Plan Review Stops For Permit 07080606 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2009-08-07 |
|
|
Cont ID |
|
Sent By |
jnguyen |
Date |
2009-08-07 |
Time |
11:29 |
Rev Time |
0.00 |
Received By |
jnguyen |
Date |
2009-08-06 |
Time |
16:00 |
Sent To |
|
|
Notes |
2009-08-07 11:07:51 | I CHECKED OUT THE SITE ON MY WAY TO WORK THIS MORNING. | | I CONFIRMED THAT THIS PERMIT WAS INDEED REFERENCING | | BUILDING U ON PCN# 74434316240000210 AT 2055 SPRUCE AVE | | (NOT BUILDING T ON PCN# 74434316240000200 AT 2037 | | SPRUCE AVE). AFTER JAMES & I ANALYZED THE SITE PLANS, I | | CALLED THE ARCHITECT, RAFAEL RODRIGUEZ OF RAR | | ARCHITECT, INC. FOR FURTHER CLARIFICATION. HE INFORMED | | ME THAT THERE WAS NO ACCESS FROM WITHIN THE PROPOSED | | RESTAURANT DOWNSTAIRS TO THE RESIDENTIAL RENTAL UNIT | | UPSTAIRS (IT HAD A SEPARATE ENTRANCE DOOR OUTSIDE ON | | THE REAR PART OF BUILDING U.). HE ALSO ACKNOWLEDGED TO | | ME THAT THE RESTAURANT HAD ANOTHER DOOR IN THE REAR | | TOO, BUT ITS FRONT MAIN ENTRANCE DOOR FACED SPRUCE AVE. | | DESPITE THE FACTS THAT ACCESS TO PARKING OCCURED OFF | | 20TH ST & THE RENTAL UNIT'S ENTRANCE WAS IN THE REAR, I | | ISSUED THE SECONDARY ADDRESS OF 2057 SPRUCE AVE FOR THE | | UPSTAIRS RENTAL UNIT BECAUSE THE FRONTAGES OF BOTH THE | | RESTAURANT & RESIDENCE FACED SPRUCE AVE. ALSO, I WANTED | | TO AVOID ANY POTENTIAL CONFUSION FOR THIS PARTICULAR | | BUILDING HAVING MULTIPLE NUMERICAL ADDRESSES OFF OF TWO | | DIFFERENT STREETS (SPRUCE AVE & 20TH ST). I CREATED THE | | GIS SPATIAL POINT FOR 2057 SPRUCE AVE & EXPORTED IT AS | | A SHAPEFILE IN MY E-MAIL NOTIFICATION TO ALL OF THE | | RELEVANT PARTIES (INCLUDING PAPA). IN COMMUNITYPLUS | | UNDER PCN# 74434316240000210, I FORMULATED SEQUENTIAL | | UNIT RECORD 0001 - 2057 SPRUCE AVE. I ALSO CORRECTED | | THE PCN# ON THE ORIGINAL PERMIT APPLICATION FROM | | 74434316240000200 TO 74434316240000210, AND ADDED THE | | SECONDARY ADDRESS OF 2057 SPRUCE AVE (RENTAL UNIT) TO | | THE PRIMARY ONE OF 2055 SPRUCE AVE (RESTAURANT). | | | | JOHN NGUYEN | | GIS SUPPORT SPECIALIST | | CITY OF WEST PALM BEACH | | OFFICE: (561) 822-1239 | | FAX: (561) 822-1249 | | [email protected] |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2008-08-05 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2008-08-05 |
Time |
08:10 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2008-08-05 |
Time |
08:10 |
Sent To |
|
|
Notes |
2008-08-05 08:22:51 | THE ENTIRE BUILDING T WAS ASSIGNED WITH A UNIQUE | | ADDRESS AS 2037 SPRUCE AVE , HOWEVER EACH UNIT INSIDE | | THE STRUCTURE MUST HAVE A UNIQUE ADDRESS NUMBER ,AS | | EXPLAINED BELOW: | | | | IF EACH UNIT HAS A SEPARATE STREET ENTRANCE THAN A | | UNIQUE ADDRESS NUMBER (SEE SECTION 1, PARAGRAPH 1.2 - | | ADDRESSING GUIDE POLICY ) IS REQUIRED . | | IF THE UNIT HAS A COMMON ENTRANCE AS THE REST OF THE | | UNITS THAN EACH UNIT SHOULD BE ASSIGNED WITH A UNIT | | DESIGNATOR; EXAMPLES OF ASSIGNING UNITS ARE: | | - FIRST FLOOR - UNITS FROM 101 TO 199 ; 2037 SPRUCE AVE | | # 101 - INDICATES THE FIRST UNIT ON THE FIRST FLOOR | | - SECOND FLOOR - UNIT FROM 201 TO 299 ; 2037 SPRUCE AVE | | # 201 - INDICATES THE FIRST UNIT ON THE SECOND FLOOR | | | | QUESTIONS/COMMENTS: | | | | LACRAMIOARA URSU, MA ,GISP | | MIS - GIS SUPPORT SPECIALIST | | CITY OF WEST PALM BEACH | | OFFICE:822-1239 | | FAX: 822-1249 | | E-MAIL:[email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2009-07-20 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-07-20 |
Time |
15:54 |
Rev Time |
0.99 |
Received By |
jwitmer |
Date |
2009-07-20 |
Time |
15:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2009-07-20 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-07-20 |
Time |
16:22 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2009-07-20 |
Time |
15:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
N |
Date |
2009-03-04 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2009-02-04 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2009-02-04 |
Time |
08:47 |
Sent To |
|
|
Notes |
2009-03-04 08:47:30 | PER ROBERT BROWN: THIS PERMIT CAN REMAIN OPEN DUE TO | | THE FACT THAT PERMIT #06011130 WHICH IS THE SHELL | | BUILDING PERMIT HAD CONTINUOUS ACTIVITY WITHIN THE PAST | | SIX MONTHS; IN FACT THE CERTIFICATE OF OCCUPANCY WAS | | ISSUED ON 2/18/09 BY CHUCK JORDAN. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2008-08-21 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-08-21 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-08-21 |
Time |
12:11 |
Sent To |
PC |
|
Notes |
