AS THE FOLLOWING COMMENT
 (FROM THE PREVIOUS FIRE PLAN REVIEW) HAVE BEEN
 ADDRESSED:
  
 2.THE DIRECTIONAL ARROW ON SHEET P-1, M-1, AND E-2 DO
 NOT CORRELATE TO WHAT IS CORRECTLY SHOWN ON SHEET A-1.
 AMEND DIRECTIONAL LEGEND
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By mawillia Date 2007-10-18 Time 15:41 Rev Time 0.00
Received By mawillia Date 2007-10-18 Time 14:48 Sent To  
Notes
2007-10-18 15:41:08******DENIED*****
  
 1.THE ADDRESS SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.THE LAYOUT OF THE PROPOSED 1ST FLOOR PLAN (SHEET
 A-1) DOES NOT CORRELATE WITH LAYOUT SHOWN ON SITE PLAN
 (SHEET SP-1) .AMEND DIRECTIONAL LEGEND.
  
 3.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 INSTALLATION OF THE COOKING HOOD SYSTEM AND FOR THE
 FIRE SUPPRESSION SYTEM FOR THE HOOD.NFPA 96 - 2001
 EDITION - SHALL BE REFERENCED.
  
 4.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 INSTALLATION OF THE FIRE ALARM SYSTEM.
  
 5.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM, AS PER WEST PALM BEACH FIRE PREVENTION.
  
 6.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 7.PLEASE ACKNOWLEDGE THAT THE NUMERICAL ADDRESS SHALL
 BE POSTED ON THE APPROPIATE EXTERIOR ELEVATION FRONTING
 SPRUCE AVENUE.THE ADDRESS IS TO BE DISPLAYED PRIOR,
 DURING, AND AFTER CONSTRUCTION OPERATIONS.AS PER WEST
 PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS THAN 6"
 IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2009-07-14 Cont ID  
Sent By kstevens Date 2009-07-14 Time 14:21 Rev Time 0.00
Received By kstevens Date 2009-07-14 Time 14:21 Sent To  
Notes
2009-07-14 14:33:21 
  
 PASSED/PROVISO:
 REVISIONS REQUIRED FOR ALL SHEETS SHOWING THE CORRECT
 ADDRESS AND UNIT/SUITE NUMBER IN THE TITLE BLOCK.
 SECTION 106.1.1

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-08-04 Cont ID  
Sent By kstevens Date 2008-08-04 Time 07:55 Rev Time 0.00
Received By kstevens Date 2008-08-04 Time 07:55 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-04-10 Cont ID  
Sent By kstevens Date 2008-04-10 Time 12:55 Rev Time 0.00
Received By kstevens Date 2008-04-10 Time 12:55 Sent To  
Notes
2008-04-10 12:56:41DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT P-2 A SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR PERMIT:
  
 A. OK
 B. OK
  
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED
  
 D. OK
 11. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-12-13 Cont ID  
Sent By kstevens Date 2007-12-13 Time 12:53 Rev Time 0.00
Received By kstevens Date 2007-12-13 Time 12:53 Sent To  
Notes
2008-04-10 12:55:04DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT P-2 A SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - NOT ALL CUT SECTION LENGTHS ARE
 INDICATED. SEE ALL SECTIONS FROM THE METER TO WHERE THE
 22 FT LENGTH, AND THE RISER LENGTHS TO EACH APPLIANCE.
 PLEASE SHOW THE LENGTH OF ALL CUT SECTIONS.--SHOW
 ALL PIPE SIZES UP THRU THE SHUT OFF VALVE OF EACH
 APPLIANCE.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED AFTER
 COMMENT "A" ADDRESSED.
  
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 D. SHUT OFF VALVES SHALL BE ACCESSIBLE PER SECTION
 409.1.3. PLEASE INDICATED ON PLANS.
  
