Plan Review Details - Permit 07080538
Plan Review Stops For Permit 07080538
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-09-01 Cont ID  
Sent By mjacobs Date 2007-09-01 Time 07:33 Rev Time 0.00
Received By mjacobs Date 2007-09-01 Time 07:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-25 Cont ID  
Sent By dpalmer Date 2007-09-25 Time 08:42 Rev Time 0.00
Received By dpalmer Date 2007-09-25 Time 08:07 Sent To  
Notes
2007-09-25 08:43:03PRINTED THE MISSING PRINTED PE LICENSE # OF ENGINEER ON
 TITLE BLOCKS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-28 Cont ID  
Sent By dpalmer Date 2007-08-28 Time 21:03 Rev Time 0.00
Received By dpalmer Date 2007-08-28 Time 21:03 Sent To  
Notes
2007-08-28 21:03:372007-08-28 21:03:37
  
 ** DENIED **
  
 1) NOTE: PLEASE SEE THE ADDRESSING LISTED ON THE TITLE
 BLOCKS AS REQUIRED PER FAC 61G15-23.002 IS REQUIRED TO
 COORDINATE WITH THE STATE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION.
 PLEASE REVISE AND ADJUST ACCORDINGLY.
 PLEASE SEE PRINT OUT ATTACHED FROM DBPR.
 ENGINEER OF RECORD MAY COME IN PERSONALLY AND REVISE
 TITLE BLOCKS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-10-01 Cont ID  
Sent By mawillia Date 2007-10-01 Time 10:56 Rev Time 0.00
Received By mawillia Date 2007-10-01 Time 10:47 Sent To  
Notes
2007-10-01 10:53:13*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN A-1 STAMPED, INITIALED, AND
 DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-08-30 Cont ID  
Sent By mawillia Date 2007-08-30 Time 14:09 Rev Time 0.00
Received By mawillia Date 2007-08-30 Time 13:29 Sent To  
Notes
2007-08-30 14:09:20*****DENIED*****
  
  
 1.THE OCCUPANCY CLASSIFICATION IS INDICATED AS A
 BUSINESS OCCUPANCY.IS THIS THE CLASSIFICATION FOR THE
 EXISTING STRUCTURE OR THE PROPOSED?
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES).
  
 5.THE FIRE PROTECTION SYSTEMS (FIRE SPRINKLER/FIRE
 ALARM) SHALL BE MAINTAINED OPERATIONAL AT ALL TIMES
 DURING ALTERATION.
  
 6.IF/WHEN IT IS NECESSARY TO SHUT DOWN THE FIRE
 PROTECTION SYSTEM, THE FIRE DEPARTMENT SHALL BE
 NOTIFIED WHEN THE SYSTEM IS SHUT DOWN AND WHEN THE
 SYSTEM IS RETURNED TO SERVICE.
  
 7.ALL REQUIRED EXIT COMPONENTS, FIRE-RESISTIVE
 ASSEMBLIES AND CONSTRUCTION SHALL BE MAINTAINED.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 14:13 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 14:13 Sent To  
Notes
2007-09-24 15:51:01TO "BOB"#10
2007-09-17 14:13:40WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-10 Cont ID  
Sent By jleech Date 2007-09-10 Time 09:54 Rev Time 0.00
Received By jleech Date 2007-08-21 Time 10:46 Sent To  
Notes
2007-08-28 14:56:06TO "BOB"#6
2007-08-21 10:46:36WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-08-30 Cont ID  
Sent By tgordon Date 2007-08-30 Time 15:37 Rev Time 0.10
Received By tgordon Date 2007-08-30 Time 15:37 Sent To  
Notes
2007-08-30 15:38:23DEMO.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-09-10 Cont ID  
Sent By jleech Date 2007-09-10 Time 09:52 Rev Time 0.00
Received By jleech Date 2007-09-10 Time 09:52 Sent To  
Notes
2007-09-10 09:53:39NO PLUMBING SHOWN ON PLANS TO BE DEMOED.

Review Stop Z ZONING
Rev No 1 Status N Date 2007-09-05 Cont ID  
Sent By choops Date 2007-09-05 Time 10:39 Rev Time 0.00
Received By choops Date 2007-09-05 Time 10:39 Sent To  
Notes
2007-09-05 10:39:23*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.