2008-08-21 15:11:10 | | | | | 3RD RREVIEW | | BUILDING PLAN REVIEW | | PERMIT: 07080606 | | ADD: 2037 SPRUCE AVE | | CONT: JHAMTEC CONSTRUCTION | | TEL: (561)602-0009 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: 3RD AUGUST 21, 2008 | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 3) OK | | | | DUE TO THE FACT THAT PERMIT #06011130 IS AN EXPIRED | | PERMIT AND THE BUILDING DOES NOT HAVE A CERTIFICATE OF | | OCCUPANCY OR FINAL INSPECTION THE SHALL MEET THE | | REQUIREMENTS OF THE SECTION BELOW. | | NOTE: THE REVISION #1 TO THE DOOR ON SHEET A-1 DOES NOT | | COMPLY WITH FIGURE 24. A 2'-8" X 6'- 8" DOOR WILL NOT | | MEET THE 32" MINIMUM REQUIREMENT. THE DISTANCE SHALL BE | | MEASURED FROM THE INSIDE FACE OF THE DOOR TO THE FACE | | OF THE DOOR STOP. PLEASE TAKE A LOOK AT THE DRAWING | | SUBMITTED ON SHEET A-1. SEE CODE SECTION MENTION BELOW. | | ACCESSIBLE PARKING SPACES SERVING BUILDINGS SHALL BE | | LOCATED ON THE SHORTEST ROUTE. | | 4) 11-4.1.6(2) DUTY TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL TO ALTERED AREAS SHALL BE DEEMED | | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE | | COST EXCEEDS 20 % OF THE COST OF THE ALTERATION TO THE | | PRIMARY FUNCTION AREA. | | (A)(I) OK | | (II) AN ACCESSIBLE ROUTE | | (III) OK | | (IIII) OK | | | | FRONT ENTRY DOOR, A PAIR OF 5'-0" DOORS, SEE11-4.13.5 | | CLEAR WIDTH. DOORWAYS SHALL HAVE A MINIMUM CLEAR | | OPENING OF 32 INCHES WITH THE DOOR OPEN 90 DEGREES, | | MEASURED BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE | | STOP [SEE FIGURE 24 (A), FIGURE 24 (B), FIGURE 24 (C), | | AND FIGURE 24 (D)]. OPENINGS MORE THAN 24 INCHES (610 | | MM) IN DEPTH SHALL COMPLY WITH SECTIONS 11-4.2.1 AND | | 11-4.3.3 [SEE FIGURE 24 (E)]. | | | | 5) OK | | | | 6) OK | | 7) OK | | | | **NOTE: ACCESSIBLE PARKING SHALL BE LOCATED ON THE | | SHORTEST ROUTE TO THE ENTRANCE OF THE BUILDING. THE | | PARKING LOT DOES NOT HAVE A FINAL INSPECTION THEREFORE, | | THE ISSUE OF THE ACCESSIBLE PARKING HAS TO BE | | ADDRESSED** | | 8) THE SITE PLAN DOES NOT INDICATE ANY ACCESSIBLE | | PARKING PLEASE INDICATE THE HANDICAPPED PARKING AND | | ACCESS ISLE. 11-4.6.2 LOCATION. ACCESSIBLE PARKING | | SPACES SERVING A PARTICULAR BUILDING SHALL BE LOCATED | | ON THE SHORTEST SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM | | ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE. IN PARKING | | FACILITIES THAT DO NOT SERVE A PARTICULAR BUILDING, | | ACCESSIBLE PARKING SHALL BE LOCATED ON THE SHORTEST | | ACCESSIBLE ROUTE OF TRAVEL TO AN ACCESSIBLE PEDESTRIAN | | ENTRANCE OF THE PARKING FACILITY. | | | | **3RD REQUEST** | | 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE | | APPLICABLE. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2008-04-04 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-04-04 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-04-02 |
Time |
14:50 |
Sent To |
|
|
Notes |
2008-04-04 14:50:59 | 2ND RREVIEW | | BUILDING PLAN REVIEW | | PERMIT: 07080606 | | ADD: 2037 SPRUCE AVE | | CONT: JHAMTEC CONSTRUCTION | | TEL: (561)602-0009 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: 2ND APRIL 2, 2008 | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | ACTUALLYOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 3) OK | | | | NOTE: THE REVISION #1 TO THE DOOR ON SHEET A-1 DOES NOT | | COMPLY WITH FIGURE 24. A 2'-8" X 6'- 8"DOOR WILL NOT | | MEET THE 32" MINIMUM REQUIREMENT. THE DISTANCE SHALL BE | | MEASURED FROM THE INSIDE FACE OF THE DOOR TO THE FACE | | OF THE DOOR STOP. PLEASE TAKE A LOOK AT THE DRAWING | | SUBMITTED ON SHEET A-1. SEE CODE SECTION MENTION BELOW. | | ACCESSIBLE PARKING SPACES SERVING BUILDINGS SHALL BE | | LOCATED ON THE SHORTEST ROUTE. | | 4) 11-4.1.6(2) DUTY TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL TO ALTERED AREAS SHALL BE DEEMED | | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE | | COST EXCEEDS 20 % OF THE COST OF THE ALTERATION TO THE | | PRIMARY FUNCTION AREA. | | (A)(I) OK | | (II) AN ACCESSIBLE ROUTE | | (III) OK | | (IIII) OK | | | | FRONT ENTRY DOOR, A PAIR OF 5'-0" DOORS, SEE11-4.13.5 | | CLEAR WIDTH. DOORWAYS SHALL HAVE A MINIMUM CLEAR | | OPENING OF 32 INCHES WITH THE DOOR OPEN 90 DEGREES, | | MEASURED BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE | | STOP [SEE FIGURE 24 (A), FIGURE 24 (B), FIGURE 24 (C), | | AND FIGURE 24 (D)]. OPENINGS MORE THAN 24 INCHES (610 | | MM) IN DEPTH SHALL COMPLY WITH SECTIONS 11-4.2.1 AND | | 11-4.3.3 [SEE FIGURE 24 (E)]. | | | | 5) OK | | | | **NOTE: THE UL NUMBER FOR THE FLOOR CEILING ASSEMBLY | | FOR THE BASE BUILDING IS L557, SO PLEASE INDICATE THIS | | NUMBER ON THE DRAWINGS. | | 6) PLEASE PROVIDE A DETAIL INDICATING THE FIRE RATING | | AT CEILING BETWEEN THIS MERCANTILE TENANT AND THE R-3 | | RESIDENCE LOCATED ON THE SECOND FLOOR? ALSO PROVIDE | | WHAT TYPE OF FIRE STOPPING MATERIALS WILL BE USED | | AROUND ANY PIPES THAT PENETRATE THE CEILING FLOOR | | ASSEMBLY SYSTEM? 106.1.2* | | | | 7) OK | | | | **NOTE: ACCESSIBLE PARKING SHALL BE LOCATED ON THE | | SHORTEST ROUTE TO THE ENTRANCE OF THE BUILDING.**8) | | THE SITE PLAN DOES NOT INDICATE ANY ACCESSIBLE PARKING | | PLEASE INDICATE THE HANDICAPPED PARKING AND ACCESS | | ISLE. 11-4.6.2 LOCATION. ACCESSIBLE PARKING SPACES | | SERVING A PARTICULAR BUILDING SHALL BE LOCATED ON THE | | SHORTEST SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM | | ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE. IN PARKING | | FACILITIES THAT DO NOT SERVE A PARTICULAR BUILDING, | | ACCESSIBLE PARKING SHALL BE LOCATED ON THE SHORTEST | | ACCESSIBLE ROUTE OF TRAVEL TO AN ACCESSIBLE PEDESTRIAN | | ENTRANCE OF THE PARKING FACILITY. | | | | **2ND REQUEST** | | 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE | | APPLICABLE. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-09-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-09-18 |