 11. ALL MECHANICAL, PLUMBING & ELECTRICAL SHEETS. THE
 CERTIFICATE OF AUTHORIZATION NUMBER IS REQUIRED FOR
 DESIGN SERVICES MEP LLC. FAC 61G15-23.002(2) & FS
 471.025. PLEASE SHOW CA NUMBER ON ALL SHEETS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-07-01 Cont ID  
Sent By kstevens Date 2009-07-01 Time 10:14 Rev Time 0.00
Received By kstevens Date 2009-07-01 Time 10:14 Sent To  
Notes
2009-07-01 10:20:27C-14

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-21 Cont ID  
Sent By adarroug Date 2008-07-21 Time 15:19 Rev Time 0.00
Received By adarroug Date 2008-07-21 Time 15:19 Sent To  
Notes
2008-07-21 15:24:38TO "COMM" BD#9

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-11 Cont ID  
Sent By adarroug Date 2008-03-11 Time 15:14 Rev Time 0.00
Received By adarroug Date 2008-03-11 Time 15:14 Sent To  
Notes
2008-03-11 15:17:42TO "COMM" BD#30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-18 Cont ID  
Sent By mawillia Date 2007-10-18 Time 14:49 Rev Time 0.00
Received By mawillia Date 2007-08-23 Time 10:23 Sent To  
Notes
2007-09-11 09:12:56TO "COMM" BD#51
2007-08-23 10:29:35WAITING FOR " COMM" BD

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2009-08-07 Cont ID  
Sent By shill Date 2009-08-06 Time 14:49 Rev Time 0.00
Received By shill Date 2009-08-06 Time 14:49 Sent To  
Notes
2009-08-06 14:50:58IMPACT FEES PAID ON SHELL

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-07-21 Cont ID  
Sent By rregueir Date 2009-07-21 Time 15:18 Rev Time 0.00
Received By rregueir Date 2009-07-20 Time 16:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-07-24 Cont ID  
Sent By tgordon Date 2008-07-24 Time 15:52 Rev Time 1.15
Received By tgordon Date 2008-07-24 Time 15:52 Sent To  
Notes
2008-07-24 16:07:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1)A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C
 EQUIPMENT SCHEDULE C/U #TTX048C100A AND A/H/U #TWE048P
 COULD NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE,
 PLEASE CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004
 FBC 13-407.1.ABC.3.1.1.
  
 2) PLEASE ADD TO THE MECHANICAL PLAN, A DETAIL FOR
 HANGING THE KITCHEN HOOD TO THE CEILING, AND A DETAIN
 FOR SECURING THE EXHAUST FAN ROOF CURB TO WITHSTAND 140
 MPH WINDS, PER 2004 FBC 1609.
  
 3) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR THE
 24X16 AND 12X16 WALL LOUVERS, SEE FS 553.842(1) AND FAC
 RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(C).
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-03-18 Cont ID  
Sent By hmoser Date 2008-03-18 Time 18:52 Rev Time 0.00
Received By hmoser Date 2008-03-18 Time 18:52 Sent To  
Notes
2008-03-18 18:55:11PLAN DENIED
 PLEASE PROVID EQUIPMENT SCHEDULE ON MECHANICAL PLANS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-26 Cont ID  
Sent By hmoser Date 2007-09-26 Time 19:11 Rev Time 0.00
Received By hmoser Date 2007-09-26 Time 19:11 Sent To  
Notes
2007-09-26 19:04:221- PLEASE PROVIDE A FULL SET OF PLANS FOR REVIEW
 ,MISSING PAGE A-3, A CEILING DETAIL, AND 2ED FLOOR
 MECHANICAL PLANS .
 2- PLEASE REFER TO NOTE 5 ON PAGE SP-1 , 1HR RATING
 BETWEEN GROUND FLOOR AND 2ED FLOOR . PLEASE REFER TO
 TABLE 302.3.2 REQUIRED SEPARATIONS OF OCCUPANCIES 2004
 FBC
 3-CONDENSER MUST BE 10 FT AWAY FROM MAKE UP AIR TO
 HOOD
 4- FIRE DAMPERS ARE REQUIRED IN ALL DUCT PENETRATIONS
 THROUGH THE CEILING.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-07-14 Cont ID  
Sent By kstevens Date 2009-07-14 Time 14:33 Rev Time 0.00
Received By kstevens Date 2009-07-14 Time 14:33 Sent To  
Notes
2009-07-14 14:34:48 
  
  
 PASSED/PROVISO:
  
 REVISIONS ARE REQUIRED FOR ALL SHEETS INDICATING THE
 CORRECT ADDRESS AND UNIT/SUITE NUMBER IN THE TITLE
 BLOCK OF EACH SHEET. SECTION 106.1.1.
  
