Plan Review Details - Permit 07080591
Plan Review Stops For Permit 07080591
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 09:14 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 09:14 Sent To M
Notes
2007-08-29 09:15:20TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-23 Cont ID  
Sent By tgordon Date 2007-08-23 Time 09:01 Rev Time 0.00
Received By tgordon Date 2007-08-22 Time 14:12 Sent To  
Notes
2007-08-22 14:12:42TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-09-10 Cont ID  
Sent By tgordon Date 2007-09-10 Time 09:10 Rev Time 0.30
Received By tgordon Date 2007-09-10 Time 09:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-23 Cont ID  
Sent By tgordon Date 2007-08-23 Time 08:50 Rev Time 0.45
Received By tgordon Date 2007-08-23 Time 08:50 Sent To  
Notes
2007-08-23 09:00:41PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) SEE YELLOW HIGH LIGHTS ON MECHANICAL PLANS SHOWING
 DUCTS THAT NEED TO BE SIZED.
  
 2) PLEASE ADD INFORMATION FOR TRAVERSAIR INC. (LICENSE
 NUMBER ADDRESS, ETC.) TO MECHANICAL PLANS, SEE WPB
 106.1.3.
  
 3) SHOW THE CFM'S FOR THE BATHROOM EXHAUST FANS ON THE
 MECHANICAL PLANS, SEE RES. R303.3 EXCEP.
  
 4) SHOW ATTIC ACCESS TO AHU ON MECHANICAL PLANS, SEE
 RES. M1305.1.3.
  
 5) BE ADVISED BUILDING AND ELECTRICAL PLANS WILL NEED
 TO BE REVISED AS THEY SHOW THE AHU'S IN A MECHANICAL
 ROOM, NOW THE MEDIA ROOM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]