Time |
20:15 |
Rev Time |
2.00 |
Received By |
jwitmer |
Date |
2007-09-18 |
Time |
20:08 |
Sent To |
|
|
Notes |
2007-09-18 21:12:39 | 2037 SPRUCE AVE | | SEPT 18, 2007 | | BUILDING PLAN REVIEW | | PERMIT: 07080606 | | ADD: 2037 SPRUCE AVE | | CONT: JHAMTREE CONSTRUCTION | | TEL: (561)602-0009 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 3) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE | | OF OCCUPANCY: | | A) THE EDITION O FTHE CODE UNDER WHICH THE PROJECT IS | | DESIGNED. | | IS THIS A FIRST OCCUPANCY FOR THIS SPACE? | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | PROVISIONS OF CHAPTER 3. | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | TABLE 601. | | D) THE OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F) | | WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | BUILDING PERMIT | | | | 4) 11-4.1.6(2) DUTY TO PROVIDE AN ACCESSIBLE PATH OF | | TRAVEL TO ALTERED AREAS SHALL BE DEEMED | | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE | | COST EXCEEDS 20 % OF THE COST OF THE ALTERATION TO THE | | PRIMARY FUNCTION AREA. | | (A)(I) AN ACCESSIBLE ENTRANCE | | (II) AN ACCESSIBLE ROUTE | | (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX | | OR A SINGLE UNISEX RESTROOM | | (IIII) ACCESSIBLE TELEPHONE | | (IV) ELEMENTS SUCH AS PARKING, STORAGE OR ALARMS. | | | | FRONT ENTRY DOOR, A PAIR OF 5'-0" DOORS, SEE11-4.13.5 | | CLEAR WIDTH. DOORWAYS SHALL HAVE A MINIMUM CLEAR | | OPENING OF 32 INCHES (813 MM) WITH THE DOOR OPEN 90 | | DEGREES, MEASURED BETWEEN THE FACE OF THE DOOR AND THE | | OPPOSITE STOP [SEE FIGURE 24 (A), FIGURE 24 (B), FIGURE | | 24 (C), AND FIGURE 24 (D)]. OPENINGS MORE THAN 24 | | INCHES (610 MM) IN DEPTH SHALL COMPLY WITH SECTIONS | | 11-4.2.1 AND 11-4.3.3 [SEE FIGURE 24 (E)]. | | | | 5) RESTROOM WALL FINISHES:1210.2 WALLS. WALLS WITHIN 2 | | FEET (610 MM) OF URINALS AND WATER CLOSETS SHALL HAVE A | | SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF 4 | | FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR | | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS | | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY | | MOISTURE. | | | | 6) PLEASE PROVIE A DETAIL INDICATING THE FIRE RATING AT | | CEILING BETWEEN THIS MERCANTILE TENANT AND THE R-3 | | RESIDENCE LOCATED ON THE SECOND FLOOR? ALSO PROVIDE | | WHAT TYPE OF FIRE STOPPING MATERIALS WILL BE USED | | AROUND ANY PIPES THAT PENETRATE THE CEILING FLOOR | | ASSEMBLY SYSTEM? 106.1.2* | | | | 7) 11-5.2 COUNTERS AND BARS. WHERE FOOD OR DRINK IS | | SERVED AT COUNTERS EXCEEDING 34 INCHES (865 MM) IN | | HEIGHT FOR CONSUMPTION BY CUSTOMERS SEATED ON STOOLS OR | | STANDING AT THE COUNTER, A PORTION OF THE MAIN COUNTER | | WHICH IS 60 INCHES (1525 MM) IN LENGTH MINIMUM SHALL BE | | PROVIDED IN COMPLIANCE WITH SECTION 11-4.32 OR SERVICE | | SHALL BE AVAILABLE AT ACCESSIBLE TABLES WITHIN THE SAME | | AREA. | | | | 8) THE SITE PLAN DOES NOT INDICATE ANY ACCESSIBLE | | PARKING PLEASE INDICATE THE HANDICAPPED PARKING AND | | ACCESS ISLE. 11-4.6.2 LOCATION. | | ACCESSIBLE PARKING SPACES SERVING A PARTICULAR BUILDING | | SHALL BE LOCATED ON THE SHORTEST SAFELY ACCESSIBLE | | ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE | | ENTRANCE. IN PARKING FACILITIES THAT DO NOT SERVE A | | PARTICULAR BUILDING, ACCESSIBLE PARKING SHALL BE | | LOCATED ON THE SHORTEST ACCESSIBLE ROUTE OF TRAVEL TO | | AN ACCESSIBLE PEDESTRIAN ENTRANCE OF THE PARKING | | FACILITY. | | | | 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | REQUIREMENT, THE SPECIFIC | | REQUIREMENT SHALL BE APPLICABLE. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2009-08-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-07-31 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-07-31 |
Time |
14:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2008-07-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-07-31 |
Time |
14:39 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-07-31 |
Time |
14:39 |
Sent To |
|
|
Notes |
2008-07-31 14:39:27 | ** DENIED3RD REVIEW ** | | | | ** THERE ARE STILL COMMENTS FROM PREVIOUS REVIEW ALONG | | WITH SEVERAL NEW COMMENTS BASED ON NEW INFORMATION NOW | | BEING PROVIDED. | | | | | | | | 1) NOTE: PLEASE KNOW THE BASE BUILDING PERMIT #06011130 | | WHICH WAS PREVIOUSLY FOR THE SHELL BUILDING HAS BEEN | | EXPIRED DUE TO INACTIVITY UNDER THE FBC 105.3.2 BY | | HAROLD PISKURA | | PERMIT FOR BASE BUILDING NEEDS TO BE RE-APPLIED FOR | | FINALS. | | PLEASE ALSO KNOW AS THE BASE BUILDING DESIGN TEAM IS | | RESPONSIBLE FOR SUCH BUILDING UNTIL SUCH TIME AS | | CERTIFICATE OF COMPLETION OR CERTIFICATE OF OCCUPANCY | | IS ISSUED ALL PLANS FOR PERMITTED WORK WHILE A SHELL | | BUILDING IS UNDER CONSTRUCTION SHALL CONTAIN A *SHOP | | DRAWING* REVIEW STAMP AND SIGNATURE FROM EACH DESIGNER | | ON THEIR RESPECTIVE