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-08-04 Cont ID  
Sent By kstevens Date 2008-08-04 Time 07:55 Rev Time 0.00
Received By kstevens Date 2008-08-01 Time 16:53 Sent To  
Notes
2008-08-04 08:10:57DENIED
 REFERENCE: FLORIDA STATUTES
 FBC-2004 CHAPTER 1
  
 PLANS ARE CODE COMPLIANT AT THIS TIME BUT THERE IS A
 COMMENT TO BE ADDRESSED BASED ON NEW INFORMATION NOW
 BEING PROVIDED.
  
 1. THE BASE BUILDING PERMIT, 06011130, FOR THE SHELL
 BUILDING HAS EXPIRED AND AS SUCH HAS NO CERTIFICATE OF
 COMPLETION. A NEW PERMIT APPLICATION IS REQUIRED TO
 FINAL OUT THE BASE BUILDING. SINCE THE BASE BUILDING
 DESIGN TEAM IS RESPONSIBLE FOR SUCH BUILDING UNTIL A
 CERTIFICATE OF COMPLETION OR CERTIFICATE OF OCCUPANCY
 IS ISSUED, ALL PLANS FOR PERMITTED WORK ON BUILDOUTS
 SHALL CONTAIN A "SHOP DRAWING" REVIEW STAMP AND
 SIGNATURE FROM EACH DESIGNER ON THEIR RESPECTIVE SHEET
 BEFORE PERMIT MAY BE ISSUED FOR THE TENANT BUILDOUT. FS
 741.481.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-04-10 Cont ID  
Sent By kstevens Date 2008-04-10 Time 12:52 Rev Time 0.00
Received By kstevens Date 2008-04-10 Time 08:43 Sent To  
Notes
2008-04-10 12:51:49DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE WPB
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
  
 6. SHT P-1 THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 UTILITY DEPT., INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT EITHER RODNEY COMPO, (561)
 822-2272, E-MAIL [email protected] OR CALVIN WILLIAMS
 (561) 822-2284, E-MAIL CWILLIAMS @WPB.ORG. THEIR FAX IS
 (561) 822-2287. A PRINTED DETERMINATION SHALL BE
 PRODUCED AND SUBMITTED WITH PLANS SHOWING INTERCEPTOR
 SIZE APPROVAL. ARTICLE III SECTION 90-124(7)(F).
 ****RESPONSE NOTED, NOT ADDRESSED.
  
 7. OK
 8. OK
 9. OK
  
 10. SHT P-2 A SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR PERMIT:
  
 A. OK
 B. OK
  
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 D. OK
 11. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-13 Cont ID  
Sent By kstevens Date 2007-10-13 Time 05:31 Rev Time 0.00
Received By kstevens Date 2007-10-12 Time 18:58 Sent To  
Notes
2007-10-13 06:10:41DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE WPB
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ROUTE THE PLANS TO THE STATE OF FLORIDA, DEPT OF
 BUSINESS REGULATION, (DBPR), DIVISION OF HOTEL &
 RESTAURANT FOOD SERVICE LICENSE FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY WPB FOR REVIEW. REVIEWED &
 STAMPED PLANS SHALL BE INSERTED INTO EACH SET OF PLANS
 SUBMITTED FOR REVIEW WITH THE TWO PAGE "SPECIFICATION
 WORKSHEETS" ATTACHED TO THE SHEETS STAMPED/REVIEWED BY
 DBPR. SECTION 102.2.1.
  