PAGES BEFORE PERMIT MAY BE ISSUED | | FOR TENANT BUILD OUT. | | FS 471,481. ONCE THE SHELL OBTAINS AS C OF C ETC THEN | | THE PLANS DO NOT NEED TO GO BACK TO THE BASE BUILDING | | DESIGN TEAM. | | | | 2) NOTE: PLEASE KNOW AS THE BASE BUILDING/SHELL | | CONTRACTOR IS THE SAME AS APPLIED FOR THIS SCOPE OF | | WORK A LETTER OF UNDERSTANDING IS NOT REQUIRED. | | | | 3) NOTE: PLEASE KNOW THIS IS THE FIRST TIME ENERGY | | CALCULATIONS ARE BEING SUBMITTED. THE PREVIOUS TWO | | REVIEWS REQUESTED LIGHTING PERFORMANCE CALCULATIONS AND | | THE SPECIFIC CODE SECTIONS GIVEN WERE | | 13-415.2.ABC.1.1,.1.2 AN D.1.3. THE CODE SECTIONS FOR | | METHOD OF CALCULATIONS GIVEN WERE 13-400.3.B, | | 13-400.3.C. SECTION 13-400.3.A WAS NOT GIVEN AS METHOD | | *A* MAY NOT BE USED. | | PLANS WERE SUBMITTED WITH METHOD *A*. PLEASE SEE THE | | FLORIDA BUILDING CODE 13-400.0.A, 13-101.1.1. PLEASE | | EXPLAIN HOW METHOD *A* MAY BE USED WHEN THIS TENANT | | BUILDING IS NOT A WHOLE BUILDING. | | PLEASE SEE THAT IN ANY CASE THE INFORMATION AS | | SUBMITTED AND SHOWN ON THE INPUT DATA REPORT IS NOT | | COMPLETE NOR DOES IT COORDINATE WITH PLANS IN SEVERAL | | ASPECTS. SOME EXAMPLES WILL BE NOTED BY THIS REVIEWER | | AND PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES AS | | WELL. | | PLEASE SEE 13-103.1. MEETING THE EXCEPTIONS UNDER FS | | 471.003 AND THIS SECTION OF THE FBC REQUIRES LICENSED | | DESIGNER. | | | | FOR EXAMPLE: | | THE IDR SHOWS ONLY TWO (2) LIGHT FIXTURES ON THE | | INTERIOR OF THIS SPACE. HOW IS THIS POSSIBLE WHEN IN | | FACT THE PLANS SHOW MANY FIXTURES? THE FACT IS THE ONLY | | TWO FIXTURES SHOWN ARE 2 WATTS EACH. THIS IS NOT | | POSSIBLE AS THE PLANS DO NOT CORRELATE WITH ANY OF | | THIS. | | | | FORE EXAMPLE; | | ONLY ONE WALL UNDER WALLS, NO WINDOWS, NO DOORS, METAL | | BUILDING ETC. THESE WILL BE NOTED BY OTHER TRADES | | HOWEVER ARE GIVEN FOR INFORMATION AT THIS TIME. | | | | 4) NOTE: PLEASE KNOW ELECTRICAL SERVICE AS SHOWN ON | | THESE PLANS DOES NOT COORDINATE WITH THE ELECTRICAL | | SERVICE ON THE BASE BUILDING. IN FACT THE ELECTRICAL | | SERVICE ON THE BASE BUILDING WHICH ALREADY HAS A FINAL | | CONTAINS MANY ITEMS WHICH ARE NOT THE SAME. | | MAINS ARE 125 AMP | | THERE IS A HOUSE PANEL NOT SHOWN. | | THE SERVICE SIZE IS NOT 400AMPS. | | THE GROUNDING ELECTRODE SYSTEM IS NOT THE SAME AND | | MEETS 250.50,250.24,250.6 ETC | | PLEASE EXPLAIN HOW THE GUTTER HAS AN EQUAL POTENTIAL IF | | THE NEUTRAL IS FLOATING TO THE FIRST MEANS OF | | DISCONNECT. BASED ON THE CODE AND THE RISER FOR BASE | | BUILDING THE SYSTEM AS SHOWN ON THIS RISER MAY NOT BE | | DONE TO MEET THE CODE. | | PLAN SHOWS THREE DISCONNECTS/MAINS | | 215.5, 230.70, 230.71, 230.72, 240.4, 310.16, 250.6, | | 250.24 ETC | | | | 5) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR CONTROL OF | | EXTERIOR LIGHTING. PLANS MENTIONS TIME CLOCK HOWEVER | | NOT FOR ALL LIGHTS AND ALSO SHOWS STANDARD SINGLE POLE | | SWITCH. MUST MEET ONE OF THE TWO MINIMUMS IN SECTION OF | | CODE GIVEN OR BOTH. | | | | ** BASED ON COMMENTS ABOVE ONE SET OF CALCULATIONS | | ALONG WITH ONE COPY OF ELECTRICAL PLANS ARE BEING | | RETAINED BY THIS OFFICE. | | | | ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE | | NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN | | CONTACTING THIS OFFICE. | | | | ***AS THERE ARE MANY ASPECTS OF THE BUILDING AND | | CALCULATIONS NOT COMPLETE AT THIS TIME THERE MAY VERY | | WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW. | | | | | | IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2008-03-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-03-18 |
Time |
12:01 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-03-18 |
Time |
12:01 |
Sent To |
|
|
Notes |
2008-03-18 12:01:25 | ** DENIED 2ND REVIEW** | | | | ** PLEASE SEE SOME COMMENTS ARE THE SAME FROM PREVIOUS | | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE | | ALSO SEE SOME NEW COMMENTS DUE TO NEW INFORMATION NOW | | ON PLANS. | | | | ** PLEASE NOTE: AS THERE IS INFORMATION STILL NOT YET | | SUBMITTED FOR REVIEW, A FULL REVIEW CAN NOT BE DONE AND | | THERE MAY VERY WELL BE NEW COMMENTS ON THE NEXT | | REVIEW. | | | | 1) NOTE: PLEASE SEE NO ENERGY CALCULATIONS WERE | | SUBMITTED, NO LIGHTING PERFORMANCE CALCULATIONS ETC. | | PLEASE SEE 13-400.3.B, 13-400.3.C, 13-415.2, | | 13-415.2.ABC.1.1, .1.2 AND .1.3. | | PLEASE SEE 13-412 FOR WATER HEATING SYSTEMS. | | PLEASE SEE MECHANICAL REVIEW COMMENTS FOR THESE | | SECTIONS. | | | | 2) NOTE: PLEASE KNOW ALTHOUGH NOT REQUIRED A RESPONSE | | LETTER FROM DESIGN PROFESSIONAL IS HELPFUL IN THE | | REVIEW PROCESS. THERE ARE RESPONSES FOR ALL OTHER | | TRADES BUT ELECTRICAL. | | THIS IS ONLY NOTED AS IT MAY HELP THE REVIEW OF SAID | | PLANS. | | | | 3) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM IS | | BEING SHOWN CONNECTED AFTER THE FIRST MEANS OF | | DISCONNECT ON THE TENANT MAINS?? | | PLEASE SEE 250.6, 250.524 AS THIS IS NOT PERMITTED. | | PLEASE SEE THE GE SYSTEM IS ALSO STILL SHOWN TO FOOTER | | STEEL, IS THIS AN EXISTING SERVICE OR NEW? IS THERE AND | | EXISTING GROUNDING ELECTRODE CONNECTED TO FOOTER? | | 250.50 | | FBC 106.1.2 FOR ADDITIONAL INFORMATION. | | | | 4) NOTE: PLEASE SEE 250.104 AS THE GAS PIPE SHOULD NOT | | BE PART OF THE GROUNDING ELECTRODE SYSTEM. IS THIS A | | BOND ONLY? | | | | 5) NOTE: PLEASE SEE THE SHOW WINDOWS WILL REQUIRE | | RECEPTACLES ABOVE WINDOW PER 210.62 | | PLEASE ADJUST LOAD CALCULATIONS PER 220.43 | | | | 6) NOTE: PLEASE BE SURE TO ADJUST LOAD CALCULATIONS FOR | | MIXED USE AS UPSTAIRS IS SHOWN AS APARTMENT. | | 220 | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-09-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-09-13 |
Time |
07:30 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-09-11 |
Time |
20:09 |
Sent To |
|
|
Notes |
2007-09-13 07:30:29 | | | | | ** DENIED ** | | | | 1) NOTE: PLEASE DECLARE IF THIS IS A CHANGE IN | | OCCUPANCY OR USE ON PLANS. | | DOES NOT INDICATE THE PREVIOUS USE BEING NEW RESTAURANT | | BUILD OUT AND APPEARS TO BE A NEW BUILD OUT OF | | RESTAURANT. | | | | 2) NOTE: PLEASE INCLUDE THE ADDRESS ON THE MEP PLANS AS | | SHOWN ON THE ARCHITECTURAL SHEETS. | | FAC 61G15-23.002 | | FBC 106.1.2, 110.1.2 | | | | 3) NOTE: PLEASE SEE THE ELECTRICAL PLANS ONLY INDICATE | | ONE A/C SYSTEM BEING FIGURED INTO LOAD CALCULATIONS AND | | PANEL, YET THE ARCHITECTURAL SHEET SP-1 INDICATES AN | | EXISTING A/C SYSTEM WITH A NEW ONE BEING ADDED? NEC, | | 220, FBC 106.3.5.1.2 | | | | 4) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS AS THE | | ADDITIONAL A/C BEING ADDED TO SPACE MAY REQUIRED ENERGY | | CALCULATIONS BY METHOD AS SPECIFIED IN 13-415.1.B, | | 13-415.1.C. | | PLEASE KNOW THAT LIGHTING PERFORMANCE CALCULATIONS ARE | | STILL REQUIRED PER 13-415.2. PLEASE SEE | | TABLES415.2.C.1, 415.2.B.1. | | PLEASE SUBMIT A FIXTURE LEGEND ON PLANS WITH | | INFORMATION ON FIXTURE TYPES WATTAGE ETC. | | FBC 106.1.2, 106.3.5.1.2 | | | | 5) NOTE: PLEASE INDICATE THE AIC RATINGS FOR NEW MAINS | | AND SERVICE EQUIPMENT AS SHOWN ON RISER. | | 110.9. | | FBC 106.3.5.1.2, 106.1.2 | | | | 6) NOTE: PLEASE INDICATE *FLOATING NEUTRAL* REQUIRED AT | | THE METERS. | | 250.6, 250.24 | | | | 7) NOTE: PLEASE SEE NFPA-96 FOR SHUT DOWN OF ALL | | ELECTRICAL UNDER HOOD. | | PLEASE INDICATE THE REQUIRED SHUNT TRIP BREAKERS. | | PLEASE SEE CHAPTERS 9 AND 10. PLEASE BE SURE TO SEE ANY | | MECHANICAL REVIEW COMMENTS. | | | | 8) NOTE: PLEASE PROVIDE THE MINIMUM ADA LEVELS FOR FIRE | | ALARMS DEVICES PER 11-4.28.1, .2 AND .3(4). | | | | 9) NOTE: PLEASE CORRELATE PLANS WITH RISER. PLANS ONLY | | INDICATE ONE METER AND ONE MAIN DISCONNECT. | | PLEASE INCLUDE ALL EQUIPMENT AS SHOWN ON RISER ON THE | | PLANS WITH THE LOCATIONS. | | 100.26, FBC 106.1.2 | | | | 10) NOTE: PLEASE SEE THE RISER WHICH INDICATES BUILDING | | STEEL AS PART OF THE GROUNDING ELECTRODE SYSTEM. THIS | | IS BEING ASSUMED THIS IS ACTUALLY *FOOTER STEEL*? IN | | EITHER CASE PLEASE KNOW AS THIS IS AN EXISTING BUILDING | | THE FOOTER STEEL WOULD NOT REQUIRE AN ATTACHMENT AS | | THIS MAY CREATE AN ADVERSE AFFECT ON THE STRUCTURAL | | INTEGRITY OF THE FOUNDATION. | | (IF SHOWN ON RISER, THEN THIS WOULD BE REQUIRED AS THIS | | IS BEING SPECIFIED.) | | PLEASE SEE MISSING GAS LINE BOND AS REQUIRED. 250.50, | | 250.104. | | | | 11) NOTE: PLEASE SEE NEC 422.13 AS THE WATER HEATER IS | | REQUIRED TO BE FIGURED AT 125% FOR LOAD. PLEASE KNOW | | THIS WAS A CHANGE IN THE 2005 NEC. | | 230.42, 215.3, 422.13 ETC | | | | 12) NOTE: PLEASE CORRELATE RISER AND PANEL SCHEDULE. | | THE PANEL SCHEDULE SHOWS PANEL WITH A 150AMP MAIN | | CIRCUIT BREAKER, AND RISER SHOWS THIS WITH A 200AMP | | MAIN CIRCUIT BREAKER. | | FBC 106.1.2 | | | | 13) NOTE: PLEASE SEE 210.8B2 AS ALL RECEPTACLES IN | | KITCHEN AREAS ARE REQUIRED TO BE GFI/GFI PROTECTED | | WHETHER OR NOT THESE ARE FEEDING COUNTER SPACE AREAS. | | PLEASE KNOW THIS WOULD INCLUDE REFRIGERATION EQUIPMENT | | ETC. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | 2007-09-13 06:58:41 | 2007-09-13 06:58:41 | | | | IN REVIEW | 2007-09-12 20:31:36 | 2007-09-12 20:31:36 | | | | REVIEW TO BE COMPLETED 9/13, NOTES TO FOLLOW. | 2007-09-12 19:58:39 | 2007-09-12 19:58:39 | | | | REVIEW COMMENCED | 2007-09-11 20:09:20 | 2007-09-11 20:09:20 | | | | IN ELEC FOR REVIEW. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2009-08-03 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-08-03 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-08-03 |
Time |
11:34 |
Sent To |
B |
|
Notes |
2009-08-03 11:41:34 | ******APPROVED***** | | | | PLAN SHEETS A-1 AND E-2 WERE STAMPED, INITIALED, AND | | DATED | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2008-08-14 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-08-14 |
Time |
12:04 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-08-14 |
Time |
11:52 |
Sent To |
|
|
Notes |