 2. SHT A-1 DETAIL FOR THE TOILET ROOM IS INDICATED AS
 DETAILD-1/A-3, BUT SHEET A-3 HAS NOT BEEN SUBMITTED.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 3. SHT A-2 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR
 W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ___FOR LAV:
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
  
 4. SHT A-2 FINISH. WALLS WITHIN 2' OF THE W/C SHALL BE
 A SMOOTH, HARD, NONABSORBENT SURFACE UP TO 4 FEET ABOVE
 THE FLOOR PER SECTION 1210.2. PLANS SHOW FINISH
 DRYWALL. PLEASE SHOW COMPLIANCE.
  
 5. SHT P-1 A CLEANOUT IS REQUIRED NEAR THE JUNCTION OF
 THE BUILDING DRAIN AND THE BUILDING SEWER PER SECTION
 708.3.5. A TWO WAY CLEANOUT WILL ENABLE CLEANOUT IN THE
 BUILDING AND OUT TO THE SEWER.
  
 6. SHT P-1 THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 UTILITY DEPT., INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT EITHER RODNEY COMPO, (561)
 822-2272, E-MAIL [email protected] OR CALVIN WILLIAMS
 (561) 822-2284, E-MAIL CWILLIAMS @WPB.ORG. THEIR FAX IS
 (561) 822-2287. A PRINTED DETERMINATION SHALL BE
 PRODUCED AND SUBMITTED WITH PLANS SHOWING INTERCEPTOR
 SIZE APPROVAL. ARTICLE III SECTION 90-124(7)(F).
  
 7. SHT P-2 SANITARY ISOMETRIC. A VENT IS REQUIRED FOR
 THE MOP SINK. SECTION 901.2.1.
  
 8. SHT P-2 SANITARY ISOMETRIC. PLEASE INDICATE THE USE
 OF THE FLOOR SINK IN THE MIDDLE OF THE FLOOR. IF THIS
 IS TO DRAIN THE FLOOR, A FLOOR DRAIN IS REQUIRED. FLOOR
 SINKS ARE FOR INDIRECT WASTE. SECTIONS 106.1.2 &
 802.3.
  
 9. SHT P-2 THE WATER ISOMETRIC DOES NOT REFLECT THE
 FLOOR PLAN AT THE MOP SINK & AT THE TOILET ROOM. PLEASE
 CORRELATE. SECTION 106.1.1. PLEASE MAKE SURE RISER
 DIAGRAM REFLECTS THE FLOOR PLAN.
  
 10. SHT P-2 A SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - NOT ALL CUT SECTION LENGTHS ARE
 INDICATED. SEE ALL SECTIONS FROM THE METER TO WHERE THE
 22 FT LENGTH, AND THE RISER LENGTHS TO EACH APPLIANCE.
 PLEASE SHOW THE LENGTH OF ALL CUT SECTIONS.--SHOW
 ALL PIPE SIZES UP THRU THE SHUT OFF VALVE OF EACH
 APPLIANCE.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED AFTER
 COMMENT "A" ADDRESSED.
  
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 D. SHUT OFF VALVES SHALL BE ACCESSIBLE PER SECTION
 409.1.3. PLEASE INDICATED ON PLANS.
  
 11. ALL MECHANICAL, PLUMBING & ELECTRICAL SHEETS. THE
 CERTIFICATE OF AUTHORIZATION NUMBER IS REQUIRED FOR
 DESIGN SERVICES MEP LLC. FAC 61G15-23.002(2) & FS
 471.025. PLEASE SHOW CA NUMBER ON ALL SHEETS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2008-03-13 Cont ID  
Sent By choops Date 2008-03-13 Time 11:21 Rev Time 0.00
Received By choops Date 2008-03-13 Time 11:21 Sent To  
Notes
2008-03-13 11:21:42SHELL BUILDING APPROVED ON #06011130

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-26 Cont ID  
Sent By choops Date 2007-09-17 Time 15:47 Rev Time 0.00
Received By lursu Date 2008-08-05 Time 08:09 Sent To  
Notes
2007-09-17 15:51:04SHELL BUILDING APPROVED ON #06011130