2008-08-14 12:04:12 | ******DENIED***** | | | | THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN | | THE OTHER REVIEWERS AS WELL AS THE FOLLOWING COMMENT | | (FROM THE PREVIOUS FIRE PLAN REVIEW) HAVE BEEN | | ADDRESSED: | | | | 2. THE DIRECTIONAL ARROW ON SHEET P-1, M-1, AND E-2 DO | | NOT CORRELATE TO WHAT IS CORRECTLY SHOWN ON SHEET A-1. | | AMEND DIRECTIONAL LEGEND | | | | BE ADVISED THAT THE ABOVE COMMENT IS THE SAME AS TAKEN | | FROM THE PREVIOUS FIRE PLAN REVIEW. PLEASE ADDRESS | | ACCORDINGLY!!!!!!! | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2008-04-10 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-04-10 |
Time |
15:58 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-04-10 |
Time |
15:09 |
Sent To |
|
|
Notes |
2008-04-10 15:26:28 | ******PROVISO***** | | | | THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN | | THE OTHER REVIEWERS AS WELL AS THE FOLLOWING COMMENT | | (FROM THE PREVIOUS FIRE PLAN REVIEW) HAVE BEEN | | ADDRESSED: | | | | 2.THE DIRECTIONAL ARROW ON SHEET P-1, M-1, AND E-2 DO | | NOT CORRELATE TO WHAT IS CORRECTLY SHOWN ON SHEET A-1. | | AMEND DIRECTIONAL LEGEND | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-10-18 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-10-18 |
Time |
15:41 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-10-18 |
Time |
14:48 |
Sent To |
|
|
Notes |
2007-10-18 15:41:08 | ******DENIED***** | | | | 1.THE ADDRESS SHALL BE IN THE TITLE BLOCK OF EACH | | SUBMITTED PLAN SHEET. | | | | 2.THE LAYOUT OF THE PROPOSED 1ST FLOOR PLAN (SHEET | | A-1) DOES NOT CORRELATE WITH LAYOUT SHOWN ON SITE PLAN | | (SHEET SP-1) .AMEND DIRECTIONAL LEGEND. | | | | 3.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | INSTALLATION OF THE COOKING HOOD SYSTEM AND FOR THE | | FIRE SUPPRESSION SYTEM FOR THE HOOD.NFPA 96 - 2001 | | EDITION - SHALL BE REFERENCED. | | | | 4.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | INSTALLATION OF THE FIRE ALARM SYSTEM. | | | | 5.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | ALARM, AS PER WEST PALM BEACH FIRE PREVENTION. | | | | 6.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | 7.PLEASE ACKNOWLEDGE THAT THE NUMERICAL ADDRESS SHALL | | BE POSTED ON THE APPROPIATE EXTERIOR ELEVATION FRONTING | | SPRUCE AVENUE.THE ADDRESS IS TO BE DISPLAYED PRIOR, | | DURING, AND AFTER CONSTRUCTION OPERATIONS.AS PER WEST | | PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS THAN 6" | | IN HEIGHT AND NO LESS THAN 1" IN WIDTH. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
4 |
Status |
P |
Date |
2009-07-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-07-14 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-07-14 |
Time |
14:21 |
Sent To |
|
|
Notes |
2009-07-14 14:33:21 | | | | | PASSED/PROVISO: | | REVISIONS REQUIRED FOR ALL SHEETS SHOWING THE CORRECT | | ADDRESS AND UNIT/SUITE NUMBER IN THE TITLE BLOCK. | | SECTION 106.1.1 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2008-08-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-08-04 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-08-04 |
Time |
07:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2008-04-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-04-10 |
Time |
12:55 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-04-10 |
Time |
12:55 |
Sent To |
|
|
Notes |
2008-04-10 12:56:41 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | ****FROM PREVIOUS REVIEW: | | | | 1. SHT P-2 A SEPARATE GAS PERMIT IS REQUIRED. THE | | FOLLOWING INFORMATION IS REQUIRED FOR PERMIT: | | | | A. OK | | B. OK | | | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****NO RESPONSE, NOT ADDRESSED | | | | D. OK | | 11. OK | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2007-12-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-12-13 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-12-13 |
Time |
12:53 |
Sent To |
|
|
Notes |
2008-04-10 12:55:04 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | 1. SHT P-2 A SEPARATE GAS PERMIT IS REQUIRED. THE | | FOLLOWING INFORMATION IS REQUIRED FOR PERMIT: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. - NOT ALL CUT SECTION LENGTHS ARE | | INDICATED. SEE ALL SECTIONS FROM THE METER TO WHERE THE | | 22 FT LENGTH, AND THE RISER LENGTHS TO EACH APPLIANCE. | | PLEASE SHOW THE LENGTH OF ALL CUT SECTIONS.--SHOW | | ALL PIPE SIZES UP THRU THE SHUT OFF VALVE OF EACH | | APPLIANCE. | | | | B. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED AFTER | | COMMENT "A" ADDRESSED. | | | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | D. SHUT OFF VALVES SHALL BE ACCESSIBLE PER SECTION | | 409.1.3. PLEASE INDICATED ON PLANS. | | | | 11. ALL MECHANICAL, PLUMBING & ELECTRICAL SHEETS. THE | | CERTIFICATE OF AUTHORIZATION NUMBER IS REQUIRED FOR | | DESIGN SERVICES MEP LLC. FAC 61G15-23.002(2) & FS | | 471.025. PLEASE SHOW CA NUMBER ON ALL SHEETS. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2009-07-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-07-01 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-07-01 |
Time |
10:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-07-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-21 |
Time |
15:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-21 |
Time |
15:19 |
Sent To |
|
|
Notes |
2008-07-21 15:24:38 | TO "COMM" BD#9 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-03-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-11 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-11 |
Time |
15:14 |
Sent To |
|
|
Notes |
2008-03-11 15:17:42 | TO "COMM" BD#30 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-10-18 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-10-18 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-08-23 |
Time |
10:23 |
Sent To |
|
|
Notes |
2007-09-11 09:12:56 | TO "COMM" BD#51 | 2007-08-23 10:29:35 | WAITING FOR " COMM" BD |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2009-08-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-08-06 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-08-06 |
Time |
14:49 |
Sent To |
|
|
Notes |
2009-08-06 14:50:58 | IMPACT FEES PAID ON SHELL |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2009-07-21 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-07-21 |
Time |
15:18 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-07-20 |
Time |
16:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2008-07-24 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-07-24 |
Time |
15:52 |
Rev Time |
1.15 |
Received By |
tgordon |
Date |
2008-07-24 |
Time |
15:52 |
Sent To |
|
|
Notes |
2008-07-24 16:07:43 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1)A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C | | EQUIPMENT SCHEDULE C/U #TTX048C100A AND A/H/U #TWE048P | | COULD NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, | | PLEASE CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004 | | FBC 13-407.1.ABC.3.1.1. | | | | 2) PLEASE ADD TO THE MECHANICAL PLAN, A DETAIL FOR | | HANGING THE KITCHEN HOOD TO THE CEILING, AND A DETAIN | | FOR SECURING THE EXHAUST FAN ROOF CURB TO WITHSTAND 140 | | MPH WINDS, PER 2004 FBC 1609. | | | | 3) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR THE | | 24X16 AND 12X16 WALL LOUVERS, SEE FS 553.842(1) AND FAC | | RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(C). | | | | *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED | | IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND | | SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B. | | AMEND. 106.3. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2008-03-18 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2008-03-18 |
Time |
18:52 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2008-03-18 |
Time |
18:52 |
Sent To |
|
|
Notes |
2008-03-18 18:55:11 | PLAN DENIED | | PLEASE PROVID EQUIPMENT SCHEDULE ON MECHANICAL PLANS . | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-09-26 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2007-09-26 |
Time |
19:11 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2007-09-26 |
Time |
19:11 |
Sent To |
|
|
Notes |
2007-09-26 19:04:22 | 1- PLEASE PROVIDE A FULL SET OF PLANS FOR REVIEW | | ,MISSING PAGE A-3, A CEILING DETAIL, AND 2ED FLOOR | | MECHANICAL PLANS . | | 2- PLEASE REFER TO NOTE 5 ON PAGE SP-1 , 1HR RATING | | BETWEEN GROUND FLOOR AND 2ED FLOOR . PLEASE REFER TO | | TABLE 302.3.2 REQUIRED SEPARATIONS OF OCCUPANCIES 2004 | | FBC | | 3-CONDENSER MUST BE 10 FT AWAY FROM MAKE UP AIR TO | | HOOD | | 4- FIRE DAMPERS ARE REQUIRED IN ALL DUCT PENETRATIONS | | THROUGH THE CEILING. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2009-07-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-07-14 |
Time |
14:33 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-07-14 |
Time |
14:33 |
Sent To |
|
|
Notes |
2009-07-14 14:34:48 | | | | | | | PASSED/PROVISO: | | | | REVISIONS ARE REQUIRED FOR ALL SHEETS INDICATING THE | | CORRECT ADDRESS AND UNIT/SUITE NUMBER IN THE TITLE | | BLOCK OF EACH SHEET. SECTION 106.1.1. | | | | | | | | | | | | | | . |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2008-08-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-08-04 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-08-01 |
Time |
16:53 |
Sent To |
|
|
Notes |
2008-08-04 08:10:57 | DENIED | | REFERENCE: FLORIDA STATUTES | | FBC-2004 CHAPTER 1 | | | | PLANS ARE CODE COMPLIANT AT THIS TIME BUT THERE IS A | | COMMENT TO BE ADDRESSED BASED ON NEW INFORMATION NOW | | BEING PROVIDED. | | | | 1. THE BASE BUILDING PERMIT, 06011130, FOR THE SHELL | | BUILDING HAS EXPIRED AND AS SUCH HAS NO CERTIFICATE OF | | COMPLETION. A NEW PERMIT APPLICATION IS REQUIRED TO | | FINAL OUT THE BASE BUILDING. SINCE THE BASE BUILDING | | DESIGN TEAM IS RESPONSIBLE FOR SUCH BUILDING UNTIL A | | CERTIFICATE OF COMPLETION OR CERTIFICATE OF OCCUPANCY | | IS ISSUED, ALL PLANS FOR PERMITTED WORK ON BUILDOUTS | | SHALL CONTAIN A "SHOP DRAWING" REVIEW STAMP AND | | SIGNATURE FROM EACH DESIGNER ON THEIR RESPECTIVE SHEET | | BEFORE PERMIT MAY BE ISSUED FOR THE TENANT BUILDOUT. FS | | 741.481. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2008-04-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-04-10 |
Time |
12:52 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-04-10 |
Time |
08:43 |
Sent To |
|
|
Notes |
2008-04-10 12:51:49 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | MUNICIPAL CODE WPB | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | ****FROM PREVIOUS REVIEW: | | | | 1. OK | | 2. OK | | 3. OK | | 4. OK | | 5. OK | | | | 6. SHT P-1 THE GREASE INTERCEPTOR SHALL BE SIZED BY THE | | UTILITY DEPT., INDUSTRIAL PRETREATMENT, ENVIRONMENTAL | | COMPLIANCE. PLEASE CONTACT EITHER RODNEY COMPO, (561) | | 822-2272, E-MAIL [email protected] OR CALVIN WILLIAMS | | (561) 822-2284, E-MAIL CWILLIAMS @WPB.ORG. THEIR FAX IS | | (561) 822-2287. A PRINTED DETERMINATION SHALL BE | | PRODUCED AND SUBMITTED WITH PLANS SHOWING INTERCEPTOR | | SIZE APPROVAL. ARTICLE III SECTION 90-124(7)(F). | | ****RESPONSE NOTED, NOT ADDRESSED. | | | | 7. OK | | 8. OK | | 9. OK | | | | 10. SHT P-2 A SEPARATE GAS PERMIT IS REQUIRED. THE | | FOLLOWING INFORMATION IS REQUIRED FOR PERMIT: | | | | A. OK | | B. OK | | | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****NO RESPONSE, NOT ADDRESSED. | | | | D. OK | | 11. OK | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-10-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-10-13 |
Time |
05:31 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-10-12 |
Time |
18:58 |
Sent To |
|
|
Notes |
2007-10-13 06:10:41 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | MUNICIPAL CODE WPB | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. ROUTE THE PLANS TO THE STATE OF FLORIDA, DEPT OF | | BUSINESS REGULATION, (DBPR), DIVISION OF HOTEL & | | RESTAURANT FOOD SERVICE LICENSE FOR REVIEW PRIOR TO | | RESUBMITTING TO THE CITY WPB FOR REVIEW. REVIEWED & | | STAMPED PLANS SHALL BE INSERTED INTO EACH SET OF PLANS | | SUBMITTED FOR REVIEW WITH THE TWO PAGE "SPECIFICATION | | WORKSHEETS" ATTACHED TO THE SHEETS STAMPED/REVIEWED BY | | DBPR. SECTION 102.2.1. | | | | 2. SHT A-1 DETAIL FOR THE TOILET ROOM IS INDICATED AS | | DETAILD-1/A-3, BUT SHEET A-3 HAS NOT BEEN SUBMITTED. | | PLEASE CLARIFY. SECTION 106.1.1. | | | | 3. SHT A-2 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR | | W/C: | | A. 11-4.16.2 CLEAR FLOOR SPACE | | ___FOR LAV: | | A. 11-4.19.2 CLEARANCES | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | C. 11-4.19.5 FAUCETS | | D. 11-4.19.6 MIRRORS | | | | 4. SHT A-2 FINISH. WALLS WITHIN 2' OF THE W/C SHALL BE | | A SMOOTH, HARD, NONABSORBENT SURFACE UP TO 4 FEET ABOVE | | THE FLOOR PER SECTION 1210.2. PLANS SHOW FINISH | | DRYWALL. PLEASE SHOW COMPLIANCE. | | | | 5. SHT P-1 A CLEANOUT IS REQUIRED NEAR THE JUNCTION OF | | THE BUILDING DRAIN AND THE BUILDING SEWER PER SECTION | | 708.3.5. A TWO WAY CLEANOUT WILL ENABLE CLEANOUT IN THE | | BUILDING AND OUT TO THE SEWER. | | | | 6. SHT P-1 THE GREASE INTERCEPTOR SHALL BE SIZED BY THE | | UTILITY DEPT., INDUSTRIAL PRETREATMENT, ENVIRONMENTAL | | COMPLIANCE. PLEASE CONTACT EITHER RODNEY COMPO, (561) | | 822-2272, E-MAIL [email protected] OR CALVIN WILLIAMS | | (561) 822-2284, E-MAIL CWILLIAMS @WPB.ORG. THEIR FAX IS | | (561) 822-2287. A PRINTED DETERMINATION SHALL BE | | PRODUCED AND SUBMITTED WITH PLANS SHOWING INTERCEPTOR | | SIZE APPROVAL. ARTICLE III SECTION 90-124(7)(F). | | | | 7. SHT P-2 SANITARY ISOMETRIC. A VENT IS REQUIRED FOR | | THE MOP SINK. SECTION 901.2.1. | | | | 8. SHT P-2 SANITARY ISOMETRIC. PLEASE INDICATE THE USE | | OF THE FLOOR SINK IN THE MIDDLE OF THE FLOOR. IF THIS | | IS TO DRAIN THE FLOOR, A FLOOR DRAIN IS REQUIRED. FLOOR | | SINKS ARE FOR INDIRECT WASTE. SECTIONS 106.1.2 & | | 802.3. | | | | 9. SHT P-2 THE WATER ISOMETRIC DOES NOT REFLECT THE | | FLOOR PLAN AT THE MOP SINK & AT THE TOILET ROOM. PLEASE | | CORRELATE. SECTION 106.1.1. PLEASE MAKE SURE RISER | | DIAGRAM REFLECTS THE FLOOR PLAN. | | | | 10. SHT P-2 A SEPARATE GAS PERMIT IS REQUIRED. THE | | FOLLOWING INFORMATION IS REQUIRED FOR PERMIT: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. - NOT ALL CUT SECTION LENGTHS ARE | | INDICATED. SEE ALL SECTIONS FROM THE METER TO WHERE THE | | 22 FT LENGTH, AND THE RISER LENGTHS TO EACH APPLIANCE. | | PLEASE SHOW THE LENGTH OF ALL CUT SECTIONS.--SHOW | | ALL PIPE SIZES UP THRU THE SHUT OFF VALVE OF EACH | | APPLIANCE. | | | | B. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED AFTER | | COMMENT "A" ADDRESSED. | | | | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | D. SHUT OFF VALVES SHALL BE ACCESSIBLE PER SECTION | | 409.1.3. PLEASE INDICATED ON PLANS. | | | | 11. ALL MECHANICAL, PLUMBING & ELECTRICAL SHEETS. THE | | CERTIFICATE OF AUTHORIZATION NUMBER IS REQUIRED FOR | | DESIGN SERVICES MEP LLC. FAC 61G15-23.002(2) & FS | | 471.025. PLEASE SHOW CA NUMBER ON ALL SHEETS. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
N |
Date |
2008-03-13 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-03-13 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-03-13 |
Time |
11:21 |
Sent To |
|
|
Notes |
2008-03-13 11:21:42 | SHELL BUILDING APPROVED ON #06011130 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-09-26 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-09-17 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2008-08-05 |
Time |
08:09 |
Sent To |
|
|
Notes |
2007-09-17 15:51:04 | SHELL BUILDING APPROVED ON #06011130 |